Analysis of Electric Field and Magnetic Field from Overhead Subtransmission Lines Affecting Occupational Health and Safety in MEA s Power System

Similar documents
METRO NORTH TRANSMISSION STUDY ELECTRIC AND MAGNETIC FIELD PROFILES (VILLAGE OF ANMORE)

Influence of Electric Field Distribution along the Line Post and Pin Post Insulator due to Lightning Strike

Feasibility Survey of Fuel Briquette Demands in Roasting Food Restaurants in Chiang Mai Province, Thailand

Available online at ScienceDirect. Energy Procedia 100 (2016 )

A. INTRODUCTION B. PRINCIPAL CONCLUSIONS AND IMPACTS C. BACKGROUND

Appendix M-2 EMF from Underground and Overhead Transmission Lines on Block Island

A. INTRODUCTION B. PRINCIPAL CONCLUSIONS AND IMPACTS C. BACKGROUND

Impact Analysis of Fast Charging to Voltage Profile in PEA Distribution System by Monte Carlo Simulation

STEEL CASING OVERHEATING ANALYSIS OF OPERATING POWER PIPE-TYPE CABLES

Mathematical Modeling and Simulation of Switched Reluctance Motor

Electromagnetic Field Analysis for Permanent Magnet Retarder by Finite Element Method

New York Science Journal 2017;10(3)

Original. M. Pang-Ngam 1, N. Soponpongpipat 1. Keywords: Optimum pipe diameter, Total cost, Engineering economic

Electric and Magnetic Field (EMF) Analysis for the Mystic-to-Woburn x and y, 115-kV Transmission Lines

/12/$ IEEE. M. Bashir M.Sc student, Student Member, IEEE Ferdowsi University of Mashhad Mashhad, Iran

Mystic to Woburn Line Project. Town of Winchester Board of Selectmen Lincoln School Auditorium February 11, 2016

Effect of Permanent Magnet Rotor Design on PMSM Properties

Magnetic Field Design for Low EMF and High Efficiency Wireless Power Transfer System in On-Line Electric Vehicles

MAGNETIC EFFECTS OF ELECTRIC CURRENT

Grounding systems for power supply facilities

National Conference on Latest Trends in Design & Testing of Transmission Line Components

Finite Element Electromagnetic and Mechanical Analysis of Micropump

AE105 PRINCIPLES OF ELECTRICAL ENGINEERING JUNE 2014

POWER DISTRIBUTION SYSTEM ANALYSIS OF URBAN ELECTRIFIED RAILWAYS

Simulation and Analysis of Vehicle Suspension System for Different Road Profile

STIFFNESS CHARACTERISTICS OF MAIN BEARINGS FOUNDATION OF MARINE ENGINE

Improvement the Possibilities of Capacitive Energy Storage in Metro Railcar by Simulation

EXPERIMENT 13 QUALITATIVE STUDY OF INDUCED EMF

TABLE OF CONTENTS 1. FEATURES CAUTION OF ELECTROMAGNETIC FIELD EXPOSURE SPECIFICATIONS...2

THE INFLUENCE OF THE MICROGROOVES ON THE HYDRODYNAMIC PRESSURE DISTRIBUTION AND LOAD CARRYING CAPACITY OF THE CONICAL SLIDE BEARING

STABILIZATION OF ISLANDING PEA MICRO GRID BY PEVS CHARGING CONTROL

LEVER OPTIMIZATION FOR TORQUE STANDARD MACHINES

Ambient Magnetic Field Compensation for the ARIEL (Advanced Rare IsotopE Laboratory) Electron Beamline. Gabriela Arias April 2014, TRIUMF

Research on the Parallelism Detection Between Nozzle and Floating Plate

International Conference on Mechanics, Materials and Structural Engineering (ICMMSE 2016)

Analyses of the grid resistance measurement of an operating transformer station

Circumstances affecting the protection against electrode potential rise (EPR)

Influence of Cylinder Bore Volume on Pressure Pulsations in a Hermetic Reciprocating Compressor

Investigation & Analysis of Three Phase Induction Motor Using Finite Element Method for Power Quality Improvement

A Smart Mobile PV-Wind Hybrid System Prototype for isolated electrification. Abstract

Inductive Power Supply (IPS ) for the Transrapid

JCP&L Verbatim Response to Middletown Township s Questions

PACIFICORP. Lassen Substation Electric and Magnetic Field Assessment. Revision B. October 16, 2015 PROJECT NUMBER:

EXPERIMENT CALIBRATION OF 1PHASE ENERGY METER

Application of Simulation-X R based Simulation Technique to Notch Shape Optimization for a Variable Swash Plate Type Piston Pump

A Prototype Measuring Set for Capturing Dissipated Force on Soft Armor

Reactive Power Compensation using 12 MVA Capacitor Bank in 132/33 KV Distribution Substation

DESIGN OF A NEW ELECTROMAGNETIC VALVE WITH A HYBRID PM/EM ACTUATOR IN SI ENGINES

Recent Trades in Distribution System

LABORATORY 2 MEASUREMENTS IN RESISTIVE NETWORKS AND CIRCUIT LAWS

Parameter optimisation design for a six-dof heavy duty vehicle seat suspension

Electromagnetic Coordination Study Objectives for Railroad and Electric Utility Shared Corridors

Design and Optimization of HTV Fuel Tank Assembly by Finite Element Analysis

ADVANCES in NATURAL and APPLIED SCIENCES

GPP PGS2 PARKING GUIDANCE SYSTEM

Modal analysis of Truck Chassis Frame IJSER

ELECTROMAGNETS ARRANGEMENT FOR ELECTROMAGNETIC WINDSHIELD WIPERS - PROPOSAL AND ANALYSIS

Magnet Optimized for Angular Position Sensor Application

Department of Electrical and Computer Engineering

TESTING OF AUTOMOBILE VW GOLF OPERATING ON THREE DIFFERENT FUELS

The Application of Simulink for Vibration Simulation of Suspension Dual-mass System

Volume II, Issue VII, July 2013 IJLTEMAS ISSN

EMF Readings in Tollgate Crossing community Robert L. Vaessen - 22 Dec 2016

Performance of DC Motor Supplied From Single Phase AC-DC Rectifier

ABSTRACT INTRODUCTION

A Comparative Analysis of Thyristor Based swiftness Organize Techniques of DC Motor

ADVANCES in NATURAL and APPLIED SCIENCES

Suburban bus route design

Noise Reduction in a Reciprocating Compressor by Optimizing the Suction Muffler

Design and dimensions calculation of Inductive Rheostat as a Control Element of Synchronization Systems


Development of a High Efficiency Induction Motor and the Estimation of Energy Conservation Effect

Optimization of Design Based on Tip Radius and Tooth Width to Minimize the Stresses on the Spur Gear with FE Analysis.

DEVELOPMENT AND EVALUATION OF HYDRAULIC SIMULATION MODEL FOR WHEEL LOADER

Final Written Examination.

A STUDY OF THE CENTRIFUGAL COMPRESSOR DISCHARGE PIPELINE CONSTRAINED OSCILLATION. KIRILL SOLODYANKIN*, JIŘÍ BĚHAL ČKD KOMPRESORY, a.s.

ANALYSIS OF GEAR QUALITY CRITERIA AND PERFORMANCE OF CURVED FACE WIDTH SPUR GEARS

Application of DSS to Evaluate Performance of Work Equipment of Wheel Loader with Parallel Linkage

Prototyping of Axial Flux Permanent Magnet Motors

Modal Analysis of Automobile Brake Drum Based on ANSYS Workbench Dan Yang1, 2,Zhen Yu1, 2, Leilei Zhang1, a * and Wentao Cheng2

Modeling of Lead-Acid Battery Bank in the Energy Storage Systems

34.5 Electric Current: Ohm s Law OHM, OHM ON THE RANGE. Purpose. Required Equipment and Supplies. Discussion. Procedure

PROBLEM IN COMMISSIONING PROCESS OF 125VDC STATIONARY BATTERY IN LAM-LUK-KA SUBSTATION

DESIGN AND ANALYSIS OF LEAF SPRING FOR SOLAR VEHICLE

Efficiency Increment on 0.35 mm and 0.50 mm Thicknesses of Non-oriented Steel Sheets for 0.5 Hp Induction Motor

694 Electric Machines

Dynamic Modelling of Hybrid System for Efficient Power Transfer under Different Condition

Quality Improvement in Design Process of Shell & Tube Type Heat Exchanger by Computer Integrated 3D Modeling

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 2.114

STATE OF MINNESOTA ENVIRONMENTAL QUALITY BOARD MEQB DOCKET NO. MP-HVTL-EA-1-99

Universal computer aided design for electrical machines

Engineering Considerations. Glenn Stapleton - Senior Electrical Design Engineer Lines

THE THREE VOLTAGE LEVEL DISTRIBUTION USING THE 1000 V LOW VOLTAGE SYSTEM

Ansys-CFX Analysis on a Hatch-Back Car with Wheels and without Wheels

Pre-lab Questions: Please review chapters 19 and 20 of your textbook

Evaluation of the Fatigue Life of Aluminum Bogie Structures for the Urban Maglev

Reliable, economical and safe siemens.com/rail-electrification

Sharjah Indian School Sharjah Boys Wing

POWER GENERATION BY MULTIPLE ROAD HUMPS

DVANCED ENERGY SOLUTIONS presents

Transcription:

Analysis of Electric Field and Magnetic Field from Overhead Subtransmission Lines Affecting Occupational Health and Safety in MEA s Power System Att Phayomhom, Tirapong Kasirawat, Surasak Phontusa, Jarin Halapee, Boonserm Ainsuk, Kiatiyuth Kveeyarn, Nattachote Rugthaicharoencheep and Arwut Puttarach Abstract Over the past decades up until the presence, the overhead subtransmission and distribution electricity networks within the cities are mainly overhead lines, owing to the lower construction costs in comparison with the high construction costs of the undergrounding of electricity lines. Also, due to the substantial urban development in the present time, a lot of towns, streets, factories, and etc. have increased significantly. This urbanization has led to the construction of buildings being built near power lines, which are the source that produces both electric and magnetic fields (EMFs). Therefore, this research aims at studying the values of EMFs, in which level that can have the adverse effects on health and analysing the limits on the exposure of the public to EMFs, which are produced by the different arrangement of conductors of the 69 kv and 115 kv high voltage subtransmission lines. Moreover, the computer-supported calculation program as Microsoft Excel is an essential tool to help analyse the values of EMFs and present the results of the analysis through graphics with the Matlab program. Matlab is used as the graphics supporting to plot values and intensity of EMFs in the form of surface and contour graphs to help have an easy understanding and to help in interpretation of EMFs around the conductors. Secondly, examining whether the derived values of EMFs gotten from each specific arrangement of conductors are acceptable in comparison with the maximum 5 Hz EMFs recognised by Metropolitan Electricity Authority (MEA) and International Commission on Non-Ionizing Radiation Protection (ICNIRP). Finally, studying the relation between a reduction of EMFs' intensity around the subtransmission lines and the negative effects on health produced by EMFs. The results of this research is to determine safety parameters or limits of EMFs and the safety clearance from the conductors. Keywords Electric field, magnetic field, occupational health and safety, 1. INTRODUCTION Metropolitan Electricity Authority (MEA) is an electric utility that is responsible for power distribution covering an area of 3,192 square kilometers in Bangkok, Nonthaburi, and Samutprakarn provinces of Thailand. MEA s power networks consist of transmission, subtransmission and distribution systems. The transmission line voltage is 23 kv, while 69 and 115 kv is subtransmission line voltages, and 12 and 24 kv are defined as distribution level as shown in Fig. 1. This work was financially supported by Metropolitan Electricity Authority (MEA), Thailand. Att Phayomhom (corresponding author) is with Power System Planning Department, Metropolitan Electricity Authority (MEA), 1192 Rama IV Rd., Klong Toey, Bangkok, 111, Thailand. Phone: +66-2- 348-5629; Fax: +66-2-348-5133; E-mail: att_powermea@hotmail.com, attp@mea.or.th. Kiatiyuth Kveeyarn is with the Department of Electrical Engineering, Faculty of Engineering, Kasetsart University, 5 Ngam Wong Wan Rd., Ladyao, Chatuchak, Bangkok, 19, Thailand. Phone: +66-2-797-999 ext.1516; E-mail: fengkyk@ku.ac.th. Nattachote Rugthaicharoencheep is with the Department of Electrical Engineering, Faculty of Rajamangala University of Technology Phra Nakhon, 1381, Pibulsongkram Rd., Bangsue, Bangkok, 18, Thailand. Phone: +66-2 - 913-2424 Ext. 15; E-mail: nattachote.r@rmutp.ac.th. Arwut Puttarach is with the Department of Electrical Engineering, Faculty of Rajamangala University of Technology Lanna, 128 Huay Kaew Road, Muang, Chiang Mai, Thailand, 53, Thailand. E-mail: a.puttarach@gmail.com. Approximately 9% of MEA s distribution networks are overhead lines. In case of subtransmission and distribution line are to be on the same route, due to the limitation of right of way, economy etc distribution lines have to be installed at the same poles as that of the subtransmission s, but of different height. As a result, distribution lines are placed at the lower part of the pole, subtransmission lines are placed at the upper part, and an OHGW hung as shield wire between pole to pole to protect lightning surge [1]. This research aim to study on the effect of EMFs whether which level affect to human being condition base on ICNIRP standard. 69/115 kv CUSTOMER TERMINAL STATION 4/23 V CUSTOMER 4/23 V 23,5 kv 69, 115 kv 12, 24 kv POWER PLANT Fig. 1. MEA Power s Distribution System. SUBSTATION 12,24 KV CUSTOMER 25

2. TWO DIMENSIONS ELECTRIC AND MAGNETIC FIELDS CALCULATION PRINCIPLE Generally, electric and magnetic fields can be calculated in several methods. It depends on the complication of the system. The uncomplicated system works with mathematic equation but another one can t be expressed in one equation. It s needed iterative calculation by computer such as finite element method or boundary element method. Not only complication of the system but also dimensions (2 dimensions or 3 dimensions) has been used to separate the calculation method. Since the high voltage overhead subtransmission system is uncomplicated, therefore; electric and magnetic fields can be calculated by 2 Dimensions Orthogonal Coordinates together with Superposition Theorem. This principle divided electric and magnetic fields into two elements which are real part (X axis) and imaginary part (Y axis). Then, sum up all of these elements in each axis. Finally, calculate the result of the electric field from both axes. Electric and magnetic fields calculation is presenting a characteristic of the electric field around the overhead subtransmission line in an open-air area. The result leads the system designer to aware whether what kind of effect might come after. By the way, the result given by using this calculation method has lower accuracy than measuring the field onsite [2-4]. Condition and Limitation of Two Dimensions Electric Field Calculation Two dimensions electric field around the overhead subtransmission line can be calculated within these condition and limitation as follows [2-4]: The calculated area must be an open-air area and electric field refraction is neglected. The refraction is caused by electric pole, building, tree and etc. due to the characteristic of materials (resistive or conductive materials). Must know the values of voltage magnitude and phase angle of all feeder lines including overhead ground wire compare with ground. Must know the conductors size, in case of bundle conductors; it needs more parameters which are quantities and spaces of the conductors. Must know height and distance of the conductors from reference point. Assuming that the conductor lengths are infinity and its arrangement is perfectly parallel between conductors and ground also. Sag and incline of the conductors are neglected. Condition and Limitation of Two Dimensions Magnetic Field Calculation Two dimensions magnetic field around the overhead subtransmission line can be calculated within these condition and limitation as follows [2-4]: Must know the values of voltage magnitude and phase angle of all conductors. Must know height and distance of the conductors from reference point. Current flows in the same direction. Assuming that the conductor lengths are infinity and its arrangement is perfectly parallel between conductors and ground also. Sag and incline of the conductors are neglected. 3. ELECTRIC AND MAGNETIC FIELDS SAFETY STANDARD MEA has installed electric power subtransmission system by controlling electric and magnetic fields within safety value in accordance with World Health Organization (WHO) standard. WHO has been working with International Commission on Non-Ionizing Radiation Protection (ICNIRP) for research and development. They have been researching on environmentally safety for people within electromagnetic field from low frequency system (5 Hz). The results, maximum electric and magnetic field are shown in Table 1 [5]. Table 1. Electric and Magnetic Fields Safety Criteria of MEA Location Period Electric Field Magnetic Field (kv/m) (mg) Establishment Working hours 1 kv/m 5, Public All day 5 kv/m 1. 4. CASE STUDY Electric field results of 69 kv subtransmission system Table 2. Electric and Magnetic Field Parameters for 69 kv Single Circuit 2-Bundled Conductor Phase Height of Conductor (m) Distance from Center of Electric Pole (m) Voltage (V) Current (A) Phase Angle Diameter of Conductor (m) R 16 1.4 39,837.17 1,6 2265 Y 14.17 1.4 39,837.17 1,6-12 2265 B 12.34 1.4 39,837.17 1,6-24 2265 OHGW 17.63.15 794 26

3. 2.5 7 m 1.5 1..5-6 -4-2 2 4 6 Fig. 4. Electric Field at 7 meters Height above Ground for 69 kv Subtransmission Line. 3.5 3. 21.5 m Fig.2. Subtransmission Line Arrangement for 69 kv Single Circuit 2-Bundled Conductor [6]. Then, calculate electric field as mentioned above. The results are shown in Figs.3-5. This level is maximum height beneath subtransmission line which electric field still within safety criteria for 69 kv This level is minimum height above subtransmission line which electric field is within safety criteria for 69 kv The results show that electric field at each height which show in Figs.3-5 are safe. 1.4 1.2 1..8.6.4.2-6 -4-2 2 4 6 Fig. 3. Electric Field at Each Height above Ground for 69 kv Subtransmission Line. m 2 m 3 m 4 m 5 m 2.5 1.5 1..5-6 -4-2 2 4 6 Fig. 5. Electric Field at 21.5 meters Height above Ground for 69 kv Subtransmission Line. 4 7 m away from street side 3 3 2 2 14. 1 1 8. 6. 4..5 1. 1.5 2.5 3. Fig. 6. Electric Field at Each Height above Ground Focusing on the for 69 kv. At 7 meters away, this distance is the nearest which electric field is within safety criteria of 69 kv 27

3. 3.5 m away from property side 2.5 1.5 Fig. 7. Electric Field at Each Height above Ground Focusing on the Property side for 69 kv. 1..5 4 3 3 2 2 14. 1 1 8. 6. 4. Table 3. Electric and Magnetic Field Parameters for Type 115 kv Single Circuit 2-Bundled Conductor Phase Height of Conductor (m) Distance from Center of Electric Pole (m) Voltage (V) Current (A) Phase Angle Diameter of Conductor (m) R 18.3 1.9 66,397.23 1,6 2265 Y 15.8 1.9 66,397.23 1,6-12 2265 B 13.3 1.9 66,397.23 1,6-24 2265 OHGW 21.8.15 794 At 3.5 meters away, this distance is the nearest which electric field is within safety criteria of 69 kv Considering on the street side in Fig.6 and the property side in Fig.7, the results show that at 17.5 meters high above ground which is the same level as phase R; electric field value is maximum but still within safety criteria. Fig.8. Electric Field Around 69 kv Conductor Carry Out by Matlab Software. The result of electric field around 69 kv can be shown in a graph format. It s plotted by Matlab software as shown in Fig.8. Electric field results of 115 kv subtransmission system Then, calculate electric field as mentioned above. The results are shown in Figs.1-14. This level is maximum height beneath subtransmission line which electric field still within safety criteria for 115 kv This level is minimum height above subtransmission line which electric field is within safety criteria for 115 kv Fig.9. Subtransmission Line Arrangement for 115 kv Single Circuit 2-Bundled Conductor [7]. At 5 meters away, this distance is the nearest which electric field is within safety criteria of 115 kv From Fig. 11-12 showing maximum value of electric field but the value is still within safety criteria. From Fig. 13-14, at 18.3 meters above ground of property side and street side. This level has the same height as R phase conductor. So, maximum value of electric field located at this point but still within safety criteria. 28

1.8 m 1.6 1.4 2 m 3 m 1.2 4 m 1. 5 m.8.6.4.2-6 -4-2 2 4 6 4 3 3 9 m away from street side 2 2 14. 1 1 8. 6. 4..5 1. 1.5 2.5 3. Fig.1. Electric Field at Each Height above Ground for 115 kv Subtransmission Line. Fig.13. Electric Field at Each Height above Ground Focusing on the for 115 kv. 3. 2.5 6.5 m At 9 meters away, this distance is the nearest which electric field is within safety criteria of 115 kv 1.5 1..5-6 -4-2 2 4 6 Fig.11. Electric Field at 6.5 meters Height above Ground for 115 kv Subtransmission Line. 3. 5 m away from property side 2.5 1.5 1..5 4 3 3 2 2 14. 1 1 8. 6. 4. 3. 2.5 25.5 m Fig.14. Electric Field at Each Height above Ground Focusing the for 115 kv. 1.5 1..5-6 -4-2 2 4 6 Fig.12. Electric Field at 25.5 meters Height above Ground for 115 kv Subtransmission Line. Fig. 15. Electric Field Around 115 kv Conductor Carry Out by Matlab Software. The result of electric field around 115 kv can be 29

shown in a graph format. It s plotted by Matlab software as shown in Fig.15. Magnetic field results of 69 kv subtransmission system Magnetic field results of subtransmission system type 69 kv single 2-bundled. The results are shown as follows: 3 25 15 1 5 m 2 m 3 m 4 m 5 m -5-4 -3-2 -1 1 2 3 4 5 Fig.16. Magnetic Field at Each height above Ground for 69 kv Subtransmission Line. Й 1 1 8 6 4-5 -4-3 -2-1 1 2 3 4 5 Fig.17. Magnetic Field at 1 meters Height above Ground for 69 kv Subtransmission Line. This level is maximum height beneath subtransmission line which magnetic field still within safety criteria for 69 kv At 4.5 meters away, this distance is the nearest which magnetic field is within safety criteria of 69 kv At 1.5 meters away, this distance is the nearest which magnetic field is within safety criteria of 69 kv Magnetic field results of 69 kv within condition and limitation above show that maximum value of magnetic field located at 12.5 meters above ground and 1.5 meters away from property side. This level is minimum height above subtransmission line which magnetic field is within safety criteria for 69 kv 1 m 7 6 5 4 3 1-5 -4-3 -2-1 1 2 3 4 5 Fig. 18. Magnetic Field at 17 meters Height above Ground for 69 kv Subtransmission Line. 4 3 3 2 2 14. 1 1 8. 6. 4. Fig.19. Magnetic Field at Each Height above Ground Focusing on the for 69 kv. 1 Fig. 2. Magnetic Field at Each Height above Ground Focusing the Property side for 69 kv. 17 m 4.5 m away from street side 4 6 8 1 1.5 m away from property side 1 8 6 4 Magnetic Field (mg 4 3 3 2 2 14. 1 1 8. 6. 4. 3

9 8 7 1.5 m 6 5 4 3 1 Fig. 21. Magnetic Field Around 69 kv Conductor Carry Out by Matlab Software. The result of magnetic field around 69 kv can be shown in a graph format. It s plotted by Matlab software as shown in Fig.21. Magnetic field results of 115 kv subtransmission system Magnetic field results of subtransmission system type 115 kv single 2-bundled. The results are shown as follows: 3 25 15 1 5-5 -4-3 -2-1 1 2 3 4 5 Fig.22. Magnetic Field at Each Height above Ground for 115 kv Subtransmission Line. This level is maximum height beneath subtransmission line which magnetic field still within safety criteria for 115 kv This level is minimum height above subtransmission line which magnetic field is within safety criteria for 115 kv At 5 meters away, this distance is the nearest which magnetic field is within safety criteria of 115 kv At 1.5 meters away, this distance is the nearest which magnetic field is within safety criteria of 115 kv m 2 m 3 m 4 m 5 m -5-4 -3-2 -1 1 2 3 4 5 Fig. 23. Magnetic Field at 1.5 meters Height above Ground for 115 kv Subtransmission Line. 6 5 4 3 1-5 -3-1 1 3 5 Fig. 24. Magnetic Field at 19.5 meters Height above Ground for 115 kv Subtransmission Line. 4 3 3 2 2 14. 1 1 8. 6. 4. 5 m away from street side Fig. 25. Magnetic Field at Each Height above Ground Focusing on the for 115 kv. 19.5 m 4 6 8 1 1 31

1 1.5 m away from property side 8 6 Fig. 26. Magnetic Field at Each Height above Ground Focusing on the Property side for 115 kv. Magnetic field results of 115 kv within condition and limitation above show that maximum value of magnetic field located at 15.5 meters above ground and 1.5 meters away from property side. 4 4 3 3 2 2 14. 1 1 8. 6. 4. Suksirithaworngule, ABB, Thailand, for teaching him the essential knowledge of power system. Sincere thanks would go to Metropolitan Electricity Authority (MEA) for the technical data used in this research. High appreciation is given to Power System Planning Department of MEA for research time and strong support of this work. REFERENCES [1] Phayomhom, A., Suwanasri, T. and Suwanasri, T., 214. Grounding Improvement for Multi-Voltage Overhead Line Installation in MEA's Power Distribution System. The 2th Conference of the Electric Power Supply Industry (CEPSI), The International Convention Center JEJU, Jeju, Kaorea, 26-3 October. [2] EPRI TR-114. Electric and Magnetic Field Management Reference Book. USA, 1999. [3] Halapee, J., 2 Subtransmission Line Electric Field Calculation in Two Diamensions, Research and Development Department, Metropolitan Electricity Authority (MEA), Bangkok [4] Halapee, J., 2 Subtransmission Line Magnetic Field Calculation in Two Diamensions, Research and Development Department, Bangkok, Metropolitan Electricity Authority (MEA). [5] Research and Development Department. Subtransmission Line Magnetic and Electric Fields. 9. Bangkok, Metropolitan Electricity Authority (MEA), Bangkok [6] Power System Planning Department, Bangkok, Metropolitan Electricity Authority (MEA). 1982. 69 kv Single Circuit 2-Bundled Conductor Tamgent Structure DWG. No.3251. [7] Power System Planning Department, Bangkok, Metropolitan Electricity Authority (MEA). 1991. 115 kv Single Circuit 2-Bundled Conductor Tamgent Structure DWG. No.3331. Fig. 27. Magnetic Field Around 115 kv Conductor Carry Out by Matlab Software. The result of magnetic field around 115 kv can be shown in a graph format. It s plotted by Matlab software as shown in Fig.27. 5. CONCLUSION This research presents electric and magnetic fields investigation and analysis. Case study information is provided from MEA s 69 and 115 kv subtransmission system by focusing on the conductors arrangement of the current system. The results show that electric and magnetic fields around the conductors are within safety criteria value of WHO which MEA using as reference. It means those area are safe for human being. ACKNOWLEDGMENT Firstly, the author would like to express his deepest gratitude to the late Assoc. Prof. Dr.Jamnarn Hokierti, Kasertsart University, Thailand and Mr. Praditpong 32