INSTALLATION AND SET-UP MANUAL FOR THE NEW: AVR-07. A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators

Similar documents
A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators

MX431 Generator Automatic Voltage Regulator Operation Manual

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual

ADVR-12. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

James Hamilton Electrical Pty Ltd (Inc in Qld) A.C.N trading as. Power Drive Systems. Generator Control Specialists

INSTRUCTION MANUAL FOR

XR500B Universal Voltage Regulator

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages.

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

FAULT FINDING MANUAL. For Stamford AC Generators

1/4HP - 7.5HP 120/240/277 VOLTS 50/60HZ

EA07. Generator Automatic Voltage Regulator Operation Manual

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

ALTERNATOR DE-EXCITATION WITH K1 AND K2 ON ANALOGUE

PM300E Voltage Regulator Instruction Manual

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

EA16. Generator Automatic Voltage Regulator Operation Manual

CUSTOMER / ACCOUNT INFORMATION Electric Utility Customer Information (As shown on utility bill)

DG SYNCHRONIZING &AMF PANEL

Graham. Vari Speed S1000 Instruction Manual. TRANSMISSIONS, Inc. Installation, Operation and Maintenance Manual

GENERATOR INTERCONNECTION APPLICATION

Model 340i / 680i / 1220i DC drive product manual HG iss 8 1

CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

Electric Utility Contact Information Indiana Michigan Power

Power-Tronics, Inc. Electronic Voltage Regulators and Static Exciters P.O. Box , Kerrville, Texas 78029

Specifications. Minimum Build Up Volts 3.5vac. Voltage Regulator

Single or Double 240VAC motor control for domestic and industrial gates and doors.

Filtered PWM Speed Control for Permanent Magnet DC Motors

Number 9 January SECTION 1 Dimming of T12 Fluorescent lamps 2. SECTION 2 Dimming of T8 Fluorescent lamps 4. SECTION 3 Do's and Don'ts 6

Model ER-340XRi / ER-680XRi / ER-1220XRi DC drive product manual HG iss 9 1

Basics of Paralleling

MAGNAMAX DVR DIGITAL VOLTAGE REGULATOR

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

SECTION V SWITCHBOARD I 4 Engine/Gen Control Cubicles II 1 Synchronizing System III 1 Ground Detection Network IV 1 600V Feeder Section V 2

CONTROL FEATURES AVAILABLE OPTIONS

5001TCP SPEED CONTROLLER

THE BATTERY CHARGER OF RON PUGH

ABB Softstarter Benefits Charnchanok Thongprad

PM300 VOLTAGE REGULATOR INSTRUCTION MANUAL

SERIES 2335 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-2 HP)

High Frequency SineWave Guardian TM

NEMA 1, NEMA 4X and Chassis Mount Adjustable Speed Controls for DC Motors

50 Hz Mini/Micro Computer Regulator (MCR) Series Installation and Operation Manual

ESD5500E Series Speed Control Unit

SE450 Static Exciter Module

DC3E Non-Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC M/N DC3N-12D AI M/N DC3N-12D-4X-010-AI

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

POWER FACTOR CORRECTION MOTOR LOAD (ML) FIXED CAPACITOR

RCP200 Series Motor Controls. Instruction Manual Model RCP Model RCP Model RCP202-BC1 Model RCP202-BC2 Model RCP205-BC2

XR500D Universal Voltage Regulator

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Euclid Full Voltage Magnet Controller

Mar H: SUPPLEMENTAL PARALLELING GEAR (16315-H)

EMPAC Metal enclosed capacitor bank for wind applications

Electronic Dynamo Regulator INSTRUCTION MANUAL. COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved

INDEX Section Page Number Remarks

5001TCP SPEED CONTROLLER

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE

Power Solutions Manager Generac Power Systems, Inc.

PI044G - Winding 06 APPROVED DOCUMENT. Technical Data Sheet

Legal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:

PI144J - Winding 05 APPROVED DOCUMENT. Technical Data Sheet

SESL H - THREE PHASE AC VOLTAGE STABILISERS & REGULATORS. SESL H SERIES - THREE PHASE to 1500 kva. AC THREE PHASE TO 1500 kva

User Guide 4Q kW D.C.Motor Regenerative Speed Controller. Part Number: Issue Number: 3

PM734E - Winding 28. Technical Data Sheet APPROVED DOCUMENT

Battery Control Center - Diesel

2301A Load Sharing & Speed Control with Dual Dynamics. Product Manual (Revision NEW, 1990) Original Instructions

60 Series Engine Controls

Instruction Manual. Installation Operation Maintenance. KCR 760 Voltage Regulator

EUROTHERM ONTROLS. Two phase thyristor power switches. Product data

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Questions Section: Do you have questions that aren't covered? Please contact us!

IVT-1260 & IVT Generator Auxiliary Excitation Booster Operation Manual. (Patent Pending)

Short Term Course On Hydropower Development Engineering (Electrical) for Teachers of Polytechnics in Uttarakhand L33-2

C.E. Niehoff & Co. C840D Alternator Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

DC3R Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC

EG3000. Generator Electronic Governor Controller Operation Manual

MGL Avionics AvioGuard. Fault protected, wide input range, isolated, DC to DC converter for avionics applications

Expert Design...Trusted Power

KBVF Adjustable Frequency Drive

Module 9. DC Machines. Version 2 EE IIT, Kharagpur

Synchronous motor control. 8/15/2007 Powerflow Technologies Inc 1

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

Series P255MM/ML Single/Dual Pressure Input Condenser Fan Speed Controllers For Three Phase Motors (incl. built-in RFI suppression filter)

EG3002. Electronic Engine Governor Controller User Manual

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

INOVA HIGHTECH Ltd. MEP 002/003 Auto Starter Manual

Model NA 2 L

Fincor DC Drives. Flexible & Powerful TYPICAL APPLICATIONS. Conveyor Rugged. Extruder Reliable. Conveyor Simple. Mixer Flexible

Rating Definitions and Conditions

elabtronics Voltage Switch

Diesel generator set QSK23 series engine

SDM72 Start on Demand Modules

Electronic Dynamo Regulator INSTRUCTION MANUAL. COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

PI734G - Winding 312. Technical Data Sheet APPROVED DOCUMENT

Transcription:

INSTALLATION AND SET-UP MANUAL FOR THE NEW: AVR-07 A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators This is a premium quality product at a reasonable price, and offers unsurpassed reliability and operating features. The following is a summary of features and capabilities: Genuine 30A DC output rating Output voltage to field: 100V DC max. @ 240V AC input Integral automatic build-up circuit works with only 1.5V AC residual Adjustable Excitation voltage limit prevents alternator damage Three-phase or single-phase application Single-phase operating range: 180V to 280V 50/60Hz Three-phase operating range: 180V to 480V 50/60Hz Three-phase sensing circuit Can be used in parallel applications with external CT and burden Very low temperature drift of voltage setpoint Totally solid-state construction (no relays) Premium quality components only are used Extremely rugged design Simplified adjustment of stability for even the slowest of alternators High energy spike protection built-in Ambient air temperature rating of 50 C Generous heatsink for good operating margin at 50 C ambient Solid, easy to use terminals Compact size: 135mm x 135mm x 115mm 1

TABLE OF CONTENTS 1. APPLICATIONS 2. LOCATION AND MOUNTING 3. EXTERNAL WIRING 4. OPERATIONAL BEHAVIOUR 5. SET-UP Document Status: Revision B, 9/1/2003 2

1. APPLICATIONS This AVR can be used in a number of applications and is designed for maximum flexibility. Alternators of brushless configuration, or with separate exciters are the normal area of application. Slip-ring machines (without exciters) can also be driven provided the current and voltage requirement does not exceed that of the AVR. The maximum voltage output of the AVR is 100V DC with a 240V AC voltage available from the machine, but will automatically deliver any voltage between zero and this figure that the machine requires at any given time. The actual current which the AVR delivers is of course dependent on the machine requirements. A feature of this unit is that an Excitation Voltage limit is presetable on the AVR to allow a limit to be set from 25V DC up to 100V DC. This Excitation Voltage limit function provides underspeed protection as well as protection in the event of other machine faults. The maximum rating of 30A DC with a field resistance of 2 Ohms would imply a voltage of 60V, which is quite OK. In summary, the AVR can be used in applications where the alternator excitation requirement is less than 100V, and a current of less than 30A. The following circumstances will require special solutions which should be obtained from the supplier: a) The field resistance (cold) is less than 2 Ohms. b) The machine output frequency is not 50 or 60Hz. c) The required DC excitation voltage exceeds one third of the AC voltage available to the AVR (e.g. 80V DC on a 240V L-N machine). If this is the case, machine output collapse may occur under sudden overload conditions. d) The required DC excitation voltage is less than 10V. e) The machine has a compound wound DC exciter with subtractive field control (very rare). 2. LOCATION AND MOUNTING Although rugged, it is always advisable to choose the best possible position for mounting the AVR. The following guidelines should be kept in mind: a) The AVR must be mounted on a vertical surface with the cooling fins vertical and the terminal block at the bottom. b) If possible, avoid locations which will expose the AVR to high levels of vibration and/or grease and oil. c) Although generously sized, the heatsink must not be enclosed in such a way as to restrict or contain the surrounding air, especially if the field current requirement is high. The ambient air temperature around the AVR must not exceed 50C. d) Use the mounting channels extruded into the heatsink base for fixing. These are designed for M5 Hex hardware. 3

3. EXTERNAL WIRING Follow the wiring diagrams supplied: Standard three - phase; Use drawing AVR-07-001 Standard single - phase; Use drawing AVR-07-002 Three phase parallel; Use drawing AVR-07-003 4

CAUTION: It is essential for safety reasons that the sensing leads coming from L1, L2, and L3 come directly from the machine output, rather than downstream of switching and protection devices. Partial loss of sensing voltage may cause abnormal drive to the exciter if the power source for the AVR remains intact. If fuses are used in the sensing wires from from L1, L2, and L3, they must be extremely reliable, and not be feeding any other equipment (not even a voltmeter). a) The power source for the AVR is fed to P1. b) Always ensure that the neutral goes to P2 of the AVR. c) For stand-alone Three-phase machines, the sensing terminals L1, L2, and L3 need to be connected to the corresponding 3 lines from the machine. d) For Single-phase machines, BOTH of the sensing terminals L1 and L2 need to be connected to the 240V line from the machine (L3 MUST be left open). e) For Three-phase machines and paralleling, the sensing terminals L1 and L3 need to be connected to phases A and C from the machine (L2 is left open). The paralleling CT then is placed in the B phase of the machine (the one NOT connected to L2). f) Terminals CT1 and CT2 are provided for connection of an external paralleling CT with a external burden resistor connected across it. The CT and Burden resistor should be chosen to produce between 3 and 5V rms at rated kva on the Alternator. CTs with 1 Amp secondaries should be used, and would therefore imply a secondary rating of 5VA for 5V output. As indicated in e) above, the CT monitors the current in B phase of the machine. WARNING: Under NO CIRCUMSTANCES CONNECT an external CT WITHOUT an appropriate burden resistor across it. Failure to observe this will destroy the AVR droop circuitry. g) The last terminal SP is a spare, and is not connected within the AVR. h) The facility for a remote voltage pot has been removed on this version of the AVR. 4. OPERATIONAL BEHAVIOUR 5

Although completely solid state (no relays), the AVR has its own build-up circuit and control. A voltage of 1.5 VAC or more is required between P1 and P2, for the build-up circuit to function. Once the build-up begins (and it may occur at any speed), an Excitation limiting circuit prevents over excitation of the machine. This is AVR build-up mode. Once the output frequency reaches a sufficient value, the normal regulation part of the AVR, regulates the machine output voltage without the Excitation limiting circuit coming into play. CAUTION: In build-up mode, the machine output voltage will be lower than normal, and possibly fluctuating due to AVR limiting action. It is important that load devices are not connected to the machine under these circumstances, as they will malfunction due to low voltage and frequency. This is normally standard practice, and dependent on the output control cubicle that the generating set should be fitted with, and is a consideration when using ANY type of AVR. Connection of the load should only be enabled when the alternator output is stable and within limits. 5. SET-UP a) 4-WAY DIP SWITCH It is ESSENTIAL that this switch be configured correctly for successful application of this AVR. A correct setting not only ensures proper operation, but also provides additional equipment protection. i) In deciding what Excitation Voltage limit to set, refer to the nameplate of the alternator. Set an excitation limit value which is just above the nameplate value. ii) In the absence of a nameplate value, run the machine with all switches set to OFF, and measure the no-load Excitation voltage (DC). A DIP switch setting of 3 times this noload value should be ample to drive the machine to full output. If the means are available (load bank), the actual excitation under rated load can be measured, and the setting further adjusted. iii) Note that an Excitation Voltage limit setting set too low can result in the alternator failing to deliver rated output. If the AVR starts to limit during normal machine operation, the alternator output voltage will fall below normal, and begin to fluctuate. iv) Note that an Excitation Voltage limit setting set too high compromises machine protection in the event of underspeed or external faults. v) Familiarise yourself as to which way is ON for the 4 switches in the bank. vi) The Excitation Voltage is limited to its LOWEST possible value with all switches OFF. This minimum value is 25V. The value set by the four switches is then added to the base figure of 25 as follows: SWITCH STAGE ASSOCIATED VALUE WHEN ON 1 2 3 4 5V 10V 20V 40V The table below provides a quick means of determining which switch to set for a particular desired Excitation Voltage limit setting: EXCITATION STAGE 1 STAGE 2 STAGE 3 STAGE 4 LIMIT 25V OFF OFF OFF OFF 30V ON OFF OFF OFF 6

35V OFF ON OFF OFF 40V ON ON OFF OFF 45V OFF OFF ON OFF 50V ON OFF ON OFF 55V OFF ON ON OFF 60V ON ON ON OFF 65V OFF OFF OFF ON 70V ON OFF OFF ON 75V OFF ON OFF ON 80V ON ON OFF ON 85V OFF OFF ON ON 90V ON OFF ON ON 95V OFF ON ON ON 100V ON ON ON ON AVR-07 b) STABILITY TRIMPOT The trimpot marked STAB (on its own, furthest from the terminal block), has about 30 turns adjustment from full anti-clockwise to full clockwise. This trimpot is normally preset to 15 turns clockwise during manufacture (about midway). However, it may well be necessary (and desirable) to adjust this to a more optimum value, depending on the AVR application. FULL CLOCKWISE on this trimpot corresponds to maximum stability (slowest response). FULL ANTI-CLOCKWISE on this trimpot corresponds to minimum stability (fastest response). More clockwise settings will be required to stabilise alternators that are particularly sensitive; that is, requiring relatively low levels of excitation voltage, and a correspondingly low setting for the Excitation Voltage limit. Conversely, more anti-clockwise settings will be required to get response times short enough (for motor starting etc), for alternators that are less sensitive; that is, requiring relatively high levels of excitation voltage, and a correspondingly high setting for the Excitation Voltage limit. The best set-up requires an oscilloscope, however an analogue meter or better still an incandescent globe, give a good indication of response speed and settling time. NOTE: The most critical circumstance to be monitored is UNLOADING (perhaps using the output breaker or similar to drop say 30% of the rated load). If stability problems exist, they will normally occur when the load is removed. c) VOLTS TRIMPOT The trimpot marked VOLTS (left hand one of pair, closest to the terminal block), has about 30 turns adjustment from full anti-clockwise to full clockwise. This trimpot is normally preset for 240V Line to Neutral during manufacture. Note that if your application is wired for 3-phase paralleling (sensing terminal L2 left open), it will be necessary to turn this VOLTS trimpot fully anti-clockwise before starting the machine (much lower settings apply for this paralleling AVR connection). 7

d) COMP (Droop) TRIMPOT The trimpot marked COMP (right hand one of pair, closest to the terminal block), has about 30 turns adjustment from full anti-clockwise to full clockwise. This trimpot is normally preset fully anti-clockwise during manufacture, and can be left there for all nonparalleling applications. This trimpot is only utilised in a paralleling application, and is used to set the quadrature droop. This droop is necessary to ensure proper reactive power sharing between alternators. To set this trimpot and ensure correct external CT wiring etc, you must be able to apply at least 50% of the rated load for the Alternator. For example, if a machine is say 300kVA 0.8 PF, the rated load is 240kW + 180kVAR. In order to set up such a machine for paralleling, you must have at least 120kW + 90kVAR load. Note that although the set up of the AVR can be done with an Inductive load only, the power sharing between prime-movers needs to be checked with resistive load also. The recommended droop for rated load is 5.0V. That is, in going from no-load to rated load, the output voltage should fall from 245.0 to 240.0 Line to Neutral. Presuming a 120kW + 90kVAR load is all you have, the droop will only be 2.5V with this load. A good quality DMM will be required. The machine should be run up, and the output voltage trimmed to 245.0V no-load. The load of 120kW + 90kVAR should be applied, and the COMP trimpot turned clockwise. As this trimpot is turned clockwise, the alternator output voltage should FALL, if it increases instead, it will be necessary to stop the set and reverse the wires on the paralleling CT secondary and start again. The COMP trimpot should then be adjusted to achieve the 2.5V Droop (242.5V) at the 50% rated load. This adjustment has to be done (also separately) on the other machine(s) to be paralleled, before their outputs are paralleled. The prime-mover no-load speeds and speed droop characteristics also need to be matched as per the governor manufacturers information prior to placing the machines online together. SALES & SERVICE Please Contact CONTROLPAK P/L 30 Glencairn Street Mulgrave Vic 3170 Ph: 03 9546 6508 Fax: 03 9546 6508 Mob: 0427 521 128 Email: brian@controlpak.com.au Website: www.controlpak.com.au 8