TAS Powertek Pvt. Ltd. Technical Note Discharge devices for high speed dynamic switching.

Similar documents
TAS POWERTEK PVT. LTD.

ABB n.v Power Quality in LV installations

Learning Objectives:

EXPERIMENT CALIBRATION OF 1PHASE ENERGY METER

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

Ignition Coil Current Waveforms 2007 Honda Accord SE 4CYL

Application Note CTAN #127

SECTION #1 - The experimental design

Features IN THIS CHAPTER

St.MARTIN S ENGINEERING COLLEGE Dhulapally, Secunderabad

International Journal of Emerging Technology and Innovative Engineering Volume 2, Issue 4, April 2016 (ISSN: )

A Transient Free Novel Control Technique for Reactive Power Compensation using Thyristor Switched Capacitor

Chapter Assessment Use with Chapter 22.

QUESTION BANK SPECIAL ELECTRICAL MACHINES

CTU 02. Thyristor switching module for fast PF compensation. User manual

Exercise 6. Three-Phase AC Power Control EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to three-phase ac power control

COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1001 SPECIAL ELECTRICAL MACHINES

DC CIRCUITS ELECTROMAGNETISM

UNIT 2. INTRODUCTION TO DC GENERATOR (Part 1) OBJECTIVES. General Objective

Eskisehir Light Train- Correcting Capacitive

Electrical Test of STATCOM Valves

Pump ED 101. Power Factor (Part 2) - - Electricity Behaving Better

Electrical Energy and Power Ratings

Common to almost all eco-friendly lighting.

Chapter 19: Direct Current Circuits

CI-TI Contactors - VLT Frequency Converters

INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

Chapter 27. Circuits

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT

Automatic COSYS PFC. Automatic power factor correction system NEW

Current Electricity. GRADE 10 PHYSICAL SCIENCE Robyn Basson CAPS

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF MECHANICAL ENGINEERING ME 6351 ELECTRICAL DRIVES AND CONTROL UNIVERSITY QUESTIONS AND ANSWERS

Ensuring the Safety Of Medical Electronics

Understanding The HA2500's Horiz Driver Test

4707 DEY ROAD LIVERPOOL, NY PHONE: (315) FAX: (315) M.S. KENNEDY CORPORATION MSK Web Site:

Iowa State University Electrical and Computer Engineering. E E 452. Electric Machines and Power Electronic Drives

Modeling and Simulation of A Bldc Motor By Using Matlab/Simulation Tool

INSTITUTE OF AERONAUTICAL ENGINEERING Dundigal, Hyderabad

Battery Back-up BBM Owner's Manual. Please read this manual BEFORE installing your inverter

ELECTRICITY: INDUCTORS QUESTIONS

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

Technical Explanation for Inverters

MYRON ZUCKER CALMANUAL POWER FACTOR CORRECTION APPLICATION GUIDE INC.

VALLIAMMAI ENGINEERING COLLEGE

Working Principle of Power Saver as per Manufacture:

Regulation: R16 Course & Branch: B.Tech EEE

Not for New Design 10 WATT WD DUAL LOW INPUT SERIES DC/DC CONVERTERS. Features

R13 SET - 1. b) Describe different braking methods employed for electrical motors. [8M]

The behavior of the cycloconverter fed gearless drive under abnormal electrical conditions

AF series contactors (9 2650)

Ohm s Law. 1-Introduction: General Physics Laboratory (PHY119) Basic Electrical Concepts:

Electromagnetic Induction, Faraday s Experiment

Supercapacitor Based Power Conditioning System for Power Quality Improvement in Industries

Modelling and Analysis of Thyristor Controlled Series Capacitor using Matlab/Simulink

Power Supplies POWER SUPPLIES TRANSIENT VOLTAGE SUPPRESSORS POWER LINE FILTERS. AC to DC Power Supply Units. AC to 24VDC Regulated Primary Switching

AF series contactors (9 2650)

Solid-State Relays. Solid-State Relays. Features. Description. Overview

smartvar Dynamic VAR Compensator

16.3 Ohm s Law / Energy and Power / Electric Meters

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Power Factor Correction

Technology of Estimating Short Circuit Current and Ground Fault for Direct Current Distribution Systems

2-1. Terms and Characteristics. Description of Terms Cooling Performance of the Automotive IGBT Module

Copyright 2016 Surya Powerfarad Energies Limited. P a g e 1

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road QUESTION BANK (DESCRIPTIVE)

Technical Workshop: Electrical December 3, 2016

STUDENT NUMBER Letter Figures Words SYSTEMS ENGINEERING. Written examination. Friday 12 November 2010

Chapter 19. DC Circuits

DYNAMO & ALTERNATOR - B FIELD LOGIC PROBE.

3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.

Lab 12: Faraday s Effect and LC Circuits

Commander SK. Technical Data Guide. Model sizes A to D and 2 to 6. AC variable speed drive for 3 phase induction motors

Protective firing in LCC HVDC: Purposes and present principles. Settings and behaviour. V. F. LESCALE* P. KARLSSON

SL Series Application Notes. SL Series - Application Notes. General Application Notes. Wire Gage & Distance to Load

HV803, HV8051, and HV8053 EL Lamp Driver Circuits

Product Groups. Standard Features

POWER SUPPLY MODEL XP-800. TWO AC VARIABLE VOLTAGES; 0-120V and 7A, PLUS UP TO 10A. Instruction Manual. Elenco Electronics, Inc.

EXPERIMENTAL VERIFICATION OF INDUCED VOLTAGE SELF- EXCITATION OF A SWITCHED RELUCTANCE GENERATOR

2014 ELECTRICAL TECHNOLOGY

Power Factor Correction

Application Notes. Calculating Mechanical Power Requirements. P rot = T x W

Q2. The diagram shows a network of four 2 Ω resistors. The effective resistance, in Ω, between X and Y is A 0.5 B 1.2 C 1.7. D 2.

A novel synthetic test system for thyristor level in the converter valve of HVDC power transmission

Dynamics of Machines. Prof. Amitabha Ghosh. Department of Mechanical Engineering. Indian Institute of Technology, Kanpur. Module No.

POWER FACTOR CORRECTION OF FAST DYNAMICS INDUSTRIAL LOADS

Power Factor Correction

Volume 2 Charts, Formulas, and Other Useful Information

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

ELECTRICITY KIT - for DC and AC

APPLICATION NOTE. Littelfuse.com. Prepared by: Alex Lara, Gabriel Gonzalez, and Dalila Ramirez Thyristor Applications Engineers

Exercise 7. Thyristor Three-Phase Rectifier/Inverter EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Thyristor three-phase rectifier/inverter

Thyristors Characteristics

Questions Section: Do you have questions that aren't covered? Please contact us!

ICS1702EB. ICS1702 Evaluation Board. Table 1 Cells R6 R8 1 Open Short 2 2.0k 2.0k 3 1.0k 2.0k 4 1.0k 3.0k 5 3.0k 12k 6 2.0k 10k 7 2.0k 12k 8 1.3k 9.

Electrical Measuring Instruments

CHAPTER 19 DC Circuits Units

Question Bank ( ODD)

Fast thyristors. When burning for induction heating solutions.

Performance means how fast will it go? How fast will it climb? How quickly it will take-off and land? How far it will go?

Basics of DC drives...

Transcription:

Technical Note Discharge devices for high speed dynamic switching. Standard Discharge Resistors: Normally the capacitor manufacturer as a part of their normal supply provides discharge resistors across the capacitor banks. This is mainly to cater for the human safety requirements, which are mandatory, part as per IEC, IS or any other internationally known standards for the Power Factor improvement capacitors. Normally, the resistors put are of a very high value and the value is adjusted such that peak voltage across the capacitors should be less than 48Volts (depends on standards) in less than a minute of disconnecting the capacitors from mains. Discharge Resistors The diagram shown above depicts the typical positioning of the standard discharge resistors. What is the situation with high-speed dynamic response: We need to analyse the situation with two different thyristor switching configurations because the different configurations put different selection criteria for the discharge device selection. Viz.: 1. Two thyristor configuration in Line: (or same as three thyristors in Line) 2. Thyristor blocks within the delta arms of capacitors. The situations can be understood from some initial explanation as given below. Conditions for switch OFF with 2 thyristor in line configuration: Consider the following diagram. This shows the various Line Voltage Waveforms and the Current waveforms passing through the thyristor switches. Ir Vr-y Iy -ry Vy-b Vb-r -yb C -br Ib

The diagram shown above is for the waveform Situation 1 where both the R-ph and Y-ph thyristor switches are conducting. Ir -ry Vpk = Peak of Line voltage. Iy -yb Ib -br Thy Capacitor switch off waveform 1000 Situation 1 Situation 2 Situation 3 800 Voltage 600 400 200 0-200 1 6 11 Vpk 16 21 26 31 36 41 46 51 56 1.367 X Vpk 2.367 X Vpk -400-600 -800 Off Command time Y-ph switch Turns off. R-ph switch Turns off. Now view what happens in Situation 1. The turn Off command from the PF controlling relay is given at any random instance. This will immediately turn off the gate driving to the thyristors. But thyristors being current sensitive elements, does not turn Off immediately. Thyristors can only turn off by its natural commutation at zero instant of current waveform. In the thyristor switches (thyristors in 2 phase only) we have assumed that B-phase is the direct phase and current through it can only be off if both the thyristors in other two phases is Off. In the above waveform situation, the first zero current is experienced by Y-phase thyristor block. Under this condition, the Y phase thyristor is switched Off and the effective diagram that can be seen (going from Situation 1 to Situation 2) is as given below.

Ir Vr-y -ry + - Vy-b Vb-r -yb + C - -br Ib Under this situation, at the instant of Y phase thyristor turn-off, we can see following points. -ry = -yb = Vpk 3 / 2 and with the polarity as shown in the diagram. -br = 0. Capacitor across R-Y phase and capacitor across Y-B phase are seen in series. Now in situation 2, only R phase thyristor is conducting, Thus, Ir current would be only due to effect of Vb-r and load being only capacitive, this current would be 90 leading the Vb-r waveform. Thus, waveform current Ir and Ib (phase opposition to Ir) are getting phase shifted accordingly. This can be seen from the waveform. Along the situation 2, -br increases from 0 to Vpk (sine wave path). This also is the voltage across the series capacitor across R-Y and Y-B phase. As these capacitors are of equal value, this incremental voltage would be divided equally between these two capacitors. Thus, effective voltage across each capacitor would be (-br/2) + (Vpk 3/2) with effective signs. Thus in the given situation, capacitor across R-Y being charged negative, it will discharge and capacitor across Y-B being charged positive, will charge more. When -br is at its peak, the current Ir through R phase thyristor comes to its zero crossing instant. Under this condition it turns off. At this instant Voltage across capacitors would be -ry = (Vpk/2) (Vpk 3/2) = -0.367 Vpk. -yb = (Vpk/2) (Vpk 3/2) = 1.367 Vpk. -br = Vpk. Same values in terms of Line voltage values can be seen as (where VLINE = Vpk/ 2) -ry = -0.519 VLINE. -yb = 1.933 VLINE. -br = 1.414 VLINE. The diagram after the change-over from Situation 2 to Situation 3 can be seen as below.

Vr-y -ry w Vy-b Vb-r -yb C -br Now w shown in this diagram is the voltage that can come across the off state thyristor switch. And from the waveform it can be seen that maximum voltage that can be seen by the blocked thyristor switch is with Y phase thyristor. From waveform it can be seen that maximum blocking voltage for this thyristor required would be: w = 1.367 Vpk + Vpk = 2.367 Vpk In terms of line voltage values, it is w = 3.348 VLINE. Conditions for switch OFF for three thyristors in Delta arm configuration: The delta arm configuration diagram is as shown below. Vr-y Vy-b Vb-r In this condition, the thyristors are seen within the delta arms. The capacitors to be used here are single cell capacitors. But under this condition, individual capacitor cell is controlled by the thyristor. Under this condition, the thyristor turn OFF is at current zero so the 90 phase shift of voltage with respect to current keeps the capacitors charged to maximum Vpk DC value and the maximum blocking voltage experienced by the thyristor switches would be 2 Vpk.

Lets even consider the conditions with addition of detuned reactor in the circuit: If the detuned reactors are added, the voltage across the capacitor proportionately increases equivalent to the reactor voltage drops. To understand this phenomenon, consider the following situation where to understand the subject better, we have consider the single phase supply condition. IC VL w C Here is the voltage applied. is the voltage across the capacitor with capacitance value as C in Farads. IC is the current flowing through the capacitor. w is the voltage across thyristor switch. VL is the voltage across series reactors. The phasor representation after neglecting w shows the value more than. Ic VL Situation: Following waveform shows the exact voltage and current situations at the instant of turn off. Note some technical considerations before analyzing the waveform Thyristors turn off only at current zero. As capacitor current leads voltage across it by 90, at current zero, voltage across the capacitor is at its peak value. The voltage across the capacitor is higher than the mains voltage due to series reactors. Voltage across the series reactors (vector summation) added to mains voltage gives the capacitor voltage. When capacitors are removed from the mains circuit, the mains supply voltage tends to dip by small amount due to the source impedances.

command Ic Actual instance w w From the diagram shown here, it can be seen that voltage across the thyristor switch never touches zero voltage level. The discharge resistors across the capacitors that are provided by the capacitor manufacturer are of high value and thus for few tens of mains cycles (typically for 2 to 4 sec), the voltage across the thyristor switch is never touching zero mark. For 415Vac line voltage (VLINE) system with and with 7% line reactors (detuned), the typical value of minimum w value observed with the turned off thyristor with maximum charged capacitor is: 1. For 2 thyristor in line configuration = 232Volts DC (can be derived from earlier explanation given for voltages) 2. For 3 thyristors in Delta arms configuration = 45Volts DC. Following chart shows minimum and maximum w values as well as maximum DC voltage across capacitor: (Values given in terms of Line to Line voltage values) Sr. Configuration w-min w-max -Max dc 1 Thyristors in 2 phases in line without Detuned reactors. 0.52 VLINE 3.35 VLINE 1.93 VLINE 2 Thyristors in 2 phases in line with Detuned reactors 7.56% 0.56 VLINE 3.58 VLINE 2.07 VLINE 3 Thyristors in 3phase inside Delta arms without reactors. 0 2.83 VLINE 1.41 VLINE 4 Thyristors in 3 phase inside Delta arms with reactors 7.56% 0.11 VLINE 2.94 VLINE 1.52 VLINE

Minimum values are useful for calculating response time as can be seen from following discussions. The maximum values are useful for calculation of worse case blocking voltages that can appear across the OFF thyristor block. Turn On Situation: Here is the typical turn-on situation waveform. Note the following technical point before analyzing the waveform: Capacitor switch-on by thyristor switches is when the differential voltage (w) across the thyristor switches is very near zero. With TAS make ZCCP or ZCTC thyristor switches; this value is typically +3Volt dc. Control Command Ic VSW VC VSW = 0. From the diagram above, it is seen that thyristor switches waits after the control command, till it observes the value of w = zero. The moment it observes the value to be zero after that, it turns on the thyristor at that instant. Practically, this instant is within the tolerance of 2 to 3µSec. But if after the control command, if w is never found near zero, the thyristor switch will never turn On the thyristors. This type of situation can be seen when the thyristor switches are turned Off and On very fast. Lets analyse this situation of Thyristor turn off and then immediately turn on. and immediate Turn On situation: This is a situation arising for the highly fluctuating loading conditions. For this the dynamic response of the system required is very fast. Lets see the situation with Switch Off and Switch On within 2 mains cycles. The value of the w will vary depending on the configuration and usage of detuned reactors. This can be arrived at from the above given chart.

command Ic Turn On command Actual instance Diagram with 2 thyristors in line configuration and with detuned reactors. Actual Turn On instance with low discharge with high discharge device command Ic Turn On command Actual instance Actual Turn On instance with low discharge Diagram with 3 thyristors in Delta arm and usage of detuned reactors. with high discharge device

This diagram shows that if the capacitor is not discharged sufficiently so as to get w to be zero, then even after the turn On command, the thyristor unit would not be switching On the capacitor banks within one mains cycle. The diagram also explains the situation if a higher discharge devices are put across the capacitors. Under this case w = 0 is achieved and switch turn-on is immediately within one cycle. It can also be observed that the discharge devices that are required to be put with 2 thyristor in line configuration should be for much faster discharge. This is because of the capacitor voltage rise above the mains peak value almost by 35%. What Kind of Discharge Device is required: The discharge devices are selected depending on the following criteria. Fastest dynamic response time required out of the system. Permissible watt-loss in discharge devices. Cost of discharge devices. Discharge resistors: The discharge resistors if used are put as shown in the diagram below. Discharge Resistors The value of the discharge resistors would depend on fastest dynamic On Off On time requirement. If C is the capacitor value in Farad, R is the resistor value in Ohm. Vp is the peak voltage (DC) across capacitor. V is the voltage reduction required in a minimum Off to On response time. τ is the minimum Off to On time expected from system. Then value of R in ohms (Ω) can be determined by formula: R = τ / [C {ln (Vp/ V)}]. ln is Log of the term to base e. Pros and Cons: Discharge device prices are low. Can get good dynamic response. Capacitor On state watt loss is quite high and faster the dynamic response required, more is the watt loss expected.

TAS has a product called as DISR-nn that gives these discharge resistor modules for thyristorised capacitor switching application. As V value with 3 thyristors in delta arm configuration is low, automatically the value of R becomes higher and thus the watt loss in it reduces. Therefore for a very fast response time requirements with the thyristorised system, it is recommended to go with this type of thyristor configuration rather than 2 thyristor in line configuration. Discharge Inductor + Resistor: The diagram shows that the connections of discharge resistors and the inductors that are put across the Delta connected capacitors. Here the value of inductor is selected such that it offers a very high impedance path for supply frequency f but has a very low value of resistance. Resistance R is normally calculated as defined earlier. Pros and Cons: Discharge device prices are much higher. Can get good dynamic response time. On state watt losses are minimized. TAS has DISI-nn which is Discharge inductor + resistor combination for the said requirement. END.