Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Similar documents
Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

Publication No.: PSG

Horizontal Circuit Switchers

Horizontal Circuit Switchers

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

CITY OF MARYVILLE ELECRIC DEPARTMENT Maryville, Tennessee SPECIFICATIONS FOR 15KV POWER CIRCUIT BREAKERS. September 2018

CENTER BREAK GROUP OPERATED AIR BREAK SWITCHES RATED 15.5kV THROUGH 170kV EFFECTIVE DATE: 10/25/16 REV B

Three-Phase Pole Mounted Recloser

Technical Specification For Outdoor Substation Harmonic Filter Banks

SDV7. Outdoor distribution circuit breaker family 15.5 kv to 38.0 kv. usa.siemens.com/sdv7

Type SDV7 distribution circuit breaker family

Submersible Vacuum Fault Interrupters

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Typical Specification

43-SDMS-01 SPECIFICATIONS FOR

Type SDV7 distribution circuit breaker family Answers for energy.

43-SDMS-04 REV. 00 SPECIFICATIONS FOR

Product Specifications for Aluminum Vertical Break Switches

Descriptive Bulletin. R-MAG magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Cobra-S. Catalog Cobra-S

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

C1000 Series Automatic Cap Bank

S&C Series 2000 Circuit-Switchers Outdoor Transmission 69 kv through 230 kv

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Medium Voltage Metal-Enclosed Switches

SECTION III SF6 GAS CIRCUIT BREAKER TECHNICAL SPECIFICATIONS TABLE OF CONTENTS

Solid Dielectric, Single Phase Recloser

SECTION III - VACUUM CIRCUIT BREAKER TECHNICAL SPECIFICATIONS TABLE OF CONTENTS 1. SCOPE PROJECT ENGINEER STANDARDS...

Solid Dielectric, Independent Pole Operated Reclosers Catalog O-vst16

Product Specifications for Phase Over Phase GOABS(r)

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Metal-Enclosed Switches

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

100 / 110 DRYWELL FUSE SPECIFICATION

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

BUSWAY Low Voltage (Pow-R-Flex)

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Power IT MV Live Tank Vacuum Circuit Breaker Model VBF

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

AIR CORE REACTORS. Phoenix Electric Corporation

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

Underground Distribution Switchgear

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

شركة كهرباء محافظة القدس المساهمة المحدودة

1VAL2401-SG Rev D. Spare parts list for Outdoor Products Reclosers, breakers, & padmount switches

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

B kv T&D GAS INSULATED SWITCHGEAR

Solid Dielectric, Triple Option Reclosers Catalog O-vst14

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

Power IT MV Live Tank Vacuum Circuit Breaker. Model OVB-SDB

Outdoor vacuum breaker for railway applications - FSK II

Special Specification 6058 Battery Back-Up System for Signal Cabinets

Extensible Unit - VCE2a

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Integrated Power Solutions

City of Jacksonville Beach

34-SDMS-01 SPECIFICATIONS FOR

The vacuum circuit breaker for commercial buildings, industrial plants and utilities

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

Switchgear Skid, C1192

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

SPECIAL SPECIFICATION 1788 Surveillance Cabinet

RUS accepted Catalog O-vst18

University of Houston Master Construction Specifications Insert Project Name

SECTION V - TECHNICAL SPECIFICATIONS TABLE OF CONTENTS

Live Tank Circuit Breakers Buyer s Guide

Underground Distribution Switchgear

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

SECTION DC POWER SUPPLY/BATTERY CHARGER

SPECIAL SPECIFICATION 6894 Communication Cabinet

Solid Dielectric, Three Phase Reclosers Catalog O-vs18

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

Copper Double Break Switch

Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC

SWITCHGEAR DIVISION PRODUCT PROFILES

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

PATENT PENDING. Phone: (877) Operation and Service Manual

Transcription:

TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 2 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads... 4 3.06 Operating Mechanism... 4 3.07 Ground Pads... 5 4.0 MANUFACTURING REQUIREMENTS... 6 4.01 Wiring... 6 4.02 Mechanism Frame... 6 4.03 Support Structure... 6 5.0 DESIGN TESTS... 6 6.0 PRODUCTION TESTS... 7 6.01 Mechanical Operation Tests... 7 6.02 Leak Test... 7 6.03 Resistance Tests... 7 6.04 Dielectric Tests... 7 7.0 SPARE PARTS... 8 8.0 DOCUMENTATION REQUIREMENTS... 8 8.01 Approval Drawings... 8 8.02 Final Drawings... 8 8.03 Instruction Books... 8 8.04 Additional Documentation... 8 9.0 SHIPPING and DELIVERY... 8 10.0 WARRANTY... 9 11.0 SPECIFIC QUOTE REQUIREMENTS... 9 12.0 ACCEPTABLE REACTOR SWITCHER... 9 Page 1 of 9 PSG-811-RLS362-R0 4/1/2011

1.0 SCOPE This specification covers the design, manufacture, and testing of a three pole, independent phase operated (IPO) outdoor reactor switcher with vertical interrupters. This switcher is to be rated for 362 kv 3 phase reactors of 395 MVAR (630 A) or less. 2.0 STANDARDS All outdoor reactor switchers shall be designed, manufactured, assembled, and tested in accordance with the latest applicable ANSI, NEMA, and ASTM standards and guidelines. If there are any conflicts between the ANSI, NEMA, or ASTM standards and this specification shall govern. 3.0 DESIGN REQUIREMENTS 3.01 Service Conditions The reactor switcher shall be suitable for outdoor installation in electric power substations under the following conditions: 3.02 Ratings 3.01.01 Temperature The reactor switcher shall perform in an ambient temperature range of -40 o C through +50 o C. 3.01.02 Altitude The reactor switcher shall perform at elevations up to 3,300 feet. 3.01.03 Seismic The reactor switcher shall be capable of withstanding seismic loading categorized as low seismic per IEEE 693-2005 when installed on the manufacturer s furnished support structure and anchor bolts and with flexible connections to the terminal pads. The device shall perform its specified functions during and after the seismic event. The reactor switcher will have the option of being fitted for service to withstand a high seismic event per IEEE 693-2005. 3.01.04 Wind Loading The reactor switcher shall be capable of withstanding wind loads up to 90 mph without loss of function. 3.01.05 Additional Requirements If any site-specific service conditions not covered in sections 3.01.01 through 3.01.04 exist (e.g. extreme cold temperature installation, corrosive environment, high altitude installation, etc.) they will be defined in the quotation request. Page 2 of 9 PSG811-RLS362-R0 4/1/2011

3.02.01 General Specifications Rated Maximum Voltage Rated Power Frequency Rated Lightning Impulse Withstand Voltage (BIL) Rated Continuous Current Rated Switching-Impulse Withstand Voltage Terminal to Ground Closed Rated Switching-Impulse Withstand Voltage Terminal to Terminal Open Rated Short Circuit Interrupting Current Rated Short-Time Withstand Current Rated Short-Circuit Making Current Peak Withstand Current Interrupting Time Rated Duty Cycle Environmental Rating Rated Reactor Switching Current REACTOR SWITCHING RATING 362 kv 50/60 Hz 1300 kv 630 A 825 kv 900 kv None 40 ka RMS 3 sec 63 ka RMS 18 cycles 63 ka 164 ka Peak 3 cycles O-CO -40 C to +50 C 630 A 3.02.02 Additional The RLSwitcher switcher shall have an endurance life of 10,000 Operations. 3.02.03 Source Supply Voltages Purchaser will supply the following sources for the motor, auxiliary, and control circuits: 1. Motor / Control Voltage: 240 VAC / 125 VDC; 2. Auxiliary Voltage: 120 VAC, 60 Hz, 1 3.03 Interrupter The reactor switcher shall use double gap SF6 puffer interrupters. Each interrupter shall be housed in a composite insulator that is ANSI 70 gray. Arc assist type interrupters are not acceptable. Each interrupter shall be provided with an overpressure relief device and shall be field refillable. Hermetically sealed interrupters are not acceptable. Page 3 of 9 PSG811-RLS362-R0 4/1/2011

Each pole will have a voltage limiter (arrestor) in parallel with each interrupter for proper voltage distribution and to control reignitions. 3.04 SF6 Gas System The gas system shall include the insulators, connecting tubing, and color-coded, temperature compensated gas density gauges that are visible from the ground and have low-pressure alarm and lockout contacts. The density switch must be at ground potential. Battery powered gas density monitors are not acceptable. The system shall be constructed such that the density gauge can be isolated from the interrupters to allow the low-pressure alarm and lockout contact set points to be verified. A means for refilling the system in the field without disassembling the reactor switcher must be provided. The reactor switcher shall have a leak rate of less than 0.5% per year. 3.05 Terminal Pads Terminal pads shall be unplated aluminum with 4 hole NEMA drilling pattern for use with purchaser furnished terminal connectors. 3.06 Operating Mechanism 3.06.01 Spring Operating Mechanism Each reactor switcher shall be provided with IPO (Independent Pole Operated) spring open-spring close mechanisms with a rated duty cycle of CO 5 min CO 5 min CO. The springs shall be charged via an electric motor in 15 seconds or less. Pneumatic, hydraulic, or combination pneumatic/hydraulic mechanisms are not acceptable. 3.06.02 Mechanism Housing and Control Components Each mechanism housing shall be painted ANSI 70 gray and shall be furnished with the following accessories: 1. Electric spring charging motor 2. Color coded, temperature compensated gas density gauge with low-pressure alarm contact and low-pressure lockout contact 3. Close coil (qty 1) per IPO mechanism 4. Trip coil (qty 2) per IPO mechanism 5. The control circuits Trip 1, Trip 2 and Close will each be on its own independent circuit. This will insure that if one circuit fails the others can operate on their own. 6. Trip coils will be connected in parallel in each of the Trip 1 and Trip 2 circuits 7. Each trip and close circuit will have provisions for coil monitoring. Page 4 of 9 PSG811-RLS362-R0 4/1/2011

8. 12 spare non-adjustable auxiliary switch contacts factory set as 6 normally open (NO) and 6 normally closed (NC) contacts 9. All auxiliary switches will be connected in such a way that the switches can be changed from parallel to series connected by field personnel 10. Thermostatically controlled field adjustable cabinet heater 11. Spring charged-discharged indicator 12. Manual closing spring charging handle 13. Open-Close position indicator 14. Manual trip1, trip2 and close push button 15. Local-remote selector switch 16. 52 Y Relay 17. Electrical operations counter 18. 120 VAC cabinet light with door actuated switch 19. 120 VAC duplex receptacle with GFCI 20. View window(s) in cabinet door for the counter, gage and indicator light 21. Circuit Breakers will be used for circuit protection 22. Hinged cabinet door with 3 point latch, open position door stop, and padlocking provisions 23. Pole disagreement circuit provided as standard 3.06.03 Control Cabinet Housing The control cabinet will be painted ANSI 70 Gray and be furnished with the following components. 1. Open-Close position indicator 2. Thermostatically controlled cabinet heater 3. Ultrasafe fusible disconnect class J fuse protection of control, motor, heater and utility circuit. 4. Operations counter 5. 120 VAC cabinet light with door actuated switch 6. 120 VAC duplex receptacle with GFCI 7. Hinged cabinet door with non corrosive 3 point latch, open position door stop and padlocking provisions 3.07 Ground Pads Two galvanized steel NEMA 2 hole ground pads shall be supplied for grounding the structure to the station ground grid. Each individual mechanism will have separate NEMA 2 hole ground pads The common IPO control cabinet will have its own ground pad. Page 5 of 9 PSG811-RLS362-R0 4/1/2011

4.0 MANUFACTURING REQUIREMENTS 4.01 Wiring and Control System Wiring shall be: 1. Point-to-point without splices or tee connections. 2. Bundled using cable ties or inside wiring duct. 3. Clearly identified with permanently affixed markers. 4. SIS wire No. 14 AWG minimum. 5. Crimped with calibrated crimpers and tested with a 100% pull test. 6. Dielectric test will be performed on the control circuits per ANSI C07.016-2006 section 7.1 4.02 Mechanism Frame Each reactor switcher shall be provided with a manufacturer furnished base frame which houses the gas piping and gauge that forms the gas system while also housing the linkage that connects the interrupter to the spring operating mechanism. The base frame shall be ANSI 70 gray painted steel. Minimum phase spacing is 150 inches when applied at 362 kv. 4.03 Support Structure Each support column shall be made from galvanized steel. The columns shall be capable of bolting directly to a 4 hole bolt pattern on 20 x 20 centers and furnished for use with 1 x 2-9 J type anchor bolts. Unless otherwise specified in the quotation request anchor bolts will be provided by the purchaser. All anchor bolts shall be sized as required for the operational loads generated by the reactor switcher. The manufacturer shall determine anchor bolt sizing and anchor bolt plan details when providing the anchor bolts. 5.0 DESIGN TESTS The RLSwitcher shall be design tested in accordance with ANSI C37.09-2001 unless otherwise specified. The testing shall include: Dielectric tests o 60 Hz power frequency: 555 kv o Lightning impulse withstand voltage: 1300 kv o Switching impulse withstand voltage: 900/825 o Chopped wave lighting impulse withstand voltage: 1680 kv o RIV: per NEMA SG4 Page 6 of 9 PSG811-RLS362-R0 4/1/2011

Power test shall include o Short-circuit making current: 164 kv Peak (63 ka rms) o Short-time withstand current: 40 ka for 3 sec o Shunt reactor bank switching current: 630 A; per IEC Standard 62271-110 (2005-6) Continuous current test: 630 A 6.0 PRODUCTION TESTS Each reactor switcher shall be fully assembled as a three-phase unit at the factory, adjusted, tested, and timed per ANSI C37.016-2006 Section 7. The tests shall include: 6.01 Mechanical Operation Tests There shall be at least 120 mechanical operations performed at the factory. Timing tests, opening and closing operations at minimum and maximum operating voltage, and spring recharge time shall be recorded. 6.02 SF6 Tightness Test An SF6 leak test shall be performed to confirm the leak rate is less than 0.5% per year. 6.03 Resistance Tests 6.03.01 Current Path Resistance Tests A terminal-to-terminal micro-ohm resistance check shall be performed on each interrupter and each full two phase interrupter set using a 100 A DC source and the values shall be recorded. 6.03.02 Heater, Coil, and Relay Resistance Tests The resistance of each heater, coil, and relay shall be confirmed to be within specifications and the value(s) shall be recorded. 6.04 Dielectric Tests per ANSI C37.016-2006 Section 7 6.04.01 Control Circuit Dielectric Test The completely assembled and wired operator control circuit shall pass a dielectric test of 1500 V for 1 minute. 6.04.02 Interrupter Dielectric Test Each phase shall pass a power frequency withstand test at 60 Hz for one minute. The required test value shall be 555 kv. Page 7 of 9 PSG811-RLS362-R0 4/1/2011

7.0 SPARE PARTS No spare parts shall be required to be purchased at the time of reactor switcher purchase. Stock shall be maintained at the manufacturer available for rush shipment in the event of an emergency need. 8.0 DOCUMENTATION REQUIREMENTS 8.01 Approval Drawings The manufacturer shall furnish approval drawings in AutoCAD.DWG format via e-mail. The purchase order will designate the name and e-mail address of the individual where the drawings should be forwarded. If there are no comments to the approval drawings purchaser will respond via e-mail that drawings are approved as submitted with no changes. If comments are required then one copy of the drawings will be returned to the manufacturer within 10 days from the date of transmittal marked approved with comments as noted. 8.02 Final Drawings The manufacturer shall furnish final drawings in AutoCAD.DWG format via e- mail. Unless otherwise specified in the purchase order, the final drawings will be forwarded to the same individual that the approval drawings were sent to. 8.03 Instruction Books The manufacturer shall furnish an electronic copy of each applicable instruction book in Adobe Acrobat.PDF format via e-mail. Unless otherwise specified in the purchase order, the instruction book(s) will be forwarded to the same individual that the approval drawings were sent to. 8.04 Additional Documentation One complete set of final drawings and one copy of each applicable instruction book shall be shipped in a weatherproof envelope with each reactor switcher. 8.05 SHIPPING and DELIVERY The reactor switcher shall be match-marked and disassembled as necessary to accommodate shipping dimensional clearance restrictions. The interrupters shall be shipped with a positive pressure of 10 psi of SF6, eliminating the need to pull a vacuum on them in the field. An SF6 fill kit shall be provided to fill the common gas system to rated pressure during installation. Page 8 of 9 PSG811-RLS362-R0 4/1/2011

9.0 WARRANTY All reactor switchers and their accessories furnished under this specification shall be covered by a two year warranty from date of invoice or 2,000 operations; whichever comes first; against failure due to design or to defects in workmanship or material. 10.0 SPECIFIC QUOTE REQUIREMENTS Information furnished by purchaser at time of quote request will include: 1. Maximum Rated Voltage in kv 2. Motor / Control voltage (240 VAC Motor / 125 VDC Control) 3. Heater voltage (120 VAC, 60 Hz, 1 or 240 VAC, 60 Hz, 1 ) 4. Who will supply anchor bolts manufacturer or purchaser 5. Column height 7 6 6. Additional requirements, if applicable (see section 3.01.05) 7. Wind loading requirements 8. Seismic requirements per IEEE 693-2005 11.0 ACCEPTABLE REACTOR SWITCHER Supply Southern States type RLSwitcher or acceptable equal. Any equal proposed must meet or exceed this specification. RLSwitcher is a registered trademark of Southern States, LLC. Page 9 of 9 PSG811-RLS362-R0 4/1/2011