FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS

Similar documents
CHILLER MODEL NO. YS SOLID STATE STARTER, MODEL NO. SSS, L B OPTIONAL FACTORY INSTALLED DISCONNECT SWITCH AMPS OR

PRODUCT DRAWING WIRING DIAGRAM FIELD CONNECTIONS MILLENNIUM MODEL YT CHILLERS (STYLE J) WITH ELECTRO-MECHANICAL STARTER JOB DATA:

FIELD CONNECTIONS MODEL YK CHILLERS (STYLE F AND G) WITH VARIABLE SPEED DRIVE

WIRING DIAGRAM MODEL YK (STYLE G) LIQUID CHILLERS OPTIVIEW CONTROL CENTER WITH ELECTRO-MECHANICAL STARTER

RENEWAL PARTS Supersedes: RP4 (1012) Form RP4 (813)

WIRING DIAGRAMS MODEL YK (STYLE G) LIQUID CHILLERS OPTIVIEW CONTROL CENTER WITH SSS, LV VSD W/ MODBUS, & MV VSD

MODELS SSS 7L-B, 14L-B, 26L-B, 33L-B AND MODELS SSS 7LK-B, 14LK-B, 26LK-B, 33LK-B

WIRING DIAGRAM, MILLENNIUM TM MODEL YT (STYLE J) LIQUID CHILLERS GRAPHIC CONTROL CENTER WITH ELECTRO-MECHANICAL STARTER PRODUCT DRAWING JOB DATA:

MODEL CYK CHILLER WITH LIQUID COOLED SOLID STATE STARTER, OR REMOTE STARTER

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT

FOR OT/HT MODEL CHILLERS STYLE B AND C CONTROL CENTERS , AND

MODELS YCRL0064, 0074, 0084, 0096, 0118, 0126, 0156, 0177, 0198, 0200, 0230, 0260, 0300, 0345, 0385, 0445, 0530 and YCRL0610 STYLE "A"

QTC2015T, 020T, 025T, 030T, 035T, 040T, and 045T

ELEMENTARY DIAGRAM CONNECTION DIAGRAM CONTROL PANEL AND CONNECTION DIAGRAM SYSTEM WIRING FOR MODELS:

WATER COOLED AIR CONDITIONING UNITS MODEL CVWSEK-060 WATER SIDE ECONOMIZER FOR CSV060B VERTICAL R-410A STYLE B R-410A

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

TON KW 60HZ

High Frequency SineWave Guardian TM

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

Water to Water Geothermal Heat Pump 3-Phase Models Both 208 & 480

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

PF Guard Power Factor Capacitor Bank Installation, Operation, and Maintenance Manual

R-410A 50Hz & 60Hz. Renewal parts /3/ MODELS ONLY. Issue Date: September 07, 2011

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation

R-410A KW 50HZ

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

YCAL0014E_ - YCAL0124E_ R-22 & HFC-407C STYLE C (60 Hz)

30GX AIR-COOLED LIQUID CHILLER

30GX AIR-COOLED LIQUID CHILLER

Supersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO:

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL REV MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 480 Volts, 60HZ PART NO. INSTR 024 REL REV MTE Corporation

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS FEATURES DESCRIPTION. H5CE090 & H3CE AND 10 NOMINAL TONS (World 50HZ)

MODELS YCAL0019, 0022, 0028, 0033, 0043, 0046, 0052, 0056, AND 0066

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

8300 Series Installation Guidelines

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

YCAS AIR-COOLED LIQUID CHILLERS YCAS0373 THROUGH YCAS0653 STYLE G (R22) (50 Hz)

Electrical Design/Build Guide

MODELS YCAV0157, 0177, 0187, 0197, 0207, 0227, 0247 AND YCAV0267 STYLE "A"

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

5300 Series Installation Guidelines

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

A. Submit manufacturer's literature and technical data before starting work.

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

Quick Connection Panel (QCP) Installation Guide

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

09DK054, 064, 074, 084, 094 AIR-COOLED CONDENSERS

RU SERIES UPGRADE TempAssure Compatible

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

Wiring Diagrams DIAGRAM INDEX

CONTROLS AND INSTRUMENTATION MODEL YST STEAM-TURBINE DRIVE CENTRIFUGAL LIQUID CHILLER

COMMERCIAL QUICK REFERENCE

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Owner's/Installation Manual

Trane Liqui-Flo Addendum. Instruction Manual D2-3415

Quick Start Guide TS 910 & TS 920

MATRIX FILTER USER MANUAL. SERIES D 400 Volts, 50HZ PART NO. INSTR 025 REL REV MTE Corporation


Precision Power Center INSTALLATION, OPERATION, & MAINTENANCE MANUAL

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

RCS1000 Data Sheet. RCS1000 Series Controllable Circuit Breaker Panel

Electric. PN April Series Electric Oven

Air-Cooled Scroll Compressor Chillers Models AGZ 010A to AGZ 034A Models AGZ 026B to AGZ 130B. Revised Electrical Data Tables.

INSTRUCTIONS FOR THE RELIANCE Fast/Tran TM ARL0909 & ARL0909R

ECET Circuit Design Motor Loads. Branch Circuits. Article 210

UARDIAN TECHNICAL GUIDE MODELS: GCGD18 THRU 60

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

Generator Set Applications FT-10 Network Control Communications Module (CCM-G) Kit

Quik-Spec Coordination Panelboard Specifications

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

Model CPV120 Waterside Economizer Kit WATERSIDE ECONOMIZER KIT FOR MODEL CPV 120 WATER-COOLED AIR CONDITIONERS INSTALLATION INSTRUCTIONS

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:

SUPPLEMENT MANUAL IM250R03. AQUAVAR CPC SUPPLEMENT A - Variable Speed Drive SUPPLEMENT TO THE INSTALLATION AND OPERATION MANUAL (IM167)

START-UP CHECKLIST. Date: Job Name: Customer Name: Address: City: State: Zip: Model Number: Serial Number: Qualified Start-up Technician:

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

OTEC Transfer switch open transition

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

Horizontal Circuit Switchers

Technical Manual. DLM Module. This manual should remain with the unit.

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H4CE090 & H2CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS

SECTION DC POWER SUPPLY/BATTERY CHARGER

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

Section 6 Electric Metering: Residential

10 Commercial, Industrial, Agricultural Services

WATER-COOLED SELF-CONTAINED UNITS MODEL CVWSEK-060BK/DP WATERSIDE ECONOMIZER FOR CSV060B LEFT-HAND VERTICAL R-410A STYLE B

GP7RD Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Air Conditioner, Single Phase WARRANTY

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

331-SV. User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER. Ashland, OH

Transcription:

Supersedes: 160.75-PW2 (508) Form 160.75-PW2 (311) FIELD CONNECTIONS FOR YK CHILLER (STYLE G) OPTIVIEW CONTROL CENTER WITH REMOTE MEDIUM VOLTAGE SSS WIRING DIAGRAM CONTRACTOR ORDER NO. YORK CONTRACT NO. YORK ORDER NO. PURCHASER JOB NAME LOCATION ENGINEER REFERENCE DATE APPROVAL DATE CONSTRUCTION DATE JOB DATA: CHILLER MODEL NO. YK NO. OF UNITS COMPRESSOR MOTOR VOLTS, 3-PHASE, Hz OIL PUMP MOTOR VOLTS, 3-PHASE, Hz, FLA MV SSS R - OPTIONAL FACTORY INSTALLED OIL PUMP POWER SUPPLY VOLTS, 3 PHASE Hz, AMPS Issue Date: March 30, 2011

IMPORTANT! READ BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES This equipment is a relatively complicated apparatus. During installation, operation maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in which it is situated, as well as severe personal injury or death to themselves and people at the site. This document is intended for use by owner-authorized operating/service personnel. It is expected that this individual posseses independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood this document and any referenced materials. This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question. External wiring, unless specified as an optional connection in the manufacturer s product line, is not to be connected inside the OptiView cabinet. Devices such as relays, switches, transducers and controls and any external wiring must not be installed inside the micro panel. All wiring must be in accordance with Johnson Controls published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this warning will void the manufacturer s warranty and cause serious damage to property or personal injury. CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls policy for continuous product improvement, the information contained in this document is subject to change without notice. While Johnson Controls makes no commitment to update or provide current information automatically to the manual owner, that information, if applicable, can be obtained by contacting the nearest Johnson Controls Service office. Operating/service personnel maintains the responsibility of the applicability of these documents to the competitive equipment the kit is installed on. If there is any question regarding the applicability of these documents, the technician should verify whether the equipment has been modified and if current literature is available with the owner of the equipment prior to performing any work on the chiller. 2 JOHNSON CONTROLS

NOTES 1. All field wiring shall be in accordance with the current edition of the National Electrical Code (N.E.C.) as well as all other applicable codes and specifications. 2. Medium Voltage Solid State Starter and Compressor motor frame shall be grounded in accordance with 2005 N.E.C. (Paragraph 250-118) for equipment grounding. When a separate grounding conductor is required, it must be a copper conductor only and sized per the 2005 N.E.C. (Table 250-122). Per 2005 N.E.C. [paragraph 250-120 (f)(1)], where multiple (parallel) conduits are used each must contain a grounding conductor. 3. Wiring, electrical conduit, junction boxes, fused disconnect switches (FDS), or circuit breakers, starters (M), push-button stations (PB), manualoff-automatic switch (S), flow switch (FLS), control relays, and control power transformer (CPT) furnished by others unless otherwise specified. 4. Items marked * furnished by Johnson Controls. 5. Items marked ** available from Johnson Controls at additional cost. 6. Control Center power supply 115V-50/60Hz, 2.0 KVA capacity for control center only should be supplied by a control power transformer (1T) mounted within the Medium Voltage Solid State Starter as standard. 7. Motor power conduit connection location, motor full load amperes (FLA) and inrush amperes per Product Drawing Form 160.54-PA1. Multiple conduits shall contain an equal number of wires from each phase in each conduit to prevent overheating per 2005 N.E.C. (Paragraph 300-20 (a)). Use copper conductors only; DO NOT USE aluminum conductors. Flexible fınal connections should be used to provide vibration isolation. 8. Power wiring and motor wiring landing pad and ground busbar connections are shown in the Service manual for the Medium Voltage Solid State Starter (See Form 160.00-M5). Power wiring and ground lugs are field supplied. 9. Condenser water pump motor starter (3M) holding coil to be furnished for 115V-50/60 Hz. The power requirements for the water pump starter (3M) must be a max. of 1 Amp holding and 10 Amps inrush. If power requirements exceed this value, furnish coil for line voltage, and control relay with 115V coil. 10. Wire #14 AWG copper for one way distance of less than 175 feet. Wire #12 AWG copper for one way distance of more than 175 feet, but less than 300 feet. 11. Wiring diagram for YORK OptiView Control Center Form 160.73-PW5. Field wiring modifications per Form 160.73-PW4. Wiring diagram for YORK Medium Voltage Solid State Starter Form 160.00-PW5. 12. The following interconnecting wires are field supplied when a YORK Medium Voltage Solid State Starter is used. (See Form 160.73-PW5.) A. 120 VAC Power - control panle wire; single condictor, starnded, 10-12 awg, 600v, 75-90 C, THWN or UL style 1028/1015, UL listed and CSA approved, insulation shall be moisture resistant theroplastic (PVC). B. System fault/run Command - control panel wire; single conductor, stranded, 14-18 awg, 600v, 75-90 C, THWN or UL style 1015, UL listed and CSA approved, insulation shall be moisture resistant thermoplastic (PVC). C. Drive to Oil Pump motor starter (optional) - wire; 3 conductor + grounded cable, stranded 14 awg, 600v 75-90 C, THNN/THWN in conduit UL listed and CSA approved. Buiding wire per current N.E.C.. D. Mod-Bus Comms - Drive to Control Panel; 025 28701 003 wire; 3 conductor w/ foil shield and drain wire 20 awg 300v, 80 C, UL style 2464, UL listed and CSA approved; Alpha 5463 Belden 9364, Quabbin 022 or equivalent range 18-22 awg. JOHNSON CONTROLS 3

13. For medium voltage compressor motors, the oil pump motor voltage shall be selected by the customer (see table below) at one of the available voltages (200-600 VAC) and wired to a separate supply (FDS1). A 3-pole, 30A fused disconnect or a 3-pole circuit breaker (FDS1) shall be field supplied. Fusing for FDS1 per table below. The Medium Voltage Solid State Starter can optionally provide power to the oil pump motor/drive panel at either 440/460/480 or 380/400/415 VAC. Oil pump motor for compressor is 2HP. Full load amperes for oil pump drive panel (furnished by Johnson Controls) and 2.0 KVA control power transformer (furnished by Johnson Controls) per table below. 14. The YORK Medium Voltage Solid State starters (2300 to 4160 volts) have high interrupting capacity current limiting fuses plus an integral non-load disconnect function and thus do not require the use of FDS2, provided the Medium Voltage Solid State Starter is placed in sight of the chiller. If the FDS2 is required minimum ampere rating shall be 1.15X (compressor motor amps and control power amps and oil pump amps). See note 13 for additional information for oil pump and control transformer amps. 15. The YORK Medium Voltage Solid State Starter input power wiring ampacity shall be calculated as follows. Model YK minimum circuit ampacity: Ampacity = 1.25X (Compressor Motor FLA) + Oil Pump Drive Panel Amps + Control Power Transformer Amps, where 125% factor is per 2005 N.E.C. Para. 440-33); FLA is per Note 7; Oil Pump Panel and Control Transformer Amps per Note 13. Oil Pump Panel and Control Transformer Amps value used, to be adjusted by ratio of (120/(MV VSD nameplate voltage). Oil pump amps to be included if MV SSS optional oil pump power supply is included. 16. Medium voltage (2300 to 4160 volts) motors have three leads. Motor leads are furnished with a crimp type connector having a clearance hole for a 3/8 bolt. Motor terminal lugs are not supplied. 17. Starter to motor power wiring ampacity shall be calculated as follows: Minimum circuit ampacity per conductor (one of three): Ampacity = 1.25 x compressor motor amps. Where 125% factor is per 2005 NEC (para 440-33); Compressor motor amps (See Note 7) are FLA. 18. The Condenser Flow Switch is optional. If not present, a jumper must be installed between TB4-11 and TB4-1. 19. The interrupting capacity of the YORK Medium Voltage Solid State Starter is 50 KA RMS symmetrical amperes at the nameplate voltage. The YORK MV SSS is suitable for use on a circuit capable of delivering not more than 50KA RMS symmetrical amperes at the nameplate voltage. 20. Three phase oil pump motor must be properly phased. L1, L2 and L3 corresponding to phase sequence A, B and C. 3-PHASE VOLTAGE HZ OIL PUMP DRIVE PANEL (AMPS) 2HP CONTROL POWER (1T) TRANSFORMER (AMPS) FDS1 OIL PUMP DRIVE PANEL FUSE 200/208 60 7.2 10.0 12.0 220/230/240 60 7.2 9.1 12.0 440/460/480 60 3.6 4.5 6.0 550/575/600 60 2.9 3.6 5.0 380/400/415 50/60 4.3 5.3 7.0 380/416 60 4.3 5.3 7.0 346 60 6.6 5.8 10.0 4 JOHNSON CONTROLS

21. If the optional Oil Pump Power supply is NOT included in the MV SSS then a separate disconnecting means must be supplied for the oil pump circuit as follows: If the fused disconnect switch (FDS1) is not located in sight (2005 N.E.C. Para. 440-14) of the Chiller, a non-fused disconnect switch (not shown) shall be located in sight of the Chiller. The ampere rating shall be determined as Amp Rating = 1.15X (Oil Pump Drive Panel Amps) Where 115% factor is per 2005 N.E.C. (Para. 44012b (2)); oil pump drive panel and control power transformer Amps per Note 13. An optional factory mounted and wired oil pump power supply in sight of the chiller is available (See Note 13). 22. Control circuit wiring for 3M condenser water pump motor starter is shown for cooling only application. For units with Flash Miniature Card Software Version C.MLM.01.00 through C.MLM.01.03, the condenser water pump should be wired to terminal 164 of TB2 instead of terminal 151, and the wire from terminal 22 of TB5 to terminal 150 of TB2 shall not be installed. For software version C.MLM.01.04 and higher, the condenser water pump connection should be as shown in the diagram. 23. The main power transformer should be adequately sized such that the transformer voltage drop does not exceed 10% during unit start-up. The supply voltage, at starter input terminals, during start-up must be maintained above the minimum value specified in the table below. Note that while the YORK chiller will perform acceptably during startup with this amount of voltage drop, the performance of other equipment connected to the supply transformer could be adversely affected. 24. Automatic control of the chilled water pump by the OptiView Control Center is shown. Chilled water pump motor starter (5M) holding coil to be furnished for 115V-50/60 Hz. The power requirements for the water pump starter (5M) must be a maximum of 1 Amp holding and 8 Amps inrush. If power requirements exceed this value, furnish coil for line voltage, and control relay with 115V coil. The pumps operate during oil pump prerun, during compressor operation and during cycling shutdown. 25. Each 115VAC field-connected inductive load, i.e. relay coil, motor starter coil, etc. shall have a transient suppressor wired (by others) in parallel with its coil, physically located at the coil. Spare transient suppressors are factory supplied in a bag attached to the keypad cable clamp in the Control Center. 30. The OptiView Control Center has a single output for condenser pump control. When using this control output for heat recovery an additional control means is needed to select operation of tower water condenser pump or heating water condenser pump. The diagram depicts use of a 3 position selector switch which may be added near the chiller for such purposes. Alternatively, a BAS control scheme may be used to control operation of the two condenser water pumps. 31. For heat recovery applications, the heating condenser is provided with a thermal type flow sensor. If an optional mechanical type flow switch is used instead, it is connected between terminal [1] on TB6 (lower right area of the panel) and terminal [1] of TB20 on the LTC I/O board in the upper right side of the control cabinet. 3-PHASE VOLTAGE Hz MINIMUM VOLTAGE AT DRIVE INPUT TERMINALS DURING START-UP 4160 60 3536 2300 60 1955 3300 50 2805 JOHNSON CONTROLS 5

FIELD CONNECTIONS SEE NOTE 25 CONDENSER WATER FLOW SWITCH NOTE 18 SEE NOTE 24 SEE NOTE 10 SEE NOTE 25 # 14 AWG. (NOTE 10) CHILLED WATER PUMP MOTOR WIRE # 14 AWG. COPPER NOTE 13 AND 16 CONDENSER WATER PUMP MOTOR CHILLED WATER FLOW SWITCH** NOTE 5 CHILLER CONTROL CENTER FIELD WIRING TERMINAL BLOCKS (TB4, TB2 AND TB6)* SEE NOTE 4 TB4 TB2 WIRE # 14 AWG. COPPER NOTE 13 WIRE # 14 AWG. COPPER NOTE 10 OPTIVIEW CONTROL CENTER GND. SCREWS* NOTES 2 AND 4 Figure 1 - FIELD CONNECTIONS LD12972a 6 JOHNSON CONTROLS

FIELD CONNECTIONS (CONT'D) FDS1 NOTES 13, 14, 20, AND 21 NOTES 8 AND 15 2M** NOTES 5, 8, AND 13 NOTES 2 AND 8 NOTES 5, 13, 20, AND 21 NOTES 5, 13, 20, AND 21 NOTES 8 AND 17 CHILLER NOTES 12 AND 16 GND NOTES 1 AND 18 NOTES 4, 13 AND 20 GROUND NOTES 2 AND 8 FIGURE 1 - FIELD CONNECTIONS (CONT'D) LD12973a JOHNSON CONTROLS 7

FIELD CONNECTIONS HEAT RECOVERY SUPPLEMENT TO CHILLED WATER PUMP FDS6 6LL1 6LL2 6LL3 HEATING CONDENSER WATER FLOW SWITCH NOTE 31 6T1 6T2 6T3 HEATING WATER PUMP MOTOR WIRE # 14 AWG. COPPER NOTE 13 AND 16 TB20 1 LTC I/O BOARD CONDENSER TOWER WATER PUMP MOTOR COOLING TOWER FAN MOTOR CHILLER CONTROL CENTER FIELD WIRING TERMINAL BLOCKS (TB20, TB2 AND TB6) OPTIVIEW CONTROL CENTER HEATING PUMP BOTH PUMP TOWER PUMP SELECTOR SWITCH OR CONTROL BOX NOTE 30 Figure 2 - FIELD CONNECTIONS HEAT RECOVERY SUPPLEMENT NOTE: When a YK is ordered with a double bundle heat recovery option, an extra pump is needed for the hot water circuit. LD15217 8 JOHNSON CONTROLS

NOTES JOHNSON CONTROLS 9

NOTES 10 JOHNSON CONTROLS

NOTES JOHNSON CONTROLS 11

P.O. Box 1592, York, Pennsylvania USA 17405-1592 Copyright by Johnson Controls 2011 Form 160.75-PW2 (311) Issue Date: March 30, 2011 Supersedes: 160.75-PW2 (508) Tele. 800-861-1001 www.york.com Subject to change without notice. Printed in USA ALL RIGHTS RESERVED