IEEE Insulated Conductors Committee. Subcommittee B, Cable Accessories

Similar documents
Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

CERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM

Not all Low Voltage Switchgear is created equal

INSTALLATION PRODUCTION TESTS

ENGINEERING COMMITTEE Interface Practices Subcommittee. ANSI/SCTE (formerly IPS TP 405)

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

Installation Instructions

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

HVS S 15kV Class

Pretest Module 29 High Voltage Unit 1

600 A 35 kv class BT-TAP deadbreak connector

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

Not all Low Voltage Switchgear is created equal

600 A 25 kv class BT-TAP deadbreak connector

600 A 15 kv class T-OP II deadbreak connector

Electrical Failure Investigations

ET-PWR-END-KIT Installation Instructions (part #JSR00)

Branch Splice QS-2001B

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation

ELASTIMOLD UNDERGROUND CABLE ACCESSORIES

600 A 35 kv class separable splices

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

Geometric vs. Capacitive Stress Control: choosing cable termination accessories to help reduce electrical stress.

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

Step Motor Lower-Loss Technology An Update

REPORT OF TEST ON Elastimold Molded Vacuum Reclosers (MVRs)

IEC Standard Compliant Vacuum Circuit-Breaker (12 kv, 24 kv) for Southeast Asian Markets

Design Guide for Integration of Fixed-Mount Circuit Breakers

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

copper stud. If a 900 A rating is desired, specify a C as the 8th digit when determining your part number (See Table 3, page 3.)

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS.

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES

ACCELERATED CABLE AGING TESTS for DISTRIBUTION and TRANSMISSION CABLES PART 1 HV AC PAPER CABLES

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

High Voltage Joints and Terminations up to 72,5 kv 145 kv

Loadbreak Apparatus Connectors

www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers

ECET Distribution System Protection. Overcurrent Protection

Presented to the IAPMO Standards Review Committee on December 9, 2013

600 A 15 and 25 kv class Cleer grounding elbow

11. CABLE SPECIFICATIONS 5kV, 15kV, AND 35kV RUBBER OR PLASTIC INSULATED CABLE

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

Selective Coordination Enforcement:

HIGH SPEED MEZZANINE PRODUCT SPECIFICATION

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

3M Cold Shrink QT-III Silicone Rubber Termination

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

100 / 110 DRYWELL FUSE SPECIFICATION

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

3M Cold Shrink Splice Kits, QS T Series

Live Wire Owner s Manual

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

Electrical Safety and Overcurrent Protection

EE 741 Over-voltage and Overcurrent. Spring 2014

Cold Shrink QS T Trifurcating Transition Splice Kit

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

4. SHIELDS. 4.1 Power Cable. 4.2 Electronic Cable Conductor Shield (Strand Shield) Outer Shield (Insulation Shield) 60

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

This section is specifically about safety matters

LCT Shielded Primary UD EPR LCT Shielded Primary UD EPR Cable

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

3.2. Current Limiting Fuses. Contents

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number:

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

3M Cold Shrink QT-III Silicone Rubber Termination 7673-S-8(S)-JCN

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

3M Cold Shrink Splice Kit QS-III 5536A

ABB AG - EPDS. Ultra-Fast Earthing Switch UFES active internal arc protection

2013 Grid of the Future Symposium. Utilizing Single Phase Operation Scheme on Untransposed 765kV lines for a Stability-Limited Plant

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

LCT Shielded Primary UD TRXLP LCT Shielded Primary UD TRXLP Cable

11. CABLE SPECIFICATIONS 5kV, 15kV, AND 35kV RUBBER OR PLASTIC INSULATED CABLE

Power systems Protection course

GENERAL. CONSTRUCTION External

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

Functional Overview and Operating Principles for the AR-OH and AR360 Overhead AutoRANGER Fault Indicators

Selective Coordination

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

Premolded cable joint with cold shrink outer jacket SOJ kv

SECTION PANELBOARDS

Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A

Eaton s Cooper Power Systems

Jun06 Rev D

Cold Shrink QS2013-3T-WS Trifurcating Transition Splice Kit

Unified requirements for systems with voltages above 1 kv up to 15 kv

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS

Product Number

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

TEMPERATURE RISE TESTS

Ultra Fast Earthing Switch UFES retrofit Overview

A. Submit manufacturer's literature and technical data before starting work.

25 kv Apparatus Bushings

Transcription:

IEEE Insulated Conductors Committee Spring 2011, St. Petersburg, FL Subcommittee B, Cable Accessories Presentation by: Thomas C. Champion

History of IEEE 592 First Edition, 1977 IEEE Standard for Exposed Semiconductive Shields on Premolded High Voltage Cable Joints and Separable Insulated Connectors N. Piccione, Chair; 10 Working Group Members 1 st Revision, 1990 IEEE Standard for Exposed Semiconductive Shields on High Voltage Cable Joints and Separable Insulated Connectors G. P. Rampley, Chair; 16 Working Group Members Dropped Premolded 2 nd Revision, 2007 IEEE Standard for Exposed Semiconducting Shields on High Voltage Cable Joints and Separable Connectors Michael W. Malia, Chair; 16 Working Group Members Dropped Insulated from Separable Connector

Purpose of Semiconductive Shield Protect the insulation Provide voltage stress relief Maintain the accessory surface at or near ground potential under normal operating conditions Initiate i fault current arcing if the accessory should fail Thi t d d t f th t t d i t t This standard sets forth tests and requirements to demonstrate that the shield will perform these duties.

What s Included? Maximum Shield Resistance Assure that the accessory provides stress relief Assure shield surface is maintained at or near ground protential Shield Fault Initiation Test Assure initiation of fault current arcs to ground that will cause overcurrent protective devices to operate Limitations: Full circuit voltage is applied during the test Doesn t attempt to simulate all service conditions nor field assembly

Performance Requirements Shield Resistance Measured from cable entrance to furthest extremity 5000 ohms Fault Current Initiation Capable of initiating two consecutive fault current arcs to ground 10kA, 10 cycles minimum Initiation within 3 seconds of voltage application Number of Samples Minimum i of 2 samples per test

Shield Resistance Test Use voltmeter ammeter method, either ac or dc power supply allowed Current Connections: Separable Connector cable entrance to furthest shield extremity, circumferential connections Joint cable entrance to physical center of the shield, circumferential connections Apply current of 1.0 ma ± 02 0.2 ma, measure voltage

Shield Resistance Test Measure shield resistance under two sets of conditions Specimen Aging Condition Unaged specimen Specimen aged in air oven for 504 hours at 121 ± 5 C Specimen Temperature Condition Test specimen at 20 ± 5 C Test specimen at 90 ± 5 C

Fault Current Initiation Test Assemble per manufacturer s instructions Exception: metallic cable shield extended over the accessory shield Fault rod of erosion resistant metal (copper tungsten) 3/8 inch diameter, threaded into accessory connector, flush with outer shield surface of accessory Mount accessories in typical field position Elbow vertical, rod close to shield extremity Joint horizontal, rod at center of connector

Fault Current Initiation Test Voltage source applied between specimen neutral ground and cable conductor Applied voltage Separable Connector Joint Test Voltage Rating Phase to Ground* Voltage Rating Phase to Ground^ Applied Voltage Phase to Ground (kv rms), Fig. 1 (kv rms), Fig. 2 (kv rms) 8.3 8.7 7.0 15.2 14.4 11.7 21.1 19.4 12.2 * For separable connector voltage ratings, see IEEE 386 ^ For joint voltage ratings, see IEEE 404 Lower test voltage may be used provided fault is initiated and sustained for minimum required cycles.

Fault Current Initiation Test Available short circuit current of 10kA (Note: No specification on tolerance, IEEE 4 assumed) Two applications of fault current Minimum current flow duration of 10 cycles Fault initiation must occur within 3 seconds Initiate second fault current application in the h shortest t practical time Do not disturb samples between fault applications

Fault Current Initiation Test Separable Connector Joint

Error in Drawing Fault Rod is in wrong position! Place Rod at GREATEST Distance from NEAREST Ground 1990 and 2007 Versions Original 1977 Version

Why the current interest? Field installation practices have changed The IEEE 592 standard was written many years ago when semiconductive shields were exposed and not covered Most cables are now jacketed, which hmeans that jackets are now applied over joints and portions of terminations The effect of a jacket on the performance of semiconductive shielding systems has never been evaluated, although most installations now use jacketed constructions

Why the current interest? Coverings may affect the distribution of the ionized plasma generated during a fault This could impact the ability of the shielding system to conduct and maintain the fault for sufficient time to clear Different types of coverings may give different response

How might a jacketed joint respond differently during a fault? Cold shrink coverings Flexible epands expands on one side, pulled in and seals on the other IONIZED GASES MAY NOT REACH AREA OF NEUTRAL WIRES RE-JACKETING MATERIAL, COLD-SHRINK JACKET MATERIAL STRETCHES IN RESPONSE TO FAULT ENERGY RELEASE

How might a jacketed joint respond differently during a fault? Heat shrink coverings Less flexible, more rigid, id allows plasma to encompass component or may burn through at the failure site RE-JACKETING MATERIAL, HEAT-SHRINK IONIZED GASES MAY NOT REACH AREA OF NEUTRAL WIRES JACKET MATERIAL MAY BURN THROUGH AND RELEASE PLASMA TO THE OUTSIDE ENVIRONMENT

How might a jacketed joint respond differently during a fault? Hand taped coverings Tapes spread apart, channeling plasma away from shield RE-JACKETING MATERIAL, HAND-TAPED COVERING IONIZED GASES MAY NOT REACH AREA OF NEUTRAL WIRES JACKET MATERIAL MAY SPREAD APART AND RELEASE PLASMA TO THE OUTSIDE ENVIRONMENT

Test Configuration for Separable Connectors RE-JACKETING MATERIAL, HEAT-SHRINK, COLD-SHRINK, OR HAND-TAPED Exposed Semi-conductive Shield Jacket Material Installed Over Semi-conductive Shield

Test Configuration for Joints Exposed Semi-conductive Shield RE-JACKETING MATERIAL, HEAT-SHRINK, COLD-SHRINK, OR HAND-TAPED Jacket Material Installed Over Semi-conductive Shield

Test Configuration for Joints Two possible issues with joint testing configuration How far above (or below) the joint body should the neutral wires be placed? Should other configurations be considered, such as spreading wires around the joint? Is the orientation top to bottom optimal? Should the fault rod be on the top side and the neutrals on the bottom? (Hot gases wouldn t rise up into the neutral) ACCESSORY INSULATION ACCESSORY SHIELD FAULTING ROD? CABLE NEUTRAL ACCESSORY GROUNDING CONNECTION COMPRESSION CONNECTOR TO SYSTEM NEUTRAL GROUND

What s Needed or Missing? No mention of what should go in the test report Time between fault applications is shortest practical time. Why not record this time in the test report? Resistance values are recorded when samples are within a given temperature range. Why not report the actual temperature at the time of test? Minimum current flow duration of 10 cycles during Minimum current flow duration of 10 cycles during fault current test. Record the actual number of cycles.

What s Needed or Missing? Developmental l Tests for use in developing new materials? Why wait to test on full scale products? Why not test on sample sheets of material? Platens How could this test be performed? Do the test values scale?

Where Do We Go From Here? IEEE 592 201? IEEE Standard for Exposed Semiconductive Shields on High Voltage Cable Joints and Separable Insulated Connectors IEEE 592 201? IEEE Standard Fault Duty Requirements for Semiconductive Shielding of High Voltage Electrical Components

Does this Apply to Oh Other Electrical l Equipment? Polymer Insulated Vacuum Recloser Pi Painted semiconductive i shield over vacuum bottle casting Shield fails to carry sufficient fault current Circuit protective devices did not operate Multiple failures

An Example Vacuum Recloser Dielectric puncture occurring at embedded metallic screen Current transfers to painted shield Shield impedance limits fault current Polymer insulation chars along path to nearest metallic ground

Consequences of Failure to Clear Fault Severe electrical noise Flicker Molten and flaming components dropping to ground Pole fire Ground fire Damage to equipment beyond initial failure Service interruption

Consequences of Failure to Clear Fault Safety hazard to personnel Damage may not be externally visible Voltage present within a normally grounded area

Problems and Solutions Problem Change in scope would broaden coverage of standard to areas outside the jurisdiction i of ICC Solution Joint Working Group with ih T&D

Are There Other Examples? Other Problems and Solutions?