Metrohm E3640 FLASH TESTER INSTRUCTION MANUAL. Martindale Electric Co Ltd.

Similar documents
MARTINDALE MARTINDALE IN2001/IN2003 INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL IN2001/IN2003 INSULATION & CONTINUITY TESTERS

IN1001/IN1003 ANALOGUE INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL IN1001/IN1003 ANALOGUE INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL

MARTINDALE INSTRUCTIONS ELITE FUSE FINDER KIT ELECTRIC. Trusted by professionals. 4.4 Storage Conditions

Instruction Manual PC104/PC105 3-PHASE SOCKET TESTER. Check out what else you can get from Martindale:

I I e k ill L ill. INDUSTRIAL DIGITAL EARTH LEAKAGE CIRCUIT BREAKER and 3 PHASE ROTATION TESTER BESANTEK BST-ELC01 INSTRUCTION MANUAL

INSTRUCTION MANUAL CM95/ CM100 TRUE RMS FLEXIBLE CLAMP METER. 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT

Instruction Manual VT4 VOLTAGE TESTER. Check out what else you can get from Martindale:

INSTRUCTION MANUAL CM69 TRMS AC EARTH LEAKAGE CLAMP METER. 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT

INSTRUCTION MANUAL MARTINDALE CM52 CLAMP METER. ELECTRIC Trusted by professionals. Other products from Martindale:

Digital Low Resistance Ohm Meter

Chek-A-Cell TM. Instruction Manual Rev A 8/12

HIGH VOLTAGE PROXIMITY DETECTOR

KV4-300 mk2. KV5-200 mk2. KV5-100T mk2. KV3-250 mk2

Instruction Manual VT25 / VT28 VOLTAGE TESTER ALWAYS READ THESE INSTRUCTIONS BEFORE PROCEEDING

Instruction Manual. Model 310 Digital Milli-Ohm Meter

OPERATING INSTRUCTION

Instruction Manual. Model 307A Analog Insulation & Continuity Meter

INSTRUCTION MANUAL DT173 DT175 DIGITAL THERMOMETERS ALWAYS READ THESE INSTRUCTIONS BEFORE PROCEEDING

KEWTECH. KT56 digital multi function tester. Instruction manual

1.Safe testing IMPORTANT:

HIGH VOLTAGE PROVING UNIT

ANALOGUE INSULATION-CONTINUITY and VOLTAGE METER

BM kv Digital Insulation Tester USER MANUAL

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions.

BATTERY OPERATED DIGITAL MILLI-OHMMETER

Go to to register your product and find more information.

INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN

Instruction Manual. 99 Washington Street Melrose, MA Fax TestEquipmentDepot.com. Model 308A Digital Insulation & Continuity Meter

MIT300 Series Insulation and Continuity Testers

OPERATING INSTRUCTION

VTC610 Series Voltage Converter. Installation & Operation Manual

INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC.

VTC1000 Series Voltage Converter. Installation & Operation Manual

INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER

Roller Door Operator

The insulation tester must only be used by a skilled and competent measuring equipment connected directly to utilization points

3 PHASE TESTER & MOTOR ROTATION TESTER

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL

This manual covers the following model:

TRIPLETT. Model 310 Type C Type 9

MODUL-CONNECT 1.2. Owner s Manual. Modular, digital wiring and control system. Document Part Number MSMC Rev 9 (04/18)

PL900 ILLUMINATOR. Fiber-Lite. Operation Manual. Setup. Fiber Optic Connection A PRODUCT OF DOLAN-JENNER INDUSTRIES. Voltage Selection:

MAX. AC 600V HOLD V M H.V. LIVE CIRCUIT DIGITAL INSULATION TESTER DO NOT OPERATE IF LIT POWER DATA HOLD TEST ON / OFF 250V 500V 1000V OFF CAT.

Dielectric Withstand Tester

1662/1663/1664 FC. Electrical Installation Tester. Safety Information. Warnings

Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.com INSTRUCTION MANUAL PSMR1

24V 3A EN54 Ancillary Power Supply

Mini Multimeter with Non-Contact Voltage Detector (NCV)

KD1E Range Potential Indicators

EZYPAT / EZYPAT+ / SMARTPAT PORTABLE APPLIANCE TESTER INSTRUCTION MANUAL

Microscope light manual

The function of this Dynamic Active Probe has divided into three preferences on the screen main Menus:

AC POWER SOURCE PURE SINE WAVE DC-AC INVERTERS OWNER S MANUAL

DC-AC Power Inverter SAM Manual. Please read this manual before installing your inverter

i400s Calibration Information Introduction

Distributor. Kewtech Corporation Limited 76 St. Catherine s Grove Lincoln LN5 8NA KEWTECH

323/324/325 Clamp Meter

Woolich Racing. Bike Harness Installation Instructions Suzuki Harness Type 4a GSX1300R (Hayabusa)

FHC-1D user manual. Features

Installation & Operation Manual PWS1000R Rack Mount Power Supply

USER MANUAL. Revision 1.0.1

HT Dielectric Withstand Tester Volts AC Output 25mA Leakage Option

OWNER S OPERATING MANUAL

Table of Contents Title Page No.

OPERATING MANUAL PHASE SEQUENCE AND MOTOR ROTATION DIRECTION TESTER TKF-13

Electrical test equipment for use on low voltage electrical systems

BellMega BM-510. Operation Manual Ver: 1.0 Rev: 1

Owner's Manual. 120 Watt DC-AC Inverter Pure Sine Wave PST-12S-12A. Please read this manual before using your inverter

1587 FC/1587/1577. Insulation Multimeter. Safety Information. Warnings

Operator s Safety and Service Manual

OPERATING INSTRUCTION

MANUAL PCE-IT111

DIGITAL RCD(ELCB) TESTER

INSTRUCTION MANUAL PET Fax: (503)

Users Manual. Phase Rotation Indicator

MOdel No: MM19.V3 WARNING CAUTION 1. SAFETY INSTRUCTIONS

IN & TM Series User Manual

PHASERS. Operating and Instruction Manual. a n d A C C E S S O R I E S

MODEL A96 SERIES. 130Vdc Switchmode Utility Rectifier / Battery Charger. Used with LaMarche Power Cage ECN/DATE

RS-3 PRO RS-1007 PRO. CAT IV Analog Clamp meter Series. Users Manual. For detailed specifications and ordering info go to

Woolich Racing. Bike Harness Installation Instructions Hayabusa Gen 2 (08+)

AC / 65 W M PLEASE READ BEFORE OPERATING THIS EQUIPMENT.

Model AS-RC3260 TV Cart. Rolling Cart for Audio Mount System & Flat Panel TVs

1 AMP CURRENT SOURCE

Autoranging Multimeter

KD LV Motor Protection Relay

PD-20 HIGH VOLTAGE PROBE INSTRUCTION MANUAL

VP-4124/VP-4124-E 24/48 VOLT DC SWITCHING POWER SUPPLY

ODY-19-1 AIR PRESSURE GAUGE

BROMAN MODEL 210 CONTACT RESISTANCE TEST SET SERIES 5

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls

OPERATING INSTRUCTIONS

362 Clamp Meter. Users Manual

User Guide. Model Insulation Tester / Megohmmeter. Introduction

Series 2100 Operating Instructions

INSTRUCTION MANUAL DM5B Fax: (503)

Generator Start Control Module

HT-25kVdc Dielectric Withstand Tester Volts DC Output

302+/303 Clamp Meter. Users Manual

The Da-Lite Difference.

Transcription:

Metrohm Martindale Electric Metrohm House, Imperial Park, Imperial Way, Watford, Hertfordshire, WD24 4PP, UK T: 01923 441717 F: 01923 446900 Email: sales@martindale-electric.co.uk web: www.martindale-electric.co.uk E3640 FLASH TESTER LITE3640 ISSUE 7 07/07 INSTRUCTION MANUAL Martindale Electric Co Ltd.

Martindale Electric Co Ltd reserves the right to discontinue models at any time, or to change specifications, price or design, without notice and without incurring any obligation.

LIMITED WARRANTY Martindale Electric Co Ltd warrants instruments and test equipment manufactured by them to be free from defective material or factory workmanship and agree to repair or replace such products which, under normal use and service, reveal the defect to be the fault of our manufacturing, with no charge for parts and service. If we are unable to repair or replace the product, we will make a refund of the purchase price. Consult the Instruction Manual for instructions regarding the proper use and servicing of instruments and test equipment. Our obligation under this warranty is limited to repairing, replacing or making refund on any instrument or test equipment which proves to be defective within 24 Months from the date of original purchase. Proof of purchase may be required.this warranty does not apply to any of our products which have been repaired or altered by unauthorised persons in any way so as, in our sole judgement, to degrade their stability or reliability, or which have been subject to misuse, abuse, misapplication, negligence or accident,or which have had the serial numbers altered, defaced or removed. Accessories, not of our manufacture, used with this product are not covered by this warranty. To register a claim under the provisions of this warranty, return the instrument or test equipment to Martindale Electric Co Ltd., Metrohm House, Penfold Trading Estate, Imperial Way, Watford WD24 4YY, UK. Upon our inspection of the product, we will advise you of the outcome of your claim. ALL WARRANTIES IMPLIED BY LAW ARE HEREBY LIMITED TO A PERIOD OF 24 MONTHS, AND THE PROVISIONS OF THE WARRANTY ARE EXPRESSLY IN LIEU OF ANY OTHER WARRANTIES EXPRESSED OR IMPLIED. The purchaser agrees to assume all liability for any damages and bodily injury which may result from the use or misuse of the product by the purchaser, his employees, or others, and the remedies provided for in this warranty are expressly in lieu of any other liability that Martindale Electric Co Ltd may have, including incidental or consequential damages. TABLE OF CONTENTS 1. SAFETY RULES 2. DESCRIPTION 2.1 GENERAL 2.2 CONTROLS 3. INSTRUCTIONS FOR USE 3.1 PRELIMINARY CHECKS 3.2 PERFORMING A TEST 4. APPLICATIONS 4.1 PRELIMINARY CHECKS 5. TECHNICAL SPECIFICATION 5.1 ELECTRICAL 5.2 MECHANICAL 5.3 ENVIRONMENTAL 6. SPARES AND ACCESSORIES 7. LIMITED WARRANTY PAGE 1 2-3 3-5 5-6 7 8 8-9 9-10 10 10 11

1 SAFETY RULES The E3640 has been designed with safety in mind. However, no design can completely protect against incorrect use. Electrical circuits can be dangerous and even lethal through lack of caution or poor safety practices. 1.1 Read the Instruction Manual carefully and completely so that you fully understand the instructions before using the tester Follow the instructions in the Manual for every test. Take all the recommended precautions. Never exceed the limits of the tester. 1.2 The device under test (DUT) must be de-energised and isolated before connections are made for any tests. 1.3 Check that the Power selector on the tester is set correctly. 1.4 Always set the voltage control to RESET or set the power switch to OFF before connecting/disconnecting the earth test lead and the HV gun probe to/from the DUT. 1.5 The earth test lead and the HV gun probe must be clean and in good working order with no broken or cracked insulation. 1.6 The HV gun probe must always be held correctly, with fingers behind the guard. Never try to defeat the safety trigger mechanism. 1.7 Do not touch the DUT during testing with any part of the body. 1.8 Always use the recommended replacement fuses. 1.9 Do not use the tester in wet conditions. Bump Test IEC 68-2-29 Vibration Test: BS EN 61010 - clause 8.3 Impact Test: BS EN 61010 - clause 8.2 Drop Test: BS EN 61010 - clause 8.4 5.3 ENVIRONMENTAL Operating Temperature: -15ºC to +55ºC Storage Temperature: -25ºC to +65ºC Operating Humidity: 80% RH at 40ºC Cold Temperature: IEC 68-2-1 Dry Heat: IEC 68-2-2 Damp Heat: IEC 68-2-3 Installation Category II: BS EN 61010 - Annex J Pollution Degree 2: BS EN 61010 - clause 3.7.3.2 6. SPARES AND ACCESSORIES Mains Power Supply Lead: MARTL205 Earth Lead: METDFH 0366 HV Gun Probe: METDFH 0369 2.0 Please ensure the test lead is pushed fully into the test socket and locked in position prior to carrying out any tests. NOTE: This tester should only be used by a competent, suitably trained person. -2- -11-

Trip Level Range: Setting Accuracy: Trip Response Leakage: Breakdown: 0.3 to 3mA 50/60Hz ±5% of full Will trip for fault duration >5mS but not for <100μS Will trip for fast transients of 30μS and above Safety: LVD:Meets BS EN 61010-1 EMC:Meets BS EN 50081-1 BS EN 50082-2 Output Terminal Characteristics: E3640 OUTPUT CHARACTERISTICS 2 DESCRIPTION 2.1 GENERAL The E3640 is an AC flash tester for leakage and breakdown testing. It is designed for voltage testing of electrical apparatus, components and insulating materials. The tester is housed in a rugged, moulded plastic case with integral carrying handle. The hinged detachable lid is fitted with a pouch which contains all accessories and the instruction manual. All operating functions are mounted on a panel underneath the protective lid. A two position power selector adjusts the tester to operate from 115 or 230V ±15% 50/60Hz. The tester has an output AC test voltage which may be set in the range 0 to 4kV by adjusting the voltage control. The mode select switch allows the selection of either breakdown, trip or burn. Leakage current passing through the DUT is detected. In the breakdown mode the high frequency current will cause the tester to trip. In the trip mode the tester will trip if the current exceeds the trip level setting (0 to 3mA) of the trip level control or if breakdown occurs. However, when the burn mode is selected the trip does not occur and the output voltage is maintained but it reduces as current increases. 5.2 MECHANICAL Case Dimensions: Case Material: Weight: 330 x 263 x 144mm ABS 4kg When the tester trips the fail lamp will illuminate, a buzzer will sound and the kvon lamp will extinguish. The output voltage will drop to zero but the output voltage and the leakage current at the instant of trip will be held on their respective displays. To reset the tester the voltage control is rotated anti-clockwise to the reset position. If the tester is switched on when the voltage control is not in the reset position the HV output is inhibited and the kv ON lamp will not illuminate. Turning the voltage control to reset will activate the HV circuits. Maximum output voltages of 2.2kV and 4.2kV are set such that if these -10- -3-

limits are exceeded the output will shut down until the voltage control is turned to reset. Illuminated displays show that the tester is switched on and the kv ON lamp indicates that high voltage may be present at the outlet. The HV gun probe has been designed with operator safety as the prime consideration. The trigger for the retractable high voltage probe sleeve is situated behind the finger guard and the integral lead is terminated in a custom designed high voltage safety connector. 2.2 CONTROLS (Fig. 1 Refers) 2.2.1 VOLTAGE This control adjusts the output of the electronic AC regulator between reset and maximum, 2kV or 4kV which ever is selected. The reset position is used to re-energise the high voltage output circuit after 4.APPLICATIONS 4. 1 PRELIMINARY CHECKS The E3640 flash tester is ideal for flash and applied AC voltage testing of all kinds of electrical and electronic equipment and components. Requirements for testing are contained in many British and International standards and in the sixteenth edition of the IEE Wiring regulations (BS7671). Testing is mainly carried out on factory assemblies, but if an on-site repair is carried out or a factory assembled item is fitted on site then the same tests are carried out. Please ensure the test lead is pushed fully into the test socket and locked in position prior to carrying out any tests. 5.TECHNICAL SPECIFICATION 5.1 ELECTRICAL exceeding the maximum level or after power switch on. Reset is also used to reset the trip circuit after a failure of the DUT. 2.2.2 VOLTAGE SELECT A two way switch allows 0-2kV or 0-4kV to be selected. Power Requirement: Fuses: Output Voltage Range: Output Voltage Accuracy: Leakage Current Range: Leakage Current Accuracy: 230 Volts ±15% 50/60Hz 40VA selectable 115 Volts ±15% 50/60Hz 40VA selectable 230V - 5x20mm 0.25A, HBC, Type F 115V - 5x20mm 0.5A, HBC, Type F 0.2-2.2, 0.2-4.2kV 50/60Hz ± 2% of reading ± 1 digit 0-5 ma (nominal) 50/60Hz in 10μA steps ±2% of reading ± 1 digit -4- -9-

To clear the displays the output voltage control is returned to reset. NOTE: a) In the burn mode the trip circuit is inoperable and the tester will continue to drive current into a fault. The fault current is limited to a nominal 5mA and the output voltage will decrease with increase in current. b) In the breakdown mode if excessive current is drawn by the DUT the desired output voltage may not be achieved. The specification for the DUT would then have to be checked to decide on the validity of the test. The leakage current is not displayed in this mode. c) It is advisable to return the output voltage control to reset before switching off the tester. d) During applied voltage tests the current which flows into and across the surface of the DUT is the leakage current and is the resultant of two components:-resistive and reactive. Resistive current is that which flows as a result of losses in the insulation of the DUT. Reactive current is that which flows as a result of capacitance in the DUT and will increase with increase in capacitance. It must be taken into account when carrying out an applied AC voltage test. e) If the voltage select switch is operated when the voltage control is not at the Reset position, the HV circuit will de-energise and it will be necessary to return the voltage control to Reset to reactivate the HV circuit. 2.2.3 MODE SELECT Three modes of operation are selectable. Breakdown:- Trip:- Burn:- The tester will trip should breakdown occur in the DUT (high frequency leakage currents). This position switches in a level detector whose input is variable over the range 0 to 3mA. The tester will trip if the leakage current in the DUT exceeds the level that is set. The tester will also trip for breakdown. The tester will not trip in this mode regardless of breakdown or leakage currents but the burn' current is limited to a nominal 5mA. 2.2.4 TRIP LEVEL This control sets the level on the trip detector that must be exceeded before a failure of the DUT is indicated. 2.2.5 POWER INLET This multi-function item combines an IEC inlet with a double pole switch, fuse drawer and 115/230 volt mains power selector. 2.2.6 INDICATORS kv ON:- A red lamp which indicates that the high voltage output circuit is energised. Fail:- A red lamp which indicates that the DUT has failed and the trip has triggered. A buzzer sounds in unison with the fail lamp to give an audible indication that the DUT has failed. 2.2.7 DISPLAYS Output Voltage kv:- The voltage applied to the DUT is displayed and the value at failure is held until the tester is reset. Leakage Current ma:- Leakage current through the DUT is displayed and the value at failure is held until the tester is reset. -8- -5-

2.2.8 HIGH VOLTAGE SOCKET This unique safety socket has an interlock which prevents accidental disconnection of the HV gun probe lead. 3. INSTRUCTIONS FOR USE 3.1 PRELIMINARY PROCEDURE NOTE: OBSERVE ALL SAFETY RULES AT ALL TIMES. Trip:- Burn:- In the trip mode, mains frequency currents associated with leakage and short circuits and high frequency arcing currents that are produced by breakdown are detected. Set the trip level to the required current by adjusting the control potentiometer. In this mode the tester will not trip regardless of any failure mode in the DUT. Current will continue to flow allowing faults to be traced by observing the resulting arcing. 3.1.1 The tester can be powered from 115 or 230V +15% 50/60Hz. Ensure that the power source available is compatible with the voltage setting on the tester. To change the setting, remove the fuse drawer using a small screwdriver and pull out the fuse holder. Fit a 5 x 20mm 0.25A type HBC fuse for 230 volt operation or a 0.5A of the same type for 115 volt operation. Insert the fuse holder so that the desired voltage shows in the drawer window, then replace the drawer. NOTE: If the voltage selector is not set correctly then the tester may be damaged. Connect the mains lead to the power inlet and plug it into a suitable power outlet. If the neon to the right of the inlet socket lights, reverse the plug in the socket 3.1.2 Select the mode of operation; either breakdown, trip or burn. Breakdown:- When this mode is selected the trip circuit responds to high frequency currents produced by arcing faults only. Note: If there is a short on the DUT there will be no indication on the displays and the trip mode should be selected. 3.2 PERFORMING A TEST 3.2.1 Attach the spade connector of the earth lead to the earth terminal ( ) on the tester and the crocodile clip to the earth (reference) point of the DUT. 3.2.2 Insert the HV gun probe into the HV socket and select 2kV or 4kV output voltage as required. 3.2.3 Set the voltage control fully anti-clockwise to reset and switch on the tester. The kv ON lamp will illuminate indicating that the high voltage circuit is energised. 3.2.4 Touch the HV gun probe onto the test point of the DUT and slowly rotate the voltage control clockwise until the value indicated on the display reaches the recommended test voltage for the DUT. 3.2.5 Maintain this voltage for the desired length of time. If, during this test period, the voltage is steady and the failure indicators do not energise (fail lamp and buzzer) then the DUT has passed its test. The recommended test time is 1 minute according to BSEN 61010. 3.2.6 A failure of the DUT will result in the fail lamp illuminating and the buzzer sounding. The kv ON lamp will extinguish but the voltage and leakage current at the instant of failure will by held on the displays. Measurements can then be recorded accurately for each item tested. -6- -7- NOTE: Leakage currents are not displayed when the break down mode is selected.