Vacuum Circuit Breaker Type VAD-3

Similar documents
S&C Type FVR Substation Circuit Breaker

Instruction Manual 15kV KVAN-1125M 1200/2000A Maxi-Vac Medium-Voltage Vacuum Circuit Breaker

MASTERCLAD. Metalclad Indoor Switchgear 27 kv with Type VR Vacuum Circuit Breakers Class Instruction Bulletin. Retain for future use.

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION

IB PowlVac CDR Vacuum Circuit Breaker. 5kV & 15kV 1200A, 2000A, & 3000A. Powered by Safety

PowlVac Type PV STD/CDR Vacuum Circuit Breaker

SecoVac * Ground & Test Device

PATENT PENDING. Phone: (877) Operation and Service Manual

Metal-Clad Indoor Switchgear

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

ibusway for Data Center

Powered by Safety 01.4IB.77000B PowlVac-ND Vacuum Circuit Breaker

ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS36

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION

Vacuum Circuit Breakers (Vehicle) Type MSV 5kV. Instructions Installation Operation Maintenance SGIM-9988

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9968

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX

MASTERCLAD Metal-Clad Indoor Switchgear

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

Vacuum Circuit Breakers (Vehicle)

ON LOAD GEARS OPERATIONAL AND MAINTENANCE MANUAL VACUUM CIRCUIT BREAKER TYPE VS12

CR193 Vacuum Limitamp* Contactors

Vacuum Circuit Breakers (Vehicle)

GE CONSUMER & INDUSTRIAL

Type 38-3AH3 38 kv vacuum circuit breaker instruction manual. Installation operation maintenance E50001-F710-A238-V1-4A00. Answers for energy.

Vacuum Circuit Breakers (Vehicle)

GE CONSUMER & INDUSTRIAL

1ZSC ABH en, Rev. 1. Motor-drive mechanisms, types BUE and BUL2 Maintenance guide

Tooling Assistance Center

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B.

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

Vacuum Circuit Breaker (Vehicle)

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

Horizontal Circuit Switchers

Instruction manual. Types GMSG and GMSG-GCB 5 kv to 15 kv vacuum circuit breakers.

EISHO TEK. Vacuum Circuit Breaker

ABB ADVAC TM. INSTALLATION/MAINTENANCE INSTRUCTIONS Medium Voltage Vacuum Power Circuit Breakers and Auxiliary Devices

AM-4.16/7.2/13.8-VR Replacement Circuit Breaker

User manual W-VACi. W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers

IB PowlVac ITE-HK Remote Racking Device

Type 3AH kv to 38 kv vacuum circuit breaker operator module instruction manual

Vacuum Circuit Breakers (Vehicle)

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Horizontal Circuit Switchers

AM4.16/7.2/13.8-VR + VR-Series + Replacement Circuit Breaker

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

Power Break Circuit Breakers

Wheel Horse 48 Blade for 5xi Garden Tractors

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII

T- VACR Fixed (up to 40kA) T-VAC Draw out (up to 40kA)

Wheel Horse. 48 Snow/Dozer Blade. Model No & Up. Operator s Manual

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Wheel Horse. 44 Snowthrower. for 5xi Lawn and Garden Tractors. Model No & Up. Operator s Manual

COOKSON OWNER'S MANUAL

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

Installation Instructions For Motor Control Center (MCC) Units

Typical Specification

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

5HK-VR, 15HK-VR, & 17HK-VR - (Model 03) Replacement Circuit Breaker

AMH-4.76-VR Replacement Circuit Breaker

Vacuum Circuit Breakers (Vehicle)

HV6FS-MLD Vacuum Circuit Breakers Drawout Type 4.8 & 7.2kV Voltage Classes (Fast Closing w/uv Release)

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism

Instructions for installation, operation, and maintenance of medium voltage VC-W MR2 (integral racking)

MA-VR Replacement Circuit Breaker

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

Submersible Vacuum Fault Interrupters

1500 Series Roll Off Hoist. Owner s Manual (5-06)

ADVAC TM Model 03 Medium Voltage Vacuum Power Circuit Breakers and Auxiliary

ADVAC Medium Voltage Vacuum Circuit Breaker Installation and Operation Manual

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

1. Safety practices General Introduction Standards...3

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons

SUREPOWR TM SERIES -SURE 49 FIELD INSTALLATION INSTRUCTIONS

Instructions for the Use, Operation and Maintenance of Types VCP-TL and VCP-TRL Linear Magnetic Vacuum Circuit Breakers

McCANNA Actuation Systems B

Instructions for Installation, Operation and Maintenance of Type VCP-W Vacuum Circuit Breakers IB131006EN

ADVAC Model 3 Medium Voltage Vacuum Circuit Breaker Installation and Operation Manual

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

SUREPOWR TM SERIES -SURE 24/25 FIELD INSTALLATION INSTRUCTIONS

Medium Voltage Metal-Enclosed Switches

38 kv Type VCPW-HD Simple Electrical Ground & Test Device (SEG&TD) lower terminal instruction booklet

HEAVY DUTY TROLLEY JACK. Operation Manual

Publication No.: PSG

Instructions for the Use, Operation and Maintenance of VCP-WG/VCP-WRG 75kA Vacuum Circuit Breakers

K-Line Plus Type KP-8 thru KP-20

Transcription:

Instruction Bulletin Bulletin 6055-11 Vacuum Circuit Breaker Type VAD-3 4.76 kv, 29 ka (250 MVA) 4.76 kv, 41 ka (350 MVA) 8.25 kv, 33 ka (500 MVA) 15.0 kv, 18 ka (500 MVA) 15.0 kv, 28 ka (750 MVA) 15,0 kv, 37 ka (1000 MVA) 1200A & 2000A 1200A & 2000A 1200A & 2000A 1200A & 2000A 1200A & 2000A 1200A & 2000A 1993 Square D Company All Rights Reserved 1

NOTICE Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this bulletin to warn of potential hazards and to call attention to additional information which clarifies or simplifies a procedure.! DANGER Used where there is a hazard of severe bodily injury or death. Failure to follow a DANGER instruction will result in severe bodily injury or death.! WARNING Used where there is a hazard of bodily injury or death. Failure to follow a WARNING instruction may result in bodily injury or death.! CAUTION Used where there is a hazard of equipment damage. Failure to follow a CAUTION instruction may result in damage to equipment. NOTE Provides additional information to clarify or simplify a procedure. Square D and are Registered Trademarks of Square D Company. 1993 Square D Company, all rights reserved. This bulletin may not be copied in whole or in part, or transferred to any other media, without the written permission of Square D Company. 2 1993 Square D Company All Rights Reserved

CONTENTS PAGE 1. INTRODUCTION... 1 Surge Protection For VAD-3 Circuit Breakers Statement Of Use... 1 2. SAFETY PRECAUTIONS... 2 3. RECEIVING, HANDLING, AND STORAGE... 3 Receiving... 3 Handling... 3 Storage... 3 4. INITIAL CIRCUIT BREAKER PREPARATION... 4 Performing A Hi-Pot Test... 4 5. INSTALLATION... 5 Site Preparation And Circuit Breaker Installation... 5 6. VACUUM CIRCUIT BREAKER DESCRIPTION... 6 Vacuum Interrupters... 6 Primary Disconnects... 6 Operating Mechanism... 6 Control Circuit... 6 Auxiliary Switch... 8 Motor Limit Switch... 8 Motor Relay... 8 Anti-Pump Relay... 9 Latch Check Switch... 9 Closing Spring Interlock... 9 Indicators... 9 7. OPERATING THE CIRCUIT BREAKER... 10 Manual Charging... 10 Slow Closing Feature... 10 Drawout Operation... 11 Racking In Procedure... 11 Racking Out Procedure... 12 Locking Provision... 12 Test Position Operation... 12 8. OPERATING MECHANISM... 13 Drive Spring Charging... 13 Closing Operation... 14 Opening Operation... 15 9. MAINTENANCE... 16 Vacuum Interrupters... 16 Insulating Surfaces... 16 Mechanism... 17 Lubrication... 17 Electrical... 17 10. REPLACEMENT PARTS... 18 Minimum Requirements... 18 Ordering Instructions... 18 11. INSTALLATION AND MAINTENANCE LOG... 19 1993 Square D Company All Rights Reserved 3

ILLUSTRATIONS PAGE 1. Circuit breaker, front view... 5 2. Circuit breaker, rear view... 6 3. Contact circuit schematic... 7 4. Circuit breaker, left front view without cover (18 ka, 28 ka, and 29 ka)... 8 5. Circuit breaker, right front view without cover (18 ka, 28 ka, and 29 ka)... 8 6. Circuit breaker, front view without cover (37 ka and 41 ka)... 9 7. Charging the drive springs... 9 8. Removing the closing spring... 10 9. Slow close feature... 10 10. Racking mechanism in test position... 11 11. Racking mechanism in operating (connected) position... 11 12. Racking mechanism padlock provision... 12 13. Circuit breaker mechanism, two views... 13 14. Mainshaft mechanism... 14 15. Contact erosion measurement... 14 TABLES PAGE 1. Lubrication Chart... 17 2. Replacement Parts... 18 3. Pole Assembly Replacement Parts... 18 4 1993 Square D Company All Rights Reserved

SECTION 1 INTRODUCTION This manual provides installation, operation, and maintenance instructions for the type VAD-3 series of horizontal drawout vacuum circuit breakers. Surge Protection For VAD-3 Circuit Breakers Statement Of Use VAD-3 medium voltage vacuum circuit breakers are designed and tested in accordance with ANSI/IEEE C37.04,.06, and.09. Used in conjunction with switchgear designed and tested to ANSI/IEEE C37.20.2, circuit breakers can be applied as general purpose devices. VAD-3 circuit breakers may be installed over a wide range of applications and system parameters. Several IEEE publications are available to provide guidance for use in industry practices (IEEE Color Book Series). Distribution systems can be exposed to lightning or switching surges. Older systems, with aging insulation or out-of-date standards, may be more susceptible to damage. For this reason, consider adding metal oxide surge arrestors to the circuitry on the load side of the terminals of VAD-3 circuit breakers used in retro-fit applications. Place the surge protection in the switchgear or at the equipment being protected, but not on the circuit breaker. Metal oxide arrestors limit the magnitude of prospective overvoltages, but do not affect the rate of rise (di/dt) of surge transients. Consider using surge capacitors for this additional protection. 1993 Square D Company All Rights Reserved 5

SECTION 2 SAFETY PRECAUTIONS! DANGER HAZARD OF ELECTRICAL SHOCK OR BURN. Only qualified electrical workers with training and experience on high voltage circuits should perform work described in this set of instructions. These workers must understand the hazards involved in working with or near high voltage equipment. Perform such work only after reading this complete set of instructions. The successful operation of circuit breakers depends upon proper handling, installation, operation, and maintenance. Neglecting fundamental installation and maintenance requirements may lead to personal injury, as well as damage to electrical equipment or other property. VAD-3 circuit breakers have features designed to direct proper operation, but it is not possible to eliminate every hazard with these features. Therefore, the person using this device is responsible for recognizing the potential hazards, wearing protective equipment, and taking adequate safety precautions. Do not make any modifications to the equipment or operate the system with safety features removed. Contact your local Square D representative for additional instructions if the VAD-3 circuit breaker does not function as described in this manual. Before performing visual inspections, tests, or maintenance on this device, disconnect all sources of electric power. Assume all circuits are live until they are completely de-energized, tested, grounded, and tagged. Pay particular attention to the design of the power system. Consider all sources of power, including the possibility of backfeeding. Before replacing covers, carefully inspect the circuit breaker work area for tools and objects left inside the equipment. All maintenance must be performed by qualified personnel in accordance with local codes and ordinances, and under the following conditions: The circuit breaker must be removed from its cell and isolated from the high voltage. Control voltage must be removed from the controls. The circuit breaker must be in the open position. All circuit breaker springs must be discharged. All instructions in this manual assume the customer has taken the above steps to obtain safe conditions before performing maintenance or testing. Failure to observe these precautions will result in severe personal injury or death! 6 1993 Square D Company All Rights Reserved

SECTION 3 RECEIVING, HANDLING, AND STORAGE Receiving Handling Upon receipt, inspect the entire circuit breaker for damage that may have occurred in transit. Check all items against the packing list provided. Notify the transportation company and Square D immediately if there are damages or shortages. Use care when uncrating and handling the circuit breaker. Roll and maneuver the circuit breaker by the handle on the front mechanism cover or by grasping the top edge of the front mechanism cover. When using a hoist, lift the circuit breaker by the holes in the frame to prevent damage.! CAUTION HAZARD OF EQUIPMENT DAMAGE. Never lift the circuit breaker by placing forklift bars beneath the circuit breaker frame. Never use racking arms or primary disconnects as handles. Failure to observe this precaution can result in equipment damage. Storage If the circuit breaker must be stored before it is put into operation, keep it in a clean, dry, corrosion-free area where it is protected from damage. Place the circuit breaker in its permanent location as soon as possible. If the circuit breaker will be used in switchgear employing space heaters, install it only after the heaters are operating. When circuit breakers are stored for prolonged periods, inspect them regularly for rusting and overall condition. Lubricate when necessary. 1993 Square D Company All Rights Reserved 7

SECTION 4 INITIAL CIRCUIT BREAKER PREPARATION Performing A Hi-Pot Test Follow these steps to prepare the circuit breaker for installation in its enclosure: 1) Examine the entire circuit breaker for damage, dirt, and moisture. 2) Use a clean, dry cloth to remove dirt and moisture that may have collected on the insulating parts. 3) Operate the circuit breaker several times to check for proper operation. 4) To ensure no damage has occurred during shipment, perform a hi-pot test across the open contacts of each vacuum interrupter. Then, with the circuit breaker in the closed position, perform a phase-to-ground and phase-to-phase hi-pot test for each pole. Gradually increase the voltage to the proper level. The hi-pot test voltage should be 27 kv rms or 38 kvdc for 15.0 kv, and 14 kv rms or 20 kvdc for 4.76 kv switchgear. The circuit breaker should sustain this potential for one minute.! WARNING HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE. Observe the following instructions when performing the hi-pot test: Do not exceed the voltages specified in step 4 above. Keep all people at least six feet away from the circuit breaker being tested. Perform tests only after all insulating parts are installed. Discharge to ground the primary disconnects before handling. These areas can retain a static charge after a hi-pot test. Failure to observe these precautions can result in severe personal injury or death! 5) To insert the circuit breaker into its enclosure, follow the applicable directions provided in the switchgear instruction manual. 6) With the main power off, cycle the circuit breaker several times and check forproper operation. The circuit breaker is now ready for normal operation. 8 1993 Square D Company All Rights Reserved

SECTION 5 INSTALLATION Site Preparation And Circuit Breaker Installation Refer to the metal-enclosed switchgear instruction bulletin that was shipped with your equipment; follow the site preparation and installation instructions found in that manual. ➇ ➁ ➈ ➀ Racking Port ➁ Front Mechanism Cover ➂ Open Lever Close Lever ➄ Secondary Disconnect Handle Manual Charging Arm Port Racking Arm ➇ Counter ➈ Open-Close Indicator ➉ Spring Charge-Discharge Indicator ➉11 Test Position Interlock ➀ ➉11 ➂ ➄ ➉ Figure 1: Circuit breaker, front view 1993 Square D Company All Rights Reserved 9

SECTION 6 VACUUM CIRCUIT BREAKER DESCRIPTION Vacuum Interrupters Vacuum interrupters (figure 2), mounted vertically within the circuit breaker frame, perform the circuit breaker interruption. Consisting of a pair of butt contacts, one movable and one fixed, interrupters require only a short contact gap for circuit interruption. The resulting high-speed operation allows the entire operating sequence, from fault to clear, to be consistently performed in three cycles or less. Primary Disconnects Operating Mechanism Control Circuit The primary connection to the associated switchgear is through the six primary disconnects (figure 2) mounted horizontally at the rear of the circuit breaker. Do not subject the primary disconnects to rough treatment. Never use the primary disconnects as handles when maneuvering the breaker. The operating mechanism is of the stored energy type. It uses charged springs to perform breaker opening and closing functions. The operating mechanism contains all necessary controls and interlocks. It is mounted at the front of the circuit breaker for easy access during inspection and maintenance. Figure 3 shows a typical schematic diagram for the control circuit. The following paragraphs discuss operation of the control circuit components. The control circuit design may vary, depending upon customer requirements. Always refer to the schematic diagram for the specific equipment in question. ➀ ➁ ➀ Primary Disconnect ➁ Shutter Roller ➂ Secondary Disconnect Code Plate ➄ Ground Contact Vacuum Interrupter Racking Arm ➂ ➄ Figure 2: Circuit breaker, rear view 10 1993 Square D Company All Rights Reserved

1 3 4 7 10 12 14 16 21 23 5 7 21 22 52/M 52MR 52Y 207 200 201 52MR 52/LS 52Y 52MR 52Y 202 52/b 203 52/CC 209 52/LC 204 52MR 11 12 4 3 8 7 9 52/a 205 52/a 210 52/TC 206 52/a 10 13 51 53 55 57 59 61 5 15 9 19 13 23 17 52/b 52/a 52/b 52/a 52/b 52/a 52/b 6 16 10 20 14 24 18 14 52 54 56 58 60 62 2 6 Charging/Closing Circuit 5 Trip Circuit 9 11 13 15 17 22 24 Auxiliary Contacts Legend 52/M Spring Charging Motor 52MR Motor Relay 52/LS Closing Springs Limit Switch; Closed When Springs Are Discharged 52Y Anti-Pump Relay 52/CC Closing Coil (Spring Release Coil) 52/TC Tripping Coil 52/a Auxiliary Switch Contact; Open When Circuit Breaker Is In Tripped (Open) Position 52/b Auxiliary Switch Contact; Closed When Circuit Breaker Is In Tripped (Open) Position 52/LC Latch Check Switch Note: Circuit breaker shown in open position with closing springs charged Rear View Of Circuit Breaker Control Plug 1 2 3 4 5 6 7 8 9 10 11 12 5 6 7 9 10 13 14 51 52 53 54 55 56 57 58 59 60 61 62 13 14 15 16 17 18 19 20 21 22 23 24 Figure 3: Control circuit schematic 1993 Square D Company All Rights Reserved 11

Auxiliary Switch Motor Limit Switch Motor Relay The auxiliary switch (figure 4) is a multi-stage switch used to operate circuits that depend on the position of the circuit breaker contacts. The schematic diagram in figure 3 (page 7) illustrates how each auxiliary switch stage interconnects with the circuit breaker circuitry. The stages function as follows: Three a-type auxiliary contacts connect in series with the trip coil. Because these stages are open when the circuit breaker is in the open position, the auxiliary contacts de-energize the trip coil when the breaker is in the open position. The b-type contact, connected in series with the closing coil, de-energizes the closing coil when the circuit breaker contacts are in the closed position. As shown, several a-type and b-type contacts are provided for optional use. The motor limit switch (figure 4) energizes the motor relay (figure 4) when a drive spring charging operation is required. The motor limit switch de-energizes the motor relay when the drive springs (figure 5) reach the fully charged position. As shown in the schematic diagram (figure 3), the motor limit switch is connected in the normally open position. When the drive springs are not in the fully charged position, the motor limit switch is closed. When energized by the closing of the motor limit switch, the motor relay energizes the spring charging motor (figure 4) through a pair of normally open contacts. The motor relay disables the closing coil (figure 5) through a pair of normally closed contacts. ➇ ➁ ➄ ➈ ➀ ➂ ➁ ➄ ➀ ➂ ➀ MOC Operator ➁ Motor Limit Switch ➂ Opening Coil Latch Check Switch ➄ Auxiliary Switch Motor Relay Anti-Pump Relay ➇ Spring Charging Motor ➈ Return Spring ➀ Return Spring (2 places) ➁ Shock Absorber ➂ Manual Charging Arm Crank Arm (2 places) ➄ Ratchet Arm Drive Spring (2 places) Closing Coil Figure 4: Circuit breaker, left front view without cover (18 ka, 28 ka, and 29 ka) Figure 5: Circuit breaker, right front view without cover (18 ka, 28 ka, and 29 ka) 12 1993 Square D Company All Rights Reserved

Anti-Pump Relay Latch Check Switch Closing Spring Interlock Indicators If the closing coil circuit (52/CC, figure 3, page 7) is continuously energized, the anti-pump relay (figure 4) ensures that the circuit breaker does not pump open and closed in the event that a trip signal is also present. The anti-pump relay performs this function by allowing the closing coil to activate only if: the circuit is energized the drive springs are fully charged, and the motor relay is de-energized The anti-pump relay activates when the close circuit and motor relay are energized. If the close circuit is energized continuously, the anti-pump relay will be latched in the energized position after the motor relay is de-energized by a pair of its own normally open contacts. When the anti-pump relay is energized, a pair of its normally closed contacts, in series with the closing coil, ensure that the closing coil cannot be energized. The closing coil activates only when the closing circuit is de-energized (de-energizing the anti-pump relay), then closed again. The latch check switch (figure 4) allows the circuit breaker to be used for instantaneous reclosing. The contacts of the latch check switch connect in series with the closing coil. When the guide cam moves out of its normal position, it activates the latch check switch. The closing circuit cannot be energized until the guide cam fully returns to its normal position and the mechanism is in position to allow a close operation. An interlock located between the manual trip and close lever at the bottom of the circuit breaker prevents the closing springs from dumping when the circuit breaker is closed. An interlock bar slides under the closing lever after the circuit breaker closes and prevents the closing lever from being pushed down. There are two indicators on the operating mechanism. The open-close indicator (figure 7) designates whether the vacuum interrupter contacts are open or closed. The charge-discharge indicator (figure 7) displays the state (charged or discharged) of the drive springs. ➀ ➂ ➁ ➀ Open-Close Indicator ➁ Manual Charging Arm ➂ Charge-Discharge Indicator Figure 6: Circuit breaker, front view without cover (37 ka and 41 ka) Figure 7: Charging the drive springs 1993 Square D Company All Rights Reserved 13

SECTION 7 OPERATING THE CIRCUIT BREAKER Manual Charging Slow Closing Feature To manually charge the drive springs (figure 7, page 9), use the handle supplied with the circuit breaker to move the manual charging arm (figure 7) up and down until the drive springs are fully charged. The drive springs are fully charged when the charge-discharge indicator (figure 7) reads charged and the manual charging arm no longer advances the gear. Occasionally, it may be necessary to manually slow close the circuit breaker. The operating mechanism has a built-in feature for this purpose. Follow the steps below to manually slow close.! WARNING HAZARD OF BODILY INJURY. Only qualified personnel should perform this operation. Stored energy in springs and sudden operation of mechanisms can cause serious bodily injury if a person touches or comes in close proximity of the mechanism. Failure to observe this precaution can result in personal injury! 1. With the circuit breaker in the open position and the drive springs discharged, slide the manual charging handle onto one of the drive spring brackets (figure 8). Press up on the manual charging handle just enough to off-load the drive spring; remove the upper 1/2" bolt (figure 8). Release the drive spring pressure; remove the spring. Repeat with the other drive spring. 2. Using the manual charging handle as described in the Manual Charging section above, advance the gear until the drive pawl (figure 13, page 13) rides up on the lift cam. Remove the manual charging handle. ➀ Manual Charging Handle ➁ 1/2" Bolt ➂ Drive Spring ➀ ➁ ➂ ➁ ➀ Close Lever ➁ 1" Open-End Wrench ➀ Figure 8: Removing the closing spring Figure 9: Slow close feature 14 1993 Square D Company All Rights Reserved

Slow Closing Feature (cont.) Drawout Operation Racking In Procedure 3. While pressing down on the close lever (figure 9), use a 1" open-end wrench to rotate the drive shaft until the drive pawl clears the lift cam and once again engages the gear. See figure 9 for use of the wrench. Press down on the wrench to achieve the correct direction of rotation. 4. Release the close lever. Remove the 1" wrench. 5. Continue using the manual charging handle to perform manual charging. The circuit breaker slowly closes with each advance of the gear. The circuit breaker must be in the open position when it is racked in or out of its cubicle. The racking mechanism (figures 10 and 11) interlocks with the circuit breaker mechanism. This prevents the racking shaft from being turned when the circuit breaker is in the closed position. 1. The racking arms (figure 10) must be in the drawout position before inserting the breaker into the cell. In the drawout position, the racking arms extend toward the rear of the breaker and are just below the horizontal. 2. If required, move the racking arms to the drawout position. Follow these steps: a. Open the circuit breaker. b. Insert the racking handle into the racking port (figure 10). c. Rotate the racking handle counterclockwise until the racking mechanism comes to a stop. Do not over-torque.! WARNING HAZARD OF BODILY INJURY OR EQUIPMENT DAMAGE. When the switchgear is energized, always open and close the circuit breaker and rack the circuit breaker from one position to another with the door closed. Never use force to move the circuit breaker inside the circuit breaker cell. Failure to observe these precautions can result in severe personal injury or death! ➁ ➀ ➂ ➀ Racking Arm ➁ Roller In Test Position ➂ Racking Port ➀ ➀ Roller In Operating Position Figure 10: Racking mechanism in test position Figure 11: Racking mechanism in operating (connected) position 1993 Square D Company All Rights Reserved 15

Racking In Procedure (cont.) Racking Out Procedure Locking Provision Test Position Operation 3. Insert the circuit breaker into the cell until the rollers on the racking arms come into contact with the channels on the sides of the cell. 4. Rotate the racking handle clockwise until the racking mechanism stops. Do not over-torque. 1. Open the circuit breaker. 2. Insert the racking handle into the racking port. 3. Rotate the racking handle counterclockwise until the racking mechanism stops. Do not over-torque. 4. Press down on the test position interlock (figure 1, page 5) at the lower left front of the circuit breaker; roll the circuit breaker out of the cell. The racking mechanism of the circuit breaker can be locked in either the test or the operating position with a multiple padlock hasp and a padlock, as shown in figure 12. The secondary disconnect (figure 2, page 6) mounts on a retractable slide so that it can connect to the control circuit of the cell while the cell shutters are down and the primary connections have not been made. This provides a convenient and safe method for electrically testing the operation of the circuit breaker mechanism and control circuit. Test position operation is achieved by following these steps: 1. Insert the circuit breaker into the test position of the cell by following steps 1through 3 of the Racking In Procedure section on page 11. (Do not rack the circuit breaker into the cell.) 2. Pull the secondary disconnect handle (figure 2, page 6) out of its retaining clip; rotate it down so that it protrudes straight out from the circuit breaker. 3. Lift slightly on the secondary disconnect handle and push it into the circuit breaker until the control circuits connect. 4. The control circuit of the circuit breaker is now connected with that of the cell. 5. Retract the secondary disconnect by reversing the above procedure. Figure 12: Racking mechanism padlock provision 16 1993 Square D Company All Rights Reserved

SECTION 8 OPERATING MECHANISM Drive Spring Charging Place the interrupter contacts in the open position; ensure that the drive springs (figure 13) and return springs (figure 5, page 8) are discharged. When power is supplied to the circuit breaker control circuit, the charging motor (figure 13) is energized. The eccentric, mounted on the charging motor shaft, drives the ratchet arm (figure 13) backward and forward. With each forward stroke of the ratchet arm, the spring-loaded drive pawl (figure 13) mounted on the ratchet arm engages a tooth on the gear (figure 13). The gear advances a few degrees clockwise. The drive pawl (figure 13) holds the gear in position while the drive pawl makes its reverse stroke to engage another tooth. The gear is free to rotate on the drive shaft (figure 13). As the gear advances, the drive pin mounted on the gear face engages and rotates the lift cam (figure 13). Because the lift cam is keyed to the drive shaft, the drive shaft rotates with the lift cam. The crank arms (figure 13) rotate with the drive shaft and pull the drive springs to the charged position. As the springloads pass top dead center and attempt to discharge, the closing roller on the drive cam contacts the close cam (figure 14, page 14). The drive springs stay in this charged position until closing is initiated. When the drive springs are fully charged, the charging motor limit switch contacts open, de-energizing the charging motor. Simultaneously, the raised ➉ ➇ ➈ ➄ ➀ Ratchet Arm ➁ Drive Pawl ➂ Lift Cam Gear ➄ Drive Shaft Manual Charging Arm Mainshaft ➇ Drive Springs ➈ Crank Arm ➉ Closing Coil ➉11 Charging Motor ➉11 ➂ ➇ ➀ ➁ ➄ Figure 13: Circuit breaker mechanism, two views 1993 Square D Company All Rights Reserved 17

Drive Spring Charging (cont.) Closing Operation surface on the lift cam lifts the drive pawl above the gear. This allows the charging motor and ratchet arm to coast smoothly to a stop. Once the drive springs are charged, close the circuit breaker by energizing the closing coil (figure 13) or by manually pressing the close lever (figure 9, page 10).! WARNING HAZARD OF BODILY INJURY OR EQUIPMENT DAMAGE. The manual closing lever should be used only in the test position, or if the power to the circuit breaker has been removed. Failure to observe this precaution can result in personal injury or equipment damage! This disengages the close cam (figure 14) from the closing roller and allows the drive springs to discharge. The discharging drive springs rotate the drive shaft (figure 13) counterclockwise. This rotation also gives the drive cam (figure 14) a counterclockwise rotation. The rotation of the drive cam pushes the drive cam follower (figure 14) down. Linkage with the mainshaft (figure 13) causes a downward motion of the racking arms (figure 14). The resulting upward motion of the rear of the racking arms closes the vacuum interrupter contacts and charges the bias springs (figure 15). ➀ ➀ ➂ ➁ ➄ ➁ ➀ Close Cam ➁ Drive Cam ➂ Drive Cam Roller Guide Cam ➄ Trip Cam Drive Cam Follower Main Link ➇ Cross Bar Pivot ➈ Cross Bar ➉ Racking Arm ➉ ➈ ➇ ➀ Vacuum Interrupter ➁ Bias Spring E Figure 14: Mainshaft mechanism Figure 15: Contact erosion measurement 18 1993 Square D Company All Rights Reserved

Closing Operation (cont.) Opening Operation The counterclockwise rotation of the drive shaft also rotates the lift cam out of contact with the drive pin. Because the gear rotates freely on the drive shaft, the gear remains stationary. The rotation of the lift cam allows the drive pawl to engage the gear. The motor limit switch (figure 4, page 8) energizes the charging motor which once again charges the drive springs. With the return springs charged and the circuit breaker closed, the operating mechanism is ready to perform an opening operation. If the open lever (figure 1, page 5) is pushed or if the opening coil (figure 4, page 8) is energized, the trip cam rotates counterclockwise away from the guide cam (figure 14). The force of the charged return springs pulling up on the mainshaft causes the guide cam to move out toward the front of the mechanism. This allows the drive cam follower to collapse off the top of the drive cam. The mainshaft is pulled up, pulling the front of the racking arms up. The resulting downward motion of the rear of the racking arms opens the vacuum interrupter contacts (figure 15). 1993 Square D Company All Rights Reserved 19

SECTION 9 MAINTENANCE Because of wide variations in operating uses and environments, each operating company should develop a maintenance schedule, based on operating experience, which will ensure proper circuit breaker condition. Until such a schedule is determined, inspect circuit breakers after three years or every 3,000 operations, whichever occurs first. Also inspect circuit breakers after severe fault operations and record any contact erosion. The following paragraphs discuss proper inspection and maintenance procedures.! WARNING HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE. Always remove the circuit breaker from its cubicle, and discharge the drive springs and return springs, before performing any maintenance or repair work. Failure to observe these precautions could result in personal injury or death, or equipment damage! Vacuum Interrupters Insulating Surfaces To ensure reliable interruption, perform the following two checks: 1. Contact erosion: Any contact erosion results in a reduction of spring overtravel. Contact erosion can be determined by closing the circuit breaker and measuring spring overtravel. Spring overtravel is represented by dimension E in figure 15. The difference between this measurement and the original spring overtravel, measured when the interrupter was first put into service, represents contact erosion. Spring overtravel is factory set at 0.210" (5.3 mm) for a new circuit breaker rated 23 ka or less maximum interrupting. For a new circuit breaker rated above 23 ka maximum interrupting, spring overtravel is 0.188" (4.8 mm). The vacuum interrupter reaches the end of its life when spring overtravel has been reduced to 0.085" (2.2 mm) on a circuit breaker rated 23 ka or less maximum interrupting, or 0.060" (1.5 mm) on a circuit breaker rated above 23 ka maximum interrupting. 2. Hi-pot test: Hi-pot test the circuit breaker in accordance with the instructions provided in the Initial Breaker Preparation section, page 4, item 4. If, because of contact erosion or hi-pot test failure, a vacuum bottle must be replaced, order a complete pole assembly (see table 3 on page 16). Vacuum interrupter contacts are sealed using fragile metal bellows and are sensitive to excessive torque and handling. See the caution on page 16. Using a clean, dry cloth, remove all dirt and moisture from insulating parts. 20 1993 Square D Company All Rights Reserved

Mechanism Lubrication Electrical Inspect the entire circuit breaker and operating mechanism for loose hardware and worn or broken parts. Check all wiring for loose connections and damaged insulation. Inspect all bearings and contact surfaces for damage or excessive wear. All ball and roller bearings used in these circuit breakers are sealed; they do not require lubrication. The lubrication chart in table 1 gives the location of each lubrication point and the method of lubrication required. Lubricate after 3,000 operations or three years, whichever occurs first. Severe operating conditions may warrant different lubrication intervals and procedures. Variations should be based on the experience of the operating company. Ensure that all electrical connections are tight and clean.! WARNING HAZARD OF BODILY INJURY OR EQUIPMENT DAMAGE. Work which requires disassembly of the mechanism or pole assembly must be performed by qualified electrical workers who have access to appropriate adjustment instructions. See section 10 of this manual for these adjustment instructions. When not following these instructions, disassembly and reassembly of this circuit breaker can cause improper operation, resulting in damage to the circuit breaker and injury to the operator. If you have questions, contact the Square D Company, Smyrna service department, at (615) 459-5026. Failure to observe this precaution can result in personal injury or equipment damage! Table 1 Lubrication Chart Lubrication Point Gear teeth Contact surfaces on guide cams and trip latch Motor eccentric and eccentric roller Method of Lubrication During Maintenance Period Wipe clean and apply lubricant.* Wipe clean and apply lubricant.* Wipe clean and apply lubricant to the slot in the ratchet arm.* Silver-plated primary disconnect Wipe clean and apply an extreme contacts and grounding contacts pressure grease, such as Mobilux EP 1, Square D part number 1615-100790. * Use Mobilgrease 28, Square D part number 1615-100950, or equivalent. 1993 Square D Company All Rights Reserved 21

SECTION 10 REPLACEMENT PARTS Minimum Requirements Maintain sufficient replacement parts in stock to ensure prompt replacement of worn, broken, or damaged parts. Tables 2 and 3 list factory-recommended replacement parts. Each replacement part is shipped with complete assembly and adjustment instructions. Because of wide variation in operating uses and environments, the recommended parts are presented only as a minimum requirement. Each operating company should develop its own parts stock, based on operating experience, to maintain proper circuit breaker condition. Ordering Instructions When ordering replacement parts: Always specify the complete rating information and circuit breaker serial number. Specify part number, description of part, and the catalog from which this information is taken. Table 2 Replacement Parts Rated Description Part No. Voltage Charging Motor 44068-505-50 48 Vdc 44068-505-51 125 Vdc 44068-505-52 250 Vdc 44068-505-51 120 Vac 44068-505-52 240 Vac Motor Relay 44068-506-50 48 Vdc 44068-506-51 125 Vdc 44068-506-52 250 Vdc 44068-506-53 120 Vac 44068-506-54 240 Vac Anti-Pump Relay 44068-507-50 48 Vdc 44068-507-51 125 Vdc 44068-507-52 250 Vdc 44068-507-53 120 Vac 44068-507-54 240 Vac Closing Solenoid 44068-508-50 48 Vdc 44068-508-51 125 Vdc 44068-508-52 250 Vdc 44068-508-53 120 Vac 44068-508-54 240 Vac Trip Solenoid 44068-509-50 24 Vdc 44068-509-51 48 Vdc 44068-509-52 125 Vdc 44068-509-53 250 Vdc 44068-509-54 120 Vac 44068-509-55 240 Vac Main Contact (1200A) 44068-516-50 Main Contact (2000A) 44068-516-51 Ground Contact 44068-510-50 Latch Check Switch 44068-511-50 Control Power Plug Ass y 44068-503-50 Auxiliary Switch 44068-512-50 Closing Spring Limit Switch 44068-513-50 22 1993 Square D Company All Rights Reserved Table 3 Pole Assembly Replacement Parts Circuit Breaker Part No. 4.76 kv 29 ka 1200 A 44068-514-50 4.76 kv 29 ka 2000A 44068-515-50 4.76 kv 41 ka 1200A 44068-514-51 4.76 kv 41 ka 2000A 44068-515-51 8.25 kv 33 ka 1200A 44068-514-52 8.25 kv 33 ka 2000A 44068-515-52 15.0 kv 18 ka 1200A 44068-514-53 15.0 kv 18 ka 2000A 44068-515-53 15.0 kv 28 ka 1200A 44068-514-54 15.0 kv 28 ka 2000A 44068-515-54 15.0 kv 37 ka 1200A 44068-514-55 15.0 kv 37 ka 2000A 44068-515-55

SECTION 11 INSTALLATION AND MAINTENANCE LOG 1993 Square D Company All Rights Reserved 23

Square D Company 330 Weakley Road Smyrna, TN 37167 U.S.A. Order No. 6055IM9207 FP 5M 10/93 Printed in U.S.A. Replaces bulletin dated 4/90 Part No. 6055-11