VoltPro VPBF8 Automatic Battery Flashing Module This Manual Covers Both VPBF8-12 and VPBF8-24 Models

Similar documents
VoltPro VP4 Automatic Voltage Regulator

AFM500X Automatic Flashing Module

XR500B Universal Voltage Regulator

ABF40 Automatic Battery Flash Unit

SE2000BX Static Exciter

SE450 Static Exciter Module

AFM500X Automatic Flashing Module

XR500D-277V Special Voltage Regulator

XR500D Universal Voltage Regulator

Specifications. Minimum Build Up Volts 3.5vac. Voltage Regulator

Power-Tronics, Inc. Electronic Voltage Regulators and Static Exciters P.O. Box , Kerrville, Texas 78029

MP24 Motorized Potentiometer

MOP1224HD Heavy-Duty Motorized Potentiometer

XC4 Commercial Series

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages.

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual

DC250i. Voltage Regulation: Specifications

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

ADVR-12. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

PBS M Marine Push Button Start

Questions Section: Do you have questions that aren't covered? Please contact us!

REVISION A (FROM SERIAL

ELECTRIC BEDROOM SLIDEOUT SYSTEM OPERATION AND SERVICE MANUAL

XR5C Specialty Series Universal Voltage Regulator

R231 A.V.R. Installation and maintenance R 231. This manual is to be given to. the end user. Armature 6- Field. Slow-blow fuse 250V 8 A

Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC. User s Manual K01-C

PM300E Voltage Regulator Instruction Manual

SERVICE SHOP NOTES. Use ohmmeter to check the resistance between the leads.

60 Series Engine Controls

Operations Manual. Zero Speed Switch Sensor Model ZS09P

Power Inverter 400 MW Owner s Manual

XR5B Hz Specialty Series Universal Voltage Regulator

IVT-1260 & IVT Generator Auxiliary Excitation Booster Operation Manual. (Patent Pending)

MAGNAMAX DVR DIGITAL VOLTAGE REGULATOR

Manufacturing of: Vehicle Mounted Generators Hydraulic Generators

PM300 VOLTAGE REGULATOR INSTRUCTION MANUAL

LC I LIPPERT COMPONENTS HYDRAULIC FULL WALL SLIDEOUT SYSTEM OPERATION AND SERVICE MANUAL

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

ELECTRONIC MANUAL VOLTAGE CONTROL Model: MVC 300. Part Number:

TIME REQUIREMENT GUIDE (TRG)

230VAC Power Inverter 400W Owner s Manual

User's Manual. High Voltage Megohmmeter. Analog Insulation Tester plus AC Voltage and Continuity Tests. Model

Generator Start Control Module

Battery Power Inverters

VOLT POT 1K R220. OPEN FOR 60 Hz STAB A.V.R. R220. Installation and maintenance

Tekleen GB6 & GB7 USERS AUTOMATIC FILTERS, INC. MANUAL

Ezyfit AC Controller INSTRUCTION BOOK 2 & 4 STATION UNITS

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

STANDARD AND GROUND SWITCHED APPLICATIONS

TROUBLESHOOTING GENERATOR UNITS

HYDRAULIC SLIDEOUT SYSTEM OPERATION AND SERVICE MANUAL

GCU-10. Automatic Engine Control Unit Operators Manual

Switching DC Power Supply

User Manual. T6 Tachometer. Online: Telephone: P.O. Box St. Petersburg, Florida 33736

BOLT-ON AND WELD-ON FLUSH FLOOR SLIDEOUT SYSTEMS OPERATION AND SERVICE MANUAL

COMPACT GLYCOL FEED SYSTEMS OPERATION & MAINTENANCE MANUAL

Nature Power Inverters. True Sinewave Inverter Modified Sinewave Inverter. Owner s Manual

OWNER S MANUAL Please read this manual before operating your power supply

Generator Start Control Module

INSTRUCTION MANUAL FOR

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

Modulating Furnace Information. Warning on Meter Setting - Read First!

INDUSTRIAL GENERATOR SERVICE

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V

MODEL 422 Submersible Pump Controller

PowerOhm Installation Manual for BM R Series Braking Modules

Hydro-Sync Slide-Out System

MANUAL TROUBLESHOOTING. ECM Motor. ECM / ECM-DX Series. v100 Issue Date: 08/15/ Price Industries Limited. All rights reserved.

Instruction Manual MINI IRRIGATION CONTROLLER.

ENGEN -100/ENGEN -200 ENGINE GENERATOR CONTROLLER

To ensure proper installation, digital pictures with contact information to before startup.

ENSC387: Introduction to Electromechanical Sensors and Actuators LAB 5: DC MOTORS WARNING:

SPC-PANEL Simplex, Single Phase Pump Control Panel

COOKSON OWNER S MANUAL

Benchmark HD Series Heavy Duty Bench Scale. Installation Manual

C802/C802D/C802TD/C820 Alternators Troubleshooting Guide

Application Engineering

MCD 500 Service Manual. Functional Tests 5 Power Circuit Test 5 Start Performance Test 5 Run Performance Test 6 Trip Messages 6 General Faults 10

Model Number Structure. Power Controllers G3PX. Single-phase Models. Model Number Legend

Cascade CD101 Auto-Start Controller. Installation and Operations Manual Sections 40 & 75

Sofa Slideout Assembly OWNER'S MANUAL. Rev: Page 1 Sofa Slideout Owners Manual

Three-Phase Soft Starters

R & D SPECIALTIES ROTROL I USER'S MANUAL

DP140e. Installation & Operations Manual

HILLSTONE DC LOAD BANK

Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate.

Pump Installation and Service Manual HRS Hydromatic Retractable System

GENERATOR START CONTROL MODULE

SECOND GENERATION Use this guide with unit serial number prefix beginning with BWF using Terra Power separator.

This manual is to be given to. the end user P.M.G. / ALTERNATORS. Installation and maintenance

GENERATOR START CONTROL MODULE

Generator Start Control Module

The Power of Reliability INSTRUCTION MANUAL

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

C.E. Niehoff & Co. C653/C653A and C625 Alternators Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

INOVA HIGHTECH Ltd. MEP 002/003 Auto Starter Manual

XENON POWER SUPPLY for 10 kw Britelight Lamphead

OPERATING INSTRUCTIONS. Note: 6V Charging. Requires Manual Shut Off.

A6Z OPERATING MANUAL

Transcription:

VoltPro VPBF8 Automatic Battery Flashing Module This Manual Covers Both VPBF8-12 and VPBF8-24 Models The VoltPro VPBF8 Automatic Battery Flashing Module is an affordable add-on module for VoltPro VP4, VP5 and VP7 voltage regulators that is designed to provide an automatic battery flashing solution for many brushless and brush-type generators up to 300kw. If you have another brand of voltage regulator, you can add the VPBF8 to your existing system, provided your maximum exciter field current is less than 8ADC at full load. VoltPro uses only high quality name-brand parts to manufacture the VPBF8, and every single unit is vigorously tested both by static and real generator testing before final packaging to ensure that each unit conforms to our strict manufacturing and performance standards. The VPBF8 is specifically designed to be very simple to install. It has a minimum of interconnections, all of which are clearly marked. Operation of the unit is fully automated and is voltagetriggered for peace of mind and reliable operation. Due to its compact design, the VPBF8 is able to fit into tight locations and is designed to complement OEM designs for many popular brands of generator sets, and owing to its totally encapsulated design it is able to withstand extremely harsh vibration and environmental conditions! Specifications: VPBF8-12 VPBF8-24 Input / Sensing Voltage 100-240vac 100-240vac Maximum Continuous Output Amperage 8adc 8adc Minimum Field Resistance 8Ω 8Ω Frequency 50/60hz 50/60hz Battery Voltage 12vdc 24vdc Automatic Pull-Out Voltage 20-25vac 20-25vac Dimensions 5.5 x 3.25 x 1in 5.5 x 3.25 x 1in Weight 8oz 8oz Customer Fusing Required Fast Blow 8A @ 250vac Fast Blow 8A @ 250vac

Warning: Do not use digital equipment to read voltage, Hz, or amperage during this installation. Use only analog sensing equipment! Failure to do so may result in damage to equipment or in personal injury! Make sure that all setup is done off line. Always wear eye protection and NEVER hold the unit in your hand when energized! Installation Instructions: Before installing the VPBF8 Automatic Battery Flash Module, you must verify that your exciter field current is less than 8adc at full load and your exciter field resistance is greater than 8Ω to determine if the VPBF8 is compatible with your application. REFER TO THE WIRING DIAGRAM FOR YOUR VOLTAGE REGULATOR TO DETERMINE THE CORRECT INTERCONNECTION WITH YOUR GENERATOR! THE VPBF8 IS DESIGNED TO GO IN-LINE WITH THE POWER/FIELD CONNECTIONS OF YOUR VOLTAGE REGULATOR! After performing a complete check of the generator and verifying that the VPBF8 is compatible with your generator, install the VPBF8 Automatic Battery Flashing Module and wire it in-line with your voltage regulator as shown in the diagram below: 100-240VAC Maximum Generator Generator Field AC1 AC2 F+ F- B+ B- Generator Side DO NOT connect the input of the VPBF8 to DPE, Aux, AREP, or PMG Windings!!! VPBF8 Automatic Battery Flashing Module Voltage Regulator Side AC1 AC2 F+ F- SPST Switch, Oil-Pressure Switch, Or Speed Switch 10A @ 24VDC VPBF8-12: 12VDC VPBF8-24: 24VDC Observe Proper F+/F- Polarity! Switch MUST REMAIN CLOSED and Battery Voltage MUST BE PRESENT for the generator to operate! Switch MUST REMAIN OPEN when generator is not operating to prevent battery from draining! Sequence of Operation: 1. Start Engine, bring to operating speed. 2. Close SPST Switch. 3. Battery Voltage is now applied to the field, flashing the generator. 4. At approximately 20-30VAC the VPBF8 will automatically switch from battery voltage to AVR field output, allowing full AVR control of the generator. 5. AC1, AC2, and B+ are all fused with 8A fast-blow fuses for adequate generator protection. 6. Should the AVR fail to control the generator after it has been flashed, the VPBF8 will reset when AC voltage drops below 12VAC and attempt to re-flash the generator. AC1 AC2 F+ F- Voltage Regulator VoltPro VP4, VP5 or VP7 Voltage Regulator Or Compatible 3 rd Party Voltage Regulator Install the VPBF8 as shown in the diagram above. Refer to the wiring information that came with your voltage regulator for interconnection with the generator and/or setup instructions. The VPBF8 is designed to be an in-line flashing solution. Observe correct battery polarity Observe correct F+ / F- field polarity Switch should be rated at 10ADC @ 24VDC or greater. Switch can be an auxiliary contact on a run/idle switch, oil-pressure switch, or relay contact. Start up the generator without load and bring up to rated speed, then close the main operating switch. The VPBF8 should build AC voltage to roughly 25VAC, then switch the internal relay to AVR control. Battery voltage MUST REMAIN PRESENT at B+ and B- for the VPBF8 to operate! Run the generator for a few minutes and observe for proper operation before adding load and operating as normal. When shutting down the generator, ensure the control switch is OPEN to prevent discharging the battery.

Bench-Test Procedure 1. Wire up the VPBF8 as shown below. 2. Connect up Multimeter set to a scale capable of reading 24VDC at the Generator Side F+ and F- Terminals. 3. Attach a 12/24V battery to B+ and B- Terminals. 4. Observation: You should read battery voltage across the Generator Side F+ and F- Terminals. If there is no battery voltage present, or if any fuse blows, do not continue this test! VPBF8 is damaged or defective! 5. Input 120vac into the VPBF8 Generator Side AC1 and AC2 Terminals. 6. Observation: You should hear a click and battery voltage across the Generator Side F+ and F- Terminals should disappear (0V). If battery voltage does not disappear, or if any fuse blows, do not continue this test! VPBF8 is damaged or defective! 7. Disconnect 120vac from the VPBF8 Generator Side AC1 and AC2 Terminals. 8. Observation: After a short delay, you should hear a click and battery voltage across the Generator Side F+ and F- Terminals should reappear (12/24V). If battery voltage does not reappear, or if any fuse blows, do not continue this test! VPBF8 is damaged or defective! 9. If you were able to successfully perform all of these tests, the VPBF8 is good. 120vac VPBF8-12: 12VDC VPBF8-24: 24VDC

Features & Sizing: VPBF8 FAQ s Q: Can the VP4 be used with generators over 240V? A: Yes. The VPBF8 can be used with higher voltage generators with a proper step-down transformer or by center-tapping your stator leads at T7 and T8 on 10 and 12 lead generators. See your AVR s instruction manual for more information. Q: How can I determine if I can use the VPBF8 on my generator? A: Your exciter field resistance should be above 8Ω, and your full load exciter field current should be less than 8Adc. Usually this information will be written on the generator nameplate. If you do not have this information, it can be easily calculated: Measure your exciter field resistance using a multimeter on your field leads. Record this value. If you have a brush-type generator, also take a resistance reading on your slip rings: the value you obtain on the slip rings should be no more than 1% difference from the value you obtained through the field leads. Next, start and run the generator and apply 12V from a battery through your field leads and record the AC voltage produced by the generator. To determine your full load exciter field voltage, use the following formula: E Exc. = " $ # E Gen.Conf. E Gen.Output E Battery *2 % ' & Where E Gen.Conf. is your Generator s configured voltage (eg: 120, 208, 240, 480V, etc), E Gen.Output is your recorded output voltage, and E Battery is your battery voltage (12V usually). Next, calculate your maximum exciter field amperage using your measured field resistance and your calculated exciter voltage using the following formula: I = E R Where I is your maximum exciter field current, E is your calculated field voltage from the above formula, and R is your measured field resistance. If your maximum exciter field current is less than 8Adc, the VPBF8 will probably fit your application. Q: Is the VP4 compatible with my X Brand Name generator? A: The VPBF8 is a universal, generic add-on module. It is compatible with all makes and models that fall within its current design limits. Q: I have a generator with a PMG, can I use the VPBF8? A: Only if you are using a standard shunt-fed AVR, although these types of generators rarely need to be flashed, even if the PMG is not in use. If you are using a PMG-fed AVR, you cannot use the VPBF8. Q: I have a 480V generator, can I power the VPBF8 with 277V? A: No. You will destroy the AVR attached to the VPBF8 if you do! If your generator is a 10 or 12 lead set, simply tap T7 and T8 for 240V input to the regulator. If you have a 4 lead generator, you will need to use a step-down transformer. Technical Help: Q: My Generator doesn t generate when I start it up with the VPBF8 connected. A: Verify you have the regulator hooked up properly as shown in its instruction booklet. Check the fuses and replace if blown. If you blow fuses when starting up, verify that the VPBF8 fits your application. Verify that the battery is producing voltage and the switch is closed to B+ on the VPBF8. Perform a bench-test as shown in the instruction booklet to verify that the VPBF8 is good. If you have a brush-type generator, check the brush and slip ring contact for potential problems. Q: My Generator doesn t come up to the proper voltage when switched on. A: The VPBF8 will only build the AC voltage to ~25-30VAC before it disconnects the battery from the field. This should be more than adequate for any make/model of AVR to continue the buildup process. If the voltage does not build up to an acceptable value, or if you cannot control the AC voltage on your generator, check the AVR settings or perform a benchtest on the AVR per the manufacturers instructions. Q: The AC voltage on the generator runs high and is not controllable by the AVR. A: Check the fuses below AC1 and AC2. If blown, replace them. If the fuses are good, perform a bench test on the VPBF8. If it tests good, inspect the AVR for failure.

Q: I have erratic voltage regulation, pulsating voltage, low flickering voltage, or wide voltage swings. A: Check that the AVR is operating correctly. This is often a symptom of AVR failure with the VPF8 switching between battery and AVR sources. Warranty Disclaimer VoltPro, a division of Power-Tronics, Inc, assumes no liability for damages, electrical or physical due to incorrect voltage or other voltage related damages resulting from either output of the generator or input to the generator exciter system. These problems should be protected with external devices provided by the customer such as fuses, surge suppressors, over/under voltage and frequency controls. Because this product is fully encapsulated and it would be impossible to determine cause of failure, there is no warranty offered. We do certify that this product is manufactured with only the highest quality parts and is fully tested by both static testing and functionally tested on an electrical generator before final packaging. This product should only be installed and maintained by a competent electrical generator technician. Technical assistance for this product is only available through our web site http://www.voltpro.com. VoltPro does not allow returns or refunds, all sales are final. No other warranty is expressed or implied.