Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

Similar documents
Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

Compact Circuit Protector (CCP) Application Note

Now - Up To 400A Mains!

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

Selecting Protective Devices

The easiest and fastest way to select and specify the right fuse

Devices for Branch Circuits and Feeders

Electrical Safety and Reliability: Short-Circuit Current Rating (SCCR) Equipment SCCR made easy

Suggestion on How to Use

A case study in solving SCCR issues

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

Downtime Reduction, Workplace Safety & Code Compliance SERVICES TO INCREASE YOUR PRODUCTIVITY THROUGH PROTECTION

Quik-Spec Coordination Panelboard

Photovoltaic System Overcurrent Protection

KT7. Methods. of Applying. & Molded Case Circuit Breakers F119. Motor Circuit Controllers

Selective Coordination Requirements

Photovoltaic System Overcurrent Protection

Selective Coordination

Equipment Protection. Transformers 600V or Less

Application note Compact Circuit Protector (CCP2) Smaller, better... the Power of Space

Equipment Protection. Transformers 600V or Less

Overcurrent protection fundamentals

Selective Coordination Enforcement:

Specification made simple for selective coordination in a compact size

Applying Interrupting Rating: Circuit Breakers

Applying Interrupting Rating: Circuit Breakers

Quik-Spec Coordination Panelboard

Overcurrent Protection According to the 2011 NEC

MAGNETIC MOTOR STARTERS

FUSES VERSUS CIRCUIT BREAKERS FOR LOW VOLTAGE APPLICATIONS

HVAC and Refrigeration Circuit Protection Solutions. Compact and safe HVAC/R circuit protection

What's New with UL508A Codes & Standards Presented by Jeff Woolfolk Manufacturing in America March 14-15, 2018

Bussmann series Quik-Spec Coordination Panelboard

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.

Electrical Safety and Overcurrent Protection

Equipment Protection. Listed or Labeled Equipment. Panelboards. Branch Circuit Protection HVAC. Appliances. Supplementary Protection

BRANCH CIRCUIT PROTECTION FUSED COORDINATION PANELBOARD

3.2. Current Limiting Fuses. Contents

ECET Distribution System Protection. Overcurrent Protection

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

Fuseology. Dual-Element, Time-Delay Fuse Operation

SIGNAL WORDS QUALIFIED PERSON

Engineering Dependable Protection

www. ElectricalPartManuals. com Engineering Dependable Protection

ACW Molded-Case Circuit Breaker UL 489 Listed

A Bulletin Providing: Important Changes to the 2002 Code Motor Disconnect Location Arc Flash Field Labeling Use of Overcurrent Protective Devices on

Fuseology. Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression. Optima Fuse Holders & Overcurrent Protection Modules.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

Fused Coordination Panelboard

Selecting Protective Devices SPD. Electrical protection handbook. Based on the 2017 NEC

Service Entrance Methods

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

Horizontal Circuit Switchers

Low-Peak 600V Class RK1

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

Fuseology. High Speed Fuses

Secondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor

Quik-Spec Electrical Gear

Recommended Procedures

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

Low Voltage Fuses For Motor Protection

TERMS AND DEFINITIONS

The easiest and fastest way to select and specify the right control circuit fuse

Fuse technology. Application Guide

Panel SCCR 50kA RMS Symmetrical 480V Maximum

Products for enhancing electrical safety and reliability

Selective Coordination

Miniature circuit breaker Application guide

SECTION MOTOR CONTROL


Cooper Bussmann. Guide. Downtime Reduction, Workplace Safety & Code Compliance. Section Contents

Bussmann Services & Application Guide

Motor Protection. Voltage Unbalance & Single-Phasing

IN2 Enclosed Switches and Circuit Breakers

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers

Horizontal Circuit Switchers

ECET Circuit Design Motor Loads. Branch Circuits. Article 210

Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals?

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Harmonization of IEC and North American Safety Standards

Evaluating Selective Coordination Between

FUSE: SAFE & RELIABLE

Overcurrent Protection (2014 NEC) (Homestudy)

Short-Circuit Current Rating - SCCR Watlow Power Controllers

TRANSMISSION SYSTEMS

YOUR ELECTRICAL SYSTEM IS YOUR LIFELINE AMP-TRAP 2000 FUSES

Type E/F Simplex & Duplex Pump Controllers

CENTERLINE 2100 Motor Control Centers

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

Selection Guide Motor Control Device Solutions

Industrial Generator Set Accessories. Standard Features. Line Circuit Breakers kw

Industrial Control Transformers

FACT SHEET Standard: Electrical Safety

Self-protected Combination Starters System PKZ 2-SP

ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits

Transcription:

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

Assembly Short-Circuit Current Ratings What Is A Short-Circuit Current Rating (SCCR)? SCCRs on components and assemblies represent the maximum level of short-circuit current that the component or assembly can withstand and is used for determining compliance with NEC 110.10.This rating can be marked on individual components or assemblies. Assembly ratings take into account all components contained within the equipment. A common mistake is to assume that the interrupting rating of the overcurrent protective device protecting the circuit represents the SCCR for the entire circuit. Interrupting ratings, used for compliance with NEC 110.9, apply solely to the overcurrent protective device. It is the characteristics of the overcurrent protective device (e.g. opening time, let-through energy) that need to be used in determining compliance with NEC 110.10, not the interrupting rating. CAUTION: Short-circuit current ratings (SCCRs) are different than interrupting ratings marked on overcurrent protective devices. Who Is Affected By The SCCR Markings The 2005 NEC has requirements for anyone building equipment listed to the 2005 NEC or to UL508A and requires the following to be marked with an SCCR: Industrial control panels [409.110 ] Industrial machinery electrical panels [670.3(A)] HVAC equipment [440.4(B)] Meter disconnect switches [230.82(3)] Motor controllers [430.8 ] Effective April, 2006, all equipment listed to UL508A will be required to be marked with an assembly SCCR. Inspectors and installers need this information in order to ensure compliance with NEC 110.10. Equipment installed where fault current levels exceed their shortcircuit current can be hazardous to persons and property. SCCRs marked on components and assemblies make it easier to verify proper protection for components and assemblies for specific applications whether it be the initial installation or relocation of equipment. How Is SCCR Determined? For meter disconnect switches and motor controllers, this withstand level or SCCR is often determined by product testing. For assemblies, the marking can be determined through product listing or by an approved method. With the release of the UL508A Industrial Control Panel standard, an industry approved method is now available. Any method used, whether UL508A or another approved method, should be based upon the weakest link approach. In other words, the assembly should be limited to installation where fault levels do not exceed the withstand rating of devices with the lowest SCCR.The marking determined should represent the limits of the assembly for a safe installation. Current-limiting overcurrent protective devices can be used in the feeder or branch circuits to increase the assembly SCCR where lower rated components are used. Who Is Affected Facility/Process Engineers/ Consulting Engineers Control Panel Builders/ Machine Builders/ HVAC Manufacturers Electrical Contractors Electrical Inspectors How Are They Affected Need to specify end use equipment with ratings adequate for available short-circuit current. Need to determine and mark the assembly short-circuit current rating on the equipment being built. Need to market equipment with ratings at least as high as their competition. Need assurance that the equipment installed is adequate for the available short-circuit current at the point of installation, to avoid red tags and lost time and labor. Need to assure that the available short-circuit current where equipment is being installed does not exceed the rating marked on the equipment. Page 2

Assembly Short-Circuit Current Ratings Determining Assembly SCCR In order to determine the short-circuit current rating for the entire assembly, every component and device used in the power circuits of the assembly needs to be assessed. The investigation is based upon two sweeps of review. Sweep 1: The Component Protection Sweep The first sweep is an investigation to determine the component with the lowest short-circuit current rating. Sweep 2: The Interrupting Rating Sweep The second sweep determines the device with the lowest interrupting rating. The ratings determined from these two sweeps directly affect the overall assembly rating as the lowest value is represented in the new mandatory marking. To determine the assembly rating for industrial control panels, HVAC equipment, and industrial machinery, there are three main areas of consideration: 1. The short-circuit current (withstand) rating of every device used in the power circuits needs to be determined. The device or component with the lowest short-circuit current rating would represent the assembly short-circuit current rating. 2 The interrupting rating of every overcurrent protective device in the assembly needs to be determined. The device or component with the lowest interrupting rating would be compared to the lowest rated component and the lower of the two ratings would represent the assembly short-circuit current rating. 3. The use of modern current-limiting fuses in the feeder circuits can increase the short-circuit current ratings of components and circuits with low short-circuit current (withstand) ratings. The example begining on page 8 highlights some weak links that could be encountered and the Cooper Bussmann fusible solutions to help... Find It, Fix It and Forget It. Sweep 1: Check for component with the lowest short-circuit current rating. Sweep 2: Check for the lowest interrupting rating of any overcurrent protective device used in the panel. Page 3

Find It, Fix It...Forget It Look For... The Weakest Link Many components used in industrial control panels, industrial machinery, and HVAC equipment may be the weakest link and therefore limit the assembly shortcircuit current rating. These include, but are not limited to, motor controllers, definite purpose contactors, supplemental protectors, circuit breakers with low interrupting ratings, and power distribution blocks. The short-circuit current rating marking for the assembly will be based upon the lowest short-circuit current or withstand rating of any component contained within the assembly, or the weakest link approach. Low rated components can result in a low assembly short-circuit current rating and therefore limit the usage of the assembly. Use this table to initiate the process of identifying the short-circuit current rating of your components. Default Value Your Value Glossary of Terms Industrial Control Panel - An assembly of a systematic and standard arrangement of two or more components such as motor controllers, overload relays, fused disconnect switches, fuses, and circuit breakers and related control devices such as pushbutton stations, selector switches, timers, switches, and control relays with associated wiring, terminal blocks, pilot lights and similar components. Interrupting Rating (IR) - The highest current at rated voltage that a device is intended to interrupt under standard test conditions. Short-Circuit Current Rating The prospective symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding the defined acceptance criteria. Control Circuit A circuit that carries the electric signals directing the performance of a controller, and which does not carry the main power circuit. A control circuit is, in most cases, limited to 15 amp. Power Circuit Conductors and components of supply, branch, and feeder circuits, supplying main line power to loads such as heaters, motors, lighting, receptacles, power transformers, and appliances. Branch Circuit Fuses UL489 Circuit Breakers UL98 Fusible Disconnect Switch UL98 Non-Fusible Disconnect Switch UL1429 Pullout Molded Case Switch 200kA* 5kA 200kA* 5kA**** 10kA* 5kA* * Class CC, J, L, R and T UL248 branch circuit type fuses. ** When used in conjunction with Class CC, J, L, R and T UL248 branch circuit type fuses. *** 50Hp or less 480V **** Default value increases to 10kA when protected by fuses. + Combination rating is used for Sweep 1. For Sweep, 2 IR = 5kA (default value) Page 4

Power Distribution Block (PDB) Class CC, J, L, R, or T Fuse Holder Busbar Magnetic Motor Starter Type E Self Protected Starter Instantaneous Trip Circuit Breaker 10kA 200kA* 10kA 5kA*** 5kA*** + Fuse Holder UL508 Manual Motor Starter UL508 Switch Drives Contactors Receptacle 10kA 5kA*** 5kA*** 5kA*** 5kA*** 10kA GFCI Receptacle 2kA * Class CC, J, L, R and T UL248 branch circuit type fuses. ** When used in conjunction with Class CC, J, L, R and T UL248 branch circuit type fuses. *** 50Hp or less 480V **** Default value increases to 10kA when protected by fuses. + Combination rating is used for Sweep 1. For Sweep, 2 IR = 5kA (default value) Page 5

Find It, Fix It...Forget It How To Get A Higher SCCR So An Assembly Isn t Limited? Once these weakest links are found, and if the desired assembly short-circuit current rating is not achieved, there are options to fix these weak links. By fixing these weak links, higher short-circuit current ratings can be achieved. In general there are three options that can be used to fix weak links encountered in a panel. Options For Fixing Weak Links 1. Use Overcurrent Protective Devices With Higher Interrupting Ratings Overcurrent protective devices with low interrupting ratings often become the weakest link and limit the short-circuit current rating of the assembly. The interrupting ratings of the overcurrent protective devices used directly affects the assembly rating. The only fix is to use devices with higher interrupting ratings. CAUTION: Combination ratings are often limited by the interrupting ratings of the overcurrent protective devices used. 3. Buy More Expensive Components With Higher Ratings A 65kA circuit breaker will more than double the cost compared to a 14kA circuit breaker. The fusible solution provides a rating as high as 200kA, at a comparable or lower cost to an existing design, making it the most economical solution. Circuit breakers add unnecessary cost, while fuses are economical. 2. Use Current Limitation To Fix Low Rated Components It only takes one component with a low short-circuit current rating to limit the entire assembly. Many of the components used in industrial control applications have low short-circuit current ratings. Fix these low rated components and the assembly rating by using current limitation. Since current-limiting fuses reduce high level short-circuit currents to a minimal level they can allow the use of these lower rated devices while providing a higher assembly short-circuit current rating. Type 2 protection, using fuses, can be used to achieve high branch SCCR. Modern current-limiting fuses have: The highest interrupting ratings of any overcurrent protective devices, and Current limitation to fix low-rated components. Example of the use of current limitation to increase a low short-circuit rated component. Page 6

Find It, Fix It...Forget It Don t Be Limited By These Weak Links Additional benefits exist with the use of Cooper Bussmann modern current-limiting fuses. Not only can modern current-limiting fusible solutions fix undesired weak links and obtain a high assembly short-circuit current rating, they can also provide enhancements to a design in the areas of flexibility of installation, increased workplace safety, and enhanced protection through the life of the equipment. These enhancements take care of the hassle associated with equipment with limited ratings so one can FORGET IT! Benefits of Straight Voltage Ratings Straight voltage ratings allow for more systems where equipment can be installed. Straight voltage rated equipment can be installed in any type of grounded, ungrounded, or impedance grounded system. Devices with slash voltage ratings, as found on some circuit breakers, and all selfprotected starters, and limited to installation in only solidly grounded WYE systems. Benefits of High Assembly SCCRs: High short-circuit current ratings allow for more installations where equipment can be installed. Meets the UL508A and NEC requirements for short-circuit current rating marking. Additional Benefits Which Provide Enhancements To A Design... Increased Flexibility In Panel Use And Installation Valuable time that was spent gathering information for proper application is drastically reduced with fuses since modern current-limiting fuses can provide high assembly short-circuit current ratings and straight voltage ratings because modern current-limiting fuses have: High interrupting ratings of 200,000A or more. Excellent current limitation to protect low rated components at high short-circuit current levels. Straight voltage ratings so they can be installed in any type of installation independent of the grounding scheme used, unlike devices with a slash voltage rating which are limited to installation in ONLY a solidly grounded WYE type system. Enhanced Protection Type 2 No Damage protection of motor starters when applied properly. Reliable protection throughout the life of the installation. After a fault occurs, fuses are replaced with new factory calibrated fuses assuring the same level of protection that existed previous to the fault. High short-circuit current ratings allow for more installations where equipment can be installed. Superior current limitation provides protection of circuit components for even the most susceptible components such as equipment grounding conductors. Fuses do not vent. Therefore fuses will not affect other components in the panel while clearing a fault. Additional guards or barriers which isolate devices that vent from other components are not required. Achieving selective coordination is simple. Typically, selective coordination can be achieved between fuses by simply maintaining a ratio between upstream and downstream fuses. Fuses have rejection features, unlike other overcurrent protective devices, assuring replacement with a device of the same voltage rating and equal or greater interrupting rating. In addition, rejection features restrict the fuses used for replacement to ones of the same class or type. Enhanced Workplace Safety Superior current limitation provides enhanced workplace safety and reduced arc-flash levels. Eliminates invitation to reset into a fault and potential OSHA violation. Resetting or manually re-energizing a circuit without investigating the cause is prohibited in OSHA CFR29:1910-334. Fuses are not resettable and eliminate the invitation to reset. Page 7

Industrial Control Panel Example The following is an example of an industrial control panel assembly along with a one line diagram of the circuitry. The components, their ratings and any special conditions associated with their use is shown in the components list to the left. Components List 1. Fusible disconnect with LPJ-100SP fuses IR = 300kA. SCCR of disconnect with fuses installed = 200kA. 2. Unmarked power distribution block SCCR = 10kA default. 3. Fusible disconnect with LP-CC fuses (IR = 200kA) SCCR = 200kA. 4. Motor starter marked 50kA when protected by fuses or circuit breaker. 5. UL489 instantaneous trip circuit breaker (MCP) used in conjunction with appropriate motor controller and overload relay as a listed and labeled assembly with a combination SCCR = 25kA. MCP not marked with an interrupting rating. 6. Self protected Type E combination controller marked with a 50kA SCCR. 7. Motor controller (contactor) marked with a 5kA SCCR. 8. Drive marked with a 10kA SCCR 9. LP-CC fuses marked with a 200kA IR in a fuse holder with a marked SCCR = 200kA. 10. Molded case circuit breaker marked with a 10kA IR. 11. Lighting contactor marked with a 2kA SCCR. 12. Unmarked UL1077 supplemental protector. SCCR = 200A by default. 13. Unmarked GFCI receptacle SCCR = 2kA by default. 14. Molded case circuit breaker marked with a 14kA IR. 15. 5kVA transformer (480:120V). 16. 10kVA isolation transformer (480:480V). 17. Motor controller (contactor) marked with a 50kA SCCR. IR = Interrupting rating SCCR = Short-circuit current rating Page 8

Weak Links and Improving SCCR The following table highlights the weak links encountered in the example on the previous page and provides Cooper Bussmann solutions, along with the added benefits that these solutions can provide for a design. This is an example of how Cooper Bussmann can help Find the weakest link, Fix the weakest link and Forget about any future worries or aggravations in a design. Cooper Bussmann will provide the most versatile and reliable design for any overcurrent protection need. Weak Link Component Fix It A UL1077 Supplementary Protectors (component #12) The default IR of 200A is less than the limits allowed for a 5kVA transformer. Assembly Limited To 200A. Increase the Interrupting Rating: Use Cooper Bussmann current-limiting fuses to achieve higher SCCRs by replacing the low short-circuit rated UL1077 supplementary protector with modern currentlimiting fuses with high IRs of up to 300kA. B UL489 Instantaneous Trip Circuit Breaker (component #5) The interrupting rating for the instantaneous trip circuit breaker is not marked on the device and therefore the default value of 5kA must be used for Sweep 2. Assembly Limited To 5kA: If weak link A is fixed. Increase the Interrupting Rating: Use Cooper Bussmann current-limiting fuses to achieve higher short-circuit current ratings by replacing the low interrupting rated instantaneous trip circuit breaker with modern current-limiting fuses with high interrupting ratings of up to 300kA. C Power Distribution Block in Feeder Circuit (component #2) The power distribution block is not marked with a SCCR so default rating of 10kA must be used. Assembly Limited To 10kA: If weak links A and B are fixed. Use Current Limitation: If the PDB is fed by a Cooper Bussmann modern current-limiting LPJ, JJS, or LP-CC fuse rated 60A or less upstream, the current limitation of the fuse can be used to raise the rating of the PDB to 100kA or more. Use NEW PDB Series of Power Distribution Blocks with High Short-Circuit Current Rating: Cooper Bussmann has introduced a line of power distribution blocks Listed to UL1953 with high SCCRs of 200kA or more. By replacing a present low rated power distribution block with the new Cooper Bussmann PDBs, a panel can achieve the high ratings desired!! Page 9

Weak Links and Improving SCCR Weak Link Component Fix It D Molded Case Circuit Breakers with Low Interrupting Ratings (component #14) Low 14kA interrupting rating becomes lowest rated component and limits assembly rating. Assembly Limited To 14kA: If weak links A, B, and C are fixed. Increase the Interrupting Rating: Use Cooper Bussmann current-limiting fuses to achieve higher short-circuit current ratings by replacing the low interrupting rated circuit breaker with modern currentlimiting fuses with high interrupting ratings of up to 300kA. E F Molded Case Circuit Breakers with Low Interrupting Ratings (component #14) This example is different from D in that the interrupting rating of the overcurrent protective device on the lineside of the 5kVA transformer can be used for the entire secondary circuitry. The low 14kA interrupting rating becomes lowest rated component and limits assembly rating. Assembly Limited To 14kA: If weak links A, B, C, and D are fixed. Type E Self Protected Combination Starter (component #6) Slash voltage rating limits the application options for an assembly to a solidly grounded Wye system line-to-ground interrupting capability is limited. Assembly Limited To 480/277V: Limited to solidly grounded WYE type systems only. Increase the Interrupting Rating: Use Cooper Bussmann current-limiting fuses to achieve higher SCCRs by replacing the low interrupting rated circuit breaker with modern current-limiting fuses with high interrupting ratings of up to 300kA. Use Device With Straight Voltage Rating: Use Cooper Bussmann current-limiting fuses with straight voltage ratings to allow for installation on any type of system grounding. If weak links A, B, C, D, E and F are fixed through the use of Cooper Bussmann current-limiting fuses, and if a new Cooper Bussmann power distribution block is used, the new short-circuit current rating is now 200kA. For further information contact your local Cooper Bussmann sales engineer, Cooper Bussmann Application Engineering, or visit www.cooperbussmann.com. Page 10

Cooper Bussmann Products And Technical Support Delivered Worldwide Customer Assistance Customer Satisfaction Team The Cooper Bussmann Customer Satisfaction Team is available to answer questions regarding Cooper Bussmann products and services. Calls should be made Monday Friday, 8:00 a.m. 4:30 p.m. Central Time for all US time zones. The Customer Satisfaction Team can be reached via: Phone: 636-527-3877 Toll-free fax: 800-544-2570 E-mail: busscustsat@cooperbussmann.com Emergency and After-Hours Orders To accommodate time-critical needs, Cooper Bussmann offers emergency and after-hours service for next flight out or will call. Customers pay only standard price for the circuit protection device, rush freight charges and a modest emergency fee for this service. Emergency and after-hours orders should be placed through the Customer Satisfaction Team. Call: Monday Friday, 8:00 a.m. 4:30 p.m. Central Time 636-527-3877 After hours 314-995-1342 Application Engineering Application Engineering assistance is available to all customers. The Application Engineering team is staffed by degreed electrical engineers and available by phone with technical and application support Monday Friday, 8:00 a.m. 5:00 p.m. Central Time. Application Engineering can be reached via phone, fax or email: Phone: 636-527-1270 Fax: 636-527-1607 E-mail: fusetech@cooperbussmann.com Online Resources Visit www.cooperbussmann.com for the following services: Product cross reference Arc-flash calculator SCCR calculator Training modules Your Authorized Cooper Bussmann Distributor is: 2006 Cooper Bussmann St. Louis, MO 63178 636-394-2877 www.cooperbussmann.com Reorder #7009 1-06