Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Similar documents
Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

Installation Manual for D154X Series Multi-Indicator, General Purpose Power Supplies

PREMIER POWER PACK INSTRUCTION MANUAL EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL. GLT.MAN-138 Issue: /05/2016 N.R.P.J.

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2

PSU EN54-4 Power Supplies

HE-PSU(4.0) Power Supply & Battery Charger Installation, Commissioning & Operating Manual

K25000 & KD25000 Series

Elmdene International Ltd

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

24V 3A EN54 Ancillary Power Supply

The 4HR-UPS 220V ac output is provided via a Pure Sine Wave inverter, allowing it to be backed up by 2x 12V standby batteries.

EC200 ELECTRONIC CONTROL SYSTEM

AWZ 110. AWZ 13,8V/1A/7Ah/LM

NON MAINTAINED TWIN SPOTLIGHT WALL MOUNT LED EMERGENCY LIGHT

Phoenix Inverter

Models. Output current max.* Output Power max. Low Line : VAC High Line: VAC 24 VDC / 12 A 240 W. Back up battery

Emergency lighting units EM powerled

Switching DC Power Supply

Emergency lighting units EM converterled

SPECIFICATIONS UPS Triple Output 13.6VDC/213W, 48VDC/153W, 48VDC/39W

Features. Description. Table of Contents

Emergency lighting units EM converterled. EM converterled BASIC 90 V BASIC series

Emergency lighting units EM converterled

Emergency lighting units EM converterled

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL

PPS20 COMMUNICATIONS POWER SUPPLY AND BATTERY MANAGEMENT SYSTEM

Emergency lighting units EM converterled. EM converterled BASIC 50 V BASIC series

User Manual Rittal PMC UPS 6kVA

Emergency lighting units EM converterled

Emergency lighting units EM converterled

RVS-DN Digital Reduced Voltage Motor Starter

DIN Rail UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS Installation/Operation Manual

RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & 6kW

DKG-114 MANUAL AND REMOTE START UNIT

CX-SERIES ADVANCED BATTERY CHARGER

Emergency lighting units EM converterled. EM converterled BASIC 200 V BASIC series

Installation Instructions

FIREMAN'S MICROPHONE POWER SUPPLY FOR THE VOICE ALARM SYSTEMS 24V

LED Driver Linear / area fixed output industry. Driver LCI 100W 350mA 900mA TOP INDUSTRY sl TOP series

Car Battery Charger Instructions for Use

Emergency lighting units EM powerled

Technical Specifications. Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER

PSBSH 2012B. PSBSH 13,8V/2A/7Ah/HERMETIC

Emergency lighting units EM powerled

Document: PRODSPEC-140 Revision: G DCN No Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger

Emergency lighting units EM series

Emergency lighting units EM converterled. EM converterled ST 90 V SELFTEST series

BellMega BM-510. Operation Manual Ver: 1.0 Rev: 1

Emergency lighting units EM powerled

Silvertel. Ag Features. Multi-Stage Charging. Battery Reversal Protection. Reduced Power Consumption. Wide DC or AC Input Voltage Range

LED Driver Linear / area fixed output industry. Driver LCI 65W 150mA 400mA TOP INDUSTRY sl TOP series

MAINTAINED LED DOUBLE SIDED SUSPENDED CEILING MOUNTED EMERGENCY LIGHT

Industrial Power Supplies

Professional Wireless Products

REVISED ATM72 Auto Transfer Module

TECHNICAL MANUAL. Inverter / Charger Combi. Combi SW 12V 1600VA Réf : PF Combi SW 24V 3800VA Réf : PF NOT_COMBI_SW-00

MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER. MicroMax. Article no. F IBC control Made in Sweden

Emergency lighting units EM converterled. EM converterled ST 50 V SELFTEST series

L5000 Plus. Installation & Setup Guide

Art. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2

RVS-DX Digital Reduced Voltage Motor Starter

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

DIN Rail UPS Model: DIN-UPS Installation/Operation Manual

Powerterm L120C Single Output PSU/Battery Chargers Model C2199A-1 (12V/8A) or Model C2199A-2 (24V/6A)

TC-500PD8. Switching Power Supply ( PS2 A T X 500W 8 0+ ) SPECIFICATION. Revision: 2.0

Central Battery Systems Loadstar AC/DC Systems

Installation and Operation Instructions 10/04/13

IBC control. MicroMax MANUAL. With adjustable boost function and threshold value. Since Set of EMC-glands as an option

AccuPower AQU126B Installation Instructions

INSTALLATION & MAINTENANCE MANUAL HBL

INFRESCO-S-4kW X20034 Issue: 7

Power Supplies. SDN-C Compact DIN Rail Series

Emergency lighting units EM powerled. EM powerled BASIC 4W Emergency lighting LED Driver

MODEL ELC-12/40-CVM-D BATTERY CHARGER

Installation Instructions

EC400 Power Control System

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

SST-ST75F-ESS The essential silver standard

Compact Sine Inverter

Output Current Input Current Over Load VDC VDC ma ma(typ.) ma(typ.) VDC μf %

DEEP SEA ELECTRONICS PLC

R series solar charger inverter 1000W to 6000W

Emergency lighting units EM powerled

Emergency lighting units EM powerled

Technical Specification SENTINEL PRO

Installation Instructions & Users Manual

Plena 24 VDC Battery Charger. Installation and User Instructions PLN-24CH10

Whad 0.8, 1, 1.5 kva. Manuel d installation Installation manual. Part. LE05733AA-07/12-01 GF

Sola 3000 Guide Specifications

DEEP SEA ELECTRONICS PLC

IQL Helios Area-/Streetlight. User Manual

Model ER-340XRi / ER-680XRi / ER-1220XRi DC drive product manual HG iss 9 1

MAINTAINED LED CIRCULAR EMERGENCY CEILING LIGHT

Manual for Inverter system type PCI05

Lithium Power Supply

EPS/ELA-Series User Manual EPS/ELA 250W

SPECIFICATION FSP350-60APN(85) Bronze. (Erp2013) DATE:MAY, 14, 2013 表單編號 :7000P Page1

Product Overview. Product Identification. Amps One CT Two CTs Three CTs

Model 340i / 680i / 1220i DC drive product manual HG iss 8 1

LDX-U20 is a microprocessor controlled DC-UPS rated 20 A usable in 12 V or 24 V systems.

Transcription:

Dycon D2430 EN54-4 Fire Alarm Power Supply Series Technical Description Installation and Operating Manual Construction Product Regulation 0359-CPR-00434 Page 1 of 14

Contents 1. General... 3 1.1 Product Range... 3 1.2 Features... 3 2. Electrical and Operational Specifications... 3 3. Compliance... 4 4. Power Supply Physical Dimensions and Features... 5 4.1 Large Box... 5 4.2 Medium Box... 6 4.3 Printed Circuit Board... 7 5. Installation and Operation... 7 5.1 Mounting... 7 5.2 AC Power Connection and Wiring... 8 5.4 Jumper Links... 8 5.5 LED Display... 9 5.6 OP1 and OP2... 9 5.7 SWI and SW2 Inputs... 10 5.8 DATA and LED Interfaces... 10 5.9 detection and Outputs... 10 5.10 Batteries... 11 5.10.1 Battery Temperature Remote Sensor... 11 5.10.2 Battery Protection... 12 5.10.3 General Maintenance... 12 6. Declared performance... 13 Page 2 of 14

1. General 1.1 Product Range The D2430 series of product consists of the following products: D2430: Remote battery temperature sensor D2431-7: 1.5A 24V power supply in medium box D2433-7: 3.0A 24V power supply in medium box D2433-17: 3.0A 24V power supply in large box D2435-17: 5.0A 24V power supply in large box The power supplies can be supplied in either a medium or large box which can house 7Ah or 17AH batteries respectively. 1.2 Features The D2430 series of power supplies are designed to be used for fire alarm control and indicating equipment complying with EN54-2 and EN54-4. The power supply range consist of a 5 amp, 3 amp and 1.5 amp devices, providing a nominal 27V with two 12V lead acid batteries for standby operation without AC power. The power supplies share the following features: Microprocessor controlled operation and protection On-demand battery charging and load output current sharing Automatic output reconnection after short circuit fault No user serviceable fuses, outputs protected by electronic E-fuses Two independent switched outputs with programmable (jumper selectable) control inputs On board or remote temperature sensing (jumper selectable) with optional remote sensor Separate AC healthy, battery fault and power supply fault outputs Three fault outputs, AC Power Fail, Battery, Form A, normally closed floating relay fault outputs Four LED status display Over-voltage output protection Battery-free option selected by a jumper The on-demand load sharing capability gives the power supply range exceptional flexibility. This allows rapid large capacity battery charging with either extended standby hold-up duration at light loads, or short high current peak loads where spare output capacity is diverted to battery charging. 2. Electrical and Operational Specifications SPECIFICATIONS AC Input Voltage Maximum Input Continuous Current Peak inrush current limit Recommended Switched Spur Input Fuses Voltage Output AC Present Voltage Output Standby 230VAC ±10%, 50Hz. D2435, 1.5A; D2433, 0.9A; D2431, 0.45A. 20A maximum. D2435, 250V T3.15A; D2433, 250V T3.15A; D2431, 250V T1A. Minimum 25.0Vdc, Maximum 28.5Vdc. Minimum 20Vdc, 24 V Nominal Page 3 of 14

SPECIFICATIONS Total Continuous Output Current (Imax.b) Current output with battery charging (Imax.a) Battery Charging Current Low Voltage detection thresholds Battery Circuit Impedance Threshold (Ri max) Deep Discharge Disconnection Threshold Overvoltage Detection Shutdown Threshold D2435, 5A; D2433, 3A; D2431, 1.5A. D2435, 4.3A; D2433, 2.3A; D2431, 1.2A On demand. Maximum D2435, 5A, D2433, 3A, D2431, 1.5A. <22V ±2%, low voltage restore, >23V ±2%. >0.18 Ohm ±5%, at a nominal test current of 5A. <21V ±2%. >30V ±2%. Output Monitoring Threshold Battery charging voltage <2V ±2%. On-Board AC Power Input Fuses Battery Fuse Relays Standby Current Maximum Ripple Voltage Battery Type Operating Temperature and Humidity Range Minimum Output Current (I min) Battery current drawn by power supply without AC supply 2435, T3.15A; 2433, T3.15A; 2431; T1A timed. All nonreplaceable. PTC, self-resetting, non-replaceable. Normally closed, 100mA at 60V. On-Resistance 16 ohms maximum, 1500VRMS Isolation voltage 32mA. 0.7V peak to peak. Sealed Lead Acid Gel, YUASA NP7-12F/RETARD, YUASA NP17-12F/RETARD, YUASA NP7-12, YUASA NP17-12I -10 o C to +40 o C, 95% maximum humidity, non-condensing 200mA for all D2430 series Maximum 55mA (Depending on fault output status) 3. Compliance The power supplies comply with the following European Directives: Low Voltage: 2006/95/EC EMC: 2004/108/EC WEEE: 2012/19/EU RoHs: 2011/65/EU IEC61140: Protection against electric shock Common aspects for installation and equipment: Class 1 EN54-4: 1997 + A1 + A2 Part 4: Power Supply Equipment Page 4 of 14

0359 4. Power Supply Physical Dimensions and Features 4.1 Large Box Overall dimensions including lid are 394.5mm x 379mm x 90mm Side knockout centres are 46.5mm above mounting surface, top and bottom knockouts are 50mm above mounting surface. 390.00 36.00 375.00 36.00 36.00 97.50 145.00 First fix keyhole mounting slot Case earth stud 195.00 Rating Label Dycon Ltd D2435 INPUT 230V ; 1.5A 50Hz OUTPUT 24V 5A 50.00 50.00 Mounting Hole 184.00 Ø20.00 50.00 290.00 274.00 51.00 110.00 Mounting Hole PCB mounting pillars x 4 LED light pipe mounting bracket 128.00 60.00 12.00 36.00 Page 5 of 14

4.2 Medium Box Overall dimensions including lid are 329.5mm x 294mm x 85mm Side knockout centres are 44mm above mounting surface, top and bottom knockouts are 45mm above mounting surface. 330.00 165.00 56.00 65.00 Rating Label 180.00 Case earth stud Dycon Ltd D2433 INPUT 230V ; 900mA 50Hz OUTPUT 24V 3A 106.75 First fix keyhole mounting slot LED light pipe mounting bracket 290.00 PCB mounting pillars x 4 184.00 135.00 Ø20.00 126.50 60.00 Mounting Hole 50.00 Mounting Hole 50.00 230.00 50.00 Page 6 of 14

4.3 Printed Circuit Board All three power supplies have a very similar form, fit and function, the dimensions are identical. The D2435 is shown as an example below. NOTE: Plastic cage is not fitted on the D2435 power supply: 168.00 7.00 10.00 145.00 6.00 3.2mm Mounting Holes x 5 Live AC power connection Protective earth connection Neutral AC power connection Case and earth connection tab SW1 and SW2 control inputs inversion jumper Battery-free operation jumper Optional external temperature sensor connector On-board temperature sensor disable jumper Power DC status LED, yellow: Indicates that DC power is available AC OK led, green: Indicates availability of external AC power Battery, yellow: Indicates if any battery faults are present, yellow: Indicates any power supply system faults are present Plastic safety cage 129.50 6.00 5.50 141.00 Serial data interface External LED interface External Power Supply (AC power) fault normally closed relay output Auxiliary Power Supply (battery) fault normally closed relay output Power Supply fault normally closed relay output Nominal 24V output 2 to load Nominal 24V output 1 to load 24V output switching control inputs with 0V return Battery Connectors 5. Installation and Operation Warning: Isolate the AC power supply before working on the power supply. Only suitably qualified personnel should install these power supplies and wiring should comply with the latest edition of IEE Wiring Regulations (BS 7671) or local national electrical standards. 5.1 Mounting The power supplies are designed for indoor use, within the specified operational temperature and humidity limits. Page 7 of 14

The metal enclosures should be mounted on a solid, flat and dry surface using the three mounting points provided. The screws should have a minimum shank diameter of 5mm (No 11 gauge) and use suitable wall plugs where needed. When a final sighting for the power supply has been decided it is highly recommended that the 20mm knockouts that are going to be used are removed before fitting the box by a sharp tap with a hammer and flat bladed screwdriver at the edge of the knockout. Separate knockout holes should be used for AC power entry and low voltage wiring and the wiring kept apart. The knockout holes are designed to accept cable glands. The power supplies should not be mounted near sources of heat or moisture and should be accessible for ease of fitting heavy batteries. The printed circuit assembly will have to be removed from the medium sized enclosure before mounting. This is done by pushing the four light pipes towards the lid until they unclip, removing the earth lead by pulling the earth connector off the tab and unscrewing the four board securing screws. The printed circuit assembly can then be removed before mounting. The keyhole slot at the top of the enclosure may be used as a first fix to hang the unit where the bottom two holes can be marked off when level and then removed for drilling. Using the enclosure directly as a drilling template should not be done as it risks dust damage. Care should be taken when refitting the board using the shake proof washers and ensuring they are tight to make good electrical contact with the printed circuit board and the metal base. The light pipes can then be clipped back into place and that they are positioned over the LEDs. The earth cable can then be pushed back on to the connector tab. 5.2 AC Power Connection and Wiring AC power with a protective earth for Class 1 equipment is to be used with an isolating switched spur using the recommended fuse ratings or a fuse rating of not greater than 5A. The fused switched spur should be fitted as close to the power supply as practicable to allow isolation when the unit is serviced. AC power cable with conductors of a cross sectional area greater than 0.75mm should be used. The AC power cables shall be segregated from the low voltage control wiring and outputs to load. 20mm diameter knockouts on the four sides of the box are provided for cable glands including mineral insulated copper-clad cable. Where batteries are fitted, the knockouts at the bottom of the box will not be available. To comply with EN54 requirements both AC power and low voltage wiring must use cable glands to meet IP30 enclosure protection standards. 5.4 Jumper Links Warning: The AC power supply and the batteries must be disconnected before the jumper positions can be changed. Failure to do so can cause damage to the, batteries and connected equipment. The power supply must not be used with the INT jumper in the off position without a D2430 external temperature sensor fitted, as this could result in a battery fire or explosion risk. The NO BAT link must be in the off position to comply with EN54-4 requirements. Page 8 of 14

Three jumper links are provided for configuring the, the off position is when the jumper is parked on a single pin and the on position is when the jumper is placed across two pins: JUMPER DEFAULT OPERATION INV (Invert inputs) NO BAT 1 (Battery free operation) Off (Not inverted) Off (Battery monitoring enabled) When left in the off position the outputs associated with the SW1 and SW2 inputs will be switched on when they are at a logic high. When in the on position the outputs associated with the SW1 and SW inputs will be switched off when they are at a logic high. With the jumper left in the off position, the will operate as normal with battery standby when AC power is not available. If operation without a battery being fitted is required, then the jumper should be in the on position. INT 2 (Internal/external temperature sensing) ON (Internal temperature sensing) When the jumper is fitted the will use the internal on-board temperature sensor, the link must be put into the off position to use an external temperature sensor. NOTES 1. This jumper can also be used to supress a battery fault condition until a new battery can be fitted. The jumper disables the battery monitoring only and allows the battery to be charged and provide standby power as normal. NOTE: disabling the battery monitoring with a battery fitted will cause an EN54-4 non-compliance. 2. The power supply must not be used with the jumper in the off position without a D2430 external temperature sensor fitted, as this could result in a battery fire or explosion risk. 5.5 LED Display Four board mounted LEDs are used to provide a status and fault display. The DC power status display indication is brought out to the lid via a light pipe and identified with the label as shown. The other yellow indicators are only visible when the lid is removed: STATUS: The yellow LED indicates that DC power is available. AC OK: The green LED is lit when AC power is available. BAT FLT: The yellow LED is lit when any battery related faults are detected. FLT: The yellow LED is lit when any power supply related faults are detected. 5.6 OP1 and OP2 Due to high instantaneous current that can flow under fault conditions, the DC output wire is recommended to be 1mm cross sectional area or greater for all D2430 series power supplies. The outputs are individually protected against short circuits. The outputs can be switched using the SW1 and SW2 output control inputs. The outputs are fully protected against switching transients and are suitable for switching highly inductive loads such as door strikes and magnets. The combined output current of the two outputs must not exceed the power supply ratings. Page 9 of 14

5.7 SWI and SW2 Inputs These inputs can be used to switch on and off their associated outputs. The polarity of these inputs are selected by the INV jumper, with the jumper in the off position the outputs can be switched off when the input is low and when in the on position (inverted) the output can be switched off with a positive input. The wiring to these inputs shall not be more than 3 meters in length. The inputs have a 100K pull-up resistor and are 30V tolerant. They are designed to be easily driven by a 5V logic output, relay contacts or open collector transistors, see drive examples below: Internal pull-up 100K 5V SW1 Internal pull-up 100K 5V SW2 5V Internal pull-up 100K SW1 INV in off position, output switched on when contacts open INV in off position, output switched off when transistor conducts INV in on position, output switched on when contacts close 5.8 DATA and LED Interfaces These interfaces are used for factory testing and are reserved. 5.9 detection and Outputs Three normally closed relay outputs in no-fault conditions are provided for fault signalling and will open when a fault is detected. The is factory fitted with two wire links as shown below. To comply with EN54 requirements the three separate normally closed fault outputs should be connected in series, so should any one of the fault relays opens in a fault condition, a generic fault condition is signalled. Normally Closed Generic Output AC FLT BAT FLT FLT Wire Links The table below shows the relation between fault and outputs. FAULT OUTPUT DISPLAY DESCRIPTION AC power missing OP1 or OP2 shorted Over-voltage 1 Battery connection fault Battery high 2 resistance fault AC BAT BAT DC Power AC Power Battery Battery The front panel DC power LED will be on to indicate that DC is available, with or without AC power, The internal AC power LED will be off. The outputs will automatically retry to restore power every 5 seconds until the short is removed. If the power supply voltage exceeds 30 volts, both outputs will be switched off and a latched fault generated 2. If any of the battery connectors are disconnected a battery fault will be generated. The battery or battery connections are tested every hour and if the resistance is over 0.18ohms, a fault is generated 4. Page 10 of 14

FAULT OUTPUT DISPLAY DESCRIPTION low voltage Failure Charging 3 Failure Battery Low APS 3 Battery If the internal power rail voltage is too low to charge the battery, a fault will be generated 5. Should the switching power supply fail due to overloading, over-temperature or a component failure, a fault will be generated. Should the charging circuit fail, then a fault will be generated. If any individual battery is left to discharge below 11.5V when the is in standby mode, a fault will be generated. NOTES 1. Over voltage protection is done at two levels, the first being where the internal power low voltage rail (nominal 24V) is monitored and the second is where the off-line, high voltage side of the switched mode power supply is monitored. Should an off-line fault be found then the high voltage switching circuit will be disabled. In both conditions the power supply should be switched off and the batteries removed for 15 minutes to reset the fault. 2. The battery and connection resistance is tested every hour, except when first powered up. On power-up the battery is tested after 5 minutes to alert the installer to any potential battery condition fault. The fault threshold is approximately 0.18 Ohm. 3. This fault condition is detected by comparing the internal rail voltage to the calculated temperature compensation voltage. If more than 1 volt lower, then a fault will be generated. 5.10 Batteries Warning: There is a risk of fire and explosion if the wrong batteries or battery connection cables are fitted. Care should be taken with polarity when connecting the batteries. Used batteries should be disposed of in accordance to the WEEE directive. Two identical batteries of the specified type shall be used, preferably from the same batch and date of manufacture. This is important to maintain a balance of charge between the two batteries. Two cable harnesses are provided for individual connection to the board, where they are connected in series. The remote temperature sensor as supplied is to be fitted between the batteries. The size of the batteries is dependent on the size of the box, the load current and the amount of standby time required. The medium box will house two 7Ah batteries and the large box two 17Ah batteries. The battery cables are to be segregated from the incoming AC power supply wiring. 5.10.1 Battery Temperature Remote Sensor Fitting A remote battery sensor is supplied for accurate temperature compensation to comply with EN54-4 requirements. The sensor is plugged into the TEMP 3-way socket and the EXT jumper must be removed to enable the sensor. The sensor is supplied with a 200mm lead so the sensor head can be fixed between the batteries with a self-adhesive fixing plate and ty-wrap as provided. The power supply is not to be used with the EXT Jumper link removed without a remote temperature sensor fitted. Page 11 of 14

5.10.2 Battery Protection The batteries are reverse connection protected and the battery charging output is protected from short circuits. The battery output is overload protected by a resettable fuse, in addition to the electronic output fuses. If this fuse is tripped then the batteries should be disconnected for 5 minutes to allow the fuse to reset. When in standby mode the battery is switched off when the battery terminal voltage reaches 20V to prevent battery deep discharge damage. This fault is normally reset by restoring the AC power supply. 5.10.3 General Maintenance Warning: Isolate the AC power supply before removing the power supply lid. Do not touch components or heat sinks as there is risk of electric shock or burn hazard. The power supply should be regularly inspected by qualified personnel and the following checked: 1. No faults are displayed. 2. Battery terminals checked for corrosion and the terminals are securely tightened. 3. All the connections into the power supply terminal blocks are secure. 4. The battery voltages are checked and the voltages are balanced within a volt to each other. The battery manufacturer s specifications should be consulted when making battery voltage measurements. 5. Battery replacement is recommended after a 5-year service life. 6. Check there are no signs of water or moisture ingress and there is no mechanical damage to the enclosure. 7. Check for signs of overheating on the power supply board and battery cases. 8. Check the voltage outputs, they should be nominally between 26.5V and 28.5V depending on temperature. 9. There are no replaceable input, battery or output fuses. In the event of a fault the power supply board will have to be replaced. Page 12 of 14

6. Declared performance 0389 Dycon Power Solutions Ltd, Unit A, Cwm Cynon Business Park, Mountain Ash, CF45 4ER, UK 14 D2431, D2433, D2435/2014/09/19 Harmonised Technical Specification EN54-4:1997 + A1:2002 + A2:2006 Essential Characteristics Performance Clause Performance of power supply - General requirements - Functions - Materials, design and manufacture Operational reliability - General requirements - Functions - Materials, design and manufacture - Documentation - Marking Durability of operational reliability (temperature resistance) 4 5 6 4 5 6 7 8 - Cold (operational) 9.5 Durability of operational reliability (vibration resistance) Page 13 of 14

- Impact (operational) - Vibration, sinusoidal (operational) - Vibration, sinusoidal (endurance) Durability of operational reliability (electrical stability) - Electrical Compatibility (EMC), - Immunity tests (operational) 9.7 9.8 9.15 9.9 Durability of operational reliability (humidity resistance) - Damp heat, steady state (operational) - Damp heat, steady state (endurance) 9.6 9.14 Products covered by this standard are assumed to function during the alarm condition, in an event of fire, before the fire becomes so large as to affect their functioning. There is therefore no requirement to function when exposed to direct attack from fire. Page 14 of 14