Cutler-Hammer. Installation Instructions for Undervoltage Release Mechanism (Handle Reset) with LED for E 2 L and E 2 LM Mining Circuit Breakers

Similar documents
Cutler-Hammer I.L. 29C160G WARNING NOTICE 1-0 INTRODUCTION. General Information

Q and M-Frame Circuit Breakers Instruciton Leaflet for Alarm Switch and Auxiliary Switch Combinaiton

I.L. 29C184A File WARNING

Cutler-Hammer. Installation Instructions for the ND OPTIM 550 PowerNet and/or Zone Interlock Accessories (ICK 550N, ZGK550N, ZGPK550N) I.L.

a WARNING Allen-Bradley Parts K-Frame Circuit Breaker Instruction Leaflet for Alarm Switch and Alarm /Auxiliary Switch Combination Bul.

I.L. 29C121A WARNING 1. INTRODUCTION. Maximum Freq. Maximum Dielectric Voltage Current Withstand (V) (A) Voltage (V)

Q and M-Frame Circuit Breaker Instruction Leaflet for Installation and Operation for Thermal Magnetic Trip Units

Installation Instructions for Type SM Safety Handle Mechanism for L-Frame Series C Circuit Breakers and Molded Case Switches

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers

Installation Instructions for the 14" Walking Beam Interlock for L-Frame and MDL-Frame Series C Circuit Breakers and Molded Case Switches

Installation Instructions for JDB, JD, HJD, JDC, JW HJW, JWC Circuit Breakers and Molded Case Switches

! WARNING I.L D WARNING GENERAL INFORMATION

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

N-frame Circuit Breaker

A WARNING. Installation Instructions for KD, HKD, KDC, CKD, CHKD Circuit Breakers I.L. 29C092C

Installation Instructions for NW, HNW, and NWC Circuit Breakers and N-frame Series C Molded Case Switches

Installation Instructions for TMQV Circuit Breakers and Molded Case Switches

www. ElectricalPartManuals. com ltciil Cutler-Hammer A WARNING

Advanced Test Equipment Rentals ATEC (2832)

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

Table Line and Load Terminals. Terminal Body Material. Wire Type. Aluminum Copper Aluminum. English English English.

Installation Instructions for R-Frame Circuit Breakers and Molded Case Switches

www. ElectricalPartManuals. com Digitrip Retrofit System for Allis-Chalmers LA-4000 F Fused Breakers IL 33-A1K-1 WARNING

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers

CM52 Network Protector with Arc Flash Reduction Module

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

section-page Table 1. Transfer switching device ratings. Conditional short circuit current

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035

Table Types LD, HLD and LDC Thermal-Magnetic Circuit Breakers with Interchangeable Trip Units

Modular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide

MCCB Accessories to suit AF

Installation, Service and Parts List Series 56,800 for Class I & II, Division 2 Manual Adjust Brakes

Florham Park, NJ USA Call (ASCO) for sales or service

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

2.3. Molded Case Circuit Breakers. Contents. Internal Accessories. Series C. Product Overview. Description

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

Westinghouse Molded Case Circuit Breakers Engine Generator FG Amperes

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

3-way multi-family drawout cable interlock kit - type 32 - RF

Instruction Bulletin Dual Sub-Feed Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640

Amperes. F-Frame. Price U.S. $ Catalog Number. Price U.S. $ EDH2100 EDH2125 EDH2150 EDH2175 EDH2200 EDH2225

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

Instruction Bulletin NF Panelboard Dual Sub-Feed Circuit Breaker Adapter Kit Installation onto an NF Panelboard Class 1670

Owner s Manual. Series 165 Automatic Transfer Switches rated 100 and 200 amps, single phase, 240 V ac for automatic 2 wire start generators

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

600 D 220 E 230 J Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2

SERIES 73 ELECTRIC ACTUATOR OPERATION AND MAINTENANCE MANUAL. The High Performance Company

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

Two-way cable interlock kit for Magnum drawout circuit breakers

Instructions for the Digitrip RMS Pole and 4-Pole Trip Unit Installation and Operation with L-Frame and MOL-Frame Series C Circuit Breakers

Interrupting Capacity (Symmetrical Amperes) Volts ac (50/60 Hz) Y/ ,000 25,000. Frame Only E2L3600F

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

L-Frame LD F. Circuit Breaker/ Frame Ampere Rating. Trip Unit Rating/ Plug Ampere Rating LD T5 7 W

Selection and Application Guide Supplement. WL UL Pole Circuit Breakers. usa.siemens.com/wlbreaker

Florham Park, NJ USA Call (ASCO) for sales or service

WARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES

www. ElectricalPartManuals. com Digitrip Retrofit System for the Westinghouse DA-50 IL 33-DAC-2 WARNING

Q-Frame Main Circuit Breaker (225 A Maximum) and Adapter Kit Installation onto an NQ Panelboard Class 1640

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

Product Line Overview. The Most Logically Designed Contact Assembly

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Digitrip Retrofit System for BBC LKD 8 Breakers

918 Remote Control Switches

H- or J-Frame Main Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640

OPERATIONS AND APPLICATIONS MANUAL MODEL NUMBER PM6. 6 KV DC HIGH POTENTIAL TESTER WITH MEGOHMMETER Version 2.0

design prefix 50 Hanover Road, Florham Park, New Jersey USA (ASCO), for service call (ASCO)

CHROME ALLEY CAT L.E.D. FUEL & BATTERY GAUGE 7381

O & M Manual for the EATON Generator Ready Loadcenter

VL Circuit Breaker DG 150A frame

Double Pole Circuit Breaker Kit for Non-Regenerative MinPak Plus DC Drives

Electrically Held to Mechanically Latched Contactor

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Cutler-Hammer IB E. O & M Manual for the Cutler-Hammer ATC-400 Controlled AGswitch

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION

www. ElectricalPartManuals. com Systems Pow-R Breaker Transfer Switches Technical Data Page 1

2.2. Molded Case Circuit Breakers. Contents. NG-Frame ( Amperes) Series G

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

Industrial Control Transformers

CONTENTS. This Product is Certified by CANADIAN STANDARDS ASSOCIATION and Bears the Mark:

Application Description

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

Table Type FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B.

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

PB-Series. GFCI/ELCI & Panel Seal

Cutler-Hammer. January 2001

RENEWAL PARTS AK-2-15 AK-2-25 AK-3-25 AKF-2-25 AK-2A-15 AK-2A-25 AK-3A-25 AKF-2A-25 AKU-2-25 AKU-3-25 AKU-2A-25 AKU-3A-25

MAGNETIC MOTOR STARTERS

SE-3SCR-LM MANUAL MOTOR LOAD MANAGER

Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

INSTALLATION INSTRUCTIONS

Instruction sheet WARNING. October, 2014

Transcription:

Cutler-Hammer Installation Instructions for Undervoltage Release Mechanism (Handle Reset) with LED for E 2 L and E 2 LM Mining Circuit Breakers CONTACT WITH ENERGIZED EQUIPMENT CAN RESULT IN DEATH, SEVERE PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAMAGE. DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTE- NANCE ON EQUIPMENT WHILE IT IS ENERGIZED. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED SAFE- TY PROCEDURES. CUTLER-HAMMER IS NOT LIABLE FOR THE MISAP- PLICATION OR MISINSTALLATION OF ITS PROD- UCTS. The user is cautioned to observe all recommendations, warnings, and cautions relating to the safety of personnel and equipment as well as all general and local health and safety laws, codes, and procedures. WARNING The recommendations and information contained herein are based on Cutler-Hammer experience and judgement, but should not be considered to be all-inclusive or covering every application or circumstance which may arise. If any questions arise, contact Cutler-Hammer for further information or instruction. 1.0 INTRODUCTION General Information The undervoltage release mechanism (UVR) (Figure 1-1) monitors a voltage (typically a line voltage and trips the circuit breaker when the voltage falls to between 70 and 35 percent of the solenoid coil rating. The UVR consists of a continuous rated solenoid with a plunger and reset lever assembled to a plug-in module. The plug-in module is mounted in slots in the top of the trip unit and occupies the accessory cavity in the circuit breaker frame. The reset lever resets the UVR when normal voltage is restored and the circuit breaker handle is moved to the resets (extreme OFF) position. With no voltage applied to the UVR, the circuit breaker contacts will not touch when a closing operation is attempted. The UVR is available for 120 VAC. Table 1.1 lists applications and electrical ratings data for the UVR. For this publication, the term circuit breaker shall also include molded case switch and motor circuit protector. Depending on the model ordered, connections for the UVR are in one of four forms. The standard wiring configuration is pigtail leads exiting the rear of the base directly behind the UVR. Optional configurations include a terminal block mounted on the same side of the base as the accessory, leads exiting the side of the base where the accessory is mounted, and leads exiting the rear of the base on the side opposite the accessory. The 18-inch long pigtail leads are color coded for identification; identification labels are provided for pigtail leads and terminal block points. This instruction leaflet (IL) gives detailed procedures for installing the UVR. Figure 1-1 Undervoltage Release Mechanism (Handle Reset) with LED installed in L-Frame Mining Circuit Breaker Effective March 1998.

Page 2 Replacement Interphase Barrier UVR Plug-in Module (With Pigtail Leads) Intermediate Plunger Intermediate Plunger MINING UVR CAT UVM4PO8K STYLE 1483D42G01 UV-1 UV UV-2 Connection Diagram Label (Pigtail Leads Shown) FREQ VOLTS VA 50/60 Hz 120 2.4 Accessory Identification Label Recessed Hole Trip Unit Trip Unit Barrier Figure 2-1 Undervoltage Release Mechanism (Handle Reset) Kit Figure 2-2 Trip Unit Barrier Removal 2.0 INSTALLATION The UVR can be field-installed in E 2 L and E 2 LM mining circuit breakers. Before attempting to install the UVR, check that the catalog number is correct as ordered. The UVR, shown in kit form in Figure 2-1, is installed in the left accessory mounting cavity of a 3-pole circuit breaker. A UVR must be installed in the circuit breaker before the circuit breaker is mounted in an electrical system. To install the UVR, perform the following procedures: A circuit breaker that is mounted in an electrical system must be removed to install the accessory. To ensure correct accessory installation, the circuit breaker must be placed on a horizontal surface. WARNING THE VOLTAGES IN ENERGIZED EQUIPMENT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY. SPECIAL ATTENTION SHOULD BE PAID TO REVERSE FEED APPLICATIONS TO ENSURE NO VOLTAGE IS PRESENT. BEFORE REMOVING A CIRCUIT BREAKER INSTALLED INA N ELECTRICAL SYSTEM, MAKE SURE THE CIRCUIT BREAKER IS SWITCHED TO THE OFF POSITION AND THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PERFORMED. For new circuit breaker installation, the trip unit must be installed in circuit breaker before attempting to install a UVR. Refer to I.L. 29C607, I.L. 29C608, I.L. 29C609 or I.L. 29C610 for instructions on how to install trip unit. 2-1. Switch circuit breaker to OFF position.

Page 3 Replacement Barrier Supplied with UVR Switch Kit Remove Interphase Barrier To install UVR, circuit breaker operating mechanism must be in tripped position. Molded case switch trip units are not equipped with a Push-to-Trip button. For molded case switches, omit step 2-3. 2-2. Disconnect and remove circuit breaker from installation and terminal connections. 2-3. Press PUSH-TO-TRIP button to trip operating mechanism, and check handle moves to trip position with white colored indicator visible in escutcheon window. 2-4. Remove circuit breaker cover screws and covers. Figure 2-3 Interphase Barrier Replacement 2-5. For high instantaneous trip-type (catalog suffix K designation) molded case switches, find recessed hole in either of the trip unit outer poles (Figure 2-2). Push intermediate plunger supplied with UVR in one hole to trip the molded case switch. Remove plunger to prevent it falling out of recessed hole in trip unit and into molded case switch mechanism. 2-6. Remove interphase barrier between accessory mounting cavity and operating mechanism (see Figure 2-3). UVR Reset Lever in Slot in Interphase Barrier in Front of Handle Arm UVR Plug-in Module Interphase Barrier 2-7. Install replacement interphase barrier (supplied with kit) in base (see Figure 2-3). 2-8. Install UVR as described in following steps (see Figure 2-4). WARNING IF UVR IS REMOVED FROM CIRCUIT BREAKER, INTERMEDIATE PLUNGER MUST ALSO BE REMOVED. FAILURE TO REMOVE THE INTERMEDI- ATE PLUNGER CAN RESULT IN EQUIPMENT DAM- AGE. a. Remove barrier from trip unit accessory mounting slots in pole bing used for accessory (Figure 2-2). b. Position intermediate plunger in trip unit (Figure 2-2). Figure 2-4 UVR Installation c. Press intermediate plunger into recess in trip unit and hold in position.

Page 4 d. Push circuit breaker handle towards the ON position and hold while sliding UVR plug-in module into slots in trip unit (Figure 2-4) until retaining clip snaps into trip unit. For terminal block assemblies, slide terminal block into mounting slot on side of base as plugin module is being positioned. Rear Exiting Leads (Preferred) Terminal Block For a UVR having rear or opposite-side exiting pigtail leads, thread leads through in side of base before attempting to insert the mounting bracket. Pigtail leads exiting in this manner should be eased through trough as mounting bracket is inserted into trip unit retaining slots. Use center trough also for leads exiting the side of the circuit breaker. Side Exiting Leads Figure 2-5 Accessory WIring Options Opposite-Side Exiting Leads LEADS SHOULD BE FORMED AND ROUTED TO CLEAR ALL MOVING PARTS WHEN ACCESSORY IS PROPERLY INSTALLED. PIGTAIL WIRES COULD BE DAMAGED IF IN CONTACT WITH MOVING PARTS. 2-9. Route wiring to meet installation requirements (Figure 2-5). If required, complete routing of leads of opposite side through rear wiring trough. Solenoid Plunger WARNING FAILURE TO KEEP FINGERS AWAY FROM MOVING PARTS CAN CAUSE PERSONAL INJURY. WHEN CHECKING ACCESSORY, DO NOT PUT FINGERS NEAR MOVING PARTS INSIDE CIRCUIT BREAKER CASE. SPRINGS CAUSE INTERNAL PARTS TO MOVE QUICKLY AND WITH FORCE. 2-10. Perform mechanical check of UVR after installation: a. WIth the circuit breaker still electrically isolated, reset the circuit breaker. Figure 2-6 Screwdriver Depressing Undervoltage Release Mechanism Solenoid Plunger Flatblade Screwdriver b. Mechanical check. Using a small flat-blade screwdriver, (Figure 2-6), push in and hold solenoid plunger. Switch circuit breaker to ON. Release solenoid plunger and check that circuit breaker trips. c. Reset circuit breaker handle and check that handle arm moves reset lever to reset the solenoid plunger. d. If mechanical check does not trip circuit breaker, see if UVR and intermediate plunger are correctly installed. If UVR and intermediate plunger are cor-

Page 5 Terminal Block Connection Diagram Label (When Used) Modification Label rectly installed. If UVR and intermediate plunger appear to be properly installed and problem persists, contact Cutler-Hammer. CAUTION Accessory Identification Label Pigtail Connection Diagram (When Used) WHEN INSTALLING CIRCUIT BREAKER MAIN COVER, MAKE SURE THAT ALL INTERNAL PARTS ARE IN PLACE: SLIDING HANDLE BARRIER IS POSITIONED SO THAT THE HANDLE OPENING IS ALIGNED WITH THE HANDLE. ALL LEADS ARE CLEAR OF THE COVER. 2--11. With circuit breaker handle in the TRIPPED position and accessory pigtail leads (if used) routed as required, install circuit breaker covers. Secure with pan-head screws. Torque to 20-22 lb-in. (2.26-2.49 N.m.) Figure 2-7 Preferred Mounting Locations for Accessory Nameplate Labels 2-12. Remove and discard UL listing label on LDB circuit breakers only. Orange Overcurrent Protection (Supplied by Customer When Required) UV1 2-13. Place accessory labels (supplied with kit) on circuit breaker (see Figure 2-7). 2-14. Where practical and after taking all necessary safety precautions, apply rated voltage to UVR. Reset and close circuit breaker. Confirm that circuit breaker trips when voltage is removed. 2-15. Install circuit breaker. Monitored Voltage Brown UVR Monitored Voltage UV2 UVR Accessory labels show connection diagram for UVR contacts. Pigtail leads are color coded orange and brown. 2-16. Connect UVR as required (see Figure 2-8). Overcurrent Protection (Supplied by Customer When Required) Cutler-Hammer assumes no responsibility for malfunctioning accessories installed improperly by the customer. Pigtail Leads Terminal Block Figure 2-8 Undervoltage Release Mechanism (Handle Reset) Connection Diagram

Page 6 Table 1.1 AC (50/60 Hz) Undervoltage Release Mechanism (Handle Reset) Ratings ➀ Application Electrical Operating Ratings Approximate Operating Time (ms) Ratings Voltage Supply Dropout Pickup VA Min.➁ Initiation➂ Maximum Dielectric➃ (V) Voltage Voltage (V) Voltage (V) UVR Circuit Circuit Withstand (V) Min. Min. Max. Response Breaker Breaker Voltage (V) Contact Contact Separation Opening 120 120 44.5 77 93.5 2.1 5 15 25 1500 ➀ Endurance 400 electrical operations plus 5600 mechanical operations ➁ UVR will override a momentary voltage dip up to the response time shown ➂ Unlatching occurs 1 millisecond before circuit breaker contacts begin to separate ➃ For 1 minute

Page 7

Page 8 Cutler-Hammer Five Parkway Center Pittsburgh, PA 15220 (ISI) Style 6603C60H01 Printed in U.S.A.