MC-351, 421, 431, MC-4311

Similar documents
MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

MA-5200 Series MA-5300 Series

MP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning Hydraulic Actuator General Instructions

MP-5200 Series. Application. Features. Applicable Literature. Electronic Hydraulic Actuator General Instructions

Instruction Manual for Barber-Colman Series EA Electric High Torque Actuators

MS Application. Features. Proportional Valve Actuator General Instructions

MF4E MF4E

MF-22xx3. Application. Features. Floating Valve Actuator General Instructions

AV-430. Application. Features. Applicable Literature. Valve Linkage for Pneumatic Actuators General Instructions

VA, VF, and VS Series Direct Mounted Globe Valve Assemblies. Application. Features

CP-8301-xxx Series. Application. Features. Applicable Literature. 1 to 15 Vdc Input Electronic Actuator Drive General Instructions

MX4X-6XXX Series MX4X-7XXX Series. Selection Guide. Applications. DuraDrive Series Actuators and Accessories

MK-6600 Series, MK-6800 Series, and MK-6911

VB-8000 Series VB-9313 Series. Selection Guide. Applications. Applicable Literature. Selection Guide Contents. Valve and Actuator Selection Procedure

CP (Vdc) CP (Milliamp) CP (Slidewire)

M100F Incremental Motor Actuator R81F Interface Board

CP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions

Powers TM Controls EA 338 Electronic Actuator

AV-497. Application. Features. Valve Linkage for MK-6811 and MK-6911 General Instructions

M436A/M836A,B Damper Motors

Selection Guide. Vx-2x13-5xx-9-xx Series Vx-2x13-8xx-9-xx Series VB-2x xx Series. Schneider Electric Ball Valve Assemblies

AK Application. Features. Applicable Literature. Positive Positioner Pneumatic Relay General Instructions

AV-608 Linkage Adapter Kit

453X Series. Application. Features. Two-Position Damper Actuator General Instructions

CP CP

IMP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning. Hyciraulic Actuator General Instructions SIEBE

VB-9323 Series. Application. Features. Applicable Literature. 2-1/2" to 6" 125 Lb. Flanged Three-Way Diverting Valves General Instructions

SLC-811X Series. Single Loop Proportional Temperature Controller General Instructions APPLICATION SPECIFICATIONS

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

MX4X-6XXX-20X Series MX4X-7XXX-20X Series

Application. Features

TAC DuraDrive Product Guide Direct Coupled Actuators

Series EA High Torque Actuators with Integrated Controller

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

GMX On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 100 to 240 VAC

LMB24-3 (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

MA40-704X Series MA41-707X Series MA41-715X Series

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

CP-8551 & CP Application. Features. Applicable Literature. Electronic to Pneumatic Transducers General Instructions

VA-8020 Floating Valve Actuator

DA-053 Series. Overview. Applications. Features & Benefits. Datasheet. 53lb-in (6 Nm), Non-Spring Return Damper Actuators

MS40-717X Series. Application. Features. DuraDrive Series Spring Return Proportional Actuators General Instructions

2006 Series Geared Rotary Limit Switches

AV-401. Application. Features. Applicable Literature. Pneumatic Actuator Valve Linkage Kit General Instructions

2211 Series. Application. Features. One-Pipe Pneumatic Room Thermostats General Instructions SPECIFICATIONS

LMCB24-SR LMCB24-SR-T. applications. Dimensions (All numbers in brackets are in millimeters.) 1/4 to 3/4 [6 to 20] 5/16 to 3/4 [8 to 26] 1.

LMX120-SR. Proportional Control, Non-Spring Return, Direct Coupled,100 to 240 VAC, for 2 to 10 VDC and 4 to 20 ma

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

Series 41 and 81 Modutrol IV Motors

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

M Remote Mounting Kit

Damper Actuator Installation

TC-200 Series. Application. Features. Applicable Literature. Single Bulb Thermostats General Instructions

Flowrite EA 599 Series SQX Electronic Valve Actuator 24 Vac, 3-Position Control

Flowrite 599 Series SKB/C Electronic Valve Actuator 24 Vac, 3-Position (Floating) Control

Non-Spring Return EconoDrive Floating Actuator

VA-640GSX024P. Overview. Applications. Features & Benefits. Datasheet. Large Globe Valve Actuators

SERIES 73 ELECTRIC ACTUATOR OPERATION AND MAINTENANCE MANUAL. The High Performance Company

MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 Fast-Acting, Two-Position Actuators

NMB (X) 24-MFT. Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

MAx1-720x Two Position Series MFx Floating Series MSx Proportional Series

VA-4233-GGx Series Electric Valve Actuators

TS , -850 Series TS , -850 Series TS-57031, TS

Flowrite EA 599 Series SKB/C Electronic Valve Actuator 24 Vac, 3-Position (Floating) Control

Minimum 90 in-lb Torque. Applications. NFB, NFX Series At A Glance. NFB and NFX Series Spring Return Direct Coupled Actuator

POWERS Controls No. 4 Pneumatic Damper Actuator

Flowrite EA 599 Series SKD Electronic Valve Actuator 24 Vac 3-Position (Floating) Control

Installation Instructions

ML6420, ML7420 Non-Spring Return Electric Linear Valve Actuators

TK-6024, TK-6124, TK-8024, TK-8124

3-Way Linked Globe Valve Assemblies with Linear Series Actuators

THC-2, THC-3, THCR-4, THCR-5. Enthalpy Control. General Instructions APPLICATION SPECIFICATIONS. ACCESSORIES None

VC2, VC4, VC60, VC8 ON-OFF ACTUATOR FOR VC SERIES BALANCED HYDRONIC VALVES SPECIFICATIONS INSTALLATION INSTRUCTIONS

OpenAir Electric Damper Actuators GBB/GIB Series NSR Rotary 24 Vac - Modulating Control

MS Series MS Series MS Series

ML6420, ML7420 Non-Spring Return Electric Linear Valve Actuators

MF Series MF Series MF Series

ML6425, ML7425 Spring Return Electric Linear Valve Actuators

VG7000 Valve Linkage for M100 Series Motor Actuators

Installation Instructions

TS Series TS Series

Y20EBA Linkage Kit, M100 to Barber-Colman 1/2 to 1-1/4 Inch Valves

Minimum 18 in-lb Torque. Applications. TF Series At A Glance. TF Series Spring Return Direct Coupled Actuator. For damper areas up to 4.

TAC TM Butterfly Valve Assemblies

VA-715x Electric Valve Actuator

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m)

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

AF Series Spring Return Direct Coupled Actuator

ML7421A,B Electric Linear Valve Actuator

NV Direct Coupled Globe Valve Actuator

OpenAir Electronic Damper Actuators GLB Series Enhanced Non-spring Return Rotary

LF Series Spring Return Direct Coupled Actuator

DuraDrive MF /MS Series Non-spring Return Rotary Electronic Damper Actuators 24 Vac Three-position/Modulating

NMQB24-MFT, NMQX24-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary

Flowrite Globe. Pneumatic 4-inch Valve Actuator. Valves. Description. Applications. Features D-141.

Installation Instructions

AV-611. Application. Applicable Literature. Schneider Electric DuraDrive Globe Valve Linkage General Instructions

M9208-xxx-x Series Electric Spring Return Actuators

Transcription:

MC-35, 42, 43, MC-43 Three-Wire, Two Position Actuators General Instructions Applications For two-position operation of dampers or valves in heating, ventilating and air-conditioning systems and similar applications where return to normal position is not required. These unidirectional actuators (clockwise rotation) require a three-wire control circuit; SPDT snap-acting switch or its equivalent such as a thermostat, pressure switch or relay. A built-in cam operated, snap-acting, adjustable SPDT auxiliary switch is standard. It is factory set to make at mid-stroke. One contact closes at end of stroke; other contact closes at end of next stroke. MC-xxx (Standard Actuator) Features 24, 20, and 240 Vac models Equipped with SPDT auxiliary switch Actuator has a rugged die cast aluminum housing with two /2 conduit openings Hazardous location actuator housing has two 3/4" pipe taped openings for rigid metal conduit connection Oil immersed gear train Requires a three wire control circuit SPDT snap-acting or equivalent Options Available 24, 20, 208, 240 Vac; 50 or 60 Hz. 50 Hz specify MC5-xxx. For hazardous locations, specify MC6-xxx (60 Hz), MC7-xxx (50 Hz). Actuators factory assembled, UL listed, CSA certified. MC6-3xx, MC6-4xx, MC7-4xx, (Hazardous Location Actuator) Applicable Literature AV-390 Series, Valve Linkage for Gear Train Actuators, General Instructions, F-24376 TAC Electric/Electronic Products Catalog, F-27382 Apparatus for Hazardous Locations EN-56-2 F-845 AV-29x Series Hazardous Location Valve Linkage for Geartrain Actuators General Instructions F-2744 Printed in U.S.A. 8/08 Copyright 2008 TAC All Rights Reserved. F-08366-3

SPECIFICATIIONS Control Circuit: Three Wire SPDT snap-acting switch or equivalent. Shaft Rotation: Unidirectional clockwise 80 when power is applied. Auxiliary Switch: Adjustable SPDT is standard. Factory set to make (or break) at mid stroke. Running, 5.8A at 20 Vac, 2.9 at 240 Vac Locked Rotor: 34.8 at 20 Vac, 7.4 at 240 Vac Non-inductive, 2A at 20 Vac, 6 at 240 Vac. Environment: Ambient temperature limits: Shipping and storage -40 to 36 F (-40 to 58 C) Operating -40 to 36 F (-40 to 58 C). Humidity: 5 to 95% RH, non-condensing. Locations: NEMA. Optional NEMA 4 with AM-363 gasket, or hazardous service locations N.E.C., Class, Groups C and D, and Class 2, Groups E, F, and G. Connections: Coded screw terminals. Options: Hazardous locations specify MC6-35, 42, or 43 (60 hz), MC7-43 (50 hz). Agency Listing: UL File #E9429 standard models. UL File #2929 Hazardous location models. Temperature code T6 for hazardous housing. Table- Model Chart. Part No. Standard Service ACCESSORIES Part No. Hazardous Location a b Input Volts Hz Watts VA Rating No Load Timing (Sec./80 ) a Class, Groups C & D, and Class 2, Groups E, F, and G hazardous locations; refer to EN-56-2, F-845. Hazardous location valve actuators can also be used for hazardous location damper applications. b Models for hazardous locations are only available as factory-built enclosure/actuator assemblies. c Damper ratings are nominal and based on standard (not low leakage) dampers at " (25.4 mm) W.C. static pressure and 2000 FPM (0 ml/s) velocity. d Not CSA approved. Damper Linkage Accessories (See Figure- Rated Torque Lb.-in. (N-m) Nominal Damper c Area Sq. Ft. (m2) Parallel Blade Opposed Blade MC-35 MC6-35 24 60 28 53 70 220 (25) 22 () 57 (5) MC-42 MC6-42 20 60 50 96 20 75 (20) 97 (9) 25 (2) MC-43 MC6-43 20 60 50 96 30 220 (25) 22 () 57 (25) MC-43 240 60 50 96 30 220 (25) 22 () 57 (5) MC5-43 d MC7-43 d 240 50 50 96 36 220 (25) 22 () 57 (5) AM- AM-2 AM-3 AM-5 AM-6 AM-22 AM-23 AM-25 AM-25-048 AM-32 AM-6 AM-6- AM-30 Crank arm for 5/6" diameter damper shaft Crank arm for 3/8" diameter damper shaft Crank arm for actuator or /2" diameter damper shaft Crank arm for 7/6" diameter damper shaft Splined crank arm for actuator Linkage connector straight type Damper clip 5/6" diameter x 20" damper rod 5/6" diameter x 48" damper rod Ball joint connector Damper linkage kit Damper linkage kit 90 degree mounting bracket Valve Linkage Accessories (See Figure-4 AV-330 AV-352 AV-393 AV-394 AV-396 Valve linkage for 2-/2" & 3" VB-9323 Valve linkage for 2-/2" to 6" VB-923 or VB-933 valve bodies and 4" to 6" for VB-9323 Valve linkage for /2" to -/4" VB-92x3 or VB-93x3 Valve linkage for -/2" & 2" VB-92x3 or VB-93x3 Valve linkage for 2-/2" to 4" VB-923 or VB-933 Valve Linkage Hazardous Location Accessories (See Figure-5 AV-293 AV-296 Valve linkage for /2" to 2" VB-7xxx series for hazardous locations Valve linkage for 2-/2" and 3" VB-9xxx (bronze) series for hazardous location 2 Copyright 2008 TAC All Rights Reserved. F-08366-3

Miscellaneous Actuator Accessories Standard models only. AM-32 Two step switch kit AM-34 Four step switch kit AM-363 NEMA 4 rated gasket kit Figure- Damper Linkage Accessories. TYPICAL APPLICATION (Wiring Diagram) Make all electrical connections in compliance with the job wiring diagram and the national and local electric codes. Typical connections are shown in (Figure-2). Figure-2 External Wiring for Heating Application. PRE-INSTALLATION The MC actuators are shipped without mounting hardware or linkage. In damper applications, crank arms (AM-3), connectors (AM-22 or AM-32), link rods (AM-25) and mounting brackets (AM-30) will be required. In valve applications, a valve body and AV type linkage will be required. Before installing the actuator, check for bent or broken parts or oil leaks. Actuators may be connected to power supply to check operation prior to installation. F-08366-3 Copyright 2008 TAC All Rights Reserved. 3

INSTALLATION Requirements Procedure Preferred mounting for the actuator is in the upright position, but other positions are acceptable. Adjustable speed units should never be mounted upside down or with the output shaft pointing upward. Allow six inches clearance above the actuator wiring compartment. If an AM type mounting bracket is not used, the base of the actuator may be used as a template for marking mounting holes. Actuator may be used in damper and valve control applications. Figure-3 illustrates linkage operating an arm through a 90 arc. To fasten damper linkage proceed as follows. Figure-3 80 Actuator Rotation Driving a Damper Rotation of 90. Damper Installation. Fasten linkage connector at end of damper crank arm. 2. Fasten linkage connector at punch mark on actuator crank arm (about.707 of the radius). 3. Move damper to normal position and clamp connecting link to connectors. 4. Check adjustment for proper operation by running actuator and driven shaft between limits of travel. Caution: If crank arm does not provide proper travel, reset connecting link in linkage connector. Never attempt to turn the actuator shaft with a wrench or a crank. This may damage the gears. Valve Installation Install all valves with pressure under seat. Refer to flow arrow on body or piping information on valve body tag. Three way mixing valves should be installed with two inlets and one outlet. Three way diverting valves should be installed with one inlet and two outlets. To assemble an actuator to a valve, refer to detailed instructions on AV-3xx General Instruction Sheet, F-9068 or AV-29x Series Hazardous Location Valve Linkage for Geartrain Actuators General Instructions, F-2744. 4 Copyright 2008 TAC All Rights Reserved. F-08366-3

Nylon Bushing Actuator Plunger Assembly "C" Ring Front Cover Plunger Cam Mounting Screws (3) Indicator Mounting Bracket Indicator Screw Stem Extension 2 Cover Screws (2) Connecting Pin Stem Locknut Packing Nut Mounting Nut Valve Body (VB-7XXX Shown) Not included in AV Kits. 2 Used with /2" through 2" valve bodies. Figure-4 Components for Valve Installation of Standard Actuator. Note: See AV-390 Series, Valve Linkage for Gear Train Actuators, General Instructions, F-24376 for detailed instructions when used as a valve actuator. F-08366-3 Copyright 2008 TAC All Rights Reserved. 5

Mxx-xxx Hazardous Location Actuator Nylon Bushing Plunger Assembly Front Cover Plunger Cam Indicator Indicator Screw Mounting Bracket Stem Extension Cover Screws (2) Connecting Pin Mounting Screws (3) Stem Locknut Packing Nut Mounting Nut Valve Body Not included in AV kits. Figure-5 Components for Valve Installation /2 to 2 VB-7xxx and VB-9xxx-xxx-4-xx 2-/2" and 3" Globe Valves for Hazardous Location Actuators. Note: See AV-29x Valve Linkage for Hazardous Location Gear Train Actuators General Instructions, F-2744 for detailed instructions when used as a valve actuator. 6 Copyright 2008 TAC All Rights Reserved. F-08366-3

WIRING For control and power wiring on low voltage actuators (H, G, R, B AND C terminals), use No. 4 wire on runs under 40 feet and No. 2 wire on longer runs. On line voltage units (L, L2, R, B, and C terminals), use No. 4 wire on runs up to 300 feet. Class I circuits must be used for connections to the control and power terminals (L, L2, R, B, and C terminals) on line voltage actuators. Class II circuits may be used for connections to the control and power terminals (H, G, R, B, and C terminals) on 24 Vac actuators. Connections to the auxiliary switch terminals (R, B, and C) may be per Class II circuits except when the switch is used on line voltage applications in which case Class I circuit must be used. When powering actuators from a common transformer, the G terminals must all connect to the same side to prevent transformer damage. Hazardous Location Models Make all electrical connections to the assembly in accordance with the job wiring diagram, the National Electric Code Article 500, and in compliance with the local electrical codes. Two 3/4" pipe tapped openings are provided in the housing for rigid conduit connections. It is recommended to insert a chase nipple from inside of the housing to prevent threads from cutting or damaging wiring. When wiring, take care to lay all leads in the wiring channel located just under the housing cover to protect the leads from any sharp edges which may be in the vicinity. The housing and the edge of the cover are stamped with the letter "O." When replacing the cover, the letters must be aligned with each other. Warning: The cover-to-housing orientation must be maintained in order to preserve the integrity of the seal. Failure to observe this warning can result in injury or death.. Remove twelve cover screws and cover. Place cover, machined surface up, in a protected location to avoid damage to machined surfaces. 2. Make all wiring connections to actuator taking care to lay all leads in the wiring channel provided. 3. Before enclosing the actuator, wipe machined surfaces of housing clean with a lint free cloth and apply one of the UL approved compounds. See Note below. Warning: Failure to observe these warnings can result in injury or death. Do not scrape, scratch, or use abrasives on the machined surfaces. Ensure the surfaces are clean. Use only the approved compounds listed below. 4. Secure cover tight against the enclosure in the same position before removal with the twelve screws provided. Note: Underwriters Laboratories has sanctioned the use of the following compounds on hazardous location ground joints: Crouse-Hinds type OSL lubricant, Crouse-Hinds type STL lubricant, or "No-OXID" oil, grade "D." Two /2" conduit knockouts are provided on the actuator case. Refer to Figure-6 for terminal locations. F-08366-3 Copyright 2008 TAC All Rights Reserved. 7

CHECKOUT Actuator Checkout After the entire system has been installed, the following checks for proper operation must be made.. Be sure that the system power is connected, and on. 2. Turn thermostat to call for cool. Actuator should rotate clockwise from 0 to 80, turning off the heating media. (View actuator from output shaft end (front).) 3. Turn thermostat to call for heat. Actuator should rotate clockwise from 80 to 360 (also 0 ), and turn on heating media. 4. If the room temperature varies excessively, see System Repair. Turn power off and connect terminals as follows:. Connect terminal C to B and actuator should run clockwise (when energized) to end of travel (usually 80 ). 2. Connect terminal C to R and actuator should run clockwise (when energized) from 80 to 360 (0 ). RUN/ADJUST Theory of Operation Unidirectional Three-Wire, Two-Position Actuators The motor, gear-train assembly with limit switches to stop the movement (usually at the end of 80 CW travel) is built in two types. The damper actuator output shaft gives rotary motion. The valve actuator has a cam-operated plunger which transforms rotary motion to linear motion to operate the valve stem. Three-wire actuators require a SPDT switching action in the controller. R contact of the thermostat is made on a call for heat; B contact is made on a call for less heat; C terminal is common. R of the actuator (assume on valve) is a starting switch that starts to open the valve; B starts to close the valve; and C is the limit switch. Auxiliary cam-operated switches are available for the operation of additional valves, actuators, relays, etc. Figure-6 Internal Wiring Diagram and Cam Chart. 8 Copyright 2008 TAC All Rights Reserved. F-08366-3

Auxiliary Switch Adjustment The adjustable built-in SPDT auxiliary switch is actuated by the cam nearest to the back of the actuator. Although it can be adjusted to operate at any point in the actuator rotation, it is factory set to operate at approximately mid-stroke. This operating point may be changed by inserting a screwdriver through the opening in the top plate directly behind the terminal block, and engaging the screwdriver with the gear-like plastic disc. Turning the disc clockwise causes the switch to operate nearer the counterclockwise end of actuator travel. Each click of the switch actuating cam represents approximately 3 angular degrees change in operating point. Figure-7 Cut-a-way of Actuator. MAINTENANCE REPAIR A minimum of maintenance is required since the motor and gear train are submerged in oil (BYZP-95) for continuous lubrication and cooling. If necessary to refill with oil, always use TAC immersion oil, available in one quart cans (refill capacity - to -/4 pints). Oil level (with the actuator upright) should be up to the edge of the oil fill hole which is located just left of the output shaft. None. Replace an inoperable actuator with a functional unit. F-08366-3 Copyright 2008 TAC All Rights Reserved. 9

DIMENSIONAL DATA Figure-8 Standard Actuator Dimensions. Hazardous Location Shown with valve linkage components. Mounting bracket, open/close cover, pointer, and plunger are not included for damper applications. 8-/4 (209) /4 (6) 4-/8 (05) 7-7/8 (200) 9 (228) OPEN 7 (78) 4-/2 (4) CLOSED Coupling Line for Actuator 5-7/6 (39) Coupling Line for Valve Body 4-/4 (08) Dimensions shown are in inches (mm). Allow 2 (300 mm) minimum service clearance above the housing top. Figure-9 Hazardous Location Actuator Front Dimensions. 0 Copyright 2008 TAC All Rights Reserved. F-08366-3

4-/2 (4) 9 (229) 0-3/6 (275) 2-/8 (54) -/4 (32) 5/8 (6) /8 (3) 3/4 (9) Pipe Tap On Each Side 2-5/6 (5) Dimensions shown are in inches (mm). Figure-0 Hazardous Location Actuator Side Dimensions. F-08366-3 Copyright 2008 TAC All Rights Reserved.

Copyright 2008, TAC All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. F-08366-3 TAC 354 Clifford Avenue P.O. Box 2940 Loves Park, IL 632-2940 www.tac.com