Rittal RiLine60. The fascinating 60 mm system of the future assembly-friendly, time-saving, individual and modular. including.

Similar documents
NEW. Rittal RiLine60 UL 508. The fascinating 60 mm system of the future

Power distribution components

RiLine mm system technology for the global market

Technical System Catalogue RiLine

Perfection in Technology Packaging

System Benefits Should you have any further questions, please contact our UL hotline at: +49 (0)9563/ Connection Technology EQUES Technology

60mm-System classic 630A (800A) / 2500A

Rittal Product Overview 2008

Technical System Catalogue Ri4Power

MANUAL 2018 AL 2018 U AN M

Rittal CM Compact System Enclosures

INNOVATION IS OUR POWER.

THE NEW TS IT RACK 8

Product Data For FARNELL

The Rittal Flex-Block base/plinth system

Busbar Systems CHAPTER11

3NP1 Fuse Switch Disconnectors up to 630 A

Distribution Blocks & Bus-bar Solutions

Product Data For FARNELL

Power distribution. RiLine fuse elements. NH fuse-switch disconnectors, size 000. For mounting plate assembly

Rittal console systems...

Power distribution. General remarks

CrossBoard. The new basic system

30Compact 200 A / 360 A

BETA Switching Switches and Light Indicators

Viking 3 - Screw connection Disconnect terminal blocks

3/2 Introduction. Unequipped Distribution Boards (Flat Pack) 3/6 8GK1 surface-mounting distribution boards

Type Pack size Weight Part no. kg/100 units for undrilled busbars 30, 40, 50, 60 x 10. Dimensions Current Pack size Weight Part no.

SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A

VSMeasy Wiring Systems and Motor Starter Combinations

Flexible. Intelligent. Trendsetting.

Electronic Circuit Breaker ESS20-0..

8WH2 Spring-Loaded Terminals

Horizontal fuse disconnects

Electrical connection systems

DOUBLE-LEVEL TERMINAL BLOCKS SRKD SSLD

XL 3 -N SimPly, EfficiEnt And SAfE. 3 - PHASE distribution boards up to 250 A

IMRAK Freestanding Cabinets

CENTRE FEED UNIT UP TO 4000A. Safety

Industrial Enclosures

PANEL PANEL MOUNTING COMPONENTS

e n e r g i a HULANICKI BEDNAREK sp. z o.o. HABeR-M Switchgear system rated up to 1600A 1

SAK A real classic that became synonymous with connection technology

2013 JEAN MÜLLER Products

8WH2 Spring-Loaded Terminals

GAE MCC Modular-C. Catalogue Standardized Motor Control Centres. PT Guna Era Manufaktura

Reliably Switching Highest Currents up to 2200 A

Plenty of space for intelligent solutions.

CABINETS AND ENCLOSURES. XL³ 400 and XL³ 800 GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

MR - MEDIUM RATING A

Reliably Switching Highest Currents up to 2000 A

Pixus Technologies Catalog

The Complete Range. Drawing of the NH Fuse-Switch, 3-pole switching, horizontal design for busbar supply on a 60 mm busbar systems

185mm-System power 2500A. Expertise

Mechanical engineering partner

Datasheet. System pitch mm (0.400 inch) - SU/BU BUZ 10.16HP/02/180F AG BK BX

LED system light Sensationally bright

stainless steel Cover hinge The cover hinge is simply screwed to the box protection channel and to the edge fold. Model No. KL

3 - Protection components Motor circuit-breakers

MULTIBLOC 2.RST8 Size 2, 400A, 690VAC, Design for bus bar installation, Triple Pole

- 1 - General ordering data Order No

Adak Behin Niroo. co.com

CRITO Connection technology. Double and triple T and TCC section busbars

PANEL-MOUNTING COMPONENTS SWITCHGEAR. Technology

Outdoor system solutions

LV switch-disconnectors. Interpact Merlin Gerin 40 to 2500 A. Catalogue. We do more with electricity

MULTIBLOC 3.ST8 Size 3, 630A, 690VAC, Design for Bottom Fitting, 3-,4-pole

Outdoor system solutions

Datasheet. BL/SL 5.08 series BLF 5.08/02/180 SN OR BX

Fuse switch disconnectors

More efficiency with the base/plinth system VX

Control Circuit Protection

8WH6 ipo Installation Terminals

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

Gemini switchboards for all applications

MODE - Multiple Occupancy Distribution Equipment Selection guide for low voltage indoor distribution up to 500A

FUSERBLOC CD. The universal Fuse Combination Switch FROM 20 TO 1250 A. Industrial Switching & Protection Systems

ACCESSORIES FOR SZE2 CABINETS

ENYSTAR Load Centers up to 250 A

EXPLOSIONPROOF PROTECTION SIMPLIFIED PLEXPOWER LIGHTING AND POWER PANELBOARDS

Key features. DESIGNS: - Conservator type - Hermetically sealed

It s as simple as A,B,C...

MULTIBLOC 1.RST8 Size 1, 250A, 690VAC, Design for bus bar installation, Triple Pole

SCREW-TYPE DISTRIBUTION BLOCKS

SION vacuum circuit-breaker.

TeSys GV2 - GV3 Manual Starters and Protectors

Page 12-2 Page Page Page DC FUSES FOR PHOTOVOLTAIC APPLICATIONS 10x38mm, IEC class gpv Rated current: 20A Rated voltage: 1000VDC.

Motor Starter Reverse MSR22-FBP

Distribution Boards AT/U Series

Circuit-Breaker Design

Miniature Circuit Breaker

Fuse holders and fuses

Main catalogue. SNK Series Terminal Blocks Accessories Marking Solutions

Snap-in covers I Voltage taps

smissline Description

SPECIFICATION GUIDE-IMRAK

ype UP T Busplugs Low Voltage Switchboard Equipment

Low Voltage Assemblies

Fuse switch disconnectors

Polycarbonate and ABS enclosures with quick release lid screws CT series

Transcription:

Rittal RiLine60 including innovations 2007 The fascinating 60 system of the future assembly-friendly, time-saving, individual and modular R

Rittal RiLine60 perfection in a 60 system Time-saving assembly, versatile applications and individual modularity are the winning features of the new Rittal RiLine60 busbar system. The Rittal system success story continues. Innovative products combined with contemporary design and outstanding safety technology. 2 Rittal RiLine60

Rittal RiLine60 busbar systems from page 4 Flat bar systems up to 800 A 3-pole...8 3-pole (UL 508)... 12 4-pole... 48 Rittal PLS busbar systems up to 800 A/1600 A 3-pole... 10 3-pole (UL 508)... 13 4-pole... 50 Connection systems from page 14 Connection adaptor 3-pole...14 4-pole... 52 Connection clamps/system covers... 16 Component adaptors from page 18 OM adaptors 32 A/65 A with tension spring clamp... 22/23 25 A (Premium adaptor)... 22 25 A/32 A/40 A/65 A with connection cables... 24/25 OT adaptors 32 A/65 A with tension spring clamp... 26 25 A (Premium adaptor)... 26 25 A/32 A/65 A with connection cables... 27 OM supports (without contact system)... 28 OT supports (without contact system)... 29 Component adaptors 100 A... 32 Circuit-breaker component adaptors 125 A/160 A/250 A/630 A... 32/33 Circuit-breaker component adaptors 160 A/250 A (4-pole)... 54 Multi-functional component adaptors from page 34 12 A/25 A... 35/36 40 A... 37 Fuse components from page 38 Bus-mounting fuse bases... 40 NH fused isolators, size 00... 42 NH on-load isolators, size 000... 43 NH bus-mounting on-load isolators, size 00 to size 3... 44 47 from page 55 Busbars and accessories... 63 65 Laminated copper bars and accessories... 65/66 Technical details from page 67 Short-circuit resistance diagrams... 68 70 Rated currents of busbars... 71 Busbar systems UL 508... 72 Allocation of switchgear... 75 NH devices... 80 Laminated copper bars... 85 List of model numbers... 86 Index... 87 Rittal RiLine60 3

Rittal RiLine60 Time-saving and individual For individual configuration, tailored to the latest switchgear concepts: New, uniform system base with five lines up to 1600 A New base tray system with an ingenious dual function: All-round encapsulation for uninterrupted contact hazard protection Innovative attachment of component adaptors User-friendly range of busbar connection adaptors New component adaptor for motor starters up to 65 A Innovative in terms of modularity, component configuration and connection system Rapid, predominantly screwless assembly High level of security, thanks to the support frame system: The busbars are always covered for contact hazard protection Flexible servicing with the system operational, thanks to a connector and modular support frame system for motor circuits New circuit-breaker adaptor for MCCB up to 630 A 1. Simply insert the bars from the front, secure and it s done! The integral slide adapts automatically to the respective bar width. The mounting surface (top edge of the busbar) to the mounting level is identical for all installed bar crosssections. 4 Rittal RiLine60

Simply insert the bars from above, secure, and it's done! This is how quickly you can mount eight flat copper crosssections in one support, with no need for any inserts! The new base tray has an ingenious dual function: Contact hazard protection and mounting rail for the new OT adaptors. The innovative separation of component adaptor and support frame in conjunction with connection using connector bushes ensures easier assembly and servicing. 2. 3. 4. The metal-reinforced base tray affords perfect protection to the mounting level, while at the same time providing the attachment basis for component adaptors with location system (OT adaptors). Locate from above, and snap into position from below and that s it! There is no need to change the contact feet to 5 or 10 busbar thickness. Configure the removable support frame with the chosen motor starter combination, and prepare the wiring of the main and auxiliary contacts using connectors. This makes the final stage of assembly or replacement unbeatably simple and fast. Snap the populated support frame into the component adaptor and latch, insert the prepared connectors and it s done! This allows servicing to be carried out whilst the system is operational, because even with the device removed, there is still complete contact hazard protection from the live busbars. Rittal RiLine60 5

Simply insert the bars and it s done! Busbar support for flat bars with integral crosssection adaptation Height compensation with 5 bars is achieved via slides. An integral locating block automatically adapts to widths of 15, 20, 25 or 30. No other accessory required. Busbar supports are available with mounting holes on the outside or inside. For flat copper and Rittal PLS section Perfect contact hazard protection, thanks to all-round encapsulation From now on, even with flat bar systems, the base tray, cover section and end cover form the ideal unit for optimum contact hazard protection. Component adaptors simply clip onto the base tray The new dual-purpose base tray: Contact hazard protection and punched rail for the Rittal RiLine60 component adaptor with location system (OT adaptors). Rittal RiLine60

New, innovative mounting benefits: The bars in rectangular and Rittal PLS format are simply inserted into the respective support. The system configuration, comprised of the support, base tray and busbars, creates new safety and functional units with identical system dimensions. Rittal PLS busbar support in a new functional design By inserting the bars and securing with a new locking system, assembly becomes much faster and easier. The tried-and-tested stepping of the Rittal PLS special busbar sections 800 A and 1600 A has been preserved, as has the unrestricted top-mountability of the PLS busbar support with power distribution components. Free positioning of the support makes planning easier, offers greater stability where necessary, and utilises the space more effectively. For flat copper and Rittal PLS section Versatile busbar connection adaptor Integral busbar connection adaptor line with a revolutionary design and impressive connection properties: Variants up to 800 A with handling-friendly box terminal for direct connection of round conductors. Variants available with feed-through function. Short circuit-protected, shielded routing of the contact tracks. Modern enclosure design with protection category IP 2X and unique slide latching of the cover. Rittal RiLine60

Rittal RiLine60 busbar systems 800 A (60 ) Busbar supports (3-pole) 3 1 3 2 4 5 6 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Short-circuit protection diagram, see page 68. Technical information for the calculation of rated currents, see page 71. 1 With attachment holes on the outside 2 With attachment holes on the inside Design Packs of 1 With external attachment 2 Internal attachment Page Number of poles 3-pole 3-pole Bar centre distance 60 60 For busbars E-Cu Tightening torque Assembly screw (M5 x 16) Cover attachment 12 x 5/10 1), 15 x 5 30 x 10 3 5 Nm 1 3 Nm 3 5 Nm 1 3 Nm 4 9340.010 9340.000 3 End covers for contact hazard protection on the sides 2 9340.070 9340.070 Spacers for SV 9340.000/.010 12 9340.090 9340.090 55 1) If 12 x 5/10 busbars are used, the spacer SV 9340.090 is additionally required. Busbars E-Cu To DIN EN 13 601. Length: 2400 /bar. Dimensions Packs of Page 12 x 5 6 3580.000 12 x 10 6 3580.100 15 x 5 6 3581.000 15 x 10 6 3581.100 20 x 5 6 3582.000 20 x 10 6 3585.000 25 x 5 6 3583.000 30 x 5 1) 6 3584.000 2) 30 x 10 1) 6 3586.000 2) Busbar cover section (length 1 m/each) 10 3092.000 63 Busbar connector for E-Cu 4 12 x 5 15 x 10 (single connection) 3 9350.075 64 5 20 x 5 30 x 10 (single connection) 3 9320.020 64 6 20 x 5 30 x 10 (bayed connection) 3) 3 9320.030 64 1) Other busbar lengths, see page 63. 2) Tin-plated version available on request. 3) From enclosure to enclosure. Busbar connection adaptor Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 8 Rittal RiLine60

Rittal RiLine60 busbar systems 800 A (60 ) System components (3-pole) 1 Base tray For rear contact hazard protection of the flat bar assembly. Cover section 2 May be cut to length as required; for clip-on mounting to the base tray. 1 2 Length (L) Packs of 500 2 9340.100 700 2 9340.110 900 2 9340.120 1100 2 9340.130 Length (L) Packs of 700 2 9340.200 1100 2 9340.210 Base tray and cover section Thermally modified hard PVC. Continuous operating temperature max. 91 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Note: If the cover section is mounted from the front, the support panel (SV 9340.220) is needed for stability. Base tray infill For rear contact hazard protection when connecting the busbars from enclosure to enclosure. Packs of 2 9340.140 Thermally modified hard PVC. Continuous operating temperature max. 91 C. Fire protection corresponding to UL 94-V0. Supply includes: Assembly parts. Colour: RAL 7035 Base tray reinforcement For clipping into the base tray. Required when using OT adaptors or supports, see page 26/27 and 29. Length (L) Packs of 500 2 9340.150 1000 2 9340.160 Aluminium Note: Self-tapping screws (Model No. SZ 2487.000) for attaching the base tray reinforcement to the mounting level, see Rittal main catalogue. Support panel for cover section To prevent side access to the cover section. The support panel also provides additional stability. Packs of 5 9340.220 Polyamide (PA 6.6). Continuous operating temperature max. 105 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Busbar connection adaptor Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 Rittal RiLine60 9

Rittal RiLine60 busbar systems 800/1600 A (60 ) PLS busbar supports (3-pole) 3 1 3 2 4 5 6 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Short-circuit protection diagram, see page 68. Technical information for the calculation of rated currents, see page 71. 1 Rittal PLS 800 2 Rittal PLS 1600 For Rittal system Packs of 1 PLS 800 2 PLS 1600 Number of poles 3-pole 3-pole Bar centre distance 60 60 Tightening torque Assembly screw (M6 x 20) Busbar anti-slip guard 3 5 Nm 0.7 Nm 3 5 Nm 0.7 Nm 4 9341.000 9342.000 3 End covers for contact hazard protection on the sides 2 9341.070 9342.070 PLS special busbars made from E-Cu For Rittal system Packs of PLS 800 PLS 1600 Page Cross-section 300 2 900 2 Bar thickness 5 10 Length For enclosure width 495 600 1) 3 3524.000 2) 3527.000 2) 695 800 1) 3 3525.000 2) 3528.000 2) 895 1000 1) 3 3525.010 2) 3528.010 2) 1095 1200 1) 3 3526.000 2) 3529.000 2) 2400 variable 1 3509.000 2) 3516.000 2) 4 PLS busbar connector (single connection) 3 3504.000 3514.000 64 5 PLS busbar connector (bayed connection) 3) 3 3505.000 3515.000 64 6 PLS expansion connectors 4) 3 9320.060 9320.070 65 1) For Rittal TS 8/ES enclosure systems. 2) To order tin-plated version, please add extension.2x0 to the Model No. Delivery times available on request. 3) From enclosure to enclosure. 4) Two PLS rail connectors (single connection) are required to fit one expansion connector. Busbar connection adaptor Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 10 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) System components (3-pole) 1 2 1 Base tray For rear contact hazard protection of the PLS busbar assembly. Length (L) Packs of For system PLS 800 PLS 1600 500 2 9341.100 9342.100 700 2 9341.110 9342.110 900 2 9341.120 9342.120 1100 2 9341.130 9342.130 Height (H) 32 43 Cover section 2 May be cut to length individually, for clip-on mounting to the base tray for PLS system 800 A and 1600 A. Length (L) Packs of 700 2 9340.200 1100 2 9340.210 Base tray and cover section Thermally modified hard PVC. Continuous operating temperature max. 91 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Note: If the cover section is mounted from the front, the support panel (SV 9340.220) is needed for stability. Base tray infill For rear contact hazard protection when connecting the busbars from enclosure to enclosure. Thermally modified hard PVC. Continuous operating temperature max. 91 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 For system Supply includes: Assembly parts. Height (H) Packs of PLS 800 32 2 9341.140 PLS 1600 43 2 9342.140 Base tray reinforcement For clipping into the base tray. Required when using OT adaptors or supports, see page 26/27 and 29. Aluminium Note: Self-tapping screws (Model No. SZ 2487.000) for attaching the base tray reinforcement to the mounting level, see Rittal main catalogue. Length (L) Packs of For system PLS 800 PLS 1600 500 2 9341.150 9342.150 1000 2 9341.160 9342.160 Support panel for cover section To prevent side access to the cover section. The support panel also provides additional stability. Packs of 5 9340.220 Polyamide (PA 6.6). Continuous operating temperature max. 105 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Busbar connection adaptor Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 Rittal RiLine60 11

Rittal RiLine60 busbar systems UL 508 (60 ) Busbar supports for feeder circuits 700 A (3-pole) 2 1 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Short-circuit protection diagram, see page 70. Note: Data given in accordance with UL may deviate from IEC data, see page 74. 1 With attachment holes on the inside Design Packs of 1 Internal attachment Page Number of poles 3-pole Bar centre distance 60 For busbars E-Cu 15 x 5 30 x 10 Tightening torque Assembly screw (M5 x 16) Cover attachment 3 5 Nm 1 3 Nm 4 9340.050 2 End covers for contact hazard protection on the sides 2 9340.070 Base tray 9 Cover section 9 Base tray infill 9 Base tray reinforcement 9 Support panel 9 Busbars E-Cu To DIN EN 13 601. Length: 2400 /bar. Dimensions Rated current max. A Packs of Page 15 x 5 175 6 3581.000 15 x 10 350 6 3581.100 20 x 5 230 6 3582.000 20 x 10 465 6 3585.000 25 x 5 290 6 3583.000 30 x 5 350 6 3584.000 1) 30 x 10 700 6 3586.000 1) Busbar cover section (length 1 m/each) 10 3092.000 63 1) Tin-plated version available on request. Connection adaptor Page 14/15 OM/OT adaptors Page 24/25, 27 OM/OT supports Page 28/29 Component adaptors Page 32/33 12 Rittal RiLine60

Rittal RiLine60 busbar systems UL 508 (60 ) PLS busbar supports for feeder circuits 700/1400 A (3-pole) 3 1 3 2 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Short-circuit protection diagram, see page 70. Note: Data given in accordance with UL may deviate from IEC data, see page 74. 1 Rittal PLS 800 2 Rittal PLS 1600 For Rittal system Packs of 1 PLS 800 2 PLS 1600 Page Number of poles 3-pole 3-pole Bar centre distance 60 60 Tightening torque Assembly screw (M6 x 20) Busbar anti-slip guard 3 5 Nm 0.7 Nm 3 5 Nm 0.7 Nm 4 9341.050 9342.050 3 End covers for contact hazard protection on the sides 2 9341.070 9342.070 Base tray 11 Cover section 11 Base tray infill 11 Base tray reinforcement 11 Support panel 11 PLS special busbars made from E-Cu For Rittal system Packs of PLS 800 PLS 1600 Rated current max. 700 A 1400 A Cross-section 300 2 900 2 Bar thickness 5 10 Length For enclosure width 495 600 1) 3 3524.000 2) 3527.000 2) 695 800 1) 3 3525.000 2) 3528.000 2) 895 1000 1) 3 3525.010 2) 3528.010 2) 1095 1200 1) 3 3526.000 2) 3529.000 2) 2400 variable 1 3509.000 2) 3516.000 2) 1) For Rittal TS 8/ES enclosure systems. 2) To order tin-plated version, please add extension.2x0 to the Model No. Delivery times available on request. Connection adaptor Page 14/15 OM/OT adaptors Page 24/25, 27 OM/OT supports Page 28/29 Component adaptors Page 32/33 Rittal RiLine60 13

Rittal RiLine60 busbar systems 800/1600 A (60 ) Busbar connection adaptor (3-pole) 1 2 3 3 4 1 2 Punched section Polyamid (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Cover ABS, fire protection corresponding to UL 94-V0. Colour: RAL 7035 Supply includes: Cover. Note: The technical data given in the tables may vary for UL applications, see page 74. 3 4 Design (3-pole) Packs of 1 2 3 4 Page Rated current up to 63 A 125 A 250 A 800 A Rated operating voltage 690 V~ 690 V~ 690 V~ 690 V~ Connection of round conductors Fine wire with wire end ferrule Multi-wire Solid 2.5 10 2 2.5 16 2 2.5 16 2 10 25 2 16 35 2 35 120 2 35 120 2 95 185 2 95 300 2 Clamping area for laminated copper bars 10 x 7.8 18.5 x 15.5 33 x 20 Tightening torque Assembly screw Terminal screw 2 Nm 2.5 Nm 2 Nm 2 3 Nm 4 6 Nm 12 Nm 6 Nm 12 14 Nm For bar thickness 5/10 5/10 5/10 5/10 Outlet top/bottom 1 9342.220 1) 9342.250 9342.280 1) Outlet at top 1 9342.200 9342.230 9342.260 9342.290 Outlet at bottom 1 9342.210 9342.240 9342.270 9342.300 Laminated copper bars 65 1) Not suitable for UL applications. Busbar systems Page 8 13 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 14 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) Busbar connection adaptor (3-pole) 1 2 3 150 60 247 54 1 2 Punched section SV 3439.010 Fibreglass-reinforced, thermoplastic polyester (PBT). Continuous operating temperature max. 140 C. Fire protection corresponding to UL 94-V0. SV 9342.310/.320 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Cover ABS, fire protection corresponding to UL 94-V0. Colour: RAL 7035 Supply includes: Cover. Note: The technical data given in the tables may vary for UL applications, see page 74. SV 3439.010 When connecting round conductors 300 2 with ring terminal, the terminal clamps fitted as standard in the busbar connection adaptors must be replaced with screws and/or bolts M10. 3 Version (3 x 1-pole) Packs of 1 2 3 Page Rated current up to 600 A 800 A 1600 A Rated operating voltage 690 V~ 690 V~ 690 V~ Outlet top/bottom top/bottom top/bottom Connection of round conductors Fine wire with wire end ferrule Multi-wire Clamping area for laminated copper bars For 5 bar thickness For 10 bar thickness Tightening torque Assembly screw Terminal screw 35 240 2 35 240 2 24 x 21 24 x 21 15 20 Nm 15 Nm 95 185 2 95 300 2 33 x 27 33 x 22 12 14 Nm 65 x 27 65 x 22 15 20 Nm For bar thickness 5/10 5/10 5/10 1 set 3439.010 1) 9342.310 9342.320 Laminated copper bars 65 1) Not suitable for UL applications. Busbar systems Page 8 13 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 Rittal RiLine60 15

Rittal RiLine60 busbar systems 800/1600 A (60 ) Connection clamps/system covers 1 3 2 B 1 Conductor connection clamps B H 22 For bar thickness Connection of round conductors 1) 2 Clamping area for laminated copper bars Tightening torque Nm Width (B) Height (H) min. max. Packs of Model No. SV 3 5 1 4 2 8.0 15 3550.000 5 1 4 2 11.0 17 23 15 3450.500 5 2.5 16 8 x 8 3 14.0 22 29 15 3451.500 5 16 50 10.5 x 11 6 8 18.5 26 39 15 3452.500 5 35 70 16.5 x 15 10 12 24.5 39 57 15 3453.500 5 70 185 22.5 x 20 12 15 30.5 44 66 15 3454.500 6 10 1 4 2 8.0 15 3555.000 10 1 4 2 11.0 17 23 15 3455.500 10 2.5 16 8 x 8 3 14.0 22 29 15 3456.500 10 16 50 10.5 x 11 6 8 18.5 26 39 15 3457.500 10 35 70 16.5 x 15 10 12 24.5 39 57 15 3458.500 10 70 185 22.5 x 20 12 15 30.5 44 66 15 3459.500 1) Wire end ferrules should be used with fine wire conductors. Sheet steel, zinc-plated, passivated (SV 3450.500 SV 3459.500), brass (SV 3550.000/SV 3555.000). : Laminated copper bars, see page 65. 40 40 55 55 Plate clamp For busbars 12 x 5 30 x 10. Clamping area for laminated copper bars: 34 x 10. Tightening torque: 6 8 Nm. 2 Packs of 3 3554.000 Sheet steel, zinc-plated, passivated : Laminated copper bars, see page 65. B H 230 325 System covers For conductor connection clamps and plate clamps. 3 Width (B) Height (H) Packs of 50 80 4 3086.000 100 80 4 3087.000 100 110 4 3090.000 200 80 4 3088.000 200 110 4 3091.000 ABS. Continuous operating temperature max. 80 C. Fire protection corresponding to UL 94-V0. Note: Only suitable for use with systems without a base tray. Busbar systems Page 8 13 Busbar connection adaptors Page 14/15 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 16 Rittal RiLine60

Notes Rittal RiLine60 17

Component adaptor with innovative modularity Multi-functional, thanks to platform technology The component adaptors are available in a choice of two mounting systems. Both systems have an identical platform technology for device assembly: The width variability, mechanical construction of motor circuit-breaker and motor starter combinations and their connection techniques are identical for both systems. This makes for easier stock holding, system assembly and servicing. 18 Rittal RiLine60

Component adaptors for motor starter combinations and universal applications with individual connection technology, 45 and 55 wide. The separation into modules (adaptor section and removable support frame) offers assembly benefits. Variant 1: OneMove (OM adaptor, see page 22 25) Snap-on mounting the traditional attachment system with brand new options Traditional variant with snap-on mounting onto the busbars. With metal-reinforced combination feet for 5 and 10 bar thickness. Suitable for universal use, even without a base tray. Accessibly positioned unlatching device operated in the direction of withdrawal. Variant 2: OneTurn (OT adaptor, see page 26 27) Base tray attachment ingeniously simple, fast and safe Innovative location system on the base tray section with fitted metal reinforcement. Time-saving mounting directly onto the Rittal RiLine60 system range. The OT adaptors are attached and contacted independently from the form and cross-section of the busbars. Minimal assembly force, thanks to generous leverage. Perfect all-round protection with base tray and OT adaptor. Assembly instruction: Maximum support spacing 300, bar thickness 10, may only be mounted in conjunction with base tray reinforcement. Rittal RiLine60 19

Efficiency redefined Modular assembly OM/OT adaptors and OM/OT supports (without contact system) are bayable as required in the base widths 45 and 55. For side auxiliary switches and expansion modules, there is a 10 extension piece available which may be bayed on both sides as often as required. A channel integrated into the extension pieces aids the optimum routing of control cables. Bayed using connection pins from the front. In this way, retrospective creation of a module is easily achieved. Multifunctional component connection Each of the three techniques for component connection accoodates particular requirements: Classic Adaptor with connection cables AWG 12 (up to 25 A), AWG 10 (up to 32 A), AWG 8 (up to 40 A) or AWG 6 (up to 65 A) fitted as standard. Flexible Adaptor with tension spring clamp up to 6 2 (32 A) or up to 16 2 (65 A). Rapid The Premium version with connector block up to 4 2 (25 A) and outgoing connector bush with sub-unit for 3 phase conductors and 8 auxiliary conductors. 20 Rittal RiLine60

New, rational approaches to device configuration: The required widths are quickly and robustly assembled using the baying connection system. Classic, flexible and rapid these three techniques meet all the requirements of device connection. System separation of the adaptor section and support frame means that device configuration is modular, safe and service-friendly. Variable platform technology for equipment assembly Without support frame Slimline, cost-effective configuration of the motor circuit-breaker directly onto the support rail. With support frame Cost-effective, modular configuration of motor starter combinations. Simple equipment preassembly even outside of the enclosure. Minimal downtime for equipment exchanges. Support rail Specially positioned bars on the underside of the support rail provide reliable protection against slipping, even with vertically configured busbar systems. Alternatively, there are also support rails without anti-slip guard for universal applications such as the configuration of circuit-breakers. With PinBlock A small addition with a big effect. The PinBlock simply clips onto the support frame and can be positioned to match the respective motor starter combination by simply sliding, allowing reliable side routing of the contactor. Rittal RiLine60 21

Rittal RiLine60 busbar systems 800/1600 A (60 ) OM adaptors 32 A with tension spring clamp/om Premium adaptors 25 A (3-pole) 1 2 3 4 5 6 7 1 2 + 4 3 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 (chassis) Note: Overview of market switchgear with allocation of the relevant adaptor, see page 75. 5 + 6 7 Design Packs Premium adaptor of 1 2 3 4 5 6 7 Construction width (B) 45 45 45 55 45 55 45 Length 208 208 208 208 208 208 272 Rated current up to 32 A 32 A 32 A 32 A 25 A 25 A 25 A Rated operating voltage 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ Connection of round conductors 1.5 6 2 1.5 6 2 1.5 6 2 1.5 6 2 1.5 4 2 1.5 4 2 1.5 4 2 Support frame 45 x 170 45 x 170 55 x 170 45 x 170 55 x 170 45 x 237 With Support frame supports PinBlock Connector outlet 1) 1) 2) Number of support rails, height 10 1 1 1 1 2 3) 2 3) 1 Support rail with anti-slip guard 4) For 5/10 bar thickness 1 9340.510 9340.530 9340.550 9340.660 9340.910 9340.930 9340.900 AWG 14 15 9340.850 9340.850 9340.850 9340.850 9340.850 9340.850 9340.850 57 AWG 12 15 9340.860 9340.860 9340.860 9340.860 9340.860 9340.860 9340.860 57 Cable set for OM adaptor AWG 10 15 9340.870 9340.870 9340.870 9340.870 57 AWG 8 6 57 AWG 6 6 57 Connection pin 20 9340.280 9340.280 9340.280 9340.280 9340.280 9340.280 9340.280 55 Insert strip 10 2 9340.290 9340.290 9340.290 9340.290 9340.290 9340.290 9340.290 55 OM support 45 x 208 1 9340.260 9340.260 9340.260 9340.260 9340.260 9340.260 9340.260 28 55 x 208 1 9340.270 9340.270 9340.270 9340.270 9340.270 9340.270 9340.270 28 Support frame 56 PinBlock for support frame 57 PinBlock Plus 57 Support rails 59 ST-Combi connector 58 1) Supply includes: Connector with connection facility for 3 main contacts (1.5 4 2 ). 2) Supply includes: Sub-unit with connection facility for 3 main contacts (1.5 4 2 ) and 8 auxiliary contacts (0.5 2.5 2 ) including connector. 3) The lower support rail with special latch is secured from behind with the support frame loosened. 4) Anti-slip guard for motor circuit-breaker brands Moeller, Siemens and Telemecanique. Without anti-slip guard for universal applications. Page Busbar systems Page 8 11 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 22 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) OM adaptors 65 A with tension spring clamp (3-pole) 1 2 1 2 3 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 (chassis) Note: Overview of market switchgear with allocation of the relevant adaptor, see page 75. 3 Design Packs of 1 2 3 Page Construction width (B) 55 55 55 Length 208 208 272 Rated current up to 65 A 65 A 65 A Rated operating voltage 690 V~ 690 V~ 690 V~ Connection of round conductors 2.5 16 2 2.5 16 2 2.5 16 2 With Support frame 55 x 170 55 x 237 Support frame supports Number of support rails, height 10 1 1 2 1) Support rail with anti-slip guard 2) For 5/10 bar thickness 1 9340.610 9340.630 9340.650 AWG 14 15 9340.850 9340.850 9340.850 57 AWG 12 15 9340.860 9340.860 9340.860 57 Cable set for OM adaptor AWG 10 15 9340.870 9340.870 9340.870 57 AWG 8 6 9340.880 9340.880 9340.880 57 AWG 6 6 9340.890 9340.890 9340.890 57 Connection pin 20 9340.280 9340.280 9340.280 55 Insert strip 10 2 9340.290 9340.290 9340.290 55 OM support 45 x 208 1 9340.260 9340.260 9340.260 28 55 x 208 1 9340.270 9340.270 9340.270 28 Support frame 56 PinBlock for support frame 57 PinBlock Plus 57 Support rails 59 1) The lower support rail with special latch is attached from the rear with the support frame loosened. 2) Anti-slip guard for motor circuit-breaker brands Moeller, Siemens and Telemecanique. Without anti-slip guard for universal applications. Busbar systems Page 8 11 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 Rittal RiLine60 23

Rittal RiLine60 busbar systems 800/1600 A (60 ) OM adaptors 25 A/32 A with connection cables (3-pole) 1 2 3 4 5 1 2 + 4 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 (chassis) Note: The technical data given in the tables may vary for UL applications, see page 74. Overview of standard coercially available switchgear with allocation of the relevant adaptor, see page 76. Current carrying capacity of the supply cables fitted as standard, see page 79. 3 5 Design Packs of 1 2 3 4 5 4 5 Page Construction width (B) 45 45 45 45 45 55 55 Length 208 208 208 208 208 208 208 Rated current up to 25 A 25 A 25 A 32 A 32 A 32 A 32 A Rated operating voltage 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ Connection cables 1) AWG 12 AWG 12 AWG 12 AWG 10 AWG 10 AWG 10 AWG 10 With Support frame 45 x 170 45 x 170 45 x 170 45 x 170 55 x 170 55 x 170 PinBlock Number of support rails, height 10 1 1 1 1 2 2) 1 2 2) Support rail with anti-slip guard 3) For 5/10 bar thickness 1 9340.310 9340.340 9340.370 9340.350 9340.380 9340.460 9340.470 Connection pin 20 9340.280 9340.280 9340.280 9340.280 9340.280 9340.280 9340.280 55 Insert strip 10 2 9340.290 9340.290 9340.290 9340.290 9340.290 9340.290 9340.290 55 OM support 45 x 208 1 9340.260 9340.260 9340.260 9340.260 9340.260 9340.260 9340.260 28 55 x 208 1 9340.270 9340.270 9340.270 9340.270 9340.270 9340.270 9340.270 28 Support frame 56 PinBlock for support frame 57 PinBlock Plus 57 Support rails 59 1) AWG = American Wire Gauges AWG 12 = 3.31 2 4 2 AWG 10 = 5.26 2 6 2 2) The lower support rail with special latch is secured from behind with the support frame loosened. 3) Anti-slip guard for motor circuit-breaker brands Moeller, Siemens and Telemecanique. Without anti-slip guard for universal applications. Busbar systems Page 8 13 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 24 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) OM adaptors 40 A/65 A with connection cables (3-pole) 1 2 3 4 5 1 2 3 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 (chassis) Note: The technical data given in the tables may vary for UL applications, see page 74. Overview of standard coercially available switchgear with allocation of the relevant adaptor, see page 76. Current carrying capacity of the supply cables fitted as standard, see page 79. 4 5 Design Packs of 1 2 3 4 5 Page Construction width (B) 55 55 55 75 75 Length 208 208 272 208 208 Rated current up to 65 A 65 A 65 A 40 A 65 A Rated operating voltage 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ Connection cables 1) AWG 6 AWG 6 AWG 6 AWG 8 AWG 6 With Support frame 55 x 170 55 x 237 Support frame supports Insert strips Number of support rails, 10 1 1 2 2) height 7.5 2 1 Support rail with anti-slip guard 3) For 5/10 bar thickness 1 9340.410 9340.430 9340.450 9340.710 9340.700 Connection pin 20 9340.280 9340.280 9340.280 9340.280 9340.280 55 Insert strip 10 2 9340.290 9340.290 9340.290 9340.290 9340.290 55 OM support 45 x 208 1 9340.260 9340.260 9340.260 9340.260 9340.260 28 55 x 208 1 9340.270 9340.270 9340.270 9340.270 9340.270 28 Support frame 56 PinBlock for support frame 57 PinBlock Plus 57 Support rails 59 1) AWG = American Wire Gauges AWG 8 = 8.37 2 10 2 AWG 6 = 13.3 2 16 2 2) The lower support rail with special latch is secured from behind with the support frame loosened. 3) Anti-slip guard for motor circuit-breaker brands Moeller, Siemens and Telemecanique. Without anti-slip guard for universal applications. Busbar systems Page 8 13 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 Rittal RiLine60 25

Rittal RiLine60 busbar systems 800/1600 A (60 ) OT adaptors 32 A/65 A with tension spring clamp/ot Premium adaptors 25 A (3-pole) 1 2 3 4 1 + 5 2 + 4 + 6 3 5 6 7 8 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 (chassis) Note: OT adaptors may only be used with 10 thick busbars or Rittal PLS 800/1600. Maximum support spacing 300. Overview of standard coercially available switchgear with allocation of the relevant adaptor, see page 77. 7 8 Packs of Premium adaptor Design 1 2 3 4 5 6 7 8 Construction width (B) 45 45 45 55 55 55 55 45 Length 230 230 230 230 230 230 272 272 Rated current up to 32 A 32 A 32 A 32 A 65 A 65 A 65 A 25 A Rated operating voltage 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ Connection of round conductors 1.5 6 2 1.5 6 2 1.5 6 2 1.5 6 2 2.5 16 2 2.5 16 2 2.5 16 2 1.5 4 2 Support frame 45 x 195 45 x 195 55 x 195 55 x 195 55 x 237 45 x 237 With PinBlock Connector outlet 1) Number of support rails, height 10 1 1 1 1 1 1 2 2) 1 Support rail with anti-slip guard 3) For 5/10 bar thickness 1 9341.510 9341.530 9341.550 9341.660 9341.610 9341.630 9341.650 9341.900 Also required Base tray 9, 11 Base tray reinforcement 9, 11 AWG 14 15 9340.850 9340.850 9340.850 9340.850 9340.850 9340.850 9340.850 9340.850 57 AWG 12 15 9340.860 9340.860 9340.860 9340.860 9340.860 9340.860 9340.860 9340.860 57 Cable set for OT adaptor AWG 10 15 9340.870 9340.870 9340.870 9340.870 9340.870 9340.870 9340.870 57 AWG 8 6 9340.880 9340.880 9340.880 57 AWG 6 6 9340.890 9340.890 9340.890 57 Connection pin 20 9340.280 9340.280 9340.280 9340.280 9340.280 9340.280 9340.280 9340.280 55 Insert strip 10 2 9341.290 9341.290 9341.290 9341.290 9341.290 9341.290 9341.290 9341.290 55 OT support 45 x 230 1 9341.260 9341.260 9341.260 9341.260 9341.260 9341.260 9341.260 9341.260 29 55 x 230 1 9341.270 9341.270 9341.270 9341.270 9341.270 9341.270 9341.270 9341.270 29 Support frame 56 PinBlock for support frame 57 PinBlock Plus 57 Support rails 59 ST-Combi connector 58 1) Supply includes: Sub-unit with connection facility for 3 main contacts (1.5 4 2 ) and 8 auxiliary contacts (0.5 2.5 2 ) including connector. 2) The lower support rail with special latch is secured from behind with the support frame loosened. 3) Anti-slip guard for motor circuit-breaker brands Moeller, Siemens and Telemecanique. Without anti-slip guard for universal applications. Busbar systems Page 8 11 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 26 Rittal RiLine60 Page

Rittal RiLine60 busbar systems 800/1600 A (60 ) OM adaptors 25 A/32 A/65 A with connection cables (3-pole) 1 2 3 4 1 + 5 2 + 4 + 6 5 6 7 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 (chassis) Note: OT adaptors may only be used with 10 thick busbars or Rittal PLS 800/1600. Maximum support spacing 300. The technical data given in the tables may vary for UL applications, see page 74. Overview of standard coercially available switchgear with allocation of the relevant adaptor, see page 78. Current carrying capacity of the supply cables fitted as standard, see page 79. 3 7 Design Packs of 1 2 3 4 5 6 7 Page Construction width (B) 45 45 45 55 55 55 55 Length 230 230 230 230 230 230 272 Rated current up to 25 A 25 A 25 A 32 A 65 A 65 A 65 A Rated operating voltage 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ Connection cables 1) AWG 12 AWG 12 AWG 12 AWG 10 AWG 6 AWG 6 AWG 6 With Support frame 45 x 195 45 x 195 55 x 195 55 x 195 55 x 237 PinBlock Number of support rails, height 10 1 1 1 1 1 1 2 2) Support rail with anti-slip guard 3) For 5/10 bar thickness 1 9341.310 9341.340 9341.370 9341.460 9341.410 9341.430 9341.450 Also required Base tray 9, 11 Base tray reinforcement 9, 11 Connection pin 20 9340.280 9340.280 9340.280 9340.280 9340.280 9340.280 9340.280 55 Insert strip 10 2 9341.290 9341.290 9341.290 9341.290 9341.290 9341.290 9341.290 55 OT support 45 x 230 1 9341.260 9341.260 9341.260 9341.260 9341.260 9341.260 9341.260 29 55 x 230 1 9341.270 9341.270 9341.270 9341.270 9341.270 9341.270 9341.270 29 Support frame 56 PinBlock for support frame 57 PinBlock Plus 57 Support rails 59 1) AWG = American Wire Gauges AWG 12 = 3.31 2 4 2 AWG 10 = 5.26 2 6 2 AWG 6 = 13.3 2 16 2 2) The lower support rail with special latch is secured from behind with the support frame loosened. 3) Anti-slip guard for motor circuit-breaker brands Moeller, Siemens and Telemecanique. Without anti-slip guard for universal applications. Busbar systems Page 8 13 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 Rittal RiLine60 27

Rittal RiLine60 busbar systems 800/1600 A (60 ) OM supports without contact system (3-pole) 1 2 1 2 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 (chassis) Note: Suitable for use in UL applications. Design Packs of 1 2 Page Construction width 45 55 Length 208 272 Support frame 45 x 170 55 x 237 With Support frame supports PinBlock Number of support rails, height 10 1 1) For 5/10 bar thickness 1 9340.260 9340.270 Connection pin 20 9340.280 9340.280 55 Insert strip 10 2 9340.290 9340.290 55 Support frame 56 PinBlock for support frame 57 PinBlock Plus 57 Support rails 59 1) The support rail with special latch is attached from the rear with the support frame loosened. Busbar systems Page 8 13 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 28 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) OT supports without contact system (3-pole) 1 2 1 2 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 (chassis) Note: OT supports may only be used with 10 thick busbars or Rittal PLS 800/1600. Maximum support spacing 300. Suitable for use in UL applications. Design Packs of 1 2 Page Construction width 45 55 Length 230 272 With Support frame 45 x 195 55 x 237 PinBlock Number of support rails, height 10 1 1) For 5/10 bar thickness 1 9341.260 9341.270 Also required Base tray 9, 11 Base tray reinforcement 9, 11 Connection pin 20 9340.280 9340.280 55 Insert strip 10 2 9341.290 9341.290 55 Support frame 56 PinBlock for support frame 57 PinBlock Plus 57 Support rails 59 1) The support rail with special latch is attached from the rear with the support frame loosened. Busbar systems Page 8 13 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 Rittal RiLine60 29

Innovative adaptation at high outputs Circuit-breaker component adaptor up to 630 A Graduated lines to fit all standard coercial power circuitbreakers (MCCB = Moulded Case Circuit Breaker). Versions are available for cable outlet at the bottom and top. Construction width 72 up to 100 A Construction width 90 up to 125 A/160 A Construction width 105 up to 250 A Construction width 140/190 up to 630 A Universal sliding block attachment system The sliding block system combined with the guide channels makes mounting the power circuit-breakers much easier, by eliminating the time-consuming process of searching for threaded holes. Simple preassembly of the standard sliding blocks on the power circuit-breaker. Assembled by inserting the sliding blocks into the guide channels. Secure positioning of the switchgear thanks to the end stop. 30 Rittal RiLine60

Brand new sliding block concept for circuit-breaker adaptors up to 630 A. Mounting of all standard power circuitbreakers is now much simpler and easier: Premount the sliding blocks on the switchgear, slide into the guide channel and secure it s that simple! Convincing connection system User-friendly box terminals for versions 100, 125, 160 and 250 A. Alternatively, may also be connected using threaded bolts. Solid connection with threaded bolts for the version up to 630 A. Positioning of the connection clamps for compact component connection e.g. with special connection bracket or variable connection with round conductors. Short circuit-resistant, fully shielded routing of the contact tracks. Generous cross-section dimensioning for optimum heat dissipation and minimal heat loss. Rittal RiLine60 31

Rittal RiLine60 busbar systems 800/1600 A (60 ) Component adaptors 100 A/circuit-breaker component adaptors 125 A, 160 A (3-pole) 1 3 3 2 2 1 SV 9342.400/ 2 SV 9342.540 SV 9342.410 3 SV 9342.500 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Supply includes Circuit-breaker component adaptor: Terminal cover and sliding blocks for switchgear attachment. Note: The technical data given in the tables may vary for UL applications, see page 74. 2 SV 9342.550 3 SV 9342.510 Design Packs of 1 Component 2 Circuit-breaker 3 Circuit-breaker adaptor component adaptor component adaptor Construction width 72 90 90 Length 210 225 215 Rated current up to 100 A 125 A 160 A Rated operating voltage 690 V~ 690 V~ Connection clamp Box terminal Box terminal Connection of round conductors 10 35 2 35 120 2 Clamping area for laminated copper bars 10 x 7.8 18.5 x 15.5 Tightening torque Terminal screw Rail attachment Switchgear attachment For switchgear make/model 2 3 Nm 2 Nm 1.5 Nm 12 Nm 4 6 Nm 1.5 Nm ABB MS 497 S2, T1, T2 GE FD Merlin Gerin NS80, NSC100 Moeller Electric PKZ2 1) NZM1 Siemens S3 Telemecanique GV3 1) Universal application 1) For bar thickness 5/10 5/10 Cable outlet at the top 2) 1 9342.400 9342.540 9342.500 3) Cable outlet at the bottom 2) 1 9342.410 9342.550 9342.510 3) Support rail Width 72, height 15 5 9320.120 59 Connection bracket 58 1) Mounting only possible with support rail SV 9320.120. 2) Switch outlet or outgoing cable. 3) Not suitable for UL applications. Page Busbar systems Page 8 13 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 32 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) Circuit-breaker component adaptors 250 A/630 A (3-pole) 1 3 2 1 SV 9342.600 2 SV 9342.700 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Supply includes: Terminal cover and sliding blocks for switchgear attachment. Note: The technical data given in the tables may vary for UL applications, see page 74. 1 SV 9342.610 2 SV 9342.710 Design Packs of 1 2 Page Construction width 105 140 Length 240 324 Rated current up to 250 A 630 A Rated operating voltage 690 V~ 690 V~ Connection clamp Box terminal Screw terminal M10 Connection of round conductors 35 120 2 max. 150 2 2) Clamping area for laminated copper bars 18.5 x 15.5 32 x 10 Tightening torque Terminal screw Rail attachment Switchgear attachment For switchgear make/model 12 Nm 4 6 Nm 1.5 Nm 30 32 Nm 12 14 Nm 2.5 Nm ABB S3, T3, T4 S5, T5 GE FE Merlin Gerin NS100, NS160, NS250 NS400, NS630 Moeller Electric NZM2 NZM3 Siemens VL160X, VL160, VL250 VL400, VL630 3) Telemecanique GV7 For bar thickness 5/10 5/10 Cable outlet at the top 1) Cable outlet at the bottom 1) Insert strip 25 3 to extend the construction width from 140 to 190 1 9342.600 9342.700 1 9342.610 9342.710 4 (1 set) 9342.720 55 Connection bracket 58 1) Switch outlet or outgoing cable. 2) With ring terminal. 3) Also required: Insert strip 25 (SV 9342.720). Busbar systems Page 8 13 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 Rittal RiLine60 33

Contact stability and assembly diversity Rittal multi-functional adaptors use modern, practical technology to set standards in terms of contact reliability, assembly rationalisation and configuration diversity of switchgear: Multifunctional busbar contacting: The contact springs, mounted in a floating configuration in the adaptor section, ensure the equalisation of levels between the bar and the contact track. In this way, optimum adaptation to the busbar and loss-free, safe power transission is achieved thanks to pocket contacting via three contact surfaces. Self-locking and unlockable adaptor mounting. Multi-functional component adaptation Support rails universally positionable, both fixed and sliding, as well as support rails secured via snapfastening, ensure fast assembly and servicing for power circuit-breakers and motor starter combinations. Mounting clip for additional mounting of motor starter combinations. The cable chamber beneath the equipment support rails provides plenty of space for control wiring. 34 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) Multi-functional component adaptors 12 A/25 A (3-pole) 1 2 3 4 45 57 45 57 45 57 168.5 5 234 A B 5 234 100 234 67.5 5 39 39 39 1 + 2 3 5 6 5 6 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 140 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035, RAL 9011 (chassis) Note: Overview of standard switchgear with allocation of the relevant adaptor, see page 79. Current carrying capacity of the supply cables fitted as standard, see page 79. For snap-on mounting 1 2 3 4 5 6 Page Construction width 45 45 45 45 45 45 Rated current up to 12 A 25 A 25 A 25 A 25 A 25 A Rated operating voltage 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ Cable outlet top top top top top bottom Connection cables 1) AWG 14 AWG 12 AWG 12 AWG 12 AWG 12 AWG 12 Support rails Qty. 1 1 2 2 2 (1 variable) 2 Height 10 10 10 10 10 10 A 68.5 55 variable B 100 125 variable Packs of 1 1 1 1 1 1 For 5 bar thickness 9320.160 9320.180 9320.200 9320.440 9320.220 9320.240 For 10 bar thickness 9320.170 9320.190 9320.210 9320.450 9320.230 9320.250 Packs of Support rails Width 45, height 10 5 9320.090 9320.090 9320.090 9320.090 9320.090 9320.090 60 Plug-in connector 1 9320.110 9320.110 9320.110 9320.110 9320.110 60 Mounting clip 5 9320.140 9320.140 9320.140 9320.140 9320.140 9320.140 60 1) AWG = American Wire Gauges AWG 14 = 2.08 2 2.5 2 AWG 12 = 3.31 2 4 2 Busbar systems Page 8 11 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 Rittal RiLine60 35

Rittal RiLine60 busbar systems 800/1600 A (60 ) Multi-functional component adaptors 25 A (3-pole) 1 2 3 4 90 57 99 57 A B 5 A B 5 234 234 39 39 45 45 54 45 1 2 108 57 45 57 39 39 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 140 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035, RAL 9011 (chassis) Note: Overview of standard switchgear with allocation of the relevant adaptor, see page 79. Current carrying capacity of the supply cables fitted as standard, see page 79. A B 5 3 54 54 234 A B 5 4 234 For snap-on mounting 1 2 3 4 4 Page Construction width 90 99 108 45 45 Rated current up to 25 A 25 A 25 A 25 A 25 A Rated operating voltage 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ Cable outlet top top top top top/bottom Connection cables 1) AWG 12 AWG 12 AWG 12 Connection of round conductors up to 16 2 16 2 Support rails Qty. 2 2 2 2 (1 variable) 2 Height 10 10 10 10 10 A 68.5 43 43 variable 68.5 B 100 125 90 variable 100 Packs of 1 1 1 1 1 For 5 bar thickness 9320.380 9320.400 9320.420 9320.260 9320.280 For 10 bar thickness 9320.390 9320.410 9320.430 9320.270 9320.290 Packs of Support rails Width 45, height 10 5 9320.090 9320.090 9320.090 9320.090 60 Support rails Width 54, height 10 5 9320.100 9320.100 60 Plug-in connector 1 9320.110 60 Mounting clip 5 9320.140 9320.140 9320.140 9320.140 60 1) AWG = American Wire Gauges AWG 12 = 3.31 2 4 2 Busbar systems Page 8 11 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 36 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) Multi-functional component adaptors 40 A (3-pole) 1 2 3 4 54 57 54 57 54 57 54 57 68.5 100 5 234 118 234 5 100 234 68.5 100 5 234 67.5 39 39 39 39 1 2 3 4 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 140 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035, RAL 9011 (chassis) Note: Overview of standard switchgear with allocation of the relevant adaptor, see page 79. Current carrying capacity of the supply cables fitted as standard, see page 79. For snap-on mounting 1 2 3 4 4 Page Construction width 54 54 54 54 54 Rated current up to 40 A 40 A 40 A 40 A 40 A Rated operating voltage 690 V~ 690 V~ 690 V~ 690 V~ 690 V~ Cable outlet top top bottom top top/bottom Connection cables 1) AWG 10 AWG 10 AWG 10 Connection of round conductors up to 16 2 16 2 Support rails Qty. 2 1 2 2 2 Height 10 15 10 10 10 Packs of 1 1 1 1 1 For 5 bar thickness For 10 bar thickness Support rails Width 54, height 10 1) AWG = American Wire Gauges AWG 10 = 5.26 2 6 2 Packs of 9320.300 9320.460 9320.320 9320.340 9320.360 9320.310 9320.470 9320.330 9320.350 9320.370 5 9320.100 9320.100 9320.100 9320.100 60 Busbar systems Page 8 11 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 Rittal RiLine60 37

Reliable function at high currents NH bus-mounting on-load isolator, size 00 to 3 Mechanical attachment and electrical contact with secure clamping screw attachment. The cable outlet is easily converted to top or bottom with the same device. Choice of electromechanical or electronic fuse monitoring. Type-tested to DIN EN 60 947-3. Contact hazard protection plate, two-piece, with service-friendly central unlatching to comply with BGV A3 (formerly VBG 4). NH fused isolator, size 00 With a construction width of just 50, the NH fused isolator sets new standards in compact, space-saving configuration. Thanks to the double-break per phase in the switching operation, particularly high switching values are achieved. User-friendly direct connection of round conductors with additional prism clamps up to 95 2, thanks to the stepped arrangement of the connection clamps. 38 Rittal RiLine60

Bus-mounting fuse bases for snap-on mounting or clamping screw attachment The three-pole components ensure reliable-contact, shake-proof connection with the busbars: A high level of contact stability and avoidance of contact heat and scorch marks thanks to the contact plate system, i.e. the fuse inserts do not contact the busbars directly. This prevents the busbars from being destroyed by contact fire if the fuse screw cap is inadequately tightened or is tightened under load during maintenance. There are integrated screw terminals on the underside of the components for clamping screw attachment, and special spring-loaded foot pieces on the components for snap-on mounting. Safety is afforded by the Rittal Contact-Plus system. The contact plate system effectively separates electrical contact-making from mechanical attachment (snap-on mounting). Optimum cable routing on the outlet side, thanks to adequate recesses on the component body. Rittal RiLine60 39

Rittal RiLine60 busbar systems 800/1600 A (60 ) Bus-mounting fuse bases (3-pole) 1 2 3 6 D D B 60 60 230 230 C A C A 7 1 3 5 + 6 with 4 + 6 8 4 5 7 Bus-mounting fuse base: Fibreglass-reinforced, thermoplastic polyester (PBT). Continuous operating temperature max. 140 C. Fire protection corresponding to UL 94-V0. Contact hazard protection cover: Polyamide (PA 6.6). Continuous operating temperature max. 105 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 For clamping screw attachment Packs of 1 2 3 Type D 02-E 18 (adaptor sleeve) D II-E 27 (adaptor screw) D III-E 33 (adaptor screw) Width (A) 27 42 57 Rated current 63 A 25 A 63 A Rated operating voltage 400 V~ 500 V~ 690 V~ Terminal for round conductors 1) 1.5 16 2 1.5 16 2 1.5 16 2 Tightening torque Assembly screw Terminal screw For 5/10 bar thickness Contact hazard protection cover 4 Extension cover 5 End caps 6 for rail system with base tray End caps for rail system without base tray Side cover 7 Identification labels 8 2 Nm 2.5 Nm 2 Nm 2.5 Nm 2 Nm 2.5 Nm 10 3418.000 3427.000 3433.000 10 3419.000 3428.000 3434.000 10 3421.000 3430.000 3436.000 10 3420.010 3429.010 3435.010 10 3420.000 3429.000 3435.000 10 3093.000 3093.000 3093.000 100 9320.080 9320.080 9320.080 Width (A) 27 42 57 Spacing (B) 57 40 40 Depth (C) 2) 67 71.5 71.5 Depth (D) 3) with base tray 47 51.5 51.5 for rail system without base tray 67 71.5 71.5 1) Wire end ferrules should be used with fine wire conductors. 2) Bottom end cap 3) Top end cap Busbar systems Page 8 11 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 40 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) Bus-mounting fuse bases (3-pole) 1 2 3 6 D D B 60 60 230 230 C A C A 7 1 3 5 + 6 with 4 + 6 8 4 5 7 Bus-mounting fuse base: Fibreglass-reinforced, thermoplastic polyester (PBT). Continuous operating temperature max. 140 C. Fire protection corresponding to UL 94-V0. Contact hazard protection cover: Polyamide (PA 6.6). Continuous operating temperature max. 105 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 For snap-on mounting Packs of 1 2 3 Type D 02-E 18 (adaptor sleeve) D II-E 27 (gauge ring) D III-E 33 (gauge ring) Width (A) 36 42 57 Rated current 63 A 25 A 63 A Rated operating voltage 400 V~ 500 V~ 690 V~ Terminal for round conductors 1) 1.5 16 2 1.5 16 2 1.5 16 2 Tightening torque Terminal screw 2.5 Nm 2.5 Nm 2.5 Nm For 5 bar thickness 10 3422.000 3520.000 3530.000 For 10 bar thickness 10 3423.000 3521.000 3531.000 4 Contact hazard protection cover 10 3424.000 3428.000 3434.000 5 Extension cover 10 3430.000 3436.000 6 End caps for rail system with base tray 10 3425.010 3429.010 3435.010 End caps for rail system without base tray 10 3425.000 3429.000 3435.000 7 Side cover 10 3093.000 3093.000 3093.000 8 Identification labels 100 9320.080 9320.080 9320.080 Width (A) 36 42 57 Spacing (B) 57 40 40 Depth (C) 2) 67 71.5 71.5 Depth (D) 3) with base tray 47 51.5 51.5 for rail system without base tray 67 71.5 71.5 1) Wire end ferrules should be used with fine wire conductors. 2) Bottom end cap 3) Top end cap Busbar systems Page 8 11 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 NH fused isolators Page 42 NH bus-mounting on-load isolators Page 43 47 Page 55 66 Rittal RiLine60 41

Rittal RiLine60 busbar systems 800/1600 A (60 ) NH fused isolators, size 00 (3-pole) 50 134 191* 50 134 191* 300 403.4 403.4 300 75 75 1 2 2 1 * Off-load position Cover, strip chassis: Fibreglass-reinforced polyamide Contact tracks: Silver-plated hard copper Technical information, see page 80. Design Packs of 1 2 Page Size Size 00 Size 00 Rated current 160 A 160 A Rated operating voltage 690 V~ 690 V~ Cable outlet top bottom Type of connection Screw M8 Screw M8 Tightening torque Assembly screw Terminal screw For bar thickness 5/10 5/10 1 3591.020 3591.030 Side panel 2 9341.230 9341.230 60 Identification label support 6 3595.010 3595.010 61 Micro-switch 5 3071.000 3071.000 61 Lug terminal connection parts 1 set 3592.020 3592.020 62 Clamp-type terminal connection 1 set 3592.010 3592.010 62 6 Nm 14 Nm 6 Nm 14 Nm Busbar systems Page 8 11 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH bus-mounting on-load isolators Page 43 47 Page 55 66 42 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) NH on-load isolators, size 000 (3-pole) 1 2 69.5 141.5 89 Chassis, lid, contact hazard protection: Fibreglass-reinforced polyamide Contact tracks: Silver-plated hard copper Technical information, see page 80. Size Packs of Size 000 Page Rated current 100 A (160 A) 1) Rated operating voltage 690 V~ Cable outlet top/bottom Type of connection Terminal Connection of round conductors 1.5 50 2 Tightening torque Terminal screw 3 Nm 1 1 3431.000 Also required Busbar adaptor see below Micro-switch 5 3071.000 61 1) 160 A at 95 2 connection cross-section (95 2 connector pieces available on request). 115 115 36.5 90 35 Busbar adaptor For mounting SV 3431.000 on 60 busbar systems. 2 For bar thickness Packs of 5 1 9320.040 10 1 9320.050 Fibreglass-reinforced, thermoplastic polyester (PBT). Continuous operating temperature max. 140 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Supply includes: 35 2 connection cables fitted as standard. Busbar systems Page 8 11 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 Page 55 66 Rittal RiLine60 43

194 194 194 40 40 40 Rittal RiLine60 busbar systems 800/1600 A (60 ) NH bus-mounting on-load isolators, size 00 (3-pole) 1 2 3 106 33 33 104 106 33 33 104 106 33 33 104 28 1 2 3 69 Chassis, lid, contact hazard protection: Polyamide PA6 Contact tracks: Electrolytic copper, silver-plated Supply includes: Top and bottom covers. Technical information, see page 80 84. Size Packs of Size 00 Page Rated current 160 A Rated operating voltage 690 V~/500 V~ 1) Cable outlet top/bottom Type of connection Box terminal Screw M8 Connection of round conductors 4 95 2 up to 95 2 Clamping area for laminated copper bars 13 x 13 20 x 5 Tightening torque Assembly screw Terminal screw 6 Nm 4.5 Nm For bar thickness 5/10 5/10 1 1 9343.000 9343.010 2 with electronic fuse monitoring 1) 1 9343.020 9343.030 3 with electromechanical fuse monitoring 1 9343.040 9343.050 Micro-switch 5 3071.000 3071.000 61 Connection space cover 2 9344.520 9344.520 61 Prism terminal 3 9344.600 62 1) Rated operating voltage 400 V~ to 500 V~ for NH isolators with electronic fuse monitoring. 6 Nm 12 Nm Busbar systems Page 8 11 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 Page 55 66 44 Rittal RiLine60

298 98 298 298 98 98 Rittal RiLine60 busbar systems 800/1600 A (60 ) NH bus-mounting on-load isolators, size 1 (3-pole) 1 2 3 184 57 57 110 184 57 57 110 1 2 28 184 57 57 110 Chassis, lid, contact hazard protection: Polyamide PA6 Contact tracks: Electrolytic copper, silver-plated Supply includes: Top and bottom covers. Technical information, see page 80 84. 3 69 Size Packs of Size 1 Page Rated current 250 A Rated operating voltage 690 V~/500 V~ 1) Cable outlet top/bottom Type of connection Box terminal Screw M10 Connection of round conductors 35 150 2 2) up to 150 2 Clamping area for laminated copper bars 20 x 14 32 x 10 Tightening torque Assembly screw Terminal screw For bar thickness 5/10 5/10 1 1 9343.100 9343.110 2 with electronic fuse monitoring 1) 1 9343.120 9343.130 3 with electromechanical fuse monitoring 1 9343.140 9343.150 Micro-switch 2 9344.510 9344.510 61 Connection space cover 2 9344.530 9344.530 61 Box terminal 3 9344.610 62 Arcing chamber 3 9344.680 9344.680 62 1) Rated operating voltage 400 V~ to 500 V~ for NH isolators with electronic fuse monitoring. 2) Connection of sector-shaped conductors 50 150 2. 6 Nm 12 Nm 6 Nm 20 Nm Busbar systems Page 8 11 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 Page 55 66 Rittal RiLine60 45

298 98 298 298 98 98 Rittal RiLine60 busbar systems 800/1600 A (60 ) NH bus-mounting on-load isolators, size 2 (3-pole) 1 2 3 210 65 65 130 210 65 65 130 28 1 2 210 65 65 130 Chassis, lid, contact hazard protection: Polyamide PA6 Contact tracks: Electrolytic copper, silver-plated Supply includes: Top and bottom covers. Technical information, see page 80 84. 3 69 Size Packs of Size 2 Page Rated current 400 A Rated operating voltage 690 V~/500 V~ 1) Cable outlet top/bottom Type of connection Box terminal Screw M10 Connection of round conductors 95 300 2 2) up to 240 2 Clamping area for laminated copper bars 32 x 20 50 x 10 Tightening torque Assembly screw Terminal screw For bar thickness 5/10 5/10 1 1 9343.200 9343.210 2 with electronic fuse monitoring 1) 1 9343.220 9343.230 3 with electromechanical fuse monitoring 1 9343.240 9343.250 Micro-switch 2 9344.510 9344.510 61 Connection space cover 2 9344.540 9344.540 61 Box terminal 3 9344.620 62 Arcing chamber 3 9344.680 9344.680 62 1) Rated operating voltage 400 V~ to 500 V~ for NH isolators with electronic fuse monitoring. 2) Connection of sector-shaped conductors 120 300 2. 8 Nm 20 Nm 8 Nm 20 Nm Busbar systems Page 8 11 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 Page 55 66 46 Rittal RiLine60

298 98 298 298 98 98 Rittal RiLine60 busbar systems 800/1600 A (60 ) NH bus-mounting on-load isolators, size 3 (3-pole) 1 2 3 250 80 80 130 250 80 80 130 28 1 2 80 250 80 130 Chassis, lid, contact hazard protection: Polyamide PA6 Contact tracks: Electrolytic copper, silver-plated Supply includes: Top and bottom covers. Technical information, see page 80 84. 3 69 Size Packs of Size 3 Page Rated current 630 A Rated operating voltage 690 V~/500 V~ 1) Cable outlet top/bottom Type of connection Box terminal Screw M10 Connection of round conductors 95 300 2 2) up to 300 2 Clamping area for laminated copper bars 32 x 20 50 x 10 Tightening torque Assembly screw Terminal screw For bar thickness 5/10 5/10 1 1 9343.300 9343.310 2 with electronic fuse monitoring 1) 1 9343.320 9343.330 3 with electromechanical fuse monitoring 1 9343.340 9343.350 Micro-switch 2 9344.510 9344.510 61 Connection space cover 2 9344.550 9344.550 61 Box terminal 3 9344.620 62 Arcing chamber 3 9344.680 9344.680 62 1) Rated operating voltage 400 V~ to 500 V~ for NH isolators with electronic fuse monitoring. 2) Connection of sector-shaped conductors 120 300 2. 8 Nm 20 Nm 8 Nm 20 Nm Busbar systems Page 8 11 Busbar connection adaptors Page 14/15 Connection clamps Page 16 OM/OT adaptors Page 22 27 OM/OT supports Page 28/29 Component adaptors Page 32 37 Bus-mounting fuse bases Page 40/41 NH fused isolators Page 42 Page 55 66 Rittal RiLine60 47

Rittal RiLine60 busbar systems 800 A (60 ) Busbar supports (4-pole) 2 1 3 4 5 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Short-circuit protection diagram, see page 69. Technical information for the calculation of rated currents, see page 71. 1 With attachment holes on the inside Design Packs of 1 Page Number of poles 4-pole Bar centre distance 60 For busbars E-Cu 12 x 5/10 1), 15 x 5 30 x 10 Tightening torque Assembly screw (M5 x 25) Cover attachment 3 5 Nm 1 3 Nm 4 9340.004 2 End covers for contact hazard protection on the sides 2 9340.074 Spacers for SV 9340.004 12 9340.090 55 1) If 12 x 5/10 busbars are used, the spacer SV 9340.090 is additionally required. Busbars E-Cu To DIN EN 13 601. Length: 2400 /bar. Dimensions Packs of Page 12 x 5 6 3580.000 12 x 10 6 3580.100 15 x 5 6 3581.000 15 x 10 6 3581.100 20 x 5 6 3582.000 20 x 10 6 3585.000 25 x 5 6 3583.000 30 x 5 1) 6 3584.000 2) 30 x 10 1) 6 3586.000 2) Busbar cover section (length 1 m/each) 10 3092.000 63 Busbar connector for E-Cu 3 12 x 5 15 x 10 (single connection) 3 9350.075 64 4 20 x 5 30 x 10 (single connection) 3 9320.020 64 5 20 x 5 30 x 10 (bayed connection) 3) 3 9320.030 64 1) Other busbar lengths, see page 63. 2) Tin-plated version available on request. 3) From enclosure to enclosure. Bus connection adaptors Page 52/53 Connection clamps Page 16 Component adaptors Page 54 48 Rittal RiLine60

Rittal RiLine60 busbar systems 800 A (60 ) System components (4-pole) 1 Base tray For rear contact hazard protection of the flat bar assembly. Length (L) Packs of 1100 2 9340.134 Cover section 2 May be cut to length as required; for clip-on mounting to the base tray. Length (L) Packs of 1100 2 9340.214 1 2 Base tray and cover section Thermally modified hard PVC. Continuous operating temperature max. 91 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Note: If the cover section is mounted from the front, the support panel (SV 9340.224) is needed for stability. Support panel for cover section To prevent side access to the cover section. The support panel also provides additional stability. Polyamide (PA 6.6). Continuous operating temperature max. 105 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Packs of 5 9340.224 Bus connection adaptors Page 52/53 Connection clamps Page 16 Component adaptors Page 54 Rittal RiLine60 49

Rittal RiLine60 busbar systems 800/1600 A (60 ) Busbar supports PLUS (4-pole) 3 1 3 2 4 5 6 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Short-circuit protection diagram, see page 69. Technical information for the calculation of rated currents, see page 71. 1 Rittal 30 x 10 PLUS 2 Rittal PLS 1600 PLUS For system Packs of 1 Rittal 30 x 10 PLUS 2 Rittal PLS 1600 PLUS Number of poles 4-pole 4-pole Bar centre distance 60 60 For busbars E-Cu 30 x 10 PLS special busbars (PLS 1600) Tightening torque Assembly screw (M6 x 20) Cover attachment 3 5 Nm 5 7 Nm 3 5 Nm 5 7 Nm 4 9342.014 9342.004 3 End covers for contact hazard protection on the sides 2 9342.074 9342.074 Busbars made from E-Cu Detailed drawing: SV 9661.300 to.380, see page 63. For system Rittal 30 x 10 PLUS Rittal PLS 1600 PLUS Page Size 30 x 10 Cross-section (bar thickness) 900 2 (10 ) 1) For enclosure width Length Packs of Model No. SV Length Packs of Model No. SV 300 2) 265 2 9661.330 400 2) 365 2 9661.340 600 2) 565 2 9661.360 495 3 3527.000 800 2) 765 2 9661.380 695 3 3528.000 1000 2) 965 2 9661.300 895 3 3528.010 1200 2) 1165 2 9661.320 1095 3 3529.000 Variable 2400 6 3586.000 2400 1 3516.000 4 PLS busbar connector (single connection) 3 3514.000 64 5 PLS busbar connector (bayed connection) 3) 3 3515.000 64 6 PLS expansion connectors 4) 3 9320.070 65 Baying bracket for SV 9661.300 to.380 (bayed connection) 95 4 9661.350 63 Single connection 3 9320.020 64 Busbar connector for SV 3586.000 Baying connection 3) 3 9320.030 64 Busbar cover section 1000 10 3092.000 63 1) PLS special busbars (1600 A). To order tin-plated version, please add extension.2x0 to the Model No. Delivery times available on request. 2) For Rittal TS 8/ES enclosure systems. 3) From enclosure to enclosure. 4) Two PLS rail connectors (single connection) are required to fit one expansion connector. Bus connection adaptors Page 52/53 Connection clamps Page 16 Component adaptors Page 54 50 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) System components (4-pole) 1 Base tray For rear contact hazard protection of the busbar assembly PLUS. Length (L) Packs of 1100 2 9342.134 Cover section 2 May be cut to length as required; for clip-on mounting to the base tray. Length (L) Packs of 1100 2 9340.214 1 2 Base tray and cover section Thermally modified hard PVC. Continuous operating temperature max. 91 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Note: If the cover section is mounted from the front, the support panel (SV 9340.224) is needed for stability. Support panel for cover section To prevent side access to the cover section. The support panel also provides additional stability. Polyamide (PA 6.6). Continuous operating temperature max. 105 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Packs of 5 9340.224 Bus connection adaptors Page 52/53 Connection clamps Page 16 Component adaptors Page 54 Rittal RiLine60 51

Rittal RiLine60 busbar systems 800/1600 A (60 ) Busbar connection adaptor (4-pole) 1 2 2 1 2 Punched section Polyamid (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Cover ABS, fire protection corresponding to UL 94-V0. Colour: RAL 7035 Supply includes: Cover. Design (4-pole) Packs of 1 2 Page Rated current up to 125 A 250 A Rated operating voltage 690 V~ 690 V~ Connection of round conductors Fine wire with wire end ferrule Multi-wire 10 25 2 16 35 2 35 120 2 35 120 2 Clamping area for laminated copper bars 10 x 7.8 18.5 x 15.5 Tightening torque Assembly screw Terminal screw 2 Nm 2 3 Nm 4 6 Nm 12 Nm For bar thickness 5/10 5/10 Outlet top/bottom 1 9342.224 9342.254 Outlet at top 1 9342.234 9342.264 Outlet at bottom 1 9342.244 9342.274 Laminated copper bars 65 Busbar systems Page 48 51 Connection clamps Page 16 Component adaptors Page 54 52 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) Busbar connection adaptor (4-pole) 1 2 1 SV 9342.310 with SV 9342.314 Punched section Polyamid (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Cover ABS, fire protection corresponding to UL 94-V0. Colour: RAL 7035 Supply includes: Cover. 2 SV 9342.320 with SV 9342.324 Design Packs of 1 2 Page Rated current up to 800 A 1600 A Rated operating voltage 690 V~ 690 V~ Outlet top/bottom top/bottom Connection of round conductors Fine wire with wire end ferrule Multi-wire Clamping area for laminated copper bars For 5 bar thickness For 10 bar thickness 95 185 2 95 300 2 33 x 27 33 x 22 65 x 27 65 x 22 Tightening torque 12 14 Nm 15 20 Nm For bar thickness 5/10 5/10 Busbar connection adaptors (3 x 1-pole) Also required Connection adaptor (expansion set for 4-pole configuration) 1 set (3) 9342.310 9342.320 1 9342.314 9342.324 Laminated copper bars 65 Busbar systems Page 48 51 Connection clamps Page 16 Component adaptors Page 54 Rittal RiLine60 53

Rittal RiLine60 busbar systems 800/1600 A (60 ) Circuit-breaker component adaptors 160 A/250 A (4-pole) 1 SV 9342.504 2 SV 9342.604 1 2 Polyamide (PA 6.6), 25 % fibreglass-reinforced. Continuous operating temperature max. 130 C. Fire protection corresponding to UL 94-V0. Colour: RAL 7035 Supply includes: Terminal cover and sliding blocks for switchgear attachment. 1 SV 9342.514 2 SV 9342.614 Design Packs of 1 2 Construction width 120 140 Length 277 310 Rated current up to 160 A 250 A Rated operating voltage 690 V~ 690 V~ Connection clamp Box terminal Box terminal Connection of round conductors 35 120 2 35 120 2 Clamping area for laminated copper bars 18.5 x 15.5 18.5 x 15.5 Tightening torque Terminal screw Rail attachment Switchgear attachment 12 Nm 4 6 Nm 1.5 Nm 12 Nm 4 6 Nm 1.5 Nm ABB T1 (160 A), T2 (160 A) T3S (250 A), T4V (315 A) For switchgear Merlin Gerin NSC100 NS100, NS160, NS250L make/model Moeller Electric NZM1-4 (125 A) NZM2-4 (250 A) Siemens VL160X, VL160, VL250 For bar thickness 5/10 5/10 Cable outlet at the top 1) 1 9342.504 9342.604 Cable outlet at the bottom 1) 1 9342.514 9342.614 1) Switch outlet or outgoing cable. Busbar systems Page 48 51 Busbar connection adaptors Page 52/53 Connection clamps Page 16 54 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) Spacers for RiLine60 busbar supports (flat busbar system) For adapting 12 x 5 and 12 x 10 size busbars. For busbar supports SV 9340.000/.010 (3-pole), see page 8. SV 9340.004 (4-pole), see page 48. Packs of 12 9340.090 Connection pin for OM and OT adaptors/supports For the mechanical connection of adaptors and supports. PA 6.6 Colour: RAL 5015 Packs of 20 9340.280 Insert strip for OM and OT adaptors/supports To extend the construction width in a 10 pitch pattern. May be bayed as often as required on both sides. With integral cable duct. PA 6.6 Colour: RAL 7035 Supply includes: 6 connection pins. For design Packs of OM 2 9340.290 OT 2 9341.290 Insert strip for circuit-breaker component adaptors To extend the construction width from 140 to 190. Width: 25. ABS Colour: RAL 7035 Note: 4 units (1 set) are needed to widen a component adaptor. For Packs of SV 9342.700 SV 9342.710 4 (1 set) 9342.720 Rittal RiLine60 55

B Rittal RiLine60 busbar systems 800/1600 A (60 ) Sliding blocks for circuit-breaker component adaptor (3-pole) For additional power circuit breakers with more than two attachment points. For circuit-breaker component adaptor SV 9342.500/.510 SV 9342.540/.550 With threaded insert Packs of Model No. SV M3/M4 6 9342.560 SV 9342.600/.610 M4/M5 6 9342.640 Support frame for OM and OT adaptors/supports For use as a spare or for the configuration of replacement assemblies. PA 6.6 For adaptor width 45 For design Width (B) Length (L) Packs of Model No. SV OM 45 170 5 9341.800 OT 45 195 5 9341.810 OM/OT 45 237 5 9341.820 L 5 For adaptor width 55 For design Width (B) Length (L) Packs of Model No. SV OM 55 170 5 9341.830 OT 55 195 5 9341.840 OM/OT 55 237 5 9341.850 8 Support frame with fitted sub-unit, for OM and OT Premium adaptors To prepare spare assemblies with fully prewired motor starters for OM/OT Premium adaptor (SV 9340.900/.910, 9341.900). Connection data of the sub-unit: 3 main contacts (1.5 6 2 ), 690 V~ 8 auxiliary contacts (0.5 2.5 2 ), 300 V~ PA 6.6 Supply includes: Sub-unit, pin block, support bar and support frame support. Packs of 2 9341.970 56 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) Support frame supports for OM adaptors To reinforce support frames 45 x 237 and 55 x 237 for use on OM adaptors. PA 6.6 Packs of 10 9340.800 PinBlock for support frames For reliable attachment and positioning of the contactor on motor starter combinations, for simple clip-on mounting onto the support frame. Individual vertical positioning is achieved by relocating the PinBlock. PA 6.6 For support frames Packs of 45 wide 5 9342.800 55 wide 5 9342.810 PinBlock Plus for starters with increased contactor attachment Mounted by simply clipping onto the PinBlock (SV 9342.800/.810). PA 6.6 Packs of 5 9342.820 Cable set Pre-assembled connection cables for individual connection of switchgear, top-mounted on OM/OT adaptors with tension spring clamps. Length: 130. PVC insulation. Temperature-resistant up to 105 C. Wire ends ultrasonically compressed at both ends. Note: For current carrying capacity of the insulated supply cables, see page 79. Design Packs of AWG 14 = 2.08 2 2.5 2 15 9340.850 AWG 12 = 3.31 2 4 2 15 9340.860 AWG 10 = 5.26 2 6 2 15 9340.870 AWG 8 = 8.37 2 10 2 6 9340.880 AWG 6 = 13.3 2 16 2 6 9340.890 AWG = American Wire Gauges Rittal RiLine60 57

Rittal RiLine60 busbar systems 800/1600 A (60 ) Connection bracket for circuit-breaker component adaptors Pre-assembled, laminated flat copper for connecting standard coercially available moulded case circuit-breakers (MCCB). Electrolyte copper F20 Insulation: Vinyl compound. Temperature resistant up to 105 C. Fire protection corresponding to UL 94-V0. SV 9342.570 Dimensions 1) 6 x 9 x 0.8 For circuit-breaker component adaptor SV 9342.500/.510 SV 9342.540/.550 10 x 15.5 x 0.8 SV 9342.600/.610 10 x 32.0 x 1.0 SV 9342.700/.710 1) Number of lamina x lamina width x lamina thickness 2) 3 = 1 set For connecting moulded case circuit-breakers (MCCB), make (model) Packs of 2) Moeller (NZM1) 3 9342.570 ABB (T3), GE (FE) 3 9342.660 Merlin Gerin (NS100/160/250), Telemecanique (GV7) 3 9342.670 ABB (S3), Moeller (NZM2), Siemens (VL250) 3 9342.680 Siemens (VL160X, VL160) 3 9342.690 ABB (T5) 3 9342.770 ABB (S5), Merlin Gerin (NS400/630) 3 9342.780 Moeller (NZM3) 3 9342.790 SV 9342.660 SV 9342.690 A B 9342.660 26 65 43 9 Ø 10 9342.670 19 66 36 10 Ø 10 9342.680 23 71 40 9 Ø 10 9342.690 23 67 40 11 Ø 7 9342.770 26 51 43 9 Ø 12 9342.780 29 57 46 12 Ø 12 9342.790 28 62 38 14 Ø 12 C D E SV 9342.770 SV 9342.790 ST-Combi connector for OM and OT Premium adaptors May be used as a spare. With tension spring clamp at the outlet end. PA 6.6 Design Packs of 3-pole 1.5 4 2 5 9341.980 8-pole 0.25 2.5 2 5 9341.990 58 Rittal RiLine60

Rittal RiLine60 busbar systems 800/1600 A (60 ) Support rails 35 x 10 for OM and OT adaptors/supports PA 6.6 Supply includes: Assembly screws. For attaching to the adaptor section Design Width Packs of TS 45C 1) 45 5 9342.850 TS 45D 45 5 9342.860 TS 55C 1) 55 5 9342.920 TS 55D 55 5 9342.930 1) With anti-slip guard for motor circuit-breaker. For attaching to the support frame Design Width Packs of TS 45A 1) 45 5 9342.830 TS 45B 45 5 9342.840 TS 45B-V 2) 45 5 9342.870 TS 55A 1) 55 5 9342.900 TS 55B 55 5 9342.910 TS 55B-V 2) 55 5 9342.940 1) With anti-slip guard for motor circuit-breaker. 2) With latch for retrospective locking of the support rail after the switchgear has been assembled. Support rails 35 x 7.5 for OM and OT adaptors/supports For assembly on 55 wide OM and OT adaptors/supports with 10 wide adaptor extension pieces mounted on the right and left. Arrangement of the mounting hole for central configuration on 55 wide adaptor section or support frame. Sheet steel, zinc-plated, passivated Supply includes: Assembly screws and side end brackets. Width Packs of 72 5 9342.980 Support rails 35 x 15 for OM and OT adaptors For attaching to the adaptor section. Sheet steel, zinc-plated, passivated Supply includes: Assembly screws and side end brackets. Width Packs of 45 5 9342.880 55 5 9342.950 Support rail 35 x 15 for component adaptors SV 9342.400/.410 Sheet steel, zinc-plated, passivated Supply includes: Assembly screws and side end brackets. Width Packs of 72 5 9320.120 Rittal RiLine60 59

Rittal RiLine60 busbar systems 800/1600 A (60 ) Support rails 35 x 10 for multi-functional component adaptors PA 6.6 Supply includes: Assembly screws. Width Packs of 45 5 9320.090 54 5 9320.100 Plug-in connector for multi-functional component adaptors (45 construction width) For fitting the AS-interface load feeder module with matching support 3RK1 901-3CA00 (Siemens) to the multi-functional component adaptor. Packs of 1 9320.110 Mounting clip for multi-functional component adaptors (45 construction width) For additional latching of motor starter combinations. Supply includes: Support rails, 45 wide. Packs of 5 9320.140 Cover for NH fused isolators, size 00 Increases contact hazard protection between the strip chassis and the base tray. PVC Colour: RAL 7035 Packs of 2 9341.230 40 50 23 60 Rittal RiLine60

T Rittal RiLine60 busbar systems 800/1600 A (60 ) Identification label support for NH fused isolators, size 00 For clip-on mounting on the isolator housing. Packs of 6 3595.010 Connection space cover for NH isolators For extending the contact hazard protection cover, e.g. when using ring terminals with a long collar. Bayable as required at the top and bottom. Polyamide PA6 B H For NH isolators Packs of Size 00 2 9344.520 Size 1 2 9344.530 Size 2 2 9344.540 Size 3 2 9344.550 W (B) H D (T) 9344.520 106 46 37 9344.530 184 70 42 9344.540 210 70 42 9344.550 250 70 42 Micro-switch for NH isolators/nh fused isolators, size 00 To indicate the switch position of the NH unit (cover). For NH unit Packs of 1 Size 000/size 00 5 3071.000 2 Size 1 3 2 9344.510 1) 1) Plastic lug for attaching the micro-switch to the isolator chassis. 1 2 Mounting set For mounting the NH on-load isolator, size 000, on 35 support rails to DIN EN 60 715 (7.5 /15 high). Packs of 1 3432.000 Rittal RiLine60 61

Rittal RiLine60 busbar systems 800/1600 A (60 ) Lug terminal connection parts for NH fused isolators size 00 For connecting laminated copper bars and round conductors 1.5 to 25 2. Clamping area: 16 x 10. Tightening torque: Terminal screw 4 Nm. Packs of 1 set 3592.020 Clamp-type terminal connection for NH fused isolators size 00 For the connection of round conductors 1.5 to 95 2. Tightening torque: Terminal screw 4 Nm. Packs of 1 set 3592.010 Prism terminals/box terminals for NH isolators, sizes 00 to 3 with screw terminal For direct connection of round and sector-shaped conductors and laminated copper bars. 1 Design For NH isolators Clamping area for laminated copper bars Round conductors Connection Sector-shaped conductors Tightening torque Packs of Model No. SV 1 Prism terminals Size 00 10 70 2 10 70 2 3 Nm 3 9344.600 2 Box terminals Size 1 20 x 14 35 150 2 50 150 2 12 Nm 3 9344.610 Size 2/3 32 x 20 95 300 2 120 300 2 20 Nm 3 9344.620 2 Arc chambers for NH isolators, sizes 1 to 3 To increase switching capacity. Technical specifications: See table NH isolators (utilisation category), page 80. Packs of 3 9344.680 62 Rittal RiLine60

Busbars and accessories Busbars made from E-Cu To DIN EN 13 601. Length: 2400 /bar Dimensions Packs of 12 x 5 6 3580.000 15 x 5 6 3581.000 20 x 5 6 3582.000 25 x 5 6 3583.000 30 x 5 6 3584.000 1) 12 x 10 6 3580.100 15 x 10 6 3581.100 20 x 10 6 3585.000 30 x 10 6 3586.000 1) 1) Tin-plated version available on request. Suitable for TS 8 enclosures For enclosure width Packs of Length (L) 30 x 5 Model No. SV 30 x 10 Model No. SV 300 2 265 9661.335 9661.330 400 2 365 9661.345 9661.340 600 2 565 9661.365 9661.360 800 2 765 9661.385 9661.380 1000 2 965 9661.305 9661.300 1200 2 1165 9661.325 9661.320 Baying bracket E-Cu 4 95 9661.355 9661.350 L 15 15 ø11 SV 9661.300.385 Busbar cover section Contact hazard protection via full encapsulation of the busbars. May be cut to required length. Thermally modified hard PVC. Continuous operating temperature max. 91 C. Fire protection corresponding to UL 94-V0. For busbars 12 x 5 30 x 10 Packs of 10 @ 1 m 20.6 3092.000 40.6 Rittal RiLine60 63

Busbars and accessories Busbar connectors For connecting busbars, no drilling required. SV 9350.075 Top part: St 37, nickel-plated surface finish Base: E-Cu SV 9320.020/SV 9320.030 Top part: Sheet steel, zinc-plated, passivated Contact plate: E-Cu, silver-plated For busbars Single connection 1 2 Application of Baying connection 1) Tightening torque Packs of 12 x 5 15 x 10 5 Nm/15 Nm 2) 3 9350.075 20 x 5 30 x 10 1) From enclosure to enclosure 2) Hex socket Screw M8 = 5 Nm Grub screw M8 = 15 Nm 20 Nm 3 9320.020 3 20 Nm 3 9320.030 A 8 15 100 110 40 45 140 M8 M8 M8 1 2 3 A = max. 10 M8 PLS busbar connectors For connecting the PLS special busbars; no drilling required. E-Cu, nickel-plated For Packs of for system PLS 800 PLS 1600 A Single connection 3 3504.000 3514.000 B Baying connection 1) 3 3505.000 3515.000 Tightening torque 10 15 Nm 15 20 Nm 1) From enclosure to enclosure (TS 8) A B 50 150 8 12 101 110 A B 64 Rittal RiLine60

Busbars/laminated copper bars and accessories A 85 B 85 PLS expansion connectors For thermal and mechanical compensation during connection of PLS special busbars from enclosure to enclosure (TS 8). E-Cu Packs of for system A PLS 800 B PLS 1600 3 9320.060 9320.070 Also required PLS busbar connectors 1) 3504.000 3514.000 1) Two busbar connectors are needed to fit one expansion connector. Note: With a temperature increase of 30 K, the busbars will expand in length by around 0.5 /m. Consequently, the use of an expansion connector is recoended for busbar systems with lengths in excess of 3 m. 101 110 101 110 A B Laminated copper bars Rittal Flexibar S Length: 2000 /bar. Cu lamina High-purity electrolyte copper F20 Insulation High-strength vinyl compound Expansion 370 % Temperature range: 30 C to +105 C Flame retardant version to UL 94-V0 Dielectric strength: 20 kv/ Short-circuit protection diagram, see page 85. Note: Universal support, see page 66. Configuration 1) I n at 50 K 2) I n at 30 K 2) I n at Packs of 10 K 2) 8 x 6.0 x 0.5 165 A 125 A 1 3565.010 6 x 9.0 x 0.8 250 A 220 A 120 A 1 3565.000 6 x 13.0 x 0.5 200 A 150 A 110 A 1 3566.000 4 x 15.5 x 0.8 300 A 210 A 140 A 1 3567.000 6 x 15.5 x 0.8 350 A 290 A 170 A 1 3568.000 10 x 15.5 x 0.8 450 A 350 A 190 A 1 3569.000 5 x 20.0 x 1.0 400 A 300 A 180 A 1 3570.000 5 x 24.0 x 1.0 450 A 370 A 230 A 1 3571.000 10 x 24.0 x 1.0 800 A 600 A 340 A 1 3572.000 5 x 32.0 x 1.0 550 A 470 A 280 A 1 3573.000 10 x 32.0 x 1.0 1000 A 800 A 460 A 1 3574.000 5 x 40.0 x 1.0 800 A 600 A 340 A 1 3575.000 10 x 40.0 x 1.0 1200 A 950 A 500 A 1 3576.000 5 x 50.0 x 1.0 900 A 700 A 400 A 1 3577.000 10 x 50.0 x 1.0 1400 A 1000 A 600 A 1 3578.000 10 x 63.0 x 1.0 1600 A 1240 A 715 A 1 3579.000 1) Number of lamina x lamina width x lamina thickness 2) The conductor temperature of the laminated copper bar is derived by adding the ambient temperature and the temperature increase together. Example: SV 3565.000 loaded with 220 A, i.e. the temperature increases by 30 K. At an ambient temperature of 35 C, this produces a resultant conductor temperature of 35 C + 30 K = 65 C. Rittal RiLine60 65

Laminated copper bars and accessories 15 49 Universal support For the attachment of laminated copper bars from 20 x 5 to 63 x 10. Fibreglass-reinforced, thermoplastic polyester (PBT). Fire protection corresponding to UL 94-V0. Supply includes: Screws and U nuts for mounting on PS/TS mounting rails. Packs of 3 3079.000 Short-circuit protection diagram, see page 85. 23 18 15 30 Universal holder For the attachment of laminated copper bars from 40 x 5 to 100 x 10. Fibreglass-reinforced, thermoplastic polyester (PBT). Fire protection corresponding to UL 94-V0. Supply includes: Screws and sliding nuts for attachment on C rails. Packs of 3 set 3079.010 : C rails 30/15, see Rittal main catalogue. 66 Rittal RiLine60

Technical information Busbar systems Rittal busbar systems When developing the Rittal SV busbar systems and their components, Rittal drew on the latest state of the art and the currently valid standards and regulations. These applications are used by specialist operations worldwide. As well as permanent in-house controls at Rittal, the quality of the SV components is further reinforced by a vast array of tests and approvals. As product development is an on-going process, we reserve the right to make amendments in line with technical progress. Basic regulations for SV busbar systems DIN EN 60 439-1 Low-voltage switchgear combinations Part 1: Type-tested and partially type-tested combinations DIN EN 60 947-1 Low-voltage switchgear Part 1: General specifications DIN EN 60 947-3 Low-voltage switchgear and controlgear: switches, disconnectors, switch disconnectors and fuse combination units DIN EN 60 664-1 Coordination of insulation for electrical operating equipment in low-voltage systems Part 1: Basic principles, requirements and tests DIN EN 60 999-1 Connector parts Electrical copper conductors Safety requirements for screw terminals and screwless terminals General and specific requirements for terminals for conductors from 0.2 2 up to and including 35 2 DIN EN 60 999-2 Connector parts Electrical copper conductors Safety requirements for screw terminals and screwless terminals Part 2: Special requirements for terminals for conductors greater than 35 2 up to and including 300 2 DIN 43 671 Copper busbars, dimensioning for constant current DIN 43 673-1 Busbar drill holes and screw fastenings, busbars with rectangular cross-section DIN EN 60 715 Dimensions of low-voltage switchgear Standardised support rails for the mechanical attachment of electrical components in switching systems DIN EN 13 601 Copper and copper alloys Copper rods and wires for general use in electrical engineering Application of In order to avoid injury and damage to property, SV busbar systems must only be assembled and used by suitably trained and qualified personnel. The valid technical regulations, standards and provisions must, of course, be observed. Users are required to carefully observe the information and instructions supplied by Rittal, and where necessary to forward them to downstream users and/or customers with a special advice note. In particular, the specified tightening torques of electrical terminal connections must be observed in order to achieve an optimum contact pressure. Technical data and catalogue information SV power distribution components are used in conjunction with a wide range of different switchgear and other components for power distribution, and in relation to a wide range of operating and ambient conditions which are outside of Rittal s control. The horizontal position of busbars is considered the standard installation position for the SV busbar system. DIN EN 60 439-1 and the ambient conditions specified therein should be considered the basis for the use of SV power distribution components. At enclosure internal temperatures of > 35 C, application-specific derating should be provided where necessary. Specifically in relation to the temperature limits admissible in DIN EN 60 439-1, the following factors should be critically reviewed: Arrangement of components inside the enclosure Heat loss of the power circuit-breakers and fuses used Passive and/or active climate control measures Connected conductor cross-sections Switching cycles Rittal RiLine60 67

Technical information Short-circuit resistance diagrams Rittal RiLine60 busbar systems Type testing to DIN EN 60 439-1 During the course of system type-testing, the following tests were conducted on the Rittal RiLine60 busbar systems and on representative Rittal RiLine60 top-mounting components: Proof of insulating properties (to DIN EN 60 439-1, 8.2.2) Test piece: Representative system configuration. Test with surge voltage 1.2/50 µs, 9.8 kv. Proof of short-circuit resistance (to DIN EN 60 439-1, 8.2.3) see short-circuit resistance diagrams below. Proof of creepage distances and clearance (to DIN EN 60 439-1, 8.2.5) Test piece: Representative system configuration. Proof of IP protection category (to DIN EN 60 439-1, 8.2.7) Test piece: Representative system configuration. Proven protection category: IP 2X. Busbar supports (3-pole) SV 9340.000/SV 9340.010 60 bar centre distance, for busbars from 15 x 5 30 x 10. Rated operating voltage: up to 690 V AC Rated insulation voltage: 1000 V AC Rated surge voltage: 8 kv Overvoltage category: IV Level of contamination: 3 Rated frequency: 50/60 Hz Test implemented: Rated surge current resistance I pk (see diagram) Ip peak short-circuit current [ka] 80 75 70 65 60 55 50 45 40 35 30 25 20 200 250 b d a c 300 350 400 450 500 550 600 Ip peak short-circuit current [ka] 80 75 70 65 60 55 50 45 40 35 30 25 20 g 200 250 300 350 400 450 500 550 600 f e Rated short-time current resistance I cw Busbar support spacing [] Busbar support spacing [] Busbar I I cw ka 30 x 10 250 37.6 30 x 5 250 25.4 20 x 10 250 29.0 Busbar Curve 30 x 10 a 20 x 10 b 25 x 5 c 15 x 5 d Busbar Curve 30 x 5 e 20 x 5 f 15 x 10 g PLS busbar supports (3-pole) SV 9341.000/SV 9342.000 60 bar centre distance, for PLS special busbars 800 A/1600 A. Rated operating voltage: up to 690 V AC Rated insulation voltage: 1000 V AC Rated surge voltage: 8 kv Overvoltage category: IV Level of contamination: 3 Rated frequency: 50/60 Hz Test implemented: Rated surge current resistance I pk (see diagram) Rated short-time current resistance I cw Ip peak short-circuit current [ka] 80 75 70 b 65 60 55 50 a 45 40 35 30 25 20 100 150 200 250 300 350 400 450 500 Busbar support spacing [] Busbar I I cw ka PLS 800 A 150 25.9 PLS 1600 A 150 37.5 Busbar PLS 800 A PLS 1600 A Curve a b 68 Rittal RiLine60

Technical information Short-circuit resistance diagrams Busbar supports (4-pole) SV 9340.004/SV 9342.014 60 bar centre distance, for 30 x 10 busbars. Rated operating voltage: up to 690 V AC Rated insulation voltage: 1000 V AC Rated surge voltage: 8 kv Overvoltage category: IV Level of contamination: 3 Rated frequency: 50/60 Hz Test implemented: Rated surge current resistance I pk (see diagram) Rated short-time current resistance I cw Ip peak short-circuit current [ka] 115 110 105 100 95 90 85 80 75 70 65 60 55 50 45 40 Busbar 30 x 10 I I cw ka 250 29 500 23 35 30 25 20 200 250 300 350 400 450 500 Busbar support spacing [] PLS busbar supports (4-pole) SV 9342.004 60 bar centre distance, for PLS special busbar 1600 A. Rated operating voltage: up to 690 V AC Rated insulation voltage: 1000 V AC Rated surge voltage: 8 kv Overvoltage category: IV Level of contamination: 3 Rated frequency: 50/60 Hz Test implemented: Rated surge current resistance I pk (see diagram) Rated short-time current resistance I cw Ip peak short-circuit current [ka] 115 110 105 100 95 90 85 80 75 70 65 60 55 50 Busbar PLS 1600 A I I cw ka 250 53 500 38 45 40 35 30 25 20 200 250 300 350 400 450 500 Busbar support spacing [] Rittal RiLine60 69

Technical information Short-circuit resistance diagrams Rittal RiLine60 UL 508 The short-circuit resistance of Rittal RiLine60 has been extensively tested. Short-circuit resistance to UL criteria is assessed via the root-mean-square value of the short-circuit current (I RMS), which must be applied for at least 3 periods. During the course of testing, the test equipment has been adjusted to the respective root-mean-square values (I RMS). The resultant peak short-circuit currents I p are shown in the short-circuit protection diagrams below. Busbar supports (3-pole) 60 bar centre distance, for busbars from 15 x 5 30 x 10. I RMS (I eff.) settings of the test equipment: I I RMS ka 250 35 500 25 SV 9340.050 with 30 x 5/10 I I RMS ka 250 30 500 22 SV 9340.050 with 25 x 5 20 x 5/10 15 x 5/15 80 75 70 80 75 70 Ip peak short-circuit current [ka] 65 60 55 50 45 40 35 30 25 20 Ip peak short-circuit current [ka] 65 60 55 50 45 40 35 30 25 20 200 250 300 350 400 450 500 550 600 Busbar support spacing [] 200 250 300 350 400 450 500 550 600 Busbar support spacing [] PLS busbar supports (3-pole) 60 bar centre distance, for PLS special busbars 800 A/1600 A. I RMS (I eff.) settings of the test equipment: I I RMS ka 200 22 500 14 I I RMS ka 150 35 500 25 SV 9341.050 (PLS 800) SV 9342.050 (PLS 1600) 80 80 75 75 70 70 Ip peak short-circuit current [ka] 65 60 55 50 45 40 35 30 Ip peak short-circuit current [ka] 65 60 55 50 45 40 35 30 25 25 20 20 150 200 250 300 350 400 450 500 550 Busbar support spacing [] 150 200 250 300 350 400 450 500 550 Busbar support spacing [] 70 Rittal RiLine60

Technical information Busbars Rated currents of busbars E-Cu (DIN 43 671) DIN 43 671 specifies the constant currents for busbars at an ambient temperature of 35 C and an average busbar temperature of 65 C. With the aid of a correction factor (k 2), the continuous currents specified in the following table may be adjusted to alternative operating temperatures. For safe operation with thermal reserve, it is advisable to limit the busbar temperature to a maximum of 85 C. However, the decisive factor is the lowest permissible continuous temperature of the components which directly contact the busbar sytem (fuse bases, outgoing cables etc.). The ambient air temperature of the busbars or busbar system should not exceed 40 C; an average of 35 C maximum is recoended. For the continuous temperatures specified in the table, an emission level of 0.4 applies, equivalent to an oxidating copper bar. In modern busbar systems built into enclosures with a protection category of IP 54 and above a more favourable emission level can be assumed. The lower emission level facilitates an additional increase in continuous currents compared with the figures in DIN 43 671, irrespective of the specified air and busbar temperature. Experience has shown an increase in the continuous current of 6 10 % compared with the table figures for uncoated copper bars, and 60 % for surface-oxidised copper bars. Example: For a Cu bar 30 x 10 (E-Cu F30), DIN 43 671 specifies a constant current of I N65 = 573 A. The correction factor diagram for square cross-sections indicates a correction factor k 2 = 1.29 at an air temperature of 35 C and a busbar temperature of 85 C. Thanks to the favourable emission level, the continuous current is increased by a further 6 10 %. In this example, a mean value of 8 % is used. Compared with the table figure from DIN 43 671, the Rittal rated current specification for a Cu bar 30 x 10 is: I N85 = I N65 k 2 + 8 % = 573 A 1.29 1.08 I N85 = 800 A Continuous currents for busbars Made from E-Cu with square cross-section in indoor locations at 35 C air temperature and 65 C bar temperature, vertical position or horizontal position of the bar width. Width x thickness Rittal PLS current load According to DIN 43 671, the correction factor k 2 (correction diagram) is used to correct the basic current with reference to the existing temperatures of the ambient air and the busbar. In accordance with DIN 43 671, the load figures of the Rittal PLS special bars have been determined on the basis of measurement trials, as follows: Rittal RiLine60 Crosssection 2 Weight 1) Material 2) Bare bar AC current up to 60 Hz Continuous current in A Coated bar Bare bar DC current + AC current 16 Hz Coated bar 12 x 2 23.5 0.209 108 123 108 123 15 x 2 29.5 0.262 128 148 128 148 15 x 3 44.5 0.396 162 187 162 187 20 x 2 39.5 0.351 162 189 162 189 20 x 3 59.5 0.529 204 237 204 237 20 x 5 99.1 0.882 274 319 274 320 20 x 10 199.0 1.770 427 497 428 499 25 x 3 74.5 0.663 245 287 245 287 25 x 5 124.0 1.110 327 384 327 384 30 x 3 89.5 0.796 285 337 286 337 30 x 5 149.0 1.330 379 447 380 448 30 x 10 299.0 2.660 E-Cu F30 573 676 579 683 40 x 3 119.0 1.060 366 435 367 436 40 x 5 199.0 1.770 482 573 484 576 40 x 10 399.0 3.550 715 850 728 865 50 x 5 249.0 2.220 583 697 588 703 50 x 10 499.0 4.440 852 1020 875 1050 60 x 5 299.0 2.660 688 826 696 836 60 x 10 599.0 5.330 985 1180 1020 1230 80 x 5 399.0 3.550 885 1070 902 1090 80 x 10 799.0 7.110 1240 1500 1310 1590 1) Calculated with a density of 8.9 kg/dm 3 2) Reference basis for the continuous current levels (figures taken from DIN 43 671) PLS special busbar for 35/75 C Rated current WS 50/60 Hz for 35/65 C (basic value) E-Cu 800 A 800 A 684 A E-Cu 1600 A 1600 A 1368 A Correction factor diagram to DIN 43 671 Factor k2 2.2 0 10 2.0 20 30 1.8 40 1.6 50 60 1.4 1.2 1.0 0.8 0.6 0.4 50 60 70 80 90 100 110 120 2.0 1.8 1.6 1.4 1.2 1.0 0.8 0.6 0.4 Busbar temperature [ C] Correction factor diagram for PLS Factor k2 50 60 70 80 90 100 110 Busbar temperature [ C] 0 10 20 30 40 50 60 70 Ambient temperature [ C] Ambient temperature [ C] 71

Technical information Busbar systems UL 508 Background information UL or Underwriter Laboratory was founded in 1894 as a non-profit-making organisation for testing and certification. UL operates five testing laboratories in the United States and subsidiaries worldwide, with an emphasis on product testing aimed at general safety. Why are UL approvals important? International regulations and standards such as NEMA and IEC are used as a basis by manufacturers for product developments and subsequent testing. Nationally recognised testing laboratories confirm and certify that a product meets specific standards. In North America, this is carried out by organisations such as UL or CSA (Canadian Standard Association). For many applications, only UL and/or CSAapproved products are acceptable. It is therefore advisable to ensure that electrical control systems intended for use in North America are designed with UL-approved components. How does the US system for electrical safety work? Every piece of electrical equipment (machine/plant) is tested by the competent local inspector (AHJ = Authority Having Jurisdiction) prior to coissioning. The AHJ has the final say with regard to coissioning. All AHJs use Standard NFPA 70 (NFPA = National Fire Protection Association) as a basis, which is generally regarded as the NEC (National Electrical Code). NFPA 70 is therefore an important basis for UL 508A (Industrial Control Panels). The AHJ considers the use of UL-recognized or UL-listed components an important indication that a system complies with the safety requirements to NFPA 70. This saves time and money during construction and coissioning of the equipment, as the UL symbol indicates that testing of the components and/or of the system did not reveal any foreseeable risks with regard to fire, electric shock and associated dangers. The UL symbol: UL listed or UL recognized When labelling UL-approved products, a general distinction is made between Recognized Components and Listed Devices: Recognized Components This label is used on products which are not complete in terms of their application. These products are listed in the UL s yellow component database. The correct use of such components must make due allowance for the Conditions of Acceptability, listing the framework conditions and application parameters approved by the UL. Listed Devices This symbol is used in products which offer a complete function in themselves. These products are listed in the UL s green component database. They may be used without restriction in accordance with the tested rating data. Application areas for UL 508 and UL 508A UL 508 describes industrial control components and is therefore the decisive standard for the assessment of Rittal SV components. For example, this standard contains information on: Starters Relays and contactors Switches Controllers UL 508A describes industrial control panels and is therefore the decisive standard for switchgear manufacturers. For example, this standard contains information on: Machine controllers Elevator controllers Crane controllers Equipment for heating, air-conditioning and ventilation systems Both standards describe control systems for general industrial applications with a rated voltage of up to 600 V. The maximum permissible ambient temperature is 40 C. 72 Rittal RiLine60

Technical information Busbar systems UL 508 Background information Distinguishing between feeder and branch circuits Standard UL 508A makes a distinction between feeder circuits and branch & control-circuits. Generally speaking, the term feeder circuits refers to the part of the circuit located at the supply end before the last over-current protective device. Increased requirements with regard to creepage distances and clearances apply to this part of the circuit. The term branch & control-circuits refers to the part of the circuit located after the last over-current protective device. When using busbar systems, it is important to know whether the application is in the feeder section or the branch section, as the requirements governing the required creepage distances and clearances are significantly higher for feeder circuits. Important notes for the use of busbar systems to UL 508/508A 1. Creepage distances and clearances One of the principal changes in UL 508A is the amendment to the required creepage distances and clearances for feeder circuits. The following distances are required for applications > 250 V: Between phases: Creepage distance 50.8 (2 inches) Clearance 25.4 (1 inch) Between phase and earthed, uninsulated metal parts: Creepage distance 25.4 (1 inch) Clearance 25.4 (1 inch) Rittal RiLine60 complies with these requirements. All busbar connection adaptors and component adaptors (OM/OT with standard AWG connection cables and circuit-breaker adaptors) in the new system have been designed in accordance with these requirements. However, users should bear in mind a small number of differences from the IEC version: Special UL busbar supports for flat bars and Rittal PLS with increased creepage distances and clearances. In order to guarantee the required distances between live parts and the earthed mounting plate, the use of a Rittal RiLine60 base tray is compulsory. 2. Rated currents For untested busbar applications, UL 508A specifies a current carrying capacity of 1000 A/inch 2 (1.55 A/ 2 ) in the absence of testing. This value may be higher if the product or application has been subjected to suitable testing. Rittal has conducted extensive testing in this respect in order to give users the maximum benefits when using the SV busbar system. The benefit of such testing is that SV busbar systems with higher rated currents may be used than permitted by the default value. For example, a busbar with the dimensions 30 x 10 can carry 700 A instead of 465 A. 3. Terminals for factory or field wiring In accordance with the UL standards, connection clamps may be approved for factory or field wiring. If a terminal is approved for factory wiring, it may only be used in switchgear assembly by suitably trained professionals. If connection clamps are to be used in the field (e.g. on a construction site), the component must be approved for field wiring. The terminals of the busbar connection adaptors and component adaptors in the Rittal RiLine60 series have therefore been tested for field wiring applications. Rittal RiLine60 73

Technical information Components with UL 508 approvals Model No. SV For feeder circuits up to 600 V Rated current 3509.000 3516.000 3524.000 3525.000 3525.010 3526.000 3527.000 3528.000 3528.010 3529.000 3581.000 3581.100 3582.000 3583.000 3584.000 3585.000 3586.000 9340.050 9340.070 9340.100 9340.110 9340.120 9340.130 9340.140 9340.150 9340.160 9340.200 9340.210 9340.220 9340.260 9340.270 9340.310 25 A 9340.340 25 A 9340.350 30 A 9340.370 25 A 9340.410 60 A 9340.430 60 A 9340.450 60 A 9340.460 30 A 9340.700 60 A 9340.710 40 A 9341.050 9341.070 9341.100 9341.110 9341.120 9341.130 9341.140 9341.150 9341.160 9341.260 9341.270 9341.310 25 A 9341.340 25 A 9341.370 25 A 9341.410 60 A 9341.430 60 A 9341.450 60 A 9341.460 30 A 9342.050 9342.070 9342.100 9342.110 Model No. SV For feeder circuits up to 600 V Rated current Specification to UL Connection cross-section 9342.120 9342.130 9342.140 9342.150 9342.160 9342.200 1) 60 A 6 16 2 (AWG 10 AWG 6) 9342.210 1) 60 A 6 16 2 (AWG 10 AWG 6) 9342.230 1) 125 A 16 35 2 (AWG 6 AWG 2) 9342.240 1) 125 A 16 35 2 (AWG 6 AWG 2) 9342.250 1) 250 A 35 120 2 (AWG 2 MCM250) 9342.260 1) 250 A 35 120 2 (AWG 2 MCM250) 9342.270 1) 250 A 35 120 2 (AWG 2 MCM250) 9342.290 1) 800 A 95 300 2 (AWG 4/0 MCM600) 9342.300 1) 800 A 95 300 2 (AWG 4/0 MCM600) 9342.310 700 A 95 300 2 (AWG 4/0 MCM600) Clamping area for laminated copper: 33 x 22 9342.320 1400 A Clamping area for laminated copper: 65 x 22 9342.400 1) 100 A 16 35 2 (AWG 6 AWG 2) 9342.410 1) 100 A 16 35 2 (AWG 6 AWG 2) 9342.540 1) 125 A 35 120 2 (AWG 2 MCM250) 9342.550 1) 125 A 35 120 2 (AWG 2 MCM250) 9342.600 1) 250 A 35 120 2 (AWG 2 MCM250) 9342.610 1) 250 A 9342.700 600 A 9342.710 600 A 1) Tightening torque to UL 35 120 2 (AWG 2 MCM250) Clamping area for laminated copper: 32 x 10 Clamping area for laminated copper: 32 x 10 Model No. Terminal screw for SV round conductors laminated copper bars 9342.200 5 Nm 9342.210 5 Nm 9342.230 5 Nm 5 Nm 9342.240 5 Nm 5 Nm 9342.250 12 Nm 8 Nm 9342.260 12 Nm 8 Nm 9342.270 12 Nm 8 Nm 9342.290 18 Nm 14 Nm 9342.300 18 Nm 14 Nm 9342.400 5 Nm 5 Nm 9342.410 5 Nm 5 Nm 9342.540 12 Nm 8 Nm 9342.550 12 Nm 8 Nm 9342.600 12 Nm 8 Nm 9342.610 12 Nm 8 Nm 74 Rittal RiLine60

Technical information Allocation of switchgear OM adaptor with tension spring clamp Page 22/23 For make/model ABB Moeller Electric Reversing Reversing MCB Starters MCB Starters Starter Starter MS-116 MS-225 MS-325 MS-450 MS-116 B6-7, A9-16 MS-225 B6-7, A9-A12-A16 MS-325 B6-7, A9-A12-A16, A26-30 MS-450 A30-A40-A50 MS-116 B6-7, A9-16 MS-225 B6-7, A9-A12-A16 MS-325 B6-7, A9-A12-A16, A26-30 MS-450 A30-A40-A50 PKZM0 PKZM01 PKZM4 PKZM0 + DILM7-9 PKZM0 + DILM12-32 PKZM4 + DILM17-65 PKZM0 + DILM7-9 PKZM0 + DILM12-32 PKZM4 + DILM17-65 Construction width Construction width 45 54 54 55 48 54 54 70 90 110 110 140 45 45 55 45 45 55 90 90 110 Design Required quantity (units) Required quantity (units) 9340.530 OM adaptor 32 A, 690 V~, 1.5 6 2 1) 1 1 1 1 1 9340.550 OM adaptor 32 A, 690 V~, 1.5 6 2 1) 1 1 1 1 9340.630 OM adaptor 65 A, 690 V~, 2.5 16 2 2) 1 1 9340.650 OM adaptor 65 A, 690 V~, 2.5 16 2 2) 1 1 1 1 9340.660 OM adaptor 32 A, 690 V~, 1.5 6 2 2) 1 1 1 1 1 1 9340.260 OM support, 45 wide 1 1 1 9340.270 OM support, 55 wide 1 1 1 1 9340.290 Insert strip, 10 wide 2 3 9340.280 Connection pin 3 3 3 3 3 3 3 9340.860 Cable set AWG 12 3 3 3 3 3 3 3 3 3 9340.870 Cable set AWG 10 3 3 3 3 3 3 9340.890 Cable set AWG 6 3 3 3 3 3 3 9342.840 Support rail TS45 B 1 1 1 9342.870 Support rail TS45 B-V 1 2 9342.940 Support rail TS55 B-V 1 1 1 1 1) 45 construction width 2) 55 construction width For make/model Siemens Telemecanique (Schneider Electric) Reversing Reversing MCB Starters MCB Starters Starter Starter S00 S0 S2 S00 + S00 S0 + S0 S2 + S2 S00 + S00 S0 + S0 S2 + S2 GV2-ME GV2-P LUB12 GV3 to 65 A GV2-P + LC1K AC GV2-P + LC1K DC GV2-ME + LC1D AC GV2-ME + LC1D DC GV3 + LC1D65 GV2-P + LC2K AC GV2-P + LC2K DC GV2-ME + LC2D AC GV2-ME + LC2D DC Construction width Construction width 45 45 55 45 45 55 90 100 120 45 45 45 62 45 45 45 45 62 90 90 90 90 Design Required quantity (units) Required quantity (units) 9340.530 OM adaptor 32 A, 690 V~, 1.5 6 2 1) 1 1 1 1 1 9340.550 OM adaptor 32 A, 690 V~, 1.5 6 2 1) 1 1 1 1 1 1 1 1 1 1 1 1 9340.630 OM adaptor 65 A, 690 V~, 2.5 16 2 2) 1 1 9340.650 OM adaptor 65 A, 690 V~, 2.5 16 2 2) 1 1 1 9340.260 OM support, 45 wide 1 1 1 1 1 1 9340.270 OM support, 55 wide 1 9340.290 Insert strip, 10 wide 1 1 1 1 9340.280 Connection pin 3 3 3 3 3 3 3 9340.860 Cable set AWG 12 3 3 3 9340.870 Cable set AWG 10 3 3 3 3 3 3 3 3 3 3 3 3 3 3 9340.890 Cable set AWG 6 3 3 3 3 3 9342.820 PinBlock Plus 1 1 2 2 1) 45 construction width 2) 55 construction width Rittal RiLine60 75

Technical information Allocation of switchgear OM adaptor with connection cables Page 24/25 For make/model ABB Moeller Electric Reversing Reversing MCB Starters MCB Starters Starter Starter MS-116 MS-225 MS-325 MS-450 MS-116 B6-7, A9-16 MS-225 B6-7, A9-A12-A16, A26-30 MS-325 B6-7, A9-A12-A16, A26-30 MS-450 A30-A40-A50 MS-116 B6-7, A9-16 MS-225 B6-7, A9-A12-A16, A26-30 MS-325 B6-7, A9-A12-A16, A26-30 MS-450 A30-A40-A50 PKZM0 PKZM01 PKZM4 PKZM0 + DILM7-9 PKZM0 + DILM12-32 PKZM4 + DILM17-65 PKZM0 + DILM7-9 PKZM0 + DILM12-32 PKZM4 + DILM17-65 Construction width Construction width 45 54 54 55 48 54 54 70 45 110 110 140 45 45 55 45 45 55 90 90 110 Design Required quantity (units) Required quantity (units) 9340.340 OM adaptor 25 A, 690 V~, AWG 12 1) 1 1 9340.370 OM adaptor 25 A, 690 V~, AWG 12 1) 1 1 1 9340.430 OM adaptor 65 A, 690 V~, AWG 6 2) 1 1 9340.450 OM adaptor 65 A, 690 V~, AWG 6 2) 1 1 1 1 9340.350 OM adaptor 32 A, 690 V~, AWG 10 1) 1 1 9340.380 OM adaptor 32 A, 690 V~, AWG 10 1) 1 1 9340.460 OM adaptor 32 A, 690 V~, AWG 10 2) 1 1 9340.470 OM adaptor 32 A, 690 V~, AWG 10 2) 1 1 1 1 9340.260 OM support, 45 wide 1 1 1 9340.270 OM support, 55 wide 1 1 1 1 9340.290 Insert strip, 10 wide 2 3 9340.280 Connection pin 3 3 3 3 3 3 3 9342.840 Support rail TS45 B 1 1 9342.870 Support rail TS45 B-V 1 1) 45 construction width 2) 55 construction width For make/model Siemens Telemecanique (Schneider Electric) Reversing Reversing MCB Starters MCB Starters Starter Starter S00 S0 S2 S00 + S00 S0 + S0 S2 + S2 S00 + S00 S0 + S0 S2 + S2 GV2-ME GV2-P LUB12 LUB32 GV3 to 65 A GV2-P + LC1K AC GV2-P + LC1K DC GV2-ME + LC1K AC GV2-ME + LC1K DC GV3 + LC1D65 GV2-P + LC2K AC GV2-P + LC2K DC GV2-ME + LC2K AC GV2-ME + LC2K DC Construction width Construction width 45 45 55 45 45 55 90 100120 45 45 45 45 62 45 45 45 45 62 90 90 90 90 Design Required quantity (units) Required quantity (units) 9340.340 OM adaptor 25 A, 690 V~, AWG 12 1) 1 1 1 1 1 9340.370 OM adaptor 25 A, 690 V~, AWG 12 1) 1 1 1 1 9340.350 OM adaptor 32 A, 690 V~, AWG 10 1) 1 1 1 1 1 1 1 1 1 1 1 1 9340.380 OM adaptor 32 A, 690 V~, AWG 10 1) 1 1 1 1 9340.430 OM adaptor 65 A, 690 V~, AWG 6 2) 1 1 9340.450 OM adaptor 65 A, 690 V~, AWG 6 2) 1 1 1 9340.260 OM support, 45 wide 1 1 1 1 1 1 9340.270 OM support, 55 wide 1 9340.290 Insert strip, 10 wide 1 1 1 1 9340.280 Connection pin 3 3 3 3 3 3 3 9342.800 PinBlock 45 1 9342.820 PinBlock Plus 1 1 2 2 1) 45 construction width 2) 55 construction width 76 Rittal RiLine60

Technical information Allocation of switchgear OT adaptor with tension spring clamp Page 26 For make/model ABB Moeller Electric Reversing Reversing MCB Starters MCB Starters Starter Starter MS-116 MS-225 MS-325 MS-450 MS-116 B6-7, A9-16 MS-225 B6-7, A9-A12-A16 MS-325 B6-7, A9-A12-A16-A30 MS-450 A30-A40-A50 MS-116 B6-7, A9-16 MS-225 B6-7, A9-A12-A16 MS-325 B6-7, A9-A12-A16-A30 MS-450 A30-A40-A50 PKZM0 PKZM01 PKZM4 PKZM0 + DILM7-9 PKZM0 + DILM12-32 PKZM4 + DILM17-65 PKZM0 + DILM7-9 PKZM0 + DILM12-32 PKZM4 + DILM17-65 Construction width Construction width 45 54 54 55 45 54 54 70 45 110 110 110 45 45 55 45 45 55 90 90 110 Design Required quantity (units) Required quantity (units) 9341.530 OT adaptor 32 A, 690 V~, 1.5 6 2 1) 1 1 1 1 1 9341.550 OT adaptor 32 A, 690 V~, 1.5 6 2 1) 1 1 1 1 9341.630 OT adaptor 65 A, 690 V~, 2.5 16 2 2) 1 1 9341.650 OT adaptor 65 A, 690 V~, 2.5 16 2 2) 1 1 1 1 9341.660 OT adaptor 32 A, 690 V~, 1.5 6 2 2) 1 1 1 1 1 1 9341.260 OM support, 45 wide 1 1 1 9341.270 OM support, 55 wide 1 1 1 1 9341.290 Insert strip, 10 wide 2 3 9340.280 Connection pin 4 4 4 4 4 4 4 9340.860 Cable set AWG 12 3 3 3 3 3 3 3 3 3 9340.870 Cable set AWG 10 3 3 3 3 3 3 9340.890 Cable set AWG 6 3 3 3 3 3 3 9342.840 Support rail TS45 B 1 1 1 9342.870 Support rail TS45 B-V 1 2 9342.940 Support rail TS55 B-V 1 1 1 1 1) 45 construction width 2) 55 construction width For make/model Siemens Telemecanique (Schneider Electric) Reversing Reversing MCB Starters MCB Starters Starter Starter S00 S0 S2 S00 + S00 S0 + S0 S2 + S2 S00 + S00 S0 + S0 S2 + S2 GV2-ME GV2-P LUB12 GV3 to 65 A GV2-P + LC1K AC GV2-P + LC1K DC GV2-ME + LC1D AC GV2-ME + LC1D DC GV3 + LC1D65 GV2-P + LC2K AC GV2-P + LC2K DC GV2-ME + LC2D AC GV2-ME + LC2D DC Construction width Construction width 45 45 55 45 45 55 90 100 120 45 45 45 62 45 45 45 45 62 90 90 90 90 Design Required quantity (units) Required quantity (units) 9341.530 OT adaptor 32 A, 690 V~, 1.5 6 2 1) 1 1 1 1 1 9341.550 OT adaptor 32 A, 690 V~, 1.5 6 2 1) 1 1 1 1 1 1 1 1 1 1 1 1 9341.630 OT adaptor 65 A, 690 V~, 2.5 16 2 2) 1 1 9341.650 OT adaptor 65 A, 690 V~, 2.5 16 2 2) 1 1 1 9341.260 OM support, 45 wide 1 1 1 1 1 1 9341.270 OM support, 55 wide 1 9341.290 Insert strip, 10 wide 1 1 1 1 9340.280 Connection pin 4 4 4 4 4 4 4 9340.860 Cable set AWG 12 3 3 3 9340.870 Cable set AWG 10 3 3 3 3 3 3 3 3 3 3 3 3 3 3 9340.890 Cable set AWG 6 3 3 3 3 3 9342.820 PinBlock Plus 1 1 2 2 1) 45 construction width 2) 55 construction width Rittal RiLine60 77

Technical information Allocation of switchgear OT adaptor with connection cables Page 27 For make/model ABB Moeller Electric Reversing Reversing MCB Starters MCB Starters Starter Starter MS-116 MS-225 MS-325 MS-450 MS-116 B6-7, A9-16 MS-225 B6-7, A9-A12-A16 MS-325 B6-7, A9-A12-A16-A30 MS-450 A30-A40-A50 MS-116 B6-7, A9-16 MS-225 B6-7, A9-A12-A16 MS-325 B6-7, A9-A12-A16-A30 MS-450 A30-A40-A50 PKZM0 PKZM01 PKZM4 PKZM0 + DILM7-9 PKZM0 + DILM12-32 PKZM4 + DILM17-65 PKZM0 + DILM7-9 PKZM0 + DILM12-32 PKZM4 + DILM17-65 Construction width Construction width 45 54 54 55 45 54 54 70 45 110 110 110 45 45 55 45 45 55 90 90 110 Design Required quantity (units) Required quantity (units) 9341.340 OT adaptor 25 A, 690 V~, AWG 12 1) 1 1 1 1 1 9341.370 OT adaptor 25 A, 690 V~, AWG 12 1) 1 1 1 1 9341.430 OT adaptor 65 A, 690 V~, AWG 6 2) 1 1 9341.450 OT adaptor 65 A, 690 V~, AWG 6 2) 1 1 1 1 9341.460 OT adaptor 32 A, 690 V~, AWG 10 2) 1 1 1 1 1 1 9341.260 OM support, 45 wide 1 1 1 9341.270 OM support, 55 wide 1 1 1 1 9341.290 Insert strip, 10 wide 2 3 9340.280 Connection pin 4 4 4 4 4 4 4 9342.840 Support rail TS45 B 1 1 1 9342.870 Support rail TS45 B-V 1 2 9342.940 Support rail TS55 B-V 1 1 1 1 1) 45 construction width 2) 55 construction width For make/model Siemens Telemecanique (Schneider Electric) Reversing Reversing MCB Starters MCB Starters Starter Starter S00 S0 S2 S00 + S00 S0 + S0 S2 + S2 S00 + S00 S0 + S0 S2 + S2 GV2-ME GV2-P LUB12 GV3 to 65 A GV2-P + LC1K AC GV2-P + LC1K DC GV2-ME + LC1D AC GV2-ME + LC1D DC GV3 + LC1D65 GV2-P + LC2K AC GV2-P + LC2K DC GV2-ME + LC2K AC GV2-ME + LC2K DC Construction width Construction width 45 45 55 45 45 55 90 100 120 45 45 45 62 45 45 45 45 62 90 90 90 90 Design Required quantity (units) Required quantity (units) 9341.340 OT adaptor 25 A, 690 V~, AWG 12 1) 1 1 1 1 1 9341.370 OT adaptor 25 A, 690 V~, AWG 12 1) 1 1 1 1 1 1 1 1 1 1 1 1 9341.430 OT adaptor 65 A, 690 V~, AWG 6 2) 1 1 9341.450 OT adaptor 65 A, 690 V~, AWG 6 2) 1 1 1 9341.260 OM support, 45 wide 1 1 1 1 1 1 9341.270 OM support, 55 wide 1 9341.290 Insert strip, 10 wide 1 1 1 1 9340.280 Connection pin 4 4 4 4 4 4 4 9342.820 PinBlock Plus 1 1 2 2 1) 45 construction width 2) 55 construction width 78 Rittal RiLine60

Technical information Allocation of switchgear Multi-functional component adaptor 12 A/25 A Page 35/36 Make/model For bar thickness 5 10 ABB MS116-.. 9320.180 9320.190 AEG Mbs25 9320.180 9320.190 Allen Bradley 103-...R 107-...R 140M-...-... 140-MN-... 190-M1-... 190-M2-... Moeller Electric PKM0... PKZM0-... PKZM0-...T PKZM0-../0.-. PKZM0.../E01-G-W PKZM0-../E-10-D PKZM0-../S00-11 PKZM0-../SE00-11 PKZM0-.../.-..-W PKZM0-.../.-..WMF Siemens S0 3RA11 20-...2.-0... 3RA12 20-...-... 3RV1. 21-...1. 3RW30 2.-1AB.. S00 3RA11 10...1.-1... 3RA12 10-...-... 3RV10 11-..A1. 3RW30 1.-1CB.4 S00 Cage Clamp 3RV10 11-..A20 Telemecanique GV2-... GV2-M..K1.. GV2-M..K2.. GV2-P..D1.. GV2-P..D2.. LD1-L.030 (max. 25 A) LH4-N1...7 LH4-N2...7 9320.180 9320.380 9320.180 9320.180 9320.440 9320.440 9320.180 9320.180 9320.180 9320.180 9320.380 9320.180 9320.180 9320.200 9320.380 9320.420 1) 9320.180 9320.400 9320.180 9320.180 9320.180 9320.380 1) 9320.180 9320.180 9320.160 9320.180 9320.180 9320.380 9320.440 9320.420 2) 9320.180 9320.180 9320.380 9320.190 9320.390 9320.190 9320.190 9320.450 9320.450 9320.190 9320.190 9320.190 9320.190 9320.390 9320.190 9320.190 9320.210 9320.390 9320.430 1) 9320.190 9320.410 9320.190 9320.190 9320.190 9320.390 1) 9320.190 9320.190 9320.170 9320.190 9320.190 9320.390 9320.450 9320.430 2) 9320.190 9320.190 9320.390 9320.140 9320.140 9320.140 9320.140 1) The bottom support rail is eliminated 2) The upper support rail is offset at a distance of 125 from the lower support rail (support rail centre-to-centre spacing) Multi-functional component adaptor 40 A Page 37 Make/model 5 For bar thickness 10 ABB MS25-TM-.. MS225-.. MS325-.. MS450-.. (max. 40 A) MS451-.. (max. 40 A) DLA..-30 9320.300 1) 9320.300 1) 9320.300 1) 9320.460 9320.460 9320.300 2) 9320.310 1) 9320.310 1) 9320.310 1) 9320.470 9320.470 9320.310 2) AEG Mbs28 9320.300 1) 9320.310 1) Allen Bradley 140M-F8.-... (max. 40 A) 9320.300 1) 9320.310 1) Moeller Electric PKZM4-... (max. 40 A) 9320.460 9320.470 Siemens S2 3RV1. 31-4..10 (max. 40 A) 3RW30 3.-1AB.. (max. 40 A) 1) The bottom support rail is eliminated 2) The top support rail is eliminated 9320.460 9320.460 9320.470 9320.470 Current carrying capacity of connection cables Current carrying capacity of insulated PVC cables at an ambient temperature of +40 C, installation type E (DIN EN 60 204-1:1998-11) Nominal cross-section ( 2 ) Current capacity (A) 1.5 16 2.5 22 4 30 6 37 10 52 16 70 25 88 35 114 Conversion factors for the load capacity of cables (DIN EN 60 204-1:1998-11) Ambient temperature ( C) Factor 30 1.15 35 1.08 40 1.00 45 0.91 50 0.82 55 0.71 60 0.58 Rittal RiLine60 79

Technical information Rittal RiLine NH NH fused isolators, size 00 Reliable isolated or off-load position of the switch cover unit, thanks to the integral multi-function key. Switch may be locked via the installation of padlocks in the closed and isolated position. For inspection purposes, there are viewing windows with integral holes in the switch cover unit or sliding viewing windows. Simple external/internal mounting of microswitches to indicate the switch position of the NH unit (lid unit). Technical specifications to VDE 0660, part 107/IEC 60 947-3 Size (NH fuse inserts to DIN 43 620) Rated operating current I e Conventional thermal current I th Rated operating voltage U e Rated insulation voltage U i Rated surge voltage resistance U imp Conditional rated short-circuit current when protected with fuses Rated breaking capacity to VDE 0660, part 107/IEC 60 947-3 (utilisation category) 400 V 690 V Size 00 160 A 160 A AC 690 V 800 V 8 kv 50 ka AC-22B I e = 160 A AC-21B I e = 160 A Mechanical life (switching cycles) 1600 Permissible ambient temperature 25 C to +55 C Fire protection corresponding to UL 94-V0 P v max./fuse insert 12 W NH isolators, size 000 to 3 Technical specifications IEC 60 947-3 Size (NH fuse inserts to VDE 0636-201) Size 000 Size 00 Size 1 Size 2 Size 3 Rated operating current I e 100 A, 160 A 4) 160 A 250 A 400 A 630 A Rated operating voltage U e 690 V AC 690 V AC 1) 690 V AC 1) 690 V AC 1) 690 V AC 1) Rated insulation voltage U i 690 V 1000 V 1000 V 1000 V 1000 V Rated surge voltage resistance U imp 6 kv 8 kv 1) 8 kv 1) 8 kv 1) 8 kv 1) Rated frequency 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz Conditional rated short-circuit current at 690 V AC 80 ka 80 ka 80 ka 50 ka 80 ka (when protected with fuses) at 500 V AC 80 ka 80 ka 80 ka 80 ka 400 V AC AC-22B (I e = 100 A) AC-23B AC-23B (AC-23B 2) ) AC-23B (AC-23B 2) ) AC-23B (AC-23B 2) ) 500 V AC AC-22B AC-23B (AC-23B 2) ) AC-22B (AC-23B 2) ) AC-22B (AC-23B 2) ) Utilisation category 690 V AC AC-21B (I e = 100 A) AC-21B AC-22B (AC-23B 2) ) AC-21B (AC-23B 2) ) AC-21B (AC-23B 2) ) 220 V DC 3) DC-22B DC-21B (DC-22B 2) ) DC-21B (DC-22B 2) ) DC-21B (DC-22B 2) ) 440 V DC 3) DC-21B (I e = 100 A) DC-22B 2) DC-22B 2) DC-22B 2) Mechanical life (switching cycles) 2000 1400 1400 800 800 Electrical life (switching cycles) 200 200 200 200 200 Permissible ambient temperature 25 C to +55 C 20 C to +60 C 20 C to +60 C 20 C to +60 C 20 C to +60 C P v max./fuse insert 7.5 W (9 W) 4) 12 W 23 W 34 W 48 W 1) When using NH isolators with electronic or electromechanical fuse monitoring, the rating data in the table Electronic and electromechanical fuse monitoring will apply, see page 81. 2) With arcing chambers ( 9344.680) for increased switching capacity. 3) DC application with population of phase L 1 and L 3. 4) For 95 2 connection cross-section (95 2 connection pieces available on request). 80 Rittal RiLine60

Technical information Rittal RiLine NH Electronic and electromechanical fuse monitoring Technical specifications Electronic fuse monitoring Electromechanical fuse monitoring Rated operating voltage U e AC 400 V to AC 500 V (50/60 Hz) AC 24 V to AC 690 V (50/60 Hz) DC 24 V to DC 250 V Rated surge voltage resistance U imp 3.5 kv 6 kv Response time < 0.5 s < 2 s Auxiliary contacts 1 NO, 1 NC 1 NO, 1 NC Load capacity of auxiliary contacts 5 A 4 A Permissible ambient temperature 20 C to +60 C 20 C to +60 C Display LED constantly green (operational) 13/14: open 21/22: solid LED flashing red (error message) 13/14: closed 21/22: open Rocker switch position 1 (operational) 13/14: closed 21/22: open Rocker switch position 0 (error message) 13/14: open 21/22: Solid Connection of auxiliary contacts Terminal up to 1.5 2 Terminal up to 1.5 2 NH fuse inserts With contacted, live puller lugs Wiring diagram L1 L2 L3 22 21 13 14 Function block 13 11 12 14 1 L1 3 L2 5 L3 22 13 21 14 2 T1 4 T2 6 T3 LED LED Electronic fuse monitoring Electromechanical fuse monitoring Rittal RiLine60 81

Technical information Rittal RiLine NH Easy changeover of the cable outlet The uniform design of the RiLine NH generation of isolators combines optimum functionality with an attractive design. This feature supports system-compatible integration into the RiLine60 contact hazard protection concept with base tray. In just 3 seconds, the same device may be used to swap the cable outlet from top to bottom for all RiLine NH bus-mounting onload isolators by simply rotating the mounting hook. In this way, there is no need to decide whether the cable outlet will go at the top or bottom until iediately prior to assembly. This function offers a clear benefit for customers, by halving the required warehousing and associated costs. Cable outlet at the bottom Rotating the mounting hook Cable outlet at the top User-friendly box terminal for all sizes as standard In addition to the current market standard connection using screws or bolts, the new Rittal RiLine NH isolator range alternatively offers all sizes as standard with a userfriendly box terminal for inexpensive, timesaving connection of round and sectorshaped conductors. This saves the expensive labour costs for preparing the wire ends as well as the material costs of ring terminals. All RiLine NH isolators with screw connection may optionally be retro-fitted with box or prism terminals. Here too, all torques are directly visible either on the unit itself or on the terminals. All RiLine NH isolators size 1 or above and all box and prism terminals from the accessory range still support the connection of round and sector-shape conductors made from Cu or Al (aluminium conductor connections must be checked at regular intervals). Conductor version Code Standard designation Single-wire e sol (solid) Multi-wire m s (stranded) Round single-wire re sol Round multi-wire rm s Sector single-wire enclosures sol Sector multi-wire sm s Fine-wire f f (flexible) Lid lock and seal All designs have a screwdriver-operated lock as standard, to prevent unintentional opening of the isolator lid. In addition, the lock position may also be sealed with sealing wire. Lid lock Lid seal 82 Rittal RiLine60

Technical information Rittal RiLine NH Electronic fuse monitoring Electronic fuse monitoring has a test button for easy simulation of a defective fuse during coissioning. The auxiliary power for the electronics is generated from the input side of the three-phase network. For technical reasons, the rated frequency of the supplying network (see technical specifications on page 81) must not be exceeded, otherwise the electronic fuse monitor will be damaged. Use in conjunction with motors in frequency converter mode is one such example. In such cases, electronic fuse monitoring must only be used as rotary current fusing for the frequency converter on the input side, and not in the frequency-modulated motor supply leads. A green and a red LED display indicate the operating status of the electronic fuse monitor. Details of how to evaluate the LEDs and the floating alarm contacts may be found in the technical specifications. In the event of a mains failure or if the isolator lid is opened, the current operating status of the alarm contacts is retained. Note: In order to ensure fault-free operation, all fuses must be properly installed in accordance with the above conditions, since all the required measuring signals are measured from the puller lugs. Electromechanical fuse monitoring The isolator lids may be removed by simply loosening the connection. Unlike electronic monitoring, this system operates without auxiliary power, yet still performs the same functions. The rocker switch on the operating housing additionally provides a visual display of the operating status. Note: The fuses used MUST be designed with live puller lugs. Simple signalling of the switching position with micro-switches All sizes have the option of accoodating micro-switches to indicate the switching position. The micro-switch simply clips into the relevant position in the isolator chassis. Two microswitch locators are available as standard for each device. This allows the switching position of the isolator lid to be counicated to a PLC, while using the second micro-switch to operate the load contactor at the same time. The micro-switch wiring is routed through the device to the rear or through the pre-punched knock-out of the contact hazard protection cover plates. Size 00 Sizes 1 to 3 Cable gland Rittal RiLine60 83

Technical information Rittal RiLine NH Comprehensive contact hazard protection Comprehensive contact hazard protection ensures the highest standards of safety, coupled with superior user-friendliness. Safe switching with integral hand protection. Optional plug-in connection space covers (see accessories) to enlarge the connection space e.g. when using ring terminals with a long press sleeve. Versatile cut-out options in the cable entry area. Perfect all-round protection in conjunction with the Rittal RiLine60 base tray. Design Front with lid closed Front with lid open IP protection category IP 20 IP 10 Top-mounting of supports even with flat bars The panels (removable at the side) allow top-mounting of Rittal RiLine60 busbar supports for all flat bars, enabling very compact configuration of the units. In conjunction with the super-slimline design, this allows a space-saving configuration. Arc chambers to increase switching capacity for NH isolators, size 1 3 Technical specifications: See table NH isolators (utilisation category), page 80. 1. Removing the plastic bar 2. Clipping the arc chambers into position 84 Rittal RiLine60

l l l Laminated copper bars Rittal Flexibar S Configuration 1) I n at 50 K 2) I n at 30 K 2) Technical information I n at 10 K 2) Laminated copper bars Curve (short-circuit resistance) Installation type 8 x 6.0 x 0.5 165 A 125 A 3565.010 6 x 9.0 x 0.8 250 A 220 A 120 A 3565.000 6 x 13.0 x 0.5 200 A 150 A 110 A 3566.000 4 x 15.5 x 0.8 300 A 210 A 140 A 3567.000 6 x 15.5 x 0.8 350 A 290 A 170 A a 1 3568.000 10 x 15.5 x 0.8 450 A 350 A 190 A a 1 3569.000 5 x 20.0 x 1.0 400 A 300 A 180 A a 1 3570.000 5 x 24.0 x 1.0 450 A 370 A 230 A a 1 3571.000 10 x 24.0 x 1.0 800 A 600 A 340 A b 1 3572.000 5 x 32.0 x 1.0 550 A 470 A 280 A b 2/3 3573.000 10 x 32.0 x 1.0 1000 A 800 A 460 A c 2/3 3574.000 5 x 40.0 x 1.0 800 A 600 A 340 A b 2/3 3575.000 10 x 40.0 x 1.0 1200 A 950 A 500 A c 2/3 3576.000 5 x 50.0 x 1.0 900 A 700 A 400 A b 2/3 3577.000 10 x 50.0 x 1.0 1400 A 1000 A 600 A c 2/3 3578.000 10 x 63.0 x 1.0 1600 A 1240 A 715 A d 2/3 3579.000 1) Number of lamina x lamina width x lamina thickness 2) The conductor temperature of the laminated copper bar is derived by adding the ambient temperature and the temperature increase together. Example: SV 3565.000 loaded with 220 A, i.e. the temperature increases by 30 K. At an ambient temperature of 35 C, this produces a resultant conductor temperature of 35 C + 30 K = 65 C. Short-circuit resistance diagram Basis of test: VDE 0660, part 500/IEC 60 439-1. Test implemented: Dynamic short-circuit resistance to IEC 60 439-1. The dimensions for the support spacing (l) and for the centre-tocentre spacing (a) must be within the specified min./max. limits. The quotients of l/a can be used to determine the permissible short-circuit current I p by using curves a to d. The prescribed installation type must be taken into account. Ip short-circuit current [ka] 90 80 70 60 50 40 30 1.5 d c b a 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 x Support spacing (l) x = Centre-to-centre spacing [a] Curve a b c d Support spacing (l) Centre-to-centre spacing (a) min. max. min. max. 150 300 34 60 150 350 42 85 200 400 51 85 200 450 81 100 Type of assembly with universal support SV 3079.000 1 2 3 a a a Rittal RiLine60 85

List of model numbers Model No. Page 3071.000 61 3079.000 66 3079.010 66 3086.000 16 3087.000 16 3088.000 16 3090.000 16 3091.000 16 3092.000 63 3093.000 40, 41 3418.000 40 3419.000 40 3420.000 40 3420.010 40 3421.000 40 3422.000 41 3423.000 41 3424.000 41 3425.000 41 3425.010 41 3427.000 40 3428.000 40, 41 3429.000 40, 41 3429.010 40, 41 3430.000 40, 41 3431.000 43 3432.000 61 3433.000 40 3434.000 40, 41 3435.000 40, 41 3435.010 40, 41 3436.000 40, 41 3439.010 15 3450.500 16 3451.500 16 3452.500 16 3453.500 16 3454.500 16 3455.500 16 3456.500 16 3457.500 16 3458.500 16 3459.500 16 3504.000 64 3505.000 64 3509.000 10, 13 3514.000 64 3515.000 64 3516.000 10, 13, 50 3520.000 41 3521.000 41 3524.000 10, 13 3525.000 10, 13 3525.010 10, 13 3526.000 10, 13 3527.000 10, 13, 50 3528.000 10, 13, 50 3528.010 10, 13, 50 3529.000 10, 13, 50 3530.000 41 3531.000 41 3550.000 16 3554.000 16 3555.000 16 3565.000 65 3565.010 65 Model No. Page 3566.000 65 3567.000 65 3568.000 65 3569.000 65 3570.000 65 3571.000 65 3572.000 65 3573.000 65 3574.000 65 3575.000 65 3576.000 65 3577.000 65 3578.000 65 3579.000 65 3580.000 8, 48, 63 3580.100 8, 48, 63 3581.000 8, 12, 48, 63 3581.100 8, 12, 48, 63 3582.000 8, 12, 48, 63 3583.000 8, 12, 48, 63 3584.000 8, 12, 48, 63 3585.000 8, 12, 48, 63 3586.000 8, 12, 48, 50, 63 3591.020 42 3591.030 42 3592.010 62 3592.020 62 3595.010 61 9320.020 64 9320.030 64 9320.040 43 9320.050 43 9320.060 65 9320.070 65 9320.080 40, 41 9320.090 60 9320.100 60 9320.110 60 9320.120 59 9320.140 60 9320.160 35 9320.170 35 9320.180 35 9320.190 35 9320.200 35 9320.210 35 9320.220 35 9320.230 35 9320.240 35 9320.250 35 9320.260 36 9320.270 36 9320.280 36 9320.290 36 9320.300 37 9320.310 37 9320.320 37 9320.330 37 9320.340 37 9320.350 37 9320.360 37 9320.370 37 9320.380 36 9320.390 36 9320.400 36 9320.410 36 Model No. Page 9320.420 36 9320.430 36 9320.440 35 9320.450 35 9320.460 37 9320.470 37 9340.000 8 9340.004 48 9340.010 8 9340.050 12 9340.070 8, 12 9340.074 48 9340.090 8, 48, 55 9340.100 9 9340.110 9 9340.120 9 9340.130 9 9340.134 49 9340.140 9 9340.150 9 9340.160 9 9340.200 9, 11 9340.210 9, 11 9340.214 49, 51 9340.220 9, 11 9340.224 49, 51 9340.260 28 9340.270 28 9340.280 55 9340.290 55 9340.310 24 9340.340 24 9340.350 24 9340.370 24 9340.380 24 9340.410 25 9340.430 25 9340.450 25 9340.460 24 9340.470 24 9340.510 22 9340.530 22 9340.550 22 9340.610 23 9340.630 23 9340.650 23 9340.660 22 9340.700 25 9340.710 25 9340.800 57 9340.850 57 9340.860 57 9340.870 57 9340.880 57 9340.890 57 9340.900 22 9340.910 22 9340.930 22 9341.000 10 9341.050 13 9341.070 10, 13 9341.100 11 9341.110 11 9341.120 11 9341.130 11 9341.140 11 Model No. Page 9341.150 11 9341.160 11 9341.230 60 9341.260 29 9341.270 29 9341.290 55 9341.310 27 9341.340 27 9341.370 27 9341.410 27 9341.430 27 9341.450 27 9341.460 27 9341.510 26 9341.530 26 9341.550 26 9341.610 26 9341.630 26 9341.650 26 9341.660 26 9341.800 56 9341.810 56 9341.820 56 9341.830 56 9341.840 56 9341.850 56 9341.900 26 9341.970 56 9341.980 58 9341.990 58 9342.000 10 9342.004 50 9342.014 50 9342.050 13 9342.070 10, 13 9342.074 50 9342.100 11 9342.110 11 9342.120 11 9342.130 11 9342.134 51 9342.140 11 9342.150 11 9342.160 11 9342.200 14 9342.210 14 9342.220 14 9342.224 52 9342.230 14 9342.234 52 9342.240 14 9342.244 52 9342.250 14 9342.254 52 9342.260 14 9342.264 52 9342.270 14 9342.274 52 9342.280 14 9342.290 14 9342.300 14 9342.310 15, 53 9342.314 53 9342.320 15, 53 9342.324 53 9342.400 32 Model No. Page 9342.410 32 9342.500 32 9342.504 54 9342.510 32 9342.514 54 9342.540 32 9342.550 32 9342.560 56 9342.570 58 9342.600 33 9342.604 54 9342.610 33 9342.614 54 9342.640 56 9342.660 58 9342.670 58 9342.680 58 9342.690 58 9342.700 33 9342.710 33 9342.720 55 9342.770 58 9342.780 58 9342.790 58 9342.800 57 9342.810 57 9342.820 57 9342.830 59 9342.840 59 9342.850 59 9342.860 59 9342.870 59 9342.880 59 9342.900 59 9342.910 59 9342.920 59 9342.930 59 9342.940 59 9342.950 59 9342.980 59 9343.000 44 9343.010 44 9343.020 44 9343.030 44 9343.040 44 9343.050 44 9343.100 45 9343.110 45 9343.120 45 9343.130 45 9343.140 45 9343.150 45 9343.200 46 9343.210 46 9343.220 46 9343.230 46 9343.240 46 9343.250 46 9343.300 47 9343.310 47 9343.320 47 9343.330 47 9343.340 47 9343.350 47 9344.510 61 9344.520 61 Model No. Page 9344.530 61 9344.540 61 9344.550 61 9344.600 62 9344.610 62 9344.620 62 9344.680 62 9350.075 64 9661.300 50, 63 9661.305 63 9661.320 50, 63 9661.325 63 9661.330 50, 63 9661.335 63 9661.340 50, 63 9661.345 63 9661.350 63 9661.355 63 9661.360 50, 63 9661.365 63 9661.380 50, 63 9661.385 63 86 Rittal RiLine60

A 55 66 Adaptor for NH isolators 43 OM 22 25 OT 26, 27 Arc chambers for NH isolators 62 B Base tray 9, 11, 49, 51 Base tray infill 9, 11 Base tray reinforcement 9, 11 Baying bracket E-Cu 63 Box terminals 62 Busbar adaptor for NH isolators, size 000 43 Busbar connector E-Cu 64 PLS 64 Busbar support 8, 12 4-pole 48 Busbar supports PLUS (4-pole) 50 PLS 10, 13 Busbars Cover sections 63 E-Cu 8, 12, 48, 63 PLS 10, 13, 50 Bus-mounting fuse bases 40, 41 C Cable set 57 Circuit-breaker component adaptor 32, 33, 54 Clamp-type terminal connection for NH fused isolators size 00 62 Component adaptor 32, 35 37 Circuit-breaker 32, 33, 54 Conductor connection clamps 16 Connection adaptor 14, 15 4-pole 52, 53 Connection bracket for circuit-breaker component adaptors58 Connection cables (AWG) 57 Connection clamps 16 Connection parts for NH fused isolators, size 00 62 Connection pin for OM and OT adaptors/supports 55 Connection space cover for NH isolators 61 Connector E-Cu 64 PLS 64, 65 Contact hazard protection cover for bus-mounting fuse bases 40, 41 Copper bars E-Cu 8, 12, 48, 63 PLS 10, 13, 50 Cover for NH fused isolators Size 00 60 Cover section 9, 11, 49, 51 for busbars 63 Covers for bus-mounting fuse bases 40, 41 for connection clamps 16 E End caps for bus-mounting fuse bases 40, 41 End covers for busbar support 3-pole 8, 10 4-pole 48, 50 UL 508 12, 13 Expansion connector PLS 65 Extension cover for bus-mounting fuse bases 40, 41 Rittal RiLine60 F Fused isolators Size 00 42 Fusible elements 40, 41 H Holder for flat copper busbars 8, 12, 48 for laminated copper bars 66 PLS 10, 13, 50 I Identification label support for NH fused isolators size 00 61 Identification labels for bus-mounting fuse bases 40, 41 Insert strip for circuit-breaker component adaptors 55 for OM and OT adaptors/supports 55 Isolators Size 00 44 Size 000 43 Size 1 45 Size 2 46 Size 3 47 L Laminated copper bars 65 Lug terminal connection parts for NH fused isolators size 00 62 M Micro-switch for NH isolators/nh fused isolators 61 Mounting clip for multi-functional component adaptors 60 Mounting set for NH isolators, size 000 61 Multi-functional component adaptors 35 37 N NH bus-mounting on-load isolators Size 00 44 Size 1 45 Size 2 46 Size 3 47 NH fused isolators Size 00 42 NH on-load isolators Size 000 43 O OM adaptors with connection cables 24, 25 with tension spring clamp 22, 23 OM premium adaptor 22 OM support 28 On-load isolators Size 00 44 Size 000 43 Size 1 45 Size 2 46 Size 3 47 OT adaptors with connection cables 27 with tension spring clamp 26 OT premium adaptor 26 OT support 29 Overview of switchgear 75 78 Index P PinBlock for support frames 57 PinBlock Plus for starters with increased contactor attachment 57 Plate clamp 16 PLS busbar connectors 64 PLS busbar supports 10, 13 Busbar supports PLUS (4-pole) 50 PLS expansion connectors 65 PLS special busbars 10, 13, 50 Plug-in connector for multi-functional component adaptors 60 Prism terminals 62 R Reinforcement for base tray 9, 11 S Short-circuit resistance diagrams Busbar systems 68, 69 Busbar systems UL 508 70 Laminated copper bars 85 Side cover for bus-mounting fuse bases 40, 41 Sliding blocks for circuit-breaker component adaptors 56 Spacers for RiLine60 busbar supports 55 ST-Combi connector for OM and OT Premium adaptors 58 Support frame for OM and OT adaptors/supports 56 with fitted sub-unit 56 Support frame supports for OM adaptors 57 Support panel for cover sections 9, 11, 49, 51 Support rails for component adaptors 59 for multi-functional component adaptors 60 for OM and OT adaptors/supports 59 Supports OM 28 OT 29 System covers 16 T Technical information 67 85 Terminal connection for NH fused isolators, size 00 62 Terminals 16, 62 Trim panel for cover sections 9, 11, 49, 51 U UL 508 Underwriter Laboratory 72, 73 Universal bracket for laminated copper bars 66 Universal support for laminated copper bars 66 We reserve the right to further developments and technical modifications of our products. Such modifications, along with errors and printing errata, shall not constitute grounds for compensation. We refer customers to our Terms of Sale and Delivery. 87

All in all solutions from Rittal Industrial Enclosures Power Distribution RiLine60 busbar systems Busbar systems 40/100/150/185 Ri4Power low-voltage distributor systems Electronic Packaging System Climate Control IT Solutions Counication Systems Rittal has one of the largest ranges of enclosures available for iediate delivery. However, Rittal also supplies integrated solutions up to Level 4. This comprises mechanical installation, power supply, electronic components, climate control and central monitoring. For all of your requirements. Fully assembled and functional. Wherever in the world you develop and implement solutions for yourself and your customers, we are close at hand. The global alliance between production, distribution and service guarantees closeness to the customer. Worldwide! 05/08 E460 Rittal GmbH & Co. KG Postfach 1662 D-35726 Herborn Telephone +49(0)2772 505-0 Fax +49(0)2772 505-2319 email: info@rittal.de www.rittal.com R Switch to perfection