GENSET CONTROL MODULE A121A / A241A

Similar documents
GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start.

GENSET CONTROL MODULE A121H / A241H. User selectable time delays for engine start and engine stop (cool down).

GENSET CONTROL MODULE LEVEL 0 A120A. User selectable time delays for engine start and engine stop (cool down).

Flight Systems. Replacement for KASSEC DESCRIPTION

1. AC VOLTS: Displays generator output in voltage. 2. AC FREQUENCY: Displays the speed of the generator set in Hertz.

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

ENGEN -100/ENGEN -200 ENGINE GENERATOR CONTROLLER

DKG-114 MANUAL AND REMOTE START UNIT

DEEP SEA ELECTRONICS PLC

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

DEEP SEA ELECTRONICS PLC

Cascade CD101 Auto-Start Controller. Installation and Operations Manual Sections 40 & 75

60 Series Engine Controls

ANALOG CONTROL PANEL

HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic

ES52 Auto Start Engine Controller Installation and User Manual for the ES52 Auto Start Engine Controller.

EPM72 Engine Protection Module

Deep Sea Electronics Plc

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

Starting System DS-102 Series 200. Elmatik AS P.O.Box 309 NO-3471, Slemmestad T F

ECU. Speed Switch Manual. Contents. ECU is a registered trademark of Engineering Concepts Unlimited Inc.

HGM72 Automatic Generator Module OPERATING MANUAL Smartgen Electronic

GSC300 Auto Start Engine Controller

ES52. Auto Start Engine Controller. Full Version. Installation and User Manual for the ES52 Auto Start Engine Controller.

702 AUTOMATIC START MODULE OPERATING INSTRUCTIONS

DEEP SEA ELECTRONICS PLC

HGM6410/6420 AUTOMATIC GENERATOR MODULE WITH J1939 INTERFACE SOFTWARE MANUAL

HGM1750 Genset Security Module USER MANUAL Smartgen Technology

HGM72 Automatic Generator Module OPERATING MANUAL Smartgen Electronic

DSEULTRA DSE6000 Quick Start Guide Document Number

Generator Start Control Module

PSM72H Push-Button Start Module

GSC300 Auto Start Engine Controller

Cat/DCG-6D1I/07-08/03/Ver 1 Page 2/10

SE-3SCR-LM MANUAL MOTOR LOAD MANAGER

Energy Division

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

5220 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL

Auto Mains Failure AMF Controller AE10113

Deep Sea Electronics Plc

Generator Start Control Module

Transfer switch GTEC open or delayed transition

Te 803 Electronic Controller. Service, Operation & Technical Information Manual

DEEP SEA ELECTRONICS PLC

Generator Sets Controller 210. Operation Manual. Ver1.0

GSC300. Auto Start Engine Controller. Installation and User Manual for the GSC300 Auto Start Engine Controller. Full Version

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

Generator Start Control Module

SURE-TRIP OEM RELACEMENT TRIP UNIT

AUTOMATIC STAND-BY AND PEAK-LOAD CONTROL

DEEP SEA ELECTRONICS PLC

ESD5500E Series Speed Control Unit

DKG-215 MANUAL AND REMOTE START UNIT

GENERATOR START CONTROL MODULE

OPERATING INSTRUCTION: DGC-6D/6D1I

REVISED ATM72 Auto Transfer Module

R & D SPECIALTIES ROTROL I USER'S MANUAL

OPERATING INSTRUCTIONS MCP-MT1

REVISION HISTORY REVISION HISTORY

DEEP SEA ELECTRONICS PLC DSE3210 Configuration Suite Software Manual

Application Engineering

GCU-10. Automatic Engine Control Unit Operators Manual

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

PowerCommand 2100 digital generator set control

GENERATOR START CONTROL MODULE

RVS-DN Digital Reduced Voltage Motor Starter

ESD5100 Series Speed Control Unit PART NUMBER ESD5120 ESD (127)

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology

ENGINE PROTECTION BOARD PDM1

DEEP SEA ELECTRONICS DSE7110 MKII / DSE7120 MKII Configuration Suite PC Software Manual

SURE TRIP RETRO KITS

R-200A Digital Controller TECHNICAL MANUAL. A new standard of reliability. This manual should remain with the unit.

AUTOSTART 705S V1.00 AUTOSTART 710S / 720S / 730S V1.04 Programming Reference and Check Sheets

IMI vibration switch USER MANUAL INSTALLATION - OPERATION - MAINTENANCE

RVS-DX Digital Reduced Voltage Motor Starter

PRODUCT SERIES: DPG-2100

Model H30 Operation Manual

DEEP SEA ELECTRONICS

PowerCommand 1.1 control system

SURE TRIP SLT-201 SECONDARY TEST SET

Energetech LLC 7427 S. Main (P.O. Box 400) Midvale, Utah (801) Ph. (801) Fx.

Commander 15i Container and Pallet Loader. Property of American Airlines

MSD 7AL-3, Ignition Control PN 7230

DKG-705 AUTOMATIC MAINS FAILURE AND REMOTE START UNIT WITH PARALLEL TO MAINS AND DUAL GENSET PARALLEL FEATURES

Troubleshooting Guide

Manual and Remote Start Unit with Key Switch, 72x72 DIN Size

design prefix 50 Hanover Road, Florham Park, New Jersey USA (ASCO), for service call (ASCO)

EDG6000 Electronic Digital Governor

TG350 User Manual. Manual Revision: Min. FW Revision: Date Released: 09/01/ DYNAGEN Technologies Inc

DEEP SEA ELECTRONICS PLC

Application Engineering

Diesel generator set C17D5T series

MODEL RMS INSTALLATION INSTRUCTIONS. CONTENTS Page A. Introduction 1. Usage 2 2. How it operates 2

Operator s Series 300 Generator Paralleling System

USER MANUAL FOR GC500 GENSET CONTROLLER SEDEMAC ABSTRACT

Owner s Manual. Series 165 Automatic Transfer Switches rated 100 and 200 amps, single phase, 240 V ac for automatic 2 wire start generators

INSTALLATION GUIDE. FCC ID NOTICE

ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI

C.E. Niehoff & Co. C703/C703A and C706 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

Transcription:

Technical Data Sheet GENSET CONTROL MODULE A121A / A241A Features: Models for both 12V and 24V systems. One model for both spark ignition and diesel engines. 4-alarm light outputs with lamp-test provisions. User selectable starting mode: full cycle cranking, or single-cycle crank limiter. User selectable time delays for engine start and engine stop (cool down). Loss of speed signal protection for crank motor circuit. Special logic to re-establish cranking following a false start. Special logic permits re-starting of hot engine. General Description: The Genset Control Module is a microprocessor based control system which provides complete automatic control of standby generator set engines. Fuel solenoid and/or ignition control, cranking control, and audible alarm control are via heavy duty industrial type relay contacts. Engine temperature and oil pressure monitoring are obtained from engine mounted sensor contacts. Adjustable overspeed shutdown and crank termination control are provided internally via a frequency monitoring input terminal. This input signal may be obtained from any frequency source related to engine speed: distributor ignition pulses, magnetic pick-up, A.C. tachometer generator, alternator tachometer terminal, etc.

Technical Data Sheet A121A / A241A Specifications Input Voltage: Model A121A: 12VDC nominal, 16VDC max; transient and reverse polarity protected. (Typical: Pickup at 10VDC, Dropout at 6VDC.) Model A241A: 24VDC nominal, 32VDC max; transient and reverse polarity protected. (Typical: Pickup at 14VDC, Dropout at 9VDC.) Supply Current: 0.4A maximum plus alarm light burden. Relay Load Contacts: FS & CS: 10A at 28VDC, inductive; AR: 2A at 28VDC, resistive. Alarm Light Load: 150mA maximum each output (incandescent inrush is permitted.) Shutdown Input Contacts: 2 (See operating instructions for start-up override times.) Frequency Input: 80V RMS max. (See note 1.) Overspeed trip point is adjustable from; A121A: 40 to 800Hz. (Ignition / Alternator Pick-up) A121A2 / A241A: 350 to 1100Hz or 1750 to 5000Hz. (Alternator / Mag. Pick-up) A121A1 / A241A1: 430 to 1350Hz or 2380 to 6800Hz. (Alternator / Mag. Pick-up) Crank Disconnect Frequency: Internally fixed at 30% of the overspeed setting. Crank Control: Single-cycle crank limiter: continuous 48 sec. crank period (non-adjustable.) Cycle cranking: 5 cycles of 12 sec. crank and 12 sec. rest (non-adjustable.) Time Delays (optional): Delay on start from remote signal: 3 seconds (non-adjustable.) Delay on shutdown from remote signal: 3 minutes (non-adjustable.) Shielding: Internal EMI shielding provided. Ambient Temperature: -25 F to +140 F Finish: PC Board: Protected with moisture/fungus proof varnish. Chassis: Zinc plated / yellow dichromate. Cover: ABS plastic. Terminal Blocks: Industrial screw-terminal type. Note 1: Other models available for other frequencies and/or voltages. Consult factory with your specific requirements. Model Number Designation: A 1 2 1 A 0 Voltage (12VDC or 24VDC) Speed Sensing Frequency Input Range (see above: Frequency Input) N11325 County Highway Y, Clintonville, WI 54929 (715) 823-7770 (715) 823-7771 Fax www.bouchette.com

Technical Data Sheet A121A / A241A Dimensions N11325 County Highway Y, Clintonville, WI 54929 (715) 823-7770 (715) 823-7771 Fax www.bouchette.com

Operating Instructions GENSET CONTROL MODULE LEVEL 1 A121A / A241A Control Switch Inputs The following operator panel controls are wired into the microprocessor through the frontmounted terminal blocks: 1. Run/Stop/Auto Switch. a. Run position causes the engine to start and run immediately. b. Auto position allows the unit to be controlled via any remote single-pole dry-type contact (transfer switch, remote start switch, etc.). Contact closure causes the unit to start and run, while contact opening causes the unit to shut down. Also see Time Delay Select for time delay options. c. Stop position de-energizes the control module for immediate shutdown. 2. Lamp Test Push-Button. Energizes all alarm lights simultaneously. This feature is disabled with the Run/Stop/Auto selector switch in the Stop position, and has no other effect on unit operation. Relay Functions 1. Master Control Relay (FS). Operates the fuel solenoid, etc. 2. Cranking Control Relay (CS). Controls engine cranking functions. 3. Alarm Relay (AR). Provides contact (2-amp. maximum) for remote alarm indication, bell, etc. The alarm relay is energized for all engine fault conditions. A121A / A241A Operating Instructions Page 1 of 4

Operating Instructions Safety Shutdown Inputs 1. Low Oil Pressure (LOP) Shutdown. Monitoring of oil pressure begins 12-seconds after the unit starts and remains in effect until the unit is shut down (except as noted in section Microprocessor Program Notes.) Except as noted, closure of this contact while engine is running results in an engine fault shutdown and alarm with light indication. The LOP signal is derived from an oil pressure sensor switch mounted on the engine. 2. High Water Temperature (HWT) Shutdown. The engine coolant temperature sensor monitoring begins immediately with the start signal. However, if the water temperature is excessive prior to start, (i.e., heat soak after shutdown), the unit is permitted to start and the high temperature condition is permitted to exist for up to 60-seconds after the unit is running, before an engine fault shutdown and alarm with light indication occurs. If the high temperature condition is corrected within that time period, the microprocessor circuit reverts to normal monitoring. Except as noted, closure of this contact while engine is running results in an engine fault shutdown and alarm with light indication. The HWT signal is derived from a temperature sensor switch mounted on the engine. 3. Overspeed (OS) Shutdown / Adjustment. Overspeed shutdown protection is provided by a frequency sensing network within the control module. The trip point of the frequency network is screwdriver adjustable through the opening in the face of the control module as shown. Clockwise rotation increases the trip frequency and thereby, raises the shutdown speed. Exceeding this speed will result in an engine fault shutdown and alarm with light indication. Genset Control Module Face A121A / A241A Operating Instructions Page 2 of 4

Operating Instructions Cranking Control 1. Overcrank (OC) Protection. Two different cranking cycles are programmed into the control modules microprocessor: a. Single-Cycle Cranking Feature. This feature provides a single, non-adjustable, crank period of 48-seconds. Failure of the engine to start within that time results in an overcrank engine fault shutdown and alarm with light indication. b. Cycle Cranking Feature. The control module may be field-converted to the cycle cranking feature by grounding the CCI terminal on the control. This feature provide a series of five cranking cycles; each containing a 12-second crank period with a 12-second rest period. Failure of the engine to start by the end of the fifth crank period results in an overcrank engine fault shutdown and alarm with light indication. 2. Cranking Disconnect. The cranking termination speed is obtained from the frequency network within the control module. The microprocessor automatically sets the cranking termination speed at 30% of the selected overspeed trip value. 3. Loss of Frequency Signal. The microprocessor will detect an absence of frequency signal while cranking. After the first 12-seconds of cranking, the overcrank light begins a staggered flashing pattern to indicate there is no frequency signal input. If the cycle cranking feature (1.b above) was selected; the microprocessor automatically converts to the single-cycle cranking feature (1.a above). This conversion prevents the starter motor from re-engaging during the second crank cycle in the event the engine is already running. Also see section Microprocessor Program Notes. Time Delay Select Combination Delay-On-Start and Cool-Down timing feature: The control module may be fieldconverted to include this feature by grounding the TDI terminal on the control. This feature will delay the start-up of the engine for 3-seconds after the Remote Run contact is closed, and it will delay the shutdown of the engine for 3-minutes after the Remote Run contact is opened. This timing feature can be made active only in the Auto switch position, and still permits instantaneous manual starting in the Run switch position. Placing the selector switch in the Stop position provides instantaneous shutdown of the engine under all conditions. The start delay is intended to prevent unnecessary start-ups from momentary remote run signals, and the stop delay is intended to provide a cool-off running period for the engine after load removal. A121A / A241A Operating Instructions Page 3 of 4

Operating Instructions Microprocessor Program Notes Internal protection against loss of frequency input signal is programmed in after the unit has started normally. In the event the frequency goes to zero (engine runs out of fuel, frequency signal source fails, etc.), the LOP shutdown circuit is bypassed and a 12-second wait period is initiated. If the frequency returns within this time period, LOP monitoring resumes and operation continues normally. If frequency has not returned at the end of this time period, the engine oil pressure status is observed to determine whether the engine is actually running or stopped. If the engine has stopped, the cranking cycle will begin in an effort to re-start the engine. If the engine has not stopped (loss of input signal, etc.), the unit is shut down with an overcrank engine fault and alarm with light indication. Caution: Overcrank indication can mean a loss of frequency input signal during the previous run period. Attempting to re-start the engine without any frequency input signal can destroy the starter motor, which can cause serious personal injury. The frequency signal source is a key component in this system and must be checked out thoroughly whenever an overcrank shutdown occurs, since the control module only provides an indication of loss of signal during startup. Resetting A Fault Shutdown A shutdown with alarm, due to any fault condition, will prevent any subsequent operation of the generator set. The Run/Stop/Auto selector switch on the operator control panel must be momentarily placed in the Stop position to reset these functions. N11325 County Highway Y, Clintonville, WI 54929 (715) 823-7770 (715) 823-7771 Fax www.bouchette.com

Important Notice GENSET CONTROL MODULE LEVEL 1 & 2 Overspeed Selection Formula The Genset manufacturer must determine the overspeed (OS) trip point based on maximum allowable speeds for both the engine and generator. The following formula should be used to determine the OS trip frequency for any engine 1. Select a Genset Control model which OS frequency range includes the desired trip frequency. 1) All engines with magnetic pick-up sensing (recommended): OS Frequency = 30 D (number of teeth on ring gear) 2) All engines with belt-driven alternator sensing: OS Frequency = 15 D (number of alt. poles) (drive pulley diameter) (alt. pulley diameter) 3) All engines with flywheel-type alternator sensing: OS Frequency = 15 D (number of alternator poles) 4) Gasoline engines only, with distributor ignition sensing: OS Frequency = 15 D number of cylinders D = Speed Multiplier i.e. If OS is set at @ 72Hz (on 60Hz generator), then D = 1.2 (1.2 60Hz = 72Hz) 1 These formulae are for nominal 1800 RPM engines; for 3600 RPM engines, the calculated OS frequency should be doubled. N11325 County Highway Y, Clintonville, WI 54929 (715) 823-7770 (715) 823-7771 Fax www.bouchette.com

Important Notice GENSET CONTROL MODULE A121 / A122 Overspeed Set-Up Instructions STOP Before installing the Genset Control Module, the proper input frequency range needs to be selected as described below. Through a hole in the back of each control (as shown in diagram below), jumper wire(s) are used to select the input frequency range. Locate your model number on the following charts for the correct range settings. A GENSET CONTROL MODULE (BACK-SIDE VIEW) B Caution: When cutting jumper wires, do not allow ends of jumper wire to come in contact with other components or the chassis. Completely remove the jumper wire, or cut in the middle and separate ends about 1/8". N11325 County Highway Y, Clintonville, WI 54929 (715) 823-7770 (715) 823-7771 Fax www.bouchette.com

Important Notice OVERSPEED MODEL SELECTION A121 / A122 Available Models A121A1 A121B1 A121C1 A121CB1 A122A1 A122D1 A122E1 A241A1 A241B1 A241C1 A241CB1 A242A1 A242D1 A242E1 At engine overspeed, the Input Frequency is between: Typical Frequency Input Sources Magnetic Pick-up Alternator tachometer terminal Tachometer generator Cut these Jumper Wires 430-1350 Hz None 2380-6800 Hz A Only Available Models A121A2 A121B2 A121C2 A121CB2 A122A2 A122D2 A122E2 A241A A241B A241C A241CB A242A A242D A242E At engine overspeed, the Input Frequency is between: Typical Frequency Input Sources Magnetic Pick-up Alternator tachometer terminal Tachometer generator Cut these Jumper Wires 350-1100 Hz None 1750-5000 Hz A Only Available Models A121A A121B A121C A121CB A122A A122D A122E Typical Frequency Input Sources Alternator tachometer terminal Distributor low-voltage input terminal At engine overspeed, the Input Frequency is between: Cut these Jumper Wires 28-90 Hz None 78-240 Hz A Only 200-600 Hz B Only 250-800 Hz A and B N11325 County Highway Y, Clintonville, WI 54929 (715) 823-7770 (715) 823-7771 Fax www.bouchette.com

FREQUENCY SENSING FROM ALTERNATOR TACH. TERMINAL

FREQUENCY SENSING FROM MAGNETIC PICK-UP