Technical News. Drives: benefits, operation, pitfalls and harmonic solutions. Issue #59 - January 2011

Similar documents
Technical News. Ensuring low voltage air circuit breakers are fit for service. Issue #61 - October 2011

Consumer Switchboards and Circuit Protection Flexible range designed for domestic and commercial installations

Sinus Penta Variable Speed Drive

MOD6 RCBOs. New and retrofit solutions providing reliable personnel protection POWER DISTRIBUTION AND PROTECTION 1300 NHP NHP 0800 NHP NHP

Technical News. High Efficiency Motors & Type 2 Coordination Motor Starting. Industrial Electrical and Automation Products, Systems and Solutions

Practical Variable Speed Drives and Power Electronics

Common Bus and Line Regeneration

When to use a Soft Starter or an AC Variable Frequency Drive

ASHRAE - Variable Speed Drives. By Dan Watkins, LEED BD+C Bornquist, Inc.

CT430 - Soft Starters on Motor Applications

Table of Contents. Foreword...xiii. Chapter One Introduction, Objectives of the Guide...1

Qingdao Zener Electric Co., Ltd

Question Number: 1. (a)

Variable Speed Pumping

Technical News. Power Factor Correction. What technology is best for you? Specialists in electrical and automation products, systems and solutions

R13 SET - 1. b) Describe different braking methods employed for electrical motors. [8M]

Introduction to Variable Speed Drives. Pekik Argo Dahono Electrical Energy Conversion Research Laboratory. Institute of Technology Bandung

Steve Schouten. Donna Densmore

VFD Best Practices: Getting the Most from Your VFD Investment

Power Quality Solutions POWER QUALITY SOLUTIONS: ACTIVE HARMONIC FILTERS

SDC,Inc. SCR-Regenerative Ac Drive

Power Quality and Energy Management

Variable Speed Drives in Electrical Energy Management. Course Content

Variable Speed Drives Controlling Centrifugal Pumps Energy Savings

ELECTRICAL POWER and POWER ELECTRONICS

Variable Frequency Drive Basics

Inverter control of low speed Linear Induction Motors

SECTION 3 HPS CENTURION R REACTORS AND RC DV/DT FILTERS

Chapter 3.2: Electric Motors

Electrical Drives I. Week 11: Three phase Induction Motor Starting

Código de rotor bloqueado Rotor bloqueado, Letra de código. Rotor bloqueado, Letra de código

Variable Frequency Drives

ADS7 AC Contactor Starters

POWER SUPPLY FOR ASYNCHRONOUS MOTORS

AC Adjustable Speed Drives (ASD s)

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Introduction to Electrical Machines

Ensuring the Safety Of Medical Electronics

ABB Softstarter Benefits Charnchanok Thongprad

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Technical Explanation for Inverters

Drive Fundamentals. Motor Control Bootcamp May 15-18, Copyright 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC CO900H

Key elements of the AS3000 Wiring standards and some of the recent changes.

Pump ED 101. Power Factor (Part 2) - - Electricity Behaving Better

NHP MODdrive TM for Building Services

Electric Motor Controls BOMA Pre-Quiz

Benefits of VFD for single to three phase conversion

Air Circuit Breaker Retrofitting

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

2 SLR Series Line Reactors... 50

FAULT ANALYSIS FOR VOLTAGE SOURCE INVERTER DRIVEN INDUCTION MOTOR DRIVE

Sensible flow saves Variable Speed Drives (VSDs) saving energy in the industrial sector

EE6351 ELECTRIC DRIVES AND CONTROL UNIT-1 INTRODUTION

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF MECHANICAL ENGINEERING ME 6351 ELECTRICAL DRIVES AND CONTROL UNIVERSITY QUESTIONS AND ANSWERS

Electrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition)

Delta Products VFD CP2000 Bypass Control Packages.

Handout Activity: HA773

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

Controls. CONTACTORS CWB Line (up to 40A)

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

Appendix: Safety and application notes for... 15

Power System Solutions (PSS)

Application manual Dry type power factor correction capacitors

ECE1750, Spring Motor Drives and Other

Liebert. FP 50Z kva

Variable Speed-Drive Troubleshooting

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment

ABB n.v Power Quality in LV installations

Instruction Manual. Harmonic Filter AHF 005/010. Drives Solutions

For motors controlled

ELECTRICIAN S THEORY EXAMINATION 21 June 2014 QUESTION AND ANSWER BOOKLET

Installation Manual for DC Injection Brake Units

The cement and minerals industry

Power Factor Correction

Product brochure. Medium voltage AC drive ACS 2000, kva, kv

Every Load. ISLe 5. The right technology matters. Everywhere. Cummins Locations. Customer Support Every place you need it. Emissions Technology.

MSC VAC. Variable Speed Drive. Proudly 100% Australian Owned Australian Manufacturers & Distributors of Variable Speed Drives & Soft Starters

Technologies & Products Press Conference LeaXield Active filter for leakage current minimization

Shaft Grounding Rings. Protecting VFD Driven Motors from Bearing Currents

A Compact, Liquid-Cooled Variable Speed Drive for High Horsepower Applications

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

DC-DC CONVERTER. 5.1 Advantages & Disadvantages of DC-DC Converters

Abstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Frequently Asked Questions. ABB low voltage drives Low Harmonic AC drives, 7.5 to 2800Hp

Chapter 3.1: Electrical System

Surabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality

SINAMICS SM150. 4/2 Overview. 4/2 Benefits. 4/2 Design. 4/6 Function. 4/8 Selection and ordering data. 4/8 Options

AC DRIVES. AC Drives. The word "drive" is used loosely in the industry. It seems that people involved

FOLLOW THE ARROWS. Alspa MV1000 Variable speed drive TEL: INSTALLATION QUICK START PROGRAMMING. FIRMWARE VERSION: 1.

Product brochure. Medium voltage AC drive ACS2000, kw, kv

Appendix: Safety and application notes for 19

Electric cars: Technology

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

PowerFlex 6000 Medium Voltage AC Drives

THE PROTECTION OF INDUSTRIAL CAPACITOR BANKS BY CURRENT LIMITING FUSES. By M.J. Smart and B. Wadcock

Is Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics

SINAMICS SM150. Siemens product performance features. Competitor product profile. Components. Power, transport units. Service friendliness

Transcription:

Issue #59 - January 2011 Technical News INDUSTRIAL ELECTRICAL AND AUTOMATION PRODUCTS, SYSTEMS AND SOLUTIONS Drives: benefits, operation, pitfalls and harmonic solutions Written by Darren Besanko Product Manager - Drives please circulate to: nhp.com.au nhp-nz.com

The electric induction motor has been used in industries since the late 1800 s. Motor speed was determined by the number of poles or multiple fixed speed windings in the stator. Early speed regulation was possible using DC motors, but these were inherently a high maintenance item and very expensive. With the onset of progress in power electronics, it was becoming possible to replace DC motor speed control with AC induction motors using electronic starting methods. Earlier electronic AC Variable Speed Drives (VSDs) were made possible by the 1957 introduction of the silicon controlled rectifier (SCR), however as they were connected to a DC bus they did not turn off automatically and needed forced commutation to turn off the SCR. In the 1980 s the Insulated-Gate Bipolar Transistor (IGBT) became the prevalent device for the inverter section of the VSD (replacing SCRs), and has remained so for low voltage drives to date. Latest developments include advanced algorithms which allow increased functionality. For example, torque control, which enables the drive to run using a torque reference, and improved sensorless vector control offering greater torque at very low speeds without the use of an encoder. Why? Some of the benefits of using Variable Speed Drives Significant energy savings are possible by running equipment like pumps and fans only at the speed needed to meet the demand - It s possible to optimise plant productivity and quality by accurate control of motor speeds to fine tune a complete process. We can also accommodate for a changing process or machine requirement. For example, we can alter a pump speed to accommodate changes in water supply demand, alter the speed of manufacturing, or cater for changing ventilation requirements in a building. - Significant energy savings are possible by running equipment like pumps and fans only at the speed needed to meet the demand. A common retrofit application removes throttling valves and uses a variable speed drive on a pump. - Significantly reduces starting current to minimise peak demand and reduce associated tariffs. Variable speed drives offer the best technology to minimise current draw on start up. Not only does this avoid the fixed cost charges associated with a huge peak demand, but it is also possible to keep starting the motor many times an hour. - High-level automation is possible, which means we can monitor the drive and change parameters on the fly. For example, if four different products are made on one process line it is possible to quickly download different parameter sets for all drives and switch to the new product. This also offers a high degree of remote monitoring. - VSDs have inherent soft starting/stopping capabilities thus reducing mechanical shock and eliminating water hammer in pumping applications. - Drives also offer a power factor close to unity, so no additional power factor equipment has to be used for motor loads which are supplied by variable speed drives. Pump energy saving tool Optimise plant productivity Energy savings Reduction of peak demand High level of Automation 2

How does a Variable Speed Drive work anyway? A drive changes the speed of the motor by changing the frequency to the motor This brief discusses in a simple way what a drive actually does to change the speed of a motor, and some of the associated benefits. Most technical issues that arise from the use of a Drive stem from the essential elements of how a drive operates, and a basic understanding of the fundamentals will help understand these more easily. An adjustable speed drive controls the speed and direction of an AC or DC motor. Advanced drives can also operate in a torque control mode. We will consider only an AC motor and low voltage drives (up to 690 V). The speed of a motor is dependent on both the number of poles and the applied frequency. n = (120f / p) - slip Where N = RPM F = frequency P = number of poles A drive changes the speed of the motor by changing the frequency to the motor. As an aside, the impedance of the motor is determined by the inductive reactance in the windings, and it changes as the frequency changes. In order to keep the current reasonable and maintain torque we lower the applied voltage to the motor as the frequency is reduced, and this is referred to as volts-hertz control. For example, consider a 4 pole induction motor, where the nominal speed rating is: 1490 rpm at 50 Hz Applying the equation we will achieve: 1192 rpm at 40 Hz, or 894 rpm at 30 Hz, etc. To control the voltage and frequency to the motor drives, employ pulse width modulation (PWM) methodology. DC voltage is applied to the motor by controlled pulses at high frequency, which results in voltage that approximates a sine wave of the chosen frequency (Fig 1.). IGBT s or Isolated Gate Bipolar Transistors are the current technology used and can switch the voltage very fast. The switching frequency is typically in the range 1.6 khz to 16 khz. Fig 1. Pulse Width Modulation (PWM) In order to obtain DC for switching, a rectifier section is at the input of a drive, and this creates DC voltage on the DC bus. The inverter section at the output side provides the PWM waveform (Fig.2). RecTifier DC bus Inverter IGBT Fig 2. Typical LV drive topology and resultant waveform 3

Affect on motor performance Using a VSD affects the torque-speed curve of the motor, and the result is that we can maintain full torque across the normal speed range up to 50 Hz (Fig 3.). With a high performance drive we have the ability to provide a high starting torque at low speed approaching the pull-out or break-away torque of the motor, providing the drive is selected with suitable overload capacity. Under normal load conditions, full motor torque can be provided up to 50 Hz, and then torque capacity reduces as shown right (Fig 3.). Running the motor above 50 Hz limits the torque output available from the motor as we move into a region of constant power, and as the speed increases the torque available decreases. Fig 3. Motor torque curve with VSD Technical considerations for the motor Using a VSD has a number of technical implications on the motor that need to be considered. MOTOR COOLING Use of the drive to run the motor at low speeds affects the cooling capacity of the motor fan, and with high torque loads this can lead to the motor overheating. Motor manufacturers usually provide data indicating when an externally powered fan is needed, in which case they fit a forced cooling kit. As a rule of thumb, anything less than half speed demands external cooling and is of particular concern with a constant torque load. BEARING CURRENTS The high switching frequency can lead to capacitive bearing currents. These currents flow through the bearings which can cause brinelling of the bearing surfaces. This is of particular concern above 132 kw, and motor manufacturers usually stipulate when their motor needs special precautions. Often the combination of an insulated non-drive end bearing is used, plus an earth brush kit. Alternatively a sine wave output filter can be applied to minimise bearing damage. Fig 4. Bearing race damage Fig 5. Current paths of capacitive current 4

NOISE Motor noise output can be regulated by altering switching frequency. Often people raise the switching frequency of the drive to make the noise less noticeable to the human ear. The quality of the electric motor can also affect how loud this is. There are implications of an increased switching frequency and this can lead to increased losses and de-rating of the drive, as well as contributing to higher earth leakage currents. On the flip side, a lower switching frequency may mean a lower drive temperature, higher motor temperature and less leakage current. A sinus filter can be implemented to obtain quieter operation without the drawbacks of raising the switching frequency. VOLTAGE SPIKES High voltage spikes up to 1200 V are possible at the motor terminals, so it is important that the motor insulation is appropriately rated. Please note that the insulation voltage rating is distinct from the temperature class of the insulation. We are not referring here to the Insulation Class of the motor which refers to temperature rise of the motor. High voltage spikes can occur due to reflected waves, and in this case we consider the cable length, impedance mismatch of motor and cable, and switching frequency. On a case by case basis we use output filtering to prevent spikes beyond what the motor can handle and mitigate reflected waves with the use of an output reactor, reflected wave filter or a sinus filter. Fig 6. Schaffner sine wave filter Fig 7. Voltage spikes in motor cable 5

HARMONICS AND SOLUTIONS Variable speed drives create disturbance on the supply, and this has become a topic of discussion in recent times as people become more aware of the Standards and hidden effects of harmonic disturbance. The presence of harmonics can result in reducing the life of other equipment on the supply, hotter cables and transformers resulting in shortened longevity, random tripping of protection devices, increased losses in DOL motors, and overload of power factor correction equipment. Five popular solutions used to minimise harmonic disturbance. MULTI-PULSE SOLUTIONS Multi-pulse solutions, often with large kw drives, can be used to reduce harmonics without adding an additional filtering device. A 12-pulse solution uses two rectifier modules for the VSD and runs duplicated supply cabling to the drive from a transformer with two secondary windings. 18 and 24-pulse solutions are also on the market. Using this, the 5th, 7th, 17th, and 19th harmonics are cancelled out at the transformer, and typically reduce current distortion down to approximately 10 %. REACTORS The most common and significant starting point is often an AC or DC choke, and many premium drives have one of these integral to the unit. Without these, harmonic current distortion can be up to 100 % and the inclusion of this base level component will bring the current distortion down to approximately 35 %. Fig 8. 12-pulse configuration ACTIVE FRONT END Active front end solutions are a second drive-based harmonic solution, and in this arrangement current harmonic distortion down to a level of approximately 4 % is achievable. As the name suggests, rather than use diode rectification we switch the incoming power to the drive using transistors and this offers a sinusoidal input current. As well as providing a low harmonic solution, a variation on this offers electrical braking with the excess energy being fed back to the supply, known as a Regenerative Solution. A higher purchase price is offset by reduced energy consumption for loads requiring frequent braking. Harmonics are also significantly reduced. Fig 9. Active front-end topology 6

ACTIVE FILTERS Active filters are a high end device for controlled and selective elimination of harmonics, and are great when there are a number of drives connected or where the load varies. They allow all standard off the shelf drives to be used and provide some flexibility for the odd drive being added or changed. The active filter also sits in parallel, so you are not relying on the device to be operational in order for drives to have power. One active filter can compensate for a number of drives, so it is a smart solution to achieve harmonic compliance, at a level of approximately 4 % current distortion. PASSIVE FILTERS Passive filters are usually applied for smaller drive installations. They sit in line with the supply to the drive and are often available as a 5, 8, or 10 % filter. Capacitors may be switched out when at low load in order to avoid a leading power factor situation. A passive filter is easy to install and helps reduce the harmonics right at the drive. Fig 10. Schaffner active filter Fig 11. Schaffner passive filter CONCLUSION AC drives have been developed to the point where they can typically match the level of performance of a constant torque DC drive system, however, doing so more economically and with less maintenance. Some advantages of using variable speed drives include optimising productivity, energy savings, reduced starting current and peak demand charges, and a high level of automation. NHP are well placed to discuss your application in detail and offer the best technical solution to your VSD system design. 7

If you would like previous copies of Technical News, please complete the following form and fax to NHP on (03) 9429 1075 to the attention of the Marketing Department. Name:... Title:... Company:... Please post to: address...... Telephone: ( )... Fax: ( )... Please email to:... Other issues currently available. Please tick those you would like to receive. 1. First edition (Latched and delayed contactors) 2. Non-standard contactor applications (Parallel and series connections of contacts varying frequencies) 3. Contactor failure (Reasons for the failure) 4. Soft start for generator loads (Advantages of electronic soft starters) 5. Set the protection (MCCB breakers and application) 6. Contactor operating speed (Difference between AC and DC systems) 7. Quick guide to fault levels (Calculating the approximate fault levels) 8. IP ratings what do they mean? (IP Ratings, use and meaning) 9. Utilisation categories (Electrical life of switches) 10. AC variable frequency drives and breaking (Regenerative energy) 11.Don t forget the motor protection (Motor protection devices and application) 12. Electrical life of contactors (How and why contactors are tested) 13. Liquid resistance starter developments (For large slipring motors) 14. Taking the hiss out of DC switching (DC switching principles) 15. Start in the correct gear (Application of different motor starters) 16. Application guide to lamp selection (Industrial pushbutton controls) 17. Electrical surges can be expensive (Electrical surges) 18. Putting the PLC in control (advantages of the PLC) 19. The thinking contactor (The development of the contactor) 20. Some don t like it hot (Temperature rise in electrical switchgear) 21. Pollution of the airwaves (Unwanted signals and their effects on motor protection devices) 22. What s different about safety? (Safety devices and their application) 23. Talk about torque (Motors and torque) 24. Power factor what is it? (Power factor and correction equipment) 25. Terminations, good or bad? (Terminals) 26. RCDs are saving lives (Earth leakage protection; RCDs) 27. The quality switchboard(switchgear and protection devices for Switchboards) 28. How does electrical equipment rate (Understanding ratings of electrical equipment) 29. EMC - what s all the noise about (Understanding EMC) 30. Controlling high short circuit currents with current limiting circuit breakers (Short circuit co-ordination KT 7) 31. Another step in electrical safety (Changes to electrical safety) 32. Keep your cables cool (New requirements on cable protection) 33. A leak to earth can be electric (RCDs) 34. Keep Cool (Derating) 35. Improving star-delta protection (Overload and short circuit protection) 36. Does your CT measure up? (Selecting the correct current transformer) 37. Is your copper flexible? (Flexible busbars) 38. Where did the 10 volts go? (World uniform voltages) 39. Motor protection and wiring rules (overload protection) 40. Confused about which RCD you should be choosing? 41. Circuit breakers working together 42. Keeping in contact 43. Is your switchboard in good form? 44. Automation in a technological world 45. Thermal simulation of switchgear 46. Cable Considerations 47. Output chokes for use with variable speed drives 48. VSD Installation Techniques 49. The modern Scada System 50. 50th Edition Special 51. Electrical design considerations for commercial buildings 52. Terminal temperatures - how hot are they? 53. Causes of premature failure 54. Control voltages for contactors 55. Will it turn you off? (Electrical switchgear welding) 56. Electrical Arcs - Beauty and the Beast 57. The Power of Copper 58. Industrial networking with Ethernet IP TNL is available as a download from NHP s Online Resource Centre (ORC), visit nhp-online.com.au. The ORC provides members with up-to-the-minute technical information and powerful product tools, all at the click of a mouse button. Register for membership today! Editorial content: Please address all enquiries to: The Editor - NHP Technical News PO Box 199, Richmond, Victoria, 3121. NHP Electrical Engineering Products Pty Ltd A.B.N. 84 004 304 812 Copyright NHP 2010 NTNL59AUS 1211 * Rockwell Automation products not available from these locations AUSTRALIA nhp.com.au 1300 NHP NHP Victoria Melbourne +61 3 9429 2999 Laverton +61 3 9368 2901 Albury/Wodonga +61 2 6049 0600 Dandenong +61 3 8773 6400 Tasmania Hobart +61 3 6228 9575 Launceston +61 3 6345 2600 New South Wales Sydney * +61 2 9748 3444 Newcastle * +61 2 4960 2220 Wollongong * + 61 2 4272 5763 Act Canberra +61 2 6280 9888 Queensland Brisbane * +61 7 3909 4999 Townsville +61 7 4779 0700 Rockhampton +61 7 4927 2277 Toowoomba * +61 7 4634 4799 Cairns +61 7 4035 6888 South Australia Adelaide +61 8 8297 9055 Western Australia Perth +61 8 9277 1777 Northern Territory Darwin +61 8 8947 2666 NEW ZEALAND nhp-nz.com 0800 NHP NHP Auckland +64 9 276 1967 Hamilton +64 7 849 0257 Napier +64 6 843 6928 New Plymouth +64 800 NHP NHP Wellington +64 4 570 0634 Christchurch +64 3 377 4407