MANUAL VALVES VS. AUTOMATIC FLOW LIMITING VALVES

Similar documents
AutoFlow. Automatic Flow Control Valves

36486_HVAC-Catalog_r1.pdf 1 1/12/17 11:57 AM HVAC CATALOG

About Us Our Mission Table of Contents 04 Automatic Flow Limiting Valves 06 Manual Balance Valves 08 2-Way & 3-Way Actuated Ball Valves

Written By : Simon Teo B. ENG (HONS)

Balancing Basics. Mike Weisman, ASHRAE Treasurer. ASHRAE Golf Outing: May 18 th, 2018! HEATHERWOODE

Automizer Combination Control Valves

Ballorex Venturi 3.1 Introduction

Figure 1710 Flow Data

Saving You Money, Protecting Your Equipment

Components of Hydronic Systems

Variable Primary Systems Add Photo/Graphic

Flow Data for NIBCO Circuit Balancing Valves 1/2 to 2 (Figure Number 1710)

Modify Section by adding subsection.02 per the following. Remainder of section is unchanged.

Commissioning chilled water TES systems

VAV AIRFLOW CONTROL. Reliable Without Limitations? Ron Simens, Facility Dynamics Engineering. 21 st National Conference on Building Commissioning

INTRODUCING THE SIX-WAY VALVE AND ACTUATOR

A. Provide all HVAC specialties required to complete the installation of all HVAC systems. B. Manufacturers: Refer to individual product item.

Section Va: Valve Actuators

Description. Ballorex Venturi. Versions. Benefits. Robinets manuels Balancing

BROCHURE. ABB drives for HVAC applications ACH550, 1 to 550 Hp

Spring Achieve System Balance Without All The Spin. PICCV. Complete Details Inside!

Ballorex Vario. Description. Versions. Benefits. Applications. Balancing

ROTARY PRESSURE INDEPENDENT CONTROL VALVE TECHNICAL MANUAL

CALEFFI. FLOWCAL Automatic flow balancing valve with polymer cartridge. 121 series 01141/11 NA. Function

Manual presetting valves LENO MSV-BD

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

Product Sheet Pre-Fabricated Flushing Bypass Assembly for Terminal Applications Mini-Flush 40

ENGG1015: lab 5. A Taste of the Project

ABB drives for HVAC applications ACH550, 1 to 550 Hp

Safety & Installation Instructions

Steeda Sport Mustang Lowering Springs (2005+) - Installation Instructions

CBV Series. Circuit Balancing Valves

Automatic balancing valves ASV-PV DN (3rd gen.)

Pressure Independent Control Valve Applications for Building Automation, Temperature Controls, and HVAC Two-Way Chilled Water Hot Water

GENERAL INFORMATION MECHANICAL INSTALLATION PRESSURE INDEPENDENT VALVES 2-1/2"-10" MVP INSTALLATION & OPERATION INSTRUCTIONS UNION CONNECTIONS

Variable Air Volume Dampers

Control Valves & Coil Packs

Chapter 13: Application of Proportional Flow Control

DWS 41. Installation Data 44 Performance Specs DWS & DW-PRV Series

2000 Series Heavy-Duty Irrigation Valves Recommended Applications Golf Courses Landscapes Parks Right-of-ways

BAS Construction Checklist

Cost Benefit Analysis of Faster Transmission System Protection Systems

HVAC Products PCS. Pettinaroli Commissioning Solutions

Johnson Controls Rooftop Units

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

Gauges, Sight Glasses and Vacuum Breakers

2014 All Rights Reserved. Top 7 Myths About Remanufactured Printers

Global Field Devices COMMERCIAL HVAC COMPONENTS ENGINEERED FOR SUCCESS. Application And Selection Guide

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

HVAC Products PCS. Pettinaroli Commissioning Solutions

Safety cap. Measuring probe. Seal. Operating principle. Advantages of balanced circuits. Balanced circuits have the following principal benefits:

EGT Plus Instructions

Why is the Breaker Tripping?

1.1 PURPOSE A. This section is intended to define the general installation and minimum product requirements for hydronic and steam valves.

PIC-V Valve... 1 Unimizer (1/2 to 3 )... 2 Unimizer (4 to 6 )... 3 Automizer... 4 MVP Valve... 5

Hydraulic & Lubrication Filters

Manual Presetting Valves LENO MSV-B

Twin-Tee. Hydronic Accessories

Balancing Valves. Venturi Commissioning Valve (FODRV) & (DRV) Cu x Cu Compression DN10-DN50. BOSS TM 901SC Venturi DRV DN

Save Thousands of Dollars Per Year!

How to: Test & Evaluate Motors in Your Application

FLOW RATE STATIC BALANCING Valves for radiators

flow measurement solutions RIM10 series rotor insertion flowmeters

ATi Max Series. Pressure Independent Control Valves 2 Way 2-1/2-6

PRICED BILL OF QUANTITIES Package : Air conditionning. Manhours (h) Unit (tariff) Discount Total Unit. Total. Material cost

SECTION METERS AND GAGES FOR PLUMBING PIPING

Baghouse Conversion to Pleated Filter Elements From Standard Bag and Cage Setup - Cost Benefit Analysis

TC62D Installation Instructions

Redefine your comfort zone. chilled beams. energy solutions

4017 M HERZ Dimensions in mm

COMMERCIAL. Product PRofile

Pressure Independent Valves for Terminal Unit Applications

42C/D SERIES Ducted Chilled Water Fan Coil Unit With District Cooling Application

Air Conditioning Clinic. HVAC System Control One of the Systems Series TRG-TRC017-EN

Electrical Depth. Josh Kreutzberger Lighting/Electrical

Working Principle of Power Saver as per Manufacture:

Prius Maintenance. Air-Conditioner Filter

Technical Service Bulletin

Pump ED 101. Variable, Fixed Speed Control - - Float Switch Activation. Introduction

0 Does this topic relate to the work the crew is doing? lf not, choose another topic.

Hydraulics in building systems. siemens.com/buildingtechnologies

energydesignresources design brief

reflect energy: the ability to do work

How to Keep your Treadmill Running

MOTORS, VOLTAGE, EFFICIENCY AND WIRING. A Deeper Understanding

EVSE Load Balancing VS Load Shedding 1: Largest number of 30 Amps EVSEs that can be fed as per the code from the 600 volts feeder

Mazda North American Operations Irvine, CA

MOROSO PERFORMANCE PRODUCTS, INC.

GRUNDFOS INSTRUCTIONS. Control HVAC. Installation and operating instructions. Other languages. net.grundfos.com/qr/i/

Technical Notes. Introduction. LED Efficacy. Light Output and Efficacy. Issue 4 April The general equation for light output can be written as:

PLANNING FOR TEMPORARY POWER: A CRITICAL MANAGEMENT DUTY. Information made available by and

VAV TERMINAL UNITS. VVD VAV Diffusers

DESCRIPTION 9.4 G 3/4"M

Innovative Wellhead Products for Landfill Gas Management

Best Practice Variable Speed Pump Systems

BOILER BLOWDOWN CONDUCTIVITY CONTROLLER (CONTINUOUS METHOD)

Engine Oil Transmission Oil + Filter

NOW INTEGRATED WITH MLM DESIGNED FOR VAV DIFFUSER SYSTEMS LINEAR CHARACTERISTICS NO REGULAR MAINTENANCE REQUIRED PRESSURE SENSOR AND CONTROLLERS

Ultrasonic heat meter

Product Catalog. Precision Control DeltaPValves. guaranteed delta T 10-year warranty made in the USA

Transcription:

MANUAL VALVES VS. AUTOMATIC FLOW LIMITING VALVES Automatic & Pressure Independent Valves the cost effective option over Manual Balance Valves H ydronic system balancing is an important part of the HVAC industry. Without hydronic balancing, some coils in a system have too much flow and other coils don t have enough flow; the building isn t balanced. An unbalanced system can lead to excessive occupancy complaints as people are either too cold or too hot in the building. Many engineers focus on carefully selecting energy efficient boilers, chillers, and terminal units. However, without proper flow through these units, their efficiencies and heat transfer capabilities are altered. The problem is exacerbated as the pressures change in the building s hydronic system, as changing pressures have a direct impact on flowrate. Q=Cv P) While the industry accepts that pressure changes cause flow changes which then causes heat transfer changes, many engineers still accept manual balance valves because the INITIAL unit cost is less than automatic or pressure independent valves. But is initial cost all there is to consider? The procedure to manually balance a system is very labor intensive. The pressure drop across each valve is measured and a ball or plug is adjusted to bring the pressure drop to design pressure. Each time a valve in the system is adjusted, the flow through the other valves will change including those previously set because of the pressure change. Hence, the previously set valves must be reset, which in turn affects the flow through the other valves...and so on. In a large system, a minimum of three balances per valve is generally recommended by ASHRAE and NEBB. Contractor price for ¾ manual balance valve with memory stop: $35. Cost to balance three times total: 20-30 minutes @ $125./hr: $42.00 to $62.50 On the other hand, each automatic flow limiting or pressure independent (PI) valve is self balancing as soon as the pump is turned on. The only labor required is for flow verification. The pressure drop across each valve is measured by using the ports provided on the valve body. As long as the PSID is within the control range listed on the valve tag, the flow, which is also listed on the tag, will be within plus/minus 5%.

Contractor price for 3/4 automatic valve with isolation valve: $60. Cost to verify flow: <5 min @ $125./hr: <$10. Manual = $77 to $97.5 Automatic = <$70 It is true the initial cost of a manual valve is less expensive than an automatic valve, but once labor to balance the valve is taken into consideration the total cost can be considerably more. More importantly, once the system is live and pressures start changing an automatic or PI valve will maintain the design flow in spite of system pressure changes. A manual valve will have an increase or decrease in flow as the pressure increases or decreases. Buy Fewer Valves Systems utilizing automatic flow limiting or PI valves require far fewer balancing valves than systems that are manually balanced. Figure 1 shows a schematic of a system serving 18 heat transfer (heating or cooling) coils. Figure 1. The manual system, shown above, requires a total of 27 valves whereas the automatic system, on the right, requires only 18 because it does not require the partner balancing valves (shown in red) on the risers and the branches. As each terminal unit automatic flow limiting and pressure independent control valve is self-balancing over a wide differential pressure control range, the flow through the risers and the branches is also automatically controlled (balanced) without the use of additional valves.

Using 18 valves instead of 27 manual valves is approximately 1/3 savings in initial product purchases. In our previous example that is 27*$77 to $97.5 or $2,079 to $2,632.50 in manual valve costs. In comparison the automatic system costs 18*$70 or $1,260 in valve costs which is a substantial savings. The elimination of the manual partner balancing valves on the mains, risers and branches in turn eliminates the head loss through them. Hence, the system head loss is reduced which lowers the pump head requirements. System Stays Balanced Even During Reduced Load Conditions No coil will starve when saving money by variable speed pumping. However, reducing the total water flow does not mean that all the coils in the building individually need the same reduction in flow. For example, on a typical spring day at 1:00 p.m., the total chilled water requirements of an 8-story office building will generally be much less than on a hot summer (design) day. However, the air-handler serving the filled-to-capacity cafeteria, on the first floor, will require almost 100% (of design) chilled water. A building with automatic flow limiting or pressure independent valves will give you this diversity whereas one with manual balancing valves cannot. Figure 2. The schematic at the top shows the design load condition. The system operation point, at design load, is at (say) 125 feet of pump head. The head loss across the various elements (which adds up to 125 feet) for the cafeteria circuit, is as shown. Since the cafeteria is on the first floor, the head loss through the risers is negligible and is ignored. Please note, for design flow at design head, the head loss through the manual balancing valve is the same as that through an automatic flow control valve (86 feet).

The schematic in the middle shows what happens when system flow is reduced (by lowering the pump speed to 52%), if the system is manually balanced. At the lower speed, the pump head will be smaller as will all the pressure losses. Since nothing else has changed in the cafeteria coil circuit, the head loss through the various elements will decrease proportionately and now add up to 65 feet instead of 125. Since the head loss through the manual flow control valve is reduced to 44.7 feet and since flow is proportional to the square root of the head loss, the flow through the manual balancing valve (and the coil) is reduced to 72% (square root of 44.7/86). There is NOW a flow deficit of 28%. The schematic at the bottom shows what happens when system flow is reduced by the same amount if the system has automatic flow limiting valves. Again, the pump head decreases to 65 feet. However, the head loss distribution is not proportional. Instead, the cartridge inside the automatic flow control valve moves by a precise amount, to absorb only 26 feet of head and keeps the flow at the required 100%. With the automatic flow limiting or pressure independent valve, there is no flow deficit at reduced system flow and reduced pump head. (Note: In all three schematics of Figure 2, all losses in the pump room are ignored for clarity of discussion.) Building Renovation Does Not Require Hydronic System Rebalance Very often, space renovation in an existing building also changes the heating/cooling requirements of that space. For example, an open office area that is converted into a large conference room will require more cooling due to the additional sensible and latent heat from the people. This may result in an additional fan-coil unit for the conference room. Figure 3 illustrates this scenario for a Manual vs. Automatic system. Figure 3. If this is a manually balanced building, as shown in Figure 3 on the left side, valve MBV #5 would have to be added and manually set. However, doing this would change the flows through existing valves MBV #1 through MBV #4 and they would also have to be reset. Similarly, upstream branch/riser balancing valves (not shown) may also have to be reset. The resulting labor cost can be significant. If this is a building with automatic flow control valves, as shown in Figure 3 on the right side, you would only have to add valve AFLV #4. Because these valves have wide control ranges, they would all automatically self balance to provide the required flows. No labor would be required to set the new valve or to reset any of the existing valves.

How does an Automatic Flow Limiting Valve Maintain Design Flow? Griswold Controls designed the first balance valve in the market in 1960, years before the first manual balance valve was designed and manufactured. The all stainless steel flow limiting cartridge is a standard in the industry because of its simply elegant design. When the differential pressure across the cartridge falls below its control range (pink colored area in Figure 4), the cup will come all the way out, exposing the maximum orifice area. Similarly, if the differential pressure across the cartridge rises DESIRED FLOW PSID CONTROL RANGE CUP FULLY OUT CUP PARTIALLY OUT CUP FULLY IN Figure 4. Below the control range, the cartridge acts as a variable flow device, allowing flow to vary below the rated amount. Within the wide control range, the cartridge modulates in response to pressure differential changes to maintain a fixed flow rate within ±5% accuracy. Above the control range, the cartridge acts as a variable control device, allowing flow to vary above the rated amount. Above its control range (blue colored area in Figure 4), the cup will move all the way in, exposing the minimum orifice area. In both cases, the cartridge will now act as a fixed orifice device, varying flow based on the out-of-range differential pressure. You do not have to worry about the cartridge ever shutting off the flow completely because a minimum orifice area is always open. 2803 Barranca Parkway Irvine CA 92606 Toll Free: 800.838.0858 griswoldcontrols.com 1/18 F-5586