V5822A/5823A,C/V5832A/V5833A,C SMALL LINEAR VALVES PN16 FOR ON/OFFCONTROL V5822A4... V5833A4... V5823A4... V5833A4... FEATURES SPECIFICATION DATA Small size Range of fittings available for different connections (compression, soldered, threaded) Soft seat provides low leakage rate and high rangeability Adjustment cap for manual operation Valve inserts changeable without draining by using insert replacement tool WV 108 Compatible with twopiece conex compression fittings Conical sealing connections Flat surfaces on body to fit installation tools 40 mm distance between port AAB and bypass (V5823C, only) GENERAL V5823C4... V5833C4... These small linear valves are used in combination with small electric linear actuators and thermoelectric actuators for on/off control of hot and/or chilled water, fan coil units and small reheaters/recoolers in electric/electronic temperature control systems. SPECIFICATIONS Models twoway: V5822A/V5832A threeway: V5823A/V5833A threeway with bypass: V5823C/ V5833C Operation twoway: stem up to open, port A to B; threeway: stem up to close, port A to AB Nominal pressure rating PN16 Capacity index (k VS) See tables on page 2 Leakage rate 0.02% of k VS Valve body Material: Brass Size DN (1/2 ), DN (3/4 ) Trim Stem stainless steel Plug EPDM disc Suitable medium water, with max. 50% Glycol Controlled water temperature 2...1 C EN0B0292GE51 R1002
Rangeability Twoway valves 100:1 Threeway valves 100:1 for controlled port Flow characteristic For ON/OFF control Port connection Conical sealing, flat sealing, soft conical connection Stroke 2.5 mm Dimensions see Fig. 4 on page 6 FLOW CAPACITIES AND CLOSEOFF PRESSURE RATINGS TWOWAY VALVES Valve DN k VS CloseOff Pressure (kpa) with Actuators M6410C,L/M7410C,E (180N) M4450/M8450 M100/Z100/M7410A 1.6 V5822A4000 10 180 180 2.5 V5822A4018 400 50* 50* 1.6 V5822A4026 10 180 180 2.5 V5822A4034 400 50* 50* 1.6 V5832A4008 10 180 180 2.5 V5832A4016 400 50* 50* * Up to 1000kPa system pressure. THREEWAY VALVES DN Valve k VS AAB/BAB M6410C,L/M7410C,E (180N) CloseOff Pressure (kpa) with Actuators M4450/M8450 M100/Z100/M7410A 1.6 V5823A4009 250 0 0 2.5 V5823A4017 100 50 50 1.6 V5823A4033 250 0 0 2.5 V5823A4025 100 50 50 1.6 V5833A4007 250 0 0 2.5 V5833A40 100 50 50 THREEWAY VALVES WITH BYPASS DN Valve k VS AAB/BAB M6410C,L/M7410C,E (180N) CloseOff Pressure (kpa) with Actuators M4450/M8450 M100/Z100/M7410A 1.6 V5823C4005 250 0 0 2.5 V5823C4013 100 50 50 1.6 V5823C4021 250 0 0 2.5 V5823C4039 100 50 50 1.6 V5833C4003 250 0 0 2.5 V5833C4011 100 50 50 EN0B0292GE51 R1002 2
OPERATION A builtin return spring in the twoway valve produces an opening force. In the threeway valve and the threeway valve with bypass, the spring produces a closing force on the A to AB ports. The valves are supplied with an adjustment cap for manual operation and to protect the stem. This allows the stem set up for filling or initial heating/cooling during the building construction phase without the use of a controller or actuator. The small electric valve actuators as well as the thermoelectric actuators provide automatic control during the opening and closing movement of the valve stem. TYPICAL OPERATION All types of valves should be mounted in the return flow. If the pvalues exceed 60 kpa, attention should be paid to the development of noise. TwoWay Valves Direction of flow always from port A to port B Port B: Outlet outlet outlet ThreeWay Valves with Bypass These valves simplify the installation, which is depending on the layout of the pipework, as the bypass pipe is part of the valve. The information for the normal threeway valves is also valid for this type. AB B A MOUNTING AB B Fig. 3. Threeway valve with bypass When installing the valve, care must be taken that the flow direction is correct (see section "Typical Operation"). Do not install the valve with the stem pointing downward. The adjustment cap must be removed from the valve only after the actuator is fitted. The valve must be installed as stressfree as possible with a tightening torque of 25...30 Nm. The water quality must meet VDI 35 requirements. The valve is supplied complete with mounting instructions. A Fig. 1. Twoway valve operation ThreeWay Valves These valves are preferably used as mixing valves, this means: Port AB: Total flow outlet Port A: Controlled flow Port B: Bypass AB B A AB B A Fig. 2. Threeway valve operation 3 EN0B0292GE51 R1002
ACCESSORIES Models V5822A needs two connection sets, models V5823A three connection sets and models V5823C four connection sets. Conical sealing, used for valves: V5822A4000, V5822A4018, V5823A4009, V5823A4017, V5823C4005, V5823C4013 Connection Pipe Size DN Connection Set Consisting of Compression mm 22 mm ACNC ACNC Union nut and ferrule Soldering 12 mm mm ACNS ACNS Union nut and solder bush External Thread R3/8" R1/2" ACNT ACNT Union nut and tailpiece Compression (Conex) mm 22 mm 63* 65* Capnut and compression ring *Cannot be purchased from Honeywell Dimensions Connection Sets a b c d 11/8 x 14 BS 84 mm 22 mm ACNC ACNC 11/8 x 14 BS 84 12 mm mm ACNS ACNS 11/8 x 14 BS 84 R3/8" R1/2" ACNT ACNT EN0B0292GE51 R1002 4
Flat sealing, used for valves: V5832A4008, V5832A4016, V5833A4007, V5833A40, V5833C4003, V5833C4011 Connection Pipe Size DN Connection Set Consisting of Soldering 12 mm mm ACFS ACFS Union nut, solder bush, and gasket External Thread R3/8" R1/2" ACFT ACFT Union nut, tailpiece, and gasket Dimensions Connection Sets a c d G3/4 12 mm mm ACFS ACFS G3/4 R3/8 R1/2 ACFT ACFT Soft conical connection, used for valves: V5822A4026, V5822A4034, V5823A4033, V5823A4025, V5823C4021, V5823C4039 Connection Pipe Size DN Connection Set Consisting of Screw joint 14 mm mm ACNSC ACNSC Soft connection Dimensions Connection Set a c a c G3/4 14 mm mm ACSC ACSC 5 EN0B0292GE51 R1002
DIMENSIONS Twoway valve 6. 5 Str ok e * 2.5 Stroke 18 M30x1.5 Allow 130mm for the actuator and clearance for removal a b d b d DN 1) 56 G1/2A 34 DN 56 G1/2A 34 DN DN 1) 66 6 11/8" 11/8 x14bs x 14 BS 84 84 33 33 DN 2) 56 G1/2A 34 DN 2) 66 G3/4A 33 Threeway valve 6. 5 Str ok e* 2.5 Stroke 14 M30x1.5 Allow 130mm for the actuator and clearance for removal a b c d a b d DN 1) 56 G1/2A 24.5 34 DN 56 G1/2A 34 DN DN 1) 66 6611/8 x14bs 11/8" x 14 84 BS 843333 33 DN 2) 56 G1/2A 24.5 34 DN 2) 66 G3/4A 33 33 c a Threeway valve with bypass 6. 5 Str ok e * 2.5 Stroke 14 M30x1.5 Allow 130mm for the actuator and clearance for removal a b c d a a b b c dc d DN 1) 56 G1/2A 40 34 DN DN 56 56 G1/2A G1/2A 40 34 40 34 DN DN DN 1) 66 66 11/8 x14bs 6611/8 x14bs 11/8" 84 x 1484 BS 40 8440 33 40 33 33 DN 2) 56 G1/2A 40 34 DN 2) 66 G3/4A 40 33 1) Conical sealing 2) Flat sealing, soft conical connection Fig. 4. Dimensions of V5822A/V5823A,C/V5832A/V5833A,C in mm EN0B0292GE51 R1002 6
Spare Parts Valve inserts are provided as spare parts for the V5822A/V5832A and V5823A,C/V5833A,C small linear valves. When the tool WV 108 is used, the valve inserts can be changed without draining the system. DN k VS Valve Insert V5822A4000 1.6 0902813 V5822A4018 2.5 0902816 V5822A4026 1.6 0902813 V5822A4034 2.5 0902816 V5832A4008 1.6 0902813 V5822A4016 2.5 0902816 V5823A4009 / V5823C4005 1.6 0902817 V5823A4017 / V5823C4013 2.5 09028 V5823A4033 / V5823C4021 1.6 0902817 V5823A4023 / V5823C4039 2.5 09028 V5833A4007 / V5833C4003 1.6 0902817 V5833A40 / V5833C4011 2.5 09028 7 EN0B0292GE51 R1002
Control Products Honeywell AG Hardhofweg D74821 Mosbach Phone: (49) 6261 810 Fax: (49) 6261 81309 http://europe.hbc.honeywell.com Subject to change without notice. Printed in Germany Manufacturing location certified to EN0B0292GE51 R1002