Similar documents
Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated

Switchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.

Benefits, typical uses

NXAirS Withdrawable Medium-Voltage Switchgear up to 24kV Air-Insulated

Air-Insulated Medium-Voltage Switchgear NXAIR, up to 24 kv

DIRECT CONTACT. Switchgear Sales Team TEL : ~9 CHANGWON PLANT Switchgear Design Team TEL : ~9

Reliable medium-voltage switchgear for fail-safe operation, up to 24 kv siemens.com/simoprime-partner

Catalog HA Edition Medium-Voltage Switchgear. siemens.com/nxair

Fixed-Mounted Circuit-Breaker Switchgear up to 36 kv, SF 6 -Insulated

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated

Air Insulated Switchgear NXAirS, 40.5kV Answers for infrastructure and cities.

NXPLUS C Single busbar. Maintenance-free for lifetime

EMC 24 SERIES METAL CLAD SWITCHGEAR. We engineer, we assure. Up to 24 kv - 25 ka With Withdrawable, Air-Insulated, Medium Voltage Distribution Panel

Power Transmission and Distribution. NXPLUS C double busbar. The economical solution when replacing old systems

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

Vacuum Circuit Breaker

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

Catalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec

Types. Fixed-mounted circuitbreaker. NXPLUS C is a factoryassembled,

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

VB1-D Generator Circuit-Breaker Switchgear

HB1 and VB1 Generator Circuit-Breaker Switchgear. Medium-Voltage Switchgear. siemens.com/generatorswitchgear. Catalog HB1 and VB1 Edition 2017

8DJ. Maintenance-free for lifetime

MEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

UniGear. Technical Guide

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE - B - C - en - REV

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Medium-Voltage Switchgear OPERATING INSTRUCTIONS

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE-B-C-en-REV

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

Air-insulated medium voltage switchgear metal-enclosed type-tested factory-assembled withdrawable-unit design 12 kv / 24 kv

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated

with Vacuum Circuit Breaker HAF

Metal Clad Switchgears

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated

HIGS Highly Integrated Generator Circuit-Breaker Switchgear

ZX2 Gas-insulated medium voltage switchgear

ZX1.5-R. Gas-insulated medium voltage for railway application DISTRIBUTION SOLUTIONS. Gas-insulated medium voltage for railway application ZX1.

the safe, reliable, and efficient choice for MV switchgear

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kv, SF 6 -Insulated. Medium-Voltage Switchgear Catalog HA 35.

UP TO 17,5 kv LSC 2B PM (METAL-CLAD) WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES

Switchgear Type 8DJH 36 for Secondary

Gas Insulated Metal-clad Switchgear, HMGS!

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

ZX-Family Gas-insulated medium voltage switchgear

Features. 2 Siemens HA Page. 8DJ10 switchgear is a factoryassembled,

OVERVIEW DESCRIPTION AND CHARACTERISTICS APPARATUS AND TYPES AVAILABLE SWITCHGEAR CHARACTERISTICS INSTRUMENT TRANSFORMERS MEASUREMENT SENSORS

Medium voltage switchgear type W 12. rated voltage 12 kv rated current 630 A

PIX-H Metal-clad switchgear up to 17.5kV

MEDIUM VOLTAGE PRODUCTS. Powerbloc Pre-assembled modules for building medium voltage switchgear

Power Systems PU. HYOSUNG Standard High-voltage Switchgear ProSWGR. Medium Voltage Metal-clad Switchgear

voltage switchgear ZX ABB ZX Family 1

ZX2.2 Gas-insulated medium voltage switchgear

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment

CPG.0 Single busbar gas-insulated cubicles

Air-insulated switchgear UniGear type ZS1

Medium voltage compact switchgears. rated voltage 12 and 25 kv rated current 400 and 630 A

e 2 ALPHA Medium Voltage Switchgear K Catalogue EN

Gas-insulated medium-voltage switchgear. For the mining industry. Answers for energy.

Switchgear Type 8DH10 up to 24 kv, Gas-Insulated, Extendable

Power Xpert UX 36 High-voltage switchgear system. Reliable and safe for high performance applications

FIXED VCB AIR INSULATED SWITCHGEAR

Metal Clad Air Insulated Switchgear

Medium Voltage Distribution PIX. Air Insulated Switchgear up to 24 kv PARS TABLEAU

MESG 12 / 17.5 / 24 / 36 KV

GAE CLAD. Catalogue Metal - Clad Switchgear Up To 24 kv. Vacuum Circuit Breaker With Embedded Poles. PT Guna Era Manufaktura

MEDIUM VOLTAGE SWITCHGEAR. DW-2, Primary switchgear, air insulated and metal clad.

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

HB3-80 Generator Circuit-Breaker Switchgear. Medium-Voltage Switchgear. Totally Integrated Power HB3-80. Catalog HB3-80.

TECHNICAL SPECIFICATION. UP TO 36 kv METAL-CLAD. With WITHDRAWABLE VACUUM CIRCUIT BREAKER MEDIUM VOLTAGE CUBICLES

Gas-insulated medium-voltage switchgear. For the metal industry. Answers for energy.

Medium voltage products UniSec DY800 New 24 kv air-insulated medium voltage switchgear to e-distribuzione specifications

HB3 Generator Circuit-Breaker Switchgear

PowerCube type PB series A complete solution for OEMs

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

UniSafe 36. Medium voltage, arc-proof, air-insulated, metal-clad switchboard

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

ATR-MIX. METAL ENCLOSED SWITCHGEAR kV A ka

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

24kV Medium Voltage Switchgear Metal-Enclosed (LSC2A)

10/2015 CUBICLE AND METAL-CLAD MEDIUM VOLTAGE SWITCHGEARS WEGA 07 WEGA 12 WEGA 17 WEGA 24 WEGA 36

Safe and Reliable. Flexible, Compact Design. Easy Installation and Maintenance

AF series contactors (9 2650)

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

with Vacuum Circuit Breaker HAF

SWITCHCRAFT. Switchcraft Europe GmbH SWITCHCRAFT

PT Guna Era Manufaktura. Catalogue GAE TPS \ Medium Voltage Switchgear 12kV - 24kV \ M GAE TPS. Medium Voltage Switchgear 12kV - 24kV

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

Gas-insulated switchgear up to 420 kv, 63 ka, 5000 A Type 8DQ1. siemens.com/energy. Answers for energy.

Ultra Fast Earthing Switch UFES retrofit Overview

Gas-insulated medium-voltage switchgear. For marine and offshore applications. Answers for energy.

The Key Link for all your Distributions Needs. A Comprehensive Range for All Your Needs

Transcription:

medium voltage switchgear manufacturer VACUUM CIRCUIT-BREAKER SWITCHGEAR TYPE SIMOPRIME, UP TO 17.5kV, AIR INSULATED MEDIUM-VOLTAGE SWITCHGEAR. UNDER LICENSE BY SIEMENS. www.simosynergy.com/simoprime

VACUUM CIRCUIT-BREAKER SWITCHGEAR TYPE SIMOPRIME, UP TO 17.5kV, AIR INSULATED MEDIUM-VOLTAGE SWITCHGEAR. UNDER LICENSE BY SIEMENS. APPLICATION - Benefits & Typical Uses SIMOPRIME PANEL The circuit-breaker switchgear type SIMOPRIME is a facty - assembled, type-tested switchgear f indo installation accding to IEC 62271-200 and VDE 0671-200. Loss of service continuity categy Partition Class Internal arc classification arc duration : LSC 2B : PM : IAC A FLR, Isc 40kA, : 1 0.1 s SIMOPRIME Panel : Maximum ratings 17.5 kv / 40kA / 3600 A TYPICAL USES The SIMOPRIME circuit-breaker switchgear can be used in transfmer and switching substations, e.g.: Power supply system Power supply companies Industry Power stations Cement industry Automobile industry Iron and steelwks Rolling mills Mining industry Textile, paper and food industries Chemical industry Petroleum industry Pipeline installations Offshe installations Electro chemical plants Petro chemical plants Ship building industry Diesel power plants Emergency power supply installations Lignite open-cast mines Traction power supplies 02

(1) Option: Higher values acc. to GOST standards (2) Depending on the rated current of the HV HRC fuses installed (3) 60 kv f vacuum contact TECHNICAL DATA - Ratings Electrical data (maximum values) of SIMOPRIME Ratings Rated values (max.) Ratings Rated values (max.) Switchgear up to 7.2 kv Switchgear 12 kv Rated voltage 7.2 kv Rated voltage 12 kv Rated frequency 50/60 Hz Rated frequency 50/60 Hz Rated sht-duration power-frequency withstand voltage 20 kv (1) Rated sht-duration power-frequency withstand voltage 28 kv (1) Rated lightning impulse withstand voltage 60 kv Rated lightning impulse withstand voltage 75 kv (3) Rated sht-time withstand current, 3 s Rated sht-time withstand current, 3 s Rated peak withstand current at 50/60 Hz 100/104 ka Rated peak withstand current at 50/60 Hz 100/104 ka Rated sht-circuit breaking current Rated sht-circuit breaking current Rated sht-circuit making current at 50/60 Hz 100/104 ka Rated sht-circuitmaking current at 50/60 Hz 100/104 ka Rated nmal current of busbar 3600 A Rated nmal current of busbar 3600 A Rated nmal current of feeders Rated nmal current of feeders with circuit-breaker with vacuum contact 3600 A 400 A (2) with circuit-breaker with vacuum contact 3600 A 400 A (2) Switchgear 15 kv Switchgear 17.5kV Rated voltage 15 kv Rated voltage 17.5 kv Rated frequency 50/60 Hz Rated frequency 50/60 Hz Rated sht-duration power-frequency withstand voltage 35 kv Rated sht-duration power-frequency withstand voltage 38 kv Rated lightning impulse withstand voltage 95 kv Rated lightning impulse withstand voltage 95 kv Rated sht-time withstand current, 3 s Rated sht-time withstand current, 3 s Rated peak withstand current at 50/60 Hz 100/104 ka Rated peak withstand current at 50/60 Hz 100/104 ka Rated sht-circuit breaking current Rated sht-circuit breaking current Rated sht-circuitmaking current at 50/60 Hz 100/104 ka Rated sht-circuitmaking current at 50/60 Hz 100/104 ka Rated nmal current of busbar 3600 A Rated nmal current of busbar 3600 A Rated nmal current of feeders Rated nmal current of feeders with circuit-breaker 3600 A with circuit-breaker 3600 A 03

TECHNICAL DATA - Classification, dimensions, room planning Classification of the SIMOPRIME switchgear accding to IEC 62271-200 Internal arc classification Construction and design Classification IAC Partition class PM (metallic partition) Accessibility Loss of service continuity categy LSC2B (metal-clad) Front Type A Compartment accessibility (standard) Rear Type A Busbar compartment Tool-based Lateral Type A Switching-device compartment Interlock-controlled Test current (ka) 25/31.5/40 Low-voltage compartment Tool-based Arc duration (s) 0.1/1.0 Connection compartment Front connection Interlock-controlled and tool-based Rear connection Tool-based Dimensions All panel types Dimensions in mm Width B Circuit-breaker panel up to 31.5 ka 1000A 600 1250 A, 2500 A, 3150 A, 3600 A Contact panel 600 600 Disconnecting panel 1000 A 600 1250 A, 2500 A, 3150 A, 3600 A H1 H2 H3 Bus sectionalizer/circuit-breaker panel 1000 A 600 1250 A, 2500 A, 3150 A, 3600 A Bus sectionalizer/bus riser panel 2500 A 600 B T 3150 A, 3600 A Metering panel 600 Height H1 With standard low-voltage compartment and IAC 0.1 s 2253 2253 H2 With standard low-voltage compartment and IAC 1.0 s 2425 2460 H3-1780 1780 Depth T Standard 1860 1860 04

Single-row arrangement (plan view) F dimensions B (width) and T (depth) refer to table on the previous page. (1) Control aisle widths 31.5 ka and 3150 A versions: 1500mm 3600 A versions: 1700mm F panel replacement: 2000mm TECHNICAL DATA - Room planning Room planning (room height 2 mm) Front connection 100 B B 40 100 FRONT 40 100 1500 (1) T Rear connection B 40 500 FRONT 40 500 B 1500 (1) T 05

(1) The details refer to conventional single-ce sealing ends. PRODUCT RANGE - Panels CIRCUIT-BREAKER PANEL DISCONNECTING PANEL VACUUM CONTRACTOR PANEL Components Current transfmer Voltage transfmer without primary fuses Current transfmer in run of busbar Voltage transfmer with primary fuses Capacitive voltage detecting system Vacuum contact with HV HRC fuses Vacuum contact with control transfmer and HV HRC fuses Make-proof earthing switch Cable sealing ends (1) max. 4 x 500mm 2 per phase Bar connection Vacuum circuit-breaker Disconnect HV HRC Fuse 06

PRODUCT RANGE - Panels BUS SECTIONALIZER (MIRROR-IMAGE INSTALLATION ALSO POSSIBLE) METERING PANEL Circuitbreaker panel Bus riser panel Components Current transfmer Voltage transfmer without primary fuses Current transfmer in run of busbar Capacitive voltage detecting system Make-proof earthing switch Vacuum circuit-breaker Withdrawable voltage transfmer with primary fuses 07

Legend f panel design (A) - (E) (A) Switching-device compartment (B) Busbar compartment (C) Connection compartment (D) Vacuum circuit-breaker truck (E) Low-voltage compartment DESIGN - Panel Design Basic panel design (example) 1 Circuit - breaker panel 12kV, 1250 A, 40kA 2 3 4 5 6 7 8 9 10 13 14 15 16 17 18 22 23 24 11 12 19 20 21 Legend f panel design: (1) Do of low-voltage compartment (2) Opening f locking unlocking the low-voltage compartment do (3) Option: Capacitive voltage detecting system f feeder and busbar (4) High-voltage do (5) Inspection window f checking the switching device truck (6) Opening f locking unlocking the high-voltage do (7) Opening f mechanical charging of circuit-breaker closing spring (8) Openings f manual operation (ON/OFF) of the circuit-breaker (9) Inspection window f reading the indicats (10) Do handle (11) Openings f switching device truck operation (12) Opening f earthing-switch operation (13) Pressure relief duct (14) Busbars (15) Bushings (16) Post insulats (17) Block-type current transfmer (18) Option: Make-proof earthing switch (19) Cable sealing ends (20) Option: Voltage transfmer (21) Earthing busbar (22) Low-voltage plug connect (23) Vacuum interrupters (24) Switching-device truck 08

DESIGN - Compartments Switching - device compartment All switching operations with high-voltage do closed Pressure relief upwards Panel powder-coated with epoxy resin Shutter operating mechanisms separately f Busbar compartment Connection compartment Metallic, earthed shutters and partitions ensure partition class PM High-voltage do pressure resistant in the event of internal arcs in the panel Metallic ducts on the side f laying control cables Interlocking between high-voltage do and circuit-breaker truck ensures interlock-based access Option: Test sockets f capacitive voltage detecting system Switching-device compartment to accommodate components f implementing various panel versions with Vacuum circuit-breaker with without voltage transfmers on the truck Disconnect truck Vacuum-contact truck Metering truck Busbar compartment Pressure relief upwards and through rear pressure relief duct Option: Busbar transverse partition between panels Busbars made of flat copper, bolted from panel to panel F rated nmal currents up to 3600 A Option: Insulated busbars Bolted rear and top covers provide tool-based access Option: Coupling electrode f capacitive voltage detecting system Options: Possibility of installing the following components Voltage transfmers Busbar earthing switch Current transfmers in the run of busbars Connection compartment Pressure relief upwards through rear pressure relief duct Suitable f connection of Single-ce XLPE cables up to max. 6 x 500 mm2 per phase Three-ce XLPE cables up to max. 3 x 300 mm2 per panel Bars made of flat copper with bushings in a flo cover fully-insulated bars including flo cover Shutters to be opened separately to permit cable testing Earthing busbar Connection from front rear Option: Pressure-resistant flo cover Use of block-type current transfmers Bolted rear covers of the connection compartment provide tool-based access f panels with connection from rear Interlocked high-voltage do and bolted partitions between connection compartment and switching-device compartment provide interlock-based and tool-based access f panels with connection from front Components at the panel connection (option) Coupling electrode f capacitive voltage detecting system Voltage transfmers Cast-resin insulated Max. 3 x 1-pole Fixed-mounted, without primary fuses Make-proof earthing switches With manual operating mechanism In addition to standard interlocking of earthing switch / circuit-breaker truck, optionally lockable with electromagnetic interlock Surge arresters limiters Surge arresters f protecting the switchgear against external overvoltages Surge limiters f protecting consumers against switching overvoltages 09

DESIGN - Interlocks, operation Interlocks Interlocking conditions are satisfied accding to IEC 62271-200 / VDE 0671-200 Earthing switch can only be operated with circuit-breaker truck in test position Circuit-breaker truck can only be moved with circuit-breaker OPEN and earthing switch OPEN Mechanical coding on the circuit-breaker truck prevents insertion of similar circuitbreaker trucks f lower rated nmal currents into panels with higher rated nmal currents Interlocking of high-voltage do against circuit-breaker truck The high-voltage do can only be opened when the circuit-breaker truck is in test position Option: Electromagnetic interlocks Low-voltage Compartment F accommodation of all protection, control, measuring and metering equipment Partitioned safe-to-touch from the high-voltage part Low-voltage compartment can be removed, bus wires and control cables are plugged in Option: Partition between panels Low-voltage Cables Control cables of the panel are flexible and have metallic covers Connection of switching device truck and panel wiring to low-voltage compartment via 64-pole coded plug connects Bus wires are pluggable from panel to panel 10

DESIGN - Benefits and features Benefits Saves lives Features All switching operations including emergency manual operations with high-voltage do closed Interlocking between high-voltage do and switching devices Rack-in, rack-out operations of the circuit-breaker truck with high-voltage do closed Metallic, earthed shutters and partitions, partition class: PM (metallic partition) Internal arc tested design up to, 1 s, accding to IEC 62271-200, VDE 0671-200 Use of vacuum circuit-breakers Peace of mind Facty-assembled, type-tested switchgear accding to IEC 62271-200 Type testing of the circuit-breaker inside the panel Use of standard, wld-wide available components Use of maintenance-free vacuum circuit-breakers Quality management accding to DIN EN ISO 9001 Design based on global best practice sharing and experience Me than 300,000 air-insulated switchgear panels powered by Siemens in operation wld-wide Increases productivity Use of metallic, earthed shutters and partitions between the compartments ensures highest loss of service continuity of the switchgear (LSC2B accding to IEC 62271-200) during maintenance Use of maintenance-free vacuum circuit-breakers Saves money Use of maintenance-free vacuum circuit-breakers 11

The products and systems described in this catalog are manufactured and sold accding to a certified quality and environmental management system (acc. to ISO 9001 and ISO 14001). (DQS Certificate Reg. No. DQS 003473 QM UM). The certificate is accepted in all IQNet countries. STANDARDS - Standards, specifications, guidelines The switchgear complies with the relevant standards and specifications applicable at the time of type tests. In accdance with the harmonization agreement reached by the EU countries, their national specifications confm to the IEC standard. Overview of standards (March 2008) IEC standard VDE standard EN standard Switchgear SIMOPRIME IEC 62271 VDE 0671-1 EN 62271-1 IEC 62271-200 VDE 0671-200 EN 62271-200 Devices Circuit-breaker IEC 62271-100 VDE 0671-100 EN 62271-100 Vacuum contact IEC 60470 VDE 0670-501 EN 60470 Disconnect and earthing switch IEC 62271-102 VDE 0671-102 EN 62271-102 HV HRC fuses IEC 60282 VDE 0670-4 EN 60282 Voltage detecting systems IEC 61243-5 VDE 0682-415 EN 61243-5 Degree of protection - IEC 60529 VDE 0470-1 EN 60529 Insulation - IEC 60071 VDE 0111 EN 60071 Instrument transfmers Current transfmer IEC 60044-1 VDE 0414-1 EN 60044-1 Voltage transfmer IEC 60044-2 VDE 0414-2 EN 60044-2 Installation - IEC 61936-1 VDE 0101-12

STANDARDS - Standards, specifications, guidelines Type of service location The switchgear can be used f indo installation in accdance with IEC 61936 (Power installations exceeding 1kV AC) and VDE 0101 Outside lockable electrical service locations at places which are not accessible to the public. Enclosures of switchgear can only be removed with tools. Inside lockable electrical service locations. A lockable electrical service location is a place outdos indos that is reserved exclusively f housing electrical equipment and which is kept under lock and key. Access is restricted to authized personnel and persons who have been properly instructed in electrical engineering. Untrained unskilled persons may only enter under the supervision of authized personnel properly instructed persons. Table - Dielectric strength (kv) Rated voltage (rms value) 7.2 12 15 17.5 Rated sht-duration power-frequency withstand voltage (rms value) Across isolating distances Between phases and to earth 23 20 32 28 39 35 45 38 Rated lightning impulse withstand voltage (peak value) Across isolating distances Between phases and to earth 70 60 85 75 105 95 110 95 Altitude crection fact Ka F site altitudes above 1000m, the altitude crection fact Ka is recommended, depending on the actual site altitude above sea level. Dielectric strength The dielectric strength is verified by testing the switchgear with rated values of shtduration power-frequency withstand voltage and lightning impulse withstand voltage accding to IEC 62271-1 / VDE 0671-1 (see table Dielectric strength ). The rated values are referred to sea level and to nmal atmospheric conditions (1013 hpa, 20 C, 11 g/m3 humidity in accdance with IEC 60071 / VDE 0111). The dielectric strength decreases with increasing altitude. F site altitudes above 1000 m (above sea level) the standards do not provide any guidelines f the insulation rating. Instead, special arrangements apply to these altitudes. Site altitude As the altitude increases, the dielectric strength in air decreases due to the decreasing air density. This reduction is permitted up to a site altitude of 1000 m accding to IEC and VDE. F site altitudes above 1000 m, a higher insulation level must be selected. It results from the multiplication of the rated insulation level f 0 to 1000 m with the altitude crection fact Ka. Altitude crection fact Site altitude in m above sea level Rated sht-dur. power-freq. withstand volt. to be selected f site altitudes>1000m Rated sht-duration power-frequency withstand voltage up to 1000m Ka Rated lightning impulse withstand volt. to be selected f site altitudes > 1000m Rated lightning impulse withstand voltage up to 1000m Ka Example: 1m site altitude above sea level 12 kv switchgear rated voltage 75 kv rated lightning impulse withstand voltage Rated lightning impulse withstand voltage to be selected 75 kv 1.10 = 82.5 kv Result: Accding to the above table, a switchgear f a rated voltage of 17.5 kv is to be selected. 13

STANDARDS - Standards, specifications, guidelines Terms Make-proof earthing switches are earthing switches with sht-circuit making capacity accding to IEC 62271-102 and VDE 0671-102 / EN 62271-102 Internal arc classification Protection of operating personnel by means of tests f verifying the internal arc classification Internal arcing tests must be perfmed in accdance with IEC 62271-200 / VDE 0671-200 The switchgear complies with criteria 1 to 5 specified in the mentioned standards f the basic version up to. Definitions of the criteria: Criterion 1 Crectly secured dos and covers do not open. Limited defmations are accepted. Criterion 2 No fragmentation of the enclosure. Projection of small parts up to an individual mass of 60 g are accepted. Criterion 3 Arcing does not cause holes in the accessible sides up to a height of 2 m. Criterion 4 Hizontal and vertical indicats do no ignite due to the effect of hot gases. Criterion 5 The enclosure remains connected to its earthing point. Current-carrying capacity Accding to IEC 62271-1 / VDE 0671-1 and IEC 62271-200 / VDE 0671-200 current carrying capacities refer to the following ambient air temperatures: Maximum of 24-hour mean + 35 C Maximum + 40 C The current-carrying capacity of the panels and busbars depends on the ambient air temperature outside the enclosure. To attain the maximum rated nmal currents, the panels are provided with natural fced ventilation. Climate and environmental influences The switchgear may be used, subject to possible additional measures, under the following environmental influences and climate classes: Environmental influences Natural feign materials Chemically active pollutants Small animals Climate classes 3K3 3K5 The climate classes are classified accding to IEC 60721-3-3. Protection against solid feign bodies, electric shock and ingress of water SIMOPRIME switchgear fulfills acc. to the standards IEC 62271-200, IEC 60529, VDE 0470-1 and VDE 0671-200, the following degrees of protection: Enclosure: IP 4X, IP 5X (protection against solid feign bodies) IP X1, IP X2 (protection against ingress of water) Compartments: IP 2X (protection against solid feign bodies) Higher degree of protection f enclosure on request. 14

CHOOSING SIMOPRIME SWITCHGEAR, PROVIDES PEACE OF MIND, IT INCREASES PRODUCTIVITY, IT IS COST EFFICIENT AND MORE IMPORTANTLY, IT SAVES LIVES. NOTES 15

Published by and copyright 2012 : SimoSynergy Sdn. Bhd. ( 1009104-W ) Lot 58, Jalan Industri 13, Kawasan Perindustrian Kelemak, 70 Al Gajah, Melaka, Malaysia www.simosynergy.com/simoprime F me infmation, please contact our Customer Suppt Center Phone : +606 556 3891 / +606 556 3898 Fax: +606 556 3892 (Charges depending on provider) E-mail: suppt@simosynergy.com Designed by : Luid Studio www.luidstudio.com Printed in Malaysia All rights reserved If not stated otherwise on the individual pages of this catalog, we reserve the right to include modifications, especially regarding the stated values, dimensions and weights. Drawings are not binding All product designations used are trademarks product names of SimoSynergy Sdn. Bhd. other suppliers. If not stated otherwise, all dimensions in this catalog are given in mm. Subject to change without pri notice The infmation in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefe be specified in the contract. www.simosynergy.com