Customer Requirements Downtown Secondary Network Service

Similar documents
Customer Requirements Meter Socket Configurations

10 Commercial, Industrial, Agricultural Services

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

Metering and Service Installation:

UNDERGROUND SERVICES - SECONDARY

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

A. Submit manufacturer's literature and technical data before starting work.

Approved Contractor Construction e-guide Residential Commercial

RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS

COMMERCIAL QUICK REFERENCE

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

PEU reserves the right to determine all meter locations. Only authorized PEU personnel will determine this location.

SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS

grounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2

ELECTRICAL METERING RESIDENTIAL

METERING REQUIREMENTS

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE

Electrical Design/Build Guide

Commercial Electric Policy

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS SECTION II RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS

ENGINEERING SPECIFICATION

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

NEW SERVICE HANDBOOK COMMERCIAL & IRRIGATION SUPPLEMENT

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

Service Entrance Methods

Customer Substation Manual

Outdoor Power Transmission & Distribution

REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

SECTION MOTOR CONTROL

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

AMENDMENT ELECTRIC SERVICE MANUAL 2014

7. SERVICES OVER 600 VOLTS

Service Requirements

PUBLIC UTILITY DISTRICT NO. 1 OF LEWIS COUNTY METERING SPECIFICATIONS

Generator Fire Safety: Generator assemblies should be located outside the building.

SECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS

For Conduit Inspections

Electric Service Standards

Clark Public Utilities Commercial Electric Service Handbook. This page left blank intentionally.

10. METERING General Requirements

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE

Metering and Control Standards OFF-PEAK & DUAL FUEL WIRING DIAGRAMS

Service Requirements

University of Houston Master Construction Specifications Insert Project Name

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Section 6 Electric Metering: Residential

Engineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes

CON EDISON EQUIPMENT

JACKSON ELECTRIC COOP METER LOOP CONSTRUCTION SPECIFICATIONS JUNE 2018

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION

SECTION PANELBOARDS

SERVICE REQUIREMENTS COMMERCIAL & INDUSTRIAL CUSTOMERS

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

SECTION 500 METERING AND ASSOCIATED EQUIPMENT

ELECTRIC SERVICE MANUAL

Table of Contents. Electrical Service Requirements. 1. General Requirements

Pretest Module 24 Three-phase Service Entrance

Parkland Light & Water Co. ELECTRIC SERVICE REQUEST AND METER STANDARDS

Document Requirements for Engineering Review PV Systems v1.0 6/9/2017

SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp

Assessing a Site for Installation of Consumption Monitoring

SECTION VII METERING INSTALLATIONS

SECTION 300 OVERHEAD SERVICE

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

GENERAL INFORMATION 1.01 PURPOSE

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

INTERCONNECTION REQUIREMENTS INVERTER-BASED DISTRIBUTED GENERATION SOURCES FOR SINGLE-PHASE CUSTOMER SERVICES

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION

Transformers 6. Gross Automation (877)

Technical Specification For Outdoor Substation Harmonic Filter Banks

Associated equipment As related to metering equipment: such as the current transformers, CT wiring and test switches.

Bussmann series Quik-Spec Coordination Panelboard

7 Single Family Service

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

Electric & Gas Service Requirements (Greenbook) Overview

New Panelboard for Lot H, EV Charger Energization, Las Positas College. Scope of Work and Technical Specifications

Design Standard. Purpose: Design Standard:

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE

7. Residential Single-Family and Duplex Buildings (Dwellings)

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

SWITCHGEAR DIVISION PRODUCT PROFILES

SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION

A. General: Deliver, store and handle wire and cable in accordance with the manufacturer's instructions and as specified in Division 1.

ADVANCED CALCULATIONS

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018

Approved Meter Sockets and Cabinets

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code

Recommended Procedures

Meter Standards COMMERCIAL. Metering Guidelines for Electric Service. March 28, 2014

WELLS RURAL ELECTRIC COMPANY Adopted: March 1976 Revised: March 21, 2017 Reviewed: August 21, 1998 RULE NO. 2

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

Transcription:

Application This standard describes the limitations and requirements for receiving service from the Tacoma Power secondary network system within the City of Tacoma downtown core area. In This Standard The following table lists the location of different parts of this standard. Topic See Page Area of Availability 2 Electrical Service Requirements 3 Service Entrance Disconnect/Switchgear 5 Service Entrance Conduit 7 Metering 8 Customer Owned Generation 8 Transmission & Distribution Standards Page 1 of 8

Area of Availability The figure below shows the approximate boundaries for providing service from the secondary network system. Figure 1 Boundary diagram for network secondary service. Transmission & Distribution Standards Page 2 of 8

Electrical Service Requirements The information below describes the requirements for receiving service from the network secondary service. Customers must submit a set of electrical plans to the Tacoma Power electrical Inspection Office for three phase services of greater than 200A for plan review. Service Panel Characteristics The electrical service panel characteristics provided by the network secondary system are: Item Characteristic Voltage 125/216 volts ONLY from the network 120/208 & 277/480 volts are available in parts of the network area but are not supplied from the network system Electrical Connection Grounded Wye 4 wire Panel Sizes 2 phases & neutral 100A and 200A 3 phases & neutral 200A to 2400A Limitations Tacoma Power may not always be able to readily accommodate panels in the 1600A to 2400A range. Each new service will be handled on an individual basis by the Tacoma Power Engineer. Necessary feeder upgrades may be required with lead times up to a year. Electrical service panels that exceed 2400A are not served by the network secondary system. The Tacoma Power Engineer will design a separate power delivery system for panels sized over 2400A of service requirement. Fault Duty 100A panels must have a brace rating of 40,000 A.I.C. 200A panels must have a brace rating of 65,000 A.I.C. 400A panels and larger must have a brace rating of 200,000 A.I.C. Transmission & Distribution Standards Page 3 of 8

Electrical Service Requirements (continued) Secondary Conductors Tacoma Power will furnish and install service conductor in customer-installed conduits from the network bus to the service panel at the customer s expense. Each secondary run or set of phase & neutral cables shall be installed in a separate conduit. The service conductor will be determined by panel size as indicated below: Panel Size 100A 200A 400A to 2400A Secondary Conductor #2 Cu, 600V, THHN, stranded 250 kcmil Cu, 600V, (RHH-2) 350 kcmil Cu, 600V, (RHW-2) Termination of Secondary Conductors Tacoma Power will terminate the secondary conductor at both the customer service panel and the secondary network bus where cable limiters are required. Customers are responsible to follow the manufacturer s recommendations for torquing and cable bracing. Cable Limiters Tacoma Power will furnish and install cable limiters as required, at the customer s expense. On 100A and 200A customer panels, cable limiters are not required at the panel side. On 400A and larger services, they are required on both ends of each phase cable. Required Information for the Tacoma Power Engineer & Electrical Inspection Plan Review Proposed panel size and A.I.C. rating Confirm desired voltage Connected load with panel schedule Expected demand in kva Service address Site plan with the electrical room location and dimensions noted The date service energization is desired by the customer For services greater than 200A, electrical drawings, stamped and signed by professional electrical engineer Manufacturer s one-line diagram of service equipment All information concerning plan review submitted to electrical plan review. Transmission & Distribution Standards Page 4 of 8

Service Entrance Disconnect/Switchgear Figure 2 Typical Disconnect Configuration Typical network service entrance switchgear configuration for 100A or 200A Service Panels DISCONNECT HEAVY DUTY w/ REJECTION TYPE CURRENT LIMITING FUSES MANUAL BY-PASS METER SOCKET SERVICE PANEL w/ MAIN BREAKER Figure 3 Typical Switchgear Configuration, With Main Disconnect The figure below shows a typical network service entrance switchgear configuration for 400A to 2400A systems. All equipment must be fully rated or series rated. 125/216V TACOMA POWER NETWORK CABLE TERMINATING FACILITIES BUS CURRENT LIMITING FUSES CABLE LIMITERS MAIN DISCONNECT METERING CT'S Combinations Per Customer Requirements CURRENT LIMITING FUSES FIRE PUMP 2Ø & NEUTRAL MULTI-MTR PACK 3Ø SINGLE MTR, SELF CONTAINED 3Ø SINGLE MTR WITH CT'S Metering Options Transmission & Distribution Standards Page 5 of 8

Service Entrance Disconnect/Switchgear (continued) Disconnect (100A to 200A Panels) Switchgear (400A to 2400A Panels) The main disconnect for 100A or 200A panels shall meet the following requirements for 2 phases and neutral or 3 phase/4-wire Y self-contained services: Area Type Disconnects or Current Limiting Fuses Breaker(s) Requirements UL or other accredited testing laboratory as required by the NEC listed Heavy Duty Safety Switch with provisions for current limiting fuses, combination or a rated breaker. Current limiting fuses must be rated for expected RMS asymmetrical fault current. Note: use only rejection-type fuse holders Series rated breaker per the NEC. The main switchgear for 400A to 2400A panels shall meet the following requirements for 3 phase/4-wire Y CT services Area Submittal of Electrical Drawings Bracing Rating Standards Meter & CT Enclosures Main Panel Protection Cable Terminals Breaker(s) Secondary Lashing Requirements The manufacturer s shop drawings of switchgear and electrical service equipment must be submitted for approval to the Tacoma Power Electrical Inspection Department during the Plan Review stage of the project. 200,000 AIC rated The switch shall meet the NEC for high fault duty applications. Manufacturer to supply service equipment elevation showing EUSERC drawings for utility meter section(s) Current limiting fuses rated for 200,000 RMS A.I.C. with disconnects or bolted-pressure contact switch The phase and neutral cables shall terminate on a bus bar that are capable of accepting NEMA Style 2-hole terminals. The 2-hole terminal locations shall be spaced 2 inches apart. Series rated breakers can be used on the load side of the current limiting fuses per the NEC. Service entrance cables must be lashed per the panel manufacturer s recommendations. Cable Pulling and Terminating Sections Adequate space for pulling and terminating cable shall meet EUSERC standards at the switchgear. The space shall be full front accessible with removable cover(s) that are sealable and have two lifting handles on each cover. A removable cover cannot be greater than 9 square feet in area. Transmission & Distribution Standards Page 6 of 8

Service Entrance Conduit The following describes the requirements for customer furnished and installed conduits that extend from the customer s service panel into Tacoma Power s secondary network vault. Number & Type of Conduits Conduit requirements are indicated in the table below: Main Service Panel Size (Amp) Number of Conduits Type Size (inch) 100 1 Steel or Sch 80 PVC 2-1/2 200 1 Steel or Sch 80 PVC 3 400 2 Steel 4 600 2 Steel 4 800 3 Steel 4 1000 4 Steel 4 1200 4 Steel 4 1600 6 Steel 4 2000 7 Steel 4 2400 9 Steel 4 Extension of Conduit The customer shall extend the service conduit(s) into the Tacoma Power vault as described below. The following must be approved by Tacoma Power prior to construction route depth joints vault entry point of the conduit. Customer Core Drilling of Tacoma Power Vaults Core drilling into Tacoma Power s vault will be performed by the customer in accordance with the following: in the presence of a Tacoma Power representative drilling points as approved by Tacoma Power Engineer drill holes large enough for conduit nipples the customer shall permanently seal and grout around the conduit Number Of Bends The conduit run shall not have more than 270 o of total bends, for example, three 90 o elbows. Conduit Proofing The completed conduit system shall be proven in the presence of a Tacoma Power Representative. The proving mandrel shall be supplied by Tacoma Power. Pull Line Each conduit shall have 1/8 pull line blown in and tied off at each end. One conduit shall have a pull tape included with printed footage markings. Transmission & Distribution Standards Page 7 of 8

Metering Metering facilities requirements are listed. Location of Metering Facilities All metering facilities are to be installed on the load side of the main disconnect due to the high available fault current from the network system. Installation Responsibilities The following table explains who will install and provide metering items: Items Provided by Installed by Meter socket and CT Customer Customer Enclosure Current Transformers Tacoma Power Tacoma Power Meter test switch Tacoma Power Tacoma Power Revenue Meters Tacoma Power Tacoma Power CT wiring Tacoma Power Tacoma Power Customer Owned Generation Connecting customer owned generation to network distribution systems is limited by Institute of Electrical and Electronics Engineers (IEEE) 1547.6. Tacoma Power s Central Business District Engineering must pre-approve all customer owned generation installations in the downtown area and at area hospitals. Approved customer owned generation installations may require the installation of net metering. Transmission & Distribution Standards Page 8 of 8