Triton. Wet Barrel Ductile Iron. Fire Hydrants. Reliable Connections. operation / Maintenance manual. Inspection and Installation 2

Similar documents
Sentinel 250 Fire Hydrant

FIRE HYDRANTS. Wet Barrel Fire Hydrants

MUELLER. Super Centurion 350 Fire Hydrant. Reliable Connections. Inspection and Maintenance 2. Filling Oil Reservoir 3. Facing the Hydrant 4

MUELLER. Centurion Series Fire Hydrant. Centurion Super Centurion 200 Super Centurion 250. Reliable Connections. Background and Forward 2

24 and Larger Butterfly Valves

AVK SAUDI VALVES MANUFACTURING COMPANY

FIREFLO - MODEL F-06 INSPECTION, INSTALLATION & MAINTENANCE MANUAL. Item No.s/Description

740G Double Disc Check. Valve. Operation / Maintenance Manual. General Information 2. Installation/Operation 3

Sentinel 250 Fire Hydrant. Solid design and features to meet any municipal requirement.

720A Wafer & 821A Globe Style

Mueller Super Centurion 250 Fire Hydrant

Rectangular Butterfly Valve

of wet barrel hydrants, hydrant valves and hydrant tools.

SECTION 8 Fire Protection

Data Sheet Issue A

3" 20" Bonded Seat Butterfly Valves

720G Wafer and 821G Globe Style Silent Check Valves

740G Double Disc Check Valve

Super Centurion Hydrants Designed for efficient flow and outstanding, long-term reliability

VALVES, FIRE HYDRANTS, AND APPURTENANCES

OPERATION AND MAINTENANCE MANUAL 5-1/4 AMERICAN-DARLING B-84-B-5 FIRE HYDRANT

OPERATION AND MAINTENANCE MANUAL 5-1/4 AMERICAN-DARLING B-62-B-5 FIRE HYDRANT

MUELLER GAS. No-Blo Valve. Changers. Reliable Connections. General Information 2-3. Plugging Unit Assembly 4-5. Removing Old Valve 5-6

TABLE OF CONTENTS. 3 Outlet Stainless Steel Body. 3 Outlet Ductile Body. 2 Outlet Ductile Body 2 Outlet Bronze Body

AMERICAN AVK COMPANY AVK SERIES 24 - HIGH PRESSURE, WET BARREL HYDRANT FIELD MAINTENANCE AND INSTRUCTION MANUAL TABLE OF CONTENTS

AMERICAN AVK COMPANY AVK SERIES 67 - HIGH PRESSURE, POST/FLUSHING HYDRANT FIELD MAINTENANCE AND INSTRUCTION MANUAL TABLE OF CONTENTS

SECTION VIII. (Sub-section 430) Wastewater Valves and Appurtenances. 1. General thru Gate Valves thru 430-3

American Flow control 5 1/4 B-62-B-5

AWWA C504. Double Eccentric AWWA C504

CLOW CANADA - M-67 HERITAGE BRIGADIER FIRE HYDRANT SPECIFICATION

AMERICAN FLOW CONTROL 5 1/4 B-84-B-5 FIRE HYDRANT

AMERICAN FLOW CONTROL 5 1/4 B-62-B-5 FIRE HYDRANT

mh-valve.com 129 HYDRANT AWWA C502 NSF 61/372 CERTIFIED UL LISTED FM APPROVED 250 PSI WORKING PRESSURE 10-YEAR LIMITED WARRANTY

American Flow control 5 1/4 b-84-b-5

MEDALLION HYDRANT. clowvalve.com AWWA C502 UL LISTED FM APPROVED NSF 61/372 CERTIFIED 250 PSI WORKING PRESSURE 10-YEAR LIMITED WARRANTY

ADMIRAL HYDRANT. clowvalve.com

Mueller 300 Ball Valves Industry-leading 300psi low lead ball valves

5 1/4 AMERICAN-DARLING B-84-B-5 FIRE HYDRANT BY AMERICAN FLOW CONTROL

Lineseal Butterfly Valves 150B, 250B, & 350B Class; Sizes 3-48

MUELLER Hydrant Security Device

MUELLER Super Centurion fire hydrants

HP250II AND HP250 BUTTERFLY VALVES Engineering Creative Solutions for Fluid Systems Since 1901

MILLCENTRIC FULL/100% POR T ECCENTRIC PLUG VALVE

AWWA SWING CHECK VALVES. Engineering Creative Solutions for Fluid Systems Since 1901

Installation & Operation Manual

ISO RESILIENT WEDGE GATE VALVE. Engineering Creative Solutions for Fluid Systems Since 1901

Fisher RSS Lined Globe Valve

PRODUCT MANUAL 5-1/4 AMERICAN-DARLING B-84-B-5 FIRE HYDRANT

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

5 1 /4 PACER. It s AMERICAN What We Know. DARLING MARK 73 2 FIRE HYDRANT AMERICAN FLOW CONTROL WATEROUS FIRE HYDRANT

CUSTOM COMBINATION AIR VALVE

BALL VALVES. Industry-Leading 300psi Low Lead Ball Valves

SUB WATER DEPARTMENT STANDARD CONSTRUCTION SPECIFICATIONS TABLE OF CONTENTS SECTION WATER DISTRIBUTION VALVES

24-48 HP250II Butterfly Valve. Operation and Maintenance Manual. Job Name: Contractor: Date: Document #: 2448HP250OOOM Revision Date: 1/10/11

DeZURIK " BAW AWWA BUTTERFLY VALVES WITH EPOXY-RETAINED SEAT

K81-D FIRE HYDRANT GUARDIAN AWWA C502 NSF YEARS. For Generations CERTIFICATIONS ISO 9001 ISO BS OHSAS

VSI, LLC SERIES 2100 RESILIENT SEATED BUTTERFLY VALVES INSTALLATION, OPERATION AND MAINTENANCE MANUAL

PRODUCT MANUAL 5-1/4 WATEROUS PACER FIRE HYDRANT

Fisher RSS Lined Globe Valve

K81-DD FIRE HYDRANT GUARDIAN AWWA C502 NSF YEARS. For Generations CERTIFICATIONS ISO 9001 ISO BS OHSAS

September 2012 / M&H C502 / Model 129

FIRE PROTECTION PRODUCTS

Trend Hydrants. Installation, Operation, Maintenance and Overhaul Instructions. Table of Contents. Illustrations. Tables H /16/10 12/04/95

FLOAT CONTROL VALVES

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

2" - 24" OS Series Butterfly Valves. Operation and Maintenance Manual. Job Name: Contractor: Date:

Crispin Valves Operating Guide. Crispin

Water Distribution Solutions

3-20 2FII & Groundhog Bonded Seat Butterfly Valve. Operation and Maintenance Manual. Job Name: Contractor: Date:

SECTION GENERAL-DUTY VALVES FOR PLUMBING PIPING

AMERICAN AVK COMPANY AVK SERIES HIGH PRESSURE, MODERN, DRY BARREL HYDRANT FIELD MAINTENANCE AND INSTRUCTION MANUAL TABLE OF CONTENTS

Baumann Series Flexsleev Control Valve Instructions

Water Distribution Solutions

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

INDEX WATEROUS 5-1/4 IN. PACER FIRE HYDRANT

SECTION VALVES AND OPERATORS

Cast Iron Liquid Relief Valves

AMERICAN FLOW CONTROL 4 3/4 WATEROUS TREND FIRE HYDRANT


Val-Matic 1-4 Combination Air Valve (Single Housing Type)

161 Series Pilots for Pilot-Operated Pressure Reducing Regulators

SOLENOID CONTROL VALVE

ALTITUDE CONTROL VALVES FOR ONE WAY FLOW

AMERICAN FLOW CONTROL 3-16 SERIES 2100 RESILIENT SEATED CHECK VALVE

HARMSCO Hurricane Swing Bolt Water Filters Models: HUR 1X170FL, HUR 3X170FL HUR 5X170FL, & HUR 8X170FL

SECTION 17 FIRE HYDRANT ASSEMBLIES General

Type 289P Pilot-Operated Relief Valve

AMERICAN FLOW CONTROL 4 3/4 WATEROUS TREND FIRE HYDRANT

Harlingen Water Works System Approved Products List For Subdivisions. January 11, 2005

Specifications For Valve Insertion System

INSTALLATION GUIDE. Model #GB1 20/25 GPM Grease Interceptor For Indoor Use. Contents

Baumann Way Control Valve

Herpteraium SECTION VALVES GENERAL

visit us online at

Sweetwater Authority Fire Hydrant Maintenance Program Standards and Procedures

type 122a three-way Switching Valve

AMERICAN AVK COMPANY AVK SERIES HIGH PRESSURE, NOSTALGIC, DRY BARREL HYDRANT FIELD MAINTENANCE AND INSTRUCTION MANUAL TABLE OF CONTENTS

PRESSURE REDUCING CONTROL VALVE

PRESSURE REDUCING CONTROL VALVES

Transcription:

operation / Maintenance manual MUELLER TAble of contents PAGE Triton Inspection and Installation 2 Installation and Testing 3 Wet Barrel Ductile Iron Maintenance Instructions 4 Parts 5 Notes 6-7 Fire Hydrants TM Reliable Connections International Division 6125 Preservation Drive, Suite 200 Chattanooga, TN 37416 USA Phone: +1.423.490.9555 UK Office: +44 1438 487410 Singapore Office: +65 6816 3088 Dubai Office: +971 4 214 6640 www.mueller-international.com international@muellercompany.com The following guidelines conform to AWWA M17, standard for the Installation, Field Testing, and Maintenance of Fire Hydrants, except as modified.

Inspection and Installation General inspection Inspection Prior to installation, hydrants must be inspected at the time of delivery to ensure there is no damage related to shipping and handling. Upon delivery, verify compliance with required specifications to include: Correct model hydrant Correct operating nut size and shape on stem & cap Correct size outlet nozzles Correct inlet flange bolt pattern The hydrant will arrive with each valve in the closed position. Each valve stem should be cycled from closed to full open and back to closed to ensure no damage occurred during shipment. If the stem is difficult to operate, repairs are needed. All external bolts and nuts should be tight. Each hydrant is shipped with an inlet flange cover in place. If this cover is damaged or has been removed, visually inspect the inside of the hydrant from the inlet flange to ensure no foreign material or debris has entered the hydrant Recover the inlet flange until time of installation. All inspected hydrants that will not be immediately installed should have valves closed, nozzle caps secured, and inlet covered. Installation hydrant general components Proper installation and selection of the hydrant location will ensure many years of service with minimal maintenance. A primary consideration to prevent damage to the hydrant while in service is locating the hydrant to avoid impact by vehicles and roadway equipment. Where a code or Municipal specification for curb set-back is not present, the recommended curb set-back (AWWA M17) is 2 ft minimum from the face of the curb to the nearest point on the hydrant. In rural areas where no curb is present, use a larger set-back, ensuring the hydrant is accessible to firefighting equipment. When installing a Mueller Tell-Tail TM break check traffic valve, a concrete thrust collar with minimal dimensions of 2 feet diameter and 6 inches thick must be installed at the ground bury line to absorb the potential shock of a traffic impact. Poor loadbearing soil conditions may warrant a larger thrust collar. The inlet main should be supported by firm footings to ensure settling or sinking of the hydrant does not occur. Connect the hydrant to a water main intended to provide adequate fire hydrant flow volume. Refer to AWWA Nozzle Cap Outlet Nozzle Nozzle Cap Cap Op Nut Inlet Flange C600, Standard for Installation of Ductile-Iron Water Mains and Their Appurtenances, and local fire codes for fire authority requirements. Always ensure an isolation valve is located between the hydrant and the main to permit the water supply to be cut-off for maintenance. Install the hydrant as plumb (vertical) as possible, allowing adequate clearance at the ground bury line MUELLER M-4060 Ductile Iron Hydrant Op Nut on Stem Stem Insert Hydrant Body to access flange bolts. The pumper outlet nozzle should face the curb without obstructions by light poles, signs, benches or other obstacles that may prevent direct access to the pumper nozzle from the street. Additionally, there should be no obstructions that prevent quick access and operation of nozzle caps and stems. 2

Installation and Testing Installation (continued) Following installation, the hydrant should be flushed to remove any foreign material and disinfectant chemicals. When closing the valves of newly installed hydrants, watch for debris or objects that may become wedged in the valve opening. Also after installation of the hydrant, ensure all caps are tight enough to prevent removal by hand and the auxiliary valve is in the full open position. Initiate a record of the hydrant to include the following essential information: location of hydrant, location of auxiliary valve, date of installation, type & model hydrant, size of nozzle outlet & op nuts and, if available, flow data. Testing Pressure Testing at Main Line Pressure The following procedure is for pressure testing a hydrant for leaks at line pressure following maintenance repairs or the installation of a new hydrant. 1. With the auxiliary valve closed, remove the top nozzle cap and slightly open the top valve. 2. Slowly open the auxiliary valve and allow any air in the system to escape from the top nozzle valve opening. 3. After all the air has escaped from the hydrant (evidenced by water coming out of the top nozzle outlet), close the top outlet valve and completely open the auxiliary valve.! CAUTION: Trapped air in a water system can become compressed and present a safety hazard. 4. With all caps removed and the hydrant pressurized to line pressure, visually inspect for leaks at the flange joint, outlet nozzles, valve discs, and stem inserts around the stem. Note: Before leaving the factory, all hydrants are pressure tested at 500psig (standard model) or 700psig (HP model). 5. If leaks are observed, repair or replace faulty component and re-test to ensure hydrant is leak free. Testing at Pressures Above Main Line Pressure The following procedure is for pressure testing a hydrant above line pressure. This test may be performed to verify that hydrant is leak free at the rated working pressure (i.e., 250 or 350psig). 1. With all nozzle caps removed, connect a water pressure test pump to a lower outlet nozzle. 2. Ensure there is no trapped air in the hydrant by slightly opening top valve. Close valve after all air has escaped and only water comes out of top nozzle outlet. 3. Close the auxiliary valve to isolate hydrant and open the hydrant outlet valve connected to the test pump. 4. Following the pump manufacture s directions, pump to the required test pressure.! CAUTION: Trapped air in a water system can become compressed and present a safety hazard. 5. With all caps removed, and the hydrant pressurized, visually inspect for leaks at the flange joint, outlet nozzles, valve disc s, and stem inserts around the stem Note: Before leaving the factory, all hydrants are pressure tested at 500psig (standard model) or 700psig (HP model). 6. If leaks are observed, repair or replace faulty component and re-test to ensure hydrant is leak free. 7. Close outlet valve at test pump and open auxiliary valve to return hydrant to service. 3

Maintenance Routine Maintenance To ensure the hydrant is in proper working condition when needed, a routine inspection and maintenance program should be implemented and followed. Hydrants should be inspected and exercised at least annually. A record should be kept on the performance of routine maintenance, findings during inspection, and recommended actions. Flow measurements should be periodically recorded for each hydrant (refer to AWWA M17 for flow measurement procedures). Inspection and maintenance crew should carry spare parts such as chains and caps to perform simple repairs. Local fire code and fire authority guidelines should be followed at all times. The following guidelines should be carried out by authorized and trained personnel. 1. With caps removed, visually inspect hydrant inlet flange joint, outlet nozzles, valve seats, and stem inserts for leaks. If leaks are present, attempt to correct the leak by tightening the component. If leak is not resolved, mark hydrant for follow-up repairs. 2. Inspect cap chains and cap rings for binding. Cap rings should rotate freely. 3. Inspect outlet nozzle threads for damage or foreign material buildup. If needed, clean threads and recoat with a non-toxic, anti-seize lubricant. Clean cap threads and ensure cap vent hole is open. 4. Note any paint condition that may require follow-up coating. For ductile iron hydrants, there should be no bare metal exposed. 5. Close auxiliary valve to isolate hydrant. 6. With hydrant isolated from line pressure, fully open and close each valve two times, or until valve stem moves freely. The valve stem and mating components are made of corrosion resistant material. Some hard water conditions will cause deposits to accumulate. Exercising the stem will clear the deposit. 7. Visually inspect the valve disc from the outlet nozzle opening. The disc material should not be indented by the seat more than 1 /8. If damage has occured to the disc or excessive indention is observed, mark hydrant for follow-up repairs. 8. Close all hydrant valves, leaving the top outlet valve slightly open to allow air to vent when water is restored to the hydrant. 9. Slowly open the auxiliary valve. 10. When all air has evacuated the hydrant (evidenced by water coming out of the outlet nozzle), close the hydrant outlet valve. 11. Attach a short length of hose to allow water to run onto the street, or attach a diffuser nozzle. Operate hydrant valve through one full cycle. Repeat for each outlet nozzle. Use caution to avoid soil erosion. 12. Close each valve and tighten each nozzle cap so that the caps may not be removed by hand. 13. Ensure the auxiliary valve is fully opened. 14. Record inspection and required follow-up actions (if needed). 15. Return hydrant to service. 4

Parts 15 7 6 11 20 13 2 12 16 4 5 14 8 3 17 10 18 1 Replacement Parts 9 19 ID Description material 1 Hydrant Body Ductile Iron 2 Nozzle Insert Brass ASTM B584 3 Hose Cap Cast Iron 4 Hydrant Stem Brass ASTM B584 5 Stem Locknut Brass ASTM B584 6 Beveled Hydrant Disc BUNA-N 7 Hydrant Disc Locknut Brass ASTM B584 8 Stem Insert Brass ASTM B584 9 Pent Nut Brass ASTM B584 10 Pent Nut Retainer Brass ASTM B62 11 Hydrant Disc Holder Brass ASTM B584 12 Nozzle Gasket Neoprene 13 Nozzle Insert O-Ring BUNA-N 14 Stem Insert O-Rings BUNA-N 15 Locknut Retainer Pin Stainless Steel 16 Stem Locknut Retainer Screw Stainless Steel 17 Stem Seal O-Rings BUNA-N Rubber 18 Chain Ring Steel 19 Chain Steel 20 S-Hook Steel 5

Notes 6

Notes 7

TM Reliable Connections International Division 6125 Preservation Drive, Suite 200 Chattanooga, TN 37416 USA Phone: +1.423.490.9555 UK Office: +44 1438 487410 Singapore Office: +65 6816 3088 Dubai Office: +971 4 214 6640 www.mueller-international.com international@muellercompany.com Copyright 2017 Mueller Co., LLC. All Rights Reserved. The trademarks, logos and service marks displayed in this document herein are the property of Mueller Co., LLC, its affiliates or other third parties. Products marked with a section symbol ( ) are subject to patents or patent applications. For details, visit www.mwppat.com. These products are intended for use in potable water applications. Please contact your Mueller Sales or Customer Service Representative concerning any other application(s). Form 13830-03/17