Excel 10 W7751H3007 VAV ACTUATOR

Similar documents
Excel 10 W7751H SMART VAV ACTUATOR BEFORE INSTALLATION INSTALLATION

Excel 10 W7751J Smart VAV Actuator

Excel 10 W7751J Smart VAV Actuator

Excel 10 W7751H Smart VAV Actuator

ComfortPoint Programmable Lon, VAV/Unitary Controllers

Excel 15 W7760A BUILDING MANAGER

Spyder BACnet Programmable Controllers

CP-VL6436A, CP-VL6438N, CP-UL6438 ComfortPoint Programmable, VAV/Unitary Controllers

S10010 / S SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS 10/20 Nm (88/177 lb-in) FOR MODULATING AND FLOATING CONTROL SPECIFICATIONS GENERAL

D690 Round Damper LOW-LEAKAGE, SINGLE-BLADE FEATURES APPLICATION PRODUCT DATA. Contents

S1024-2POS / S POS S2024-2POS / S POS

Minimum 27 in-lb torque

22 POINT FULLY PROGRAMMABLE HVAC CONTROLLER

Versatile and Powerful

35 and 70 lb-in. Non-Spring Return Direct Coupled Actuators ML6161, ML7161, ML6174, ML7174

Minimum 27 in-lb Torque

Versatile and Powerful

Installation/ Operation Maintenance. VariTrac Dampers

LF Series At A Glance

ZG-JSL, ZG-JSLA Jackshaft Retrofit Linkage For AF, NF, LF, NMX and AMX Series Actuators

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

LF Series Spring Return Direct Coupled Actuator

ML7420A/ML7425A,B. Honeywell. Electric Linear Valve Actuator FEATURES SPECIFICATIONS GENERAL SPECIFICATION DATA

Installation Instructions

MS Application. Features. Proportional Valve Actuator General Instructions

ML6420A/ML6425A,B. Electric Linear Valve Actuators

NFB24, NFB24-S, NFX24, NFX24-S On/Off, Spring Return, 24 V

UHC-202 Hardware Guide

Installation Instructions

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

MF4E MF4E

V5050A,B FLANGED LINEAR VALVE PN16 AND PN25/40

NMB (X) 24-MFT. Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators

Minimum 18 in-lb Torque. Applications. TF Series At A Glance. TF Series Spring Return Direct Coupled Actuator. For damper areas up to 4.

VA-7450 Series. Electric Valve Actuators

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators

Installation, Start-Up and Configuration Instructions

Metasys Zoning Package Installation

M100F Incremental Motor Actuator R81F Interface Board

MS4104, MS4109, MS4604, MS4609, MS8104, MS8109 Fast-Acting, Two-Position Actuators

Minimum 90 in-lb Torque. Applications. NFB, NFX Series At A Glance. NFB and NFX Series Spring Return Direct Coupled Actuator

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

M7410E SMALL MODULATING LINEAR VALVE ACTUATOR

LMCB24-SR LMCB24-SR-T. applications. Dimensions (All numbers in brackets are in millimeters.) 1/4 to 3/4 [6 to 20] 5/16 to 3/4 [8 to 26] 1.

DuraDrive MF /MS Series Non-spring Return Rotary Electronic Damper Actuators 24 Vac Three-position/Modulating

Laboratory Room Controller

Generator Set Applications FT-10 Network Control Communications Module (CCM-G) Kit

Torque min. 35 in-lb, for control of air dampers

Installation, Service, and Troubleshooting Instructions

SLIM LINE FUME HOOD MONITOR

Installation Instructions

MVN Rotary Valve Actuators FOR CONTROL BALL VALVES VBG (DN15 TO DN32)

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS

Installation Instructions for the PowerCommand 3100 FT-10 Network Genset Communications Module (GCM) Kit

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

MODEL 8682 SUREFLOW ADAPTIVE OFFSET CONTROLLER

Mount directly to 1.05 jackshafts. AF230 US (p. 02) AF230-S US (p. 20) AF24-S US (p. 18)

AF Series Spring Return Direct Coupled Actuator

V5049A FLANGED LINEAR VALVE PN25/40

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m)

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS

AF Series Spring Return Direct Coupled Actuator

EDA-8100 Electric Damper Actuator

Hardware Installation. Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN

Digital Room Thermostats with Touch Screen LCD

M9206-GGx-2S Series Proportional Electric Spring Return Actuators

CP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions

ATP-2040 Electric Damper Actuator/Transmitter

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return Rotary 24 Vac 3-position Control

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

NV Direct Coupled Globe Valve Actuator

CP-8301-xxx Series. Application. Features. Applicable Literature. 1 to 15 Vdc Input Electronic Actuator Drive General Instructions

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

Excel 10 W7751B,D,F,H,J VARIABLE AIR VOLUME CONTROLLER

MicroTech II Applied Rooftop Unit Controller

MF /MS Series

Installation and Start-Up Instructions

M7410E SMALL MODULATING LINEAR VALVE ACTUATOR

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

N05, N10 SERIES NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND TWO-POSITION CONTROL

QUICK START GUIDE VAV CONTROLLERS & WALL SENSORS rue Charles, Suite 100, Mirabel, QC, J7J 1X9

Powers TM Controls EA 338 Electronic Actuator

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary

Logic module. Brief description. Features. Block structure. Data Sheet Page 1/5

LMX120-SR. Proportional Control, Non-Spring Return, Direct Coupled,100 to 240 VAC, for 2 to 10 VDC and 4 to 20 ma

BCS Modutrol Motor M7484A

SECTION AIR TERMINAL UNITS

FT-10 Network Digital I/O Module Kits and

NMQB24-MFT, NMQX24-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

MA40-704X Series MA41-707X Series MA41-715X Series

MX4X-6XXX Series MX4X-7XXX Series. Selection Guide. Applications. DuraDrive Series Actuators and Accessories

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

Q7130A, Q7230A, Q7330A Modutrol IV Interface Modules

M9208-AGx-x Series On/Off and Floating Point Electric Spring Return Actuators

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Proportional Control

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

MS40-717X Series. Application. Features. DuraDrive Series Spring Return Proportional Actuators General Instructions

Transcription:

HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION The Smart VAV Actuator consists of a factorycombined variable air volume (VAV) box controller and a direct-coupled damper actuator with de-clutch mechanism. The actuator/controller assembly is field-mounted to the VAV box damper shaft similar to the mounting of a standard actuator, and the controller wiring is terminated to the screw terminals accessible inside the detachable wiring box. See Fig. 2. The built-in actuator with de-clutch mechanism of the allows the installer to manually open or close its built-in VAV box damper without power or software tool. The contains a Free Topology Transceiver (FTT) LonMark compliant controller containing a Microbridge flowthrough pressure sensor and communicates via the 78 kbaud WORKS Network. The mounts directly onto the VAV box damper shaft and has up to 6 Nm torque, 95 degree stroke, and 110 sec. timing at 50 Hz and 90 sec at 60 Hz. NOTE: Any hardware driven by the triac outputs must have a min. current draw, when energized, of 25 ma at 24 Vac and a max. current draw of 770 ma. MAIN FEATURES Legend for Fig. 2: 1) Universal shaft adapter 2) Mechanical end limits (manually adjustable in increments of 5.5 ) 3) Air flow pick-up connector (-LO) 4) Air flow pick-up connector (-HI) 5) WORKS service 6) Declutch button 7) WORKS service pin 8) Detachable wiring box 9) Anti-rotation bracket 1 2 3 4 6 9 Excel 10 3007 VAV ACTUATOR INSTALLATION INSTRUCTIONS Fig. 1. Excel 10 Smart VAV Actuator 5 7 8 Fig. 2. main features U.S. Registered Trademark EN1B-0279GE51 R0512C Copyright 2012 Honeywell Inc. All rights reserved

EXCEL 10 SMART VAV ACTUATOR INSTALLATION INSTRUCTIONS INSTALLATION The provides IP40 in all mounting orientations. IP40 IP40 1 2 3 4 5 6 7 8 9 101112 Fig. 4. Opening wiring box (1) 360 360 Fig. 3. Permissible orientations providing IP40 Mount the on the damper shaft and allow clearance for wiring, servicing, and module removal. Avoid mounting the in areas where acid fumes or other corrosive vapors can attack the actuator's metal parts, or in areas where escaping gas or other explosive vapors are present. See Fig. 23 for mounting dimensions. The is field-mounted to the VAV box damper shaft. The actuator opens or closes a damper by driving the damper shaft in either the counterclockwise (CCW) or clockwise (CW) direction. If the is to be mounted directly onto a damper shaft, use the mounting bracket and screw included in the delivery. The wiring of the is terminated to a screw terminal block accessible inside the detachable wiring box. See section "Wiring". The is shipped in the fully counterclockwise (CCW) position (95 degrees). Mount the so that the actuator is parallel with the VAV box damper housing. CAUTION Equipment damage hazard. Mounting actuator unevenly with damper housing can damage actuator. Mount the actuator flush with the damper housing or add a spacer between the anti-rotation bracket and the VAV damper box housing (see Fig. 6). VAV box damper shaft 1 2 3 4 5 6 7 8 9 101112 Fig. 5. Opening wiring box (2) VAV box damper housing spacer or washer Fig. 6. Mounting with washer/spacer Before mounting the onto the VAV box damper shaft, do the following: 1. Ensure that the diameter of the damper shaft is within the allowed limits (round: 8 16 mm, square: 6 13 mm). EN1B-0279GE51 R0512C 2

EXCEL 10 SMART VAV ACTUATOR INSTALLATION INSTRUCTIONS 2. Ensure that the damper shaft has a length of at least 40 mm. 3. Determine the direction (CW or CCW) in which the damper shaft rotates to open the damper (see Fig. 7). 4. Determine the angle of the damper opening (can be adjusted in increments of 5.5 ). COOLING AIR FLOW TYPE A DAMPER CW TO OPEN, CCW TO CLOSE COOLING AIR FLOW TYPE B DAMPER CCW TO OPEN, CW TO CLOSE Fig. 7. Determining direction of rotation The is shipped in the fully counterclockwise (CCW) position (95 degrees). The installation procedure varies depending on the damper direction. NOTE: Be aware that, until the is powered and the damper is driven open, starting the fan system with all the VAV box dampers closed can cause duct over-pressurization and damage. Fig. 8. Setting the mechanical end limits Reconfiguring to Match Rotation Direction Using the LNS plug-in, the can be reconfigured to match the direction the damper shaft rotates to open the damper. Reconfigure the damper's direction of rotation to "open" or "closed," according to your needs. To change the damper direction from CW to CCW using the LNS plug-in, proceed as follows. 1. Open the configuration part of the plug-in and select the "Wiring" tab (see Fig. 9). If Damper Rotates CW to Open If the damper rotates clockwise (CW) to open, mount the as follows: 1. Manually open the damper. 2. Push down the declutch button of the, and while holding it down, manually rotate its shaft adapter fully to the clockwise position. 3. Mount the to the VAV damper box and shaft. 4. Set the mechanical end limits of the (see Fig. 8). When the closes, the damper will thus rotate CCW until the mechanical end limits are reached. If Damper Rotates CCW to Open If the damper rotates counterclockwise (CCW) to open, mount the as follows: 1. Manually open the damper. 2. Push the declutch button of the, and while holding it down, manually rotate its shaft adapter fully to the counterclockwise position. 3. Mount the to the VAV damper box and shaft. 4. Set the mechanical end limits of the (see Fig. 8). When the closes, the damper will thus rotate CW until the mechanical end limits are reached. Fig. 9. Wiring tab (default configuration) 2. Then deselect the output configuration (see Fig. 10). 3 EN1B-0279GE51 R0512C

EXCEL 10 SMART VAV ACTUATOR INSTALLATION INSTRUCTIONS fan startup. Use the de-clutch button to open the 's box damper only after the has been powered down (this is to prevent overpressurization in the ductwork on fan startup). To use the de-clutch button, press and hold down the button (this disengages the motor). Turn the damper shaft until the damper is open and then release the button. When power is restored to the, it synchronizes the damper actuator so that the damper is in the correct position on startup. Air Flow Pick-up Connect the air flow pick-up to the two connectors on the. See Fig. 12. AIRFLOW DELTA-P PICK-UP AIRFLOW DIRECTION Fig. 10. Deselecting the output configuration 3. Now, configure the outputs so that the operates counterclockwise (CCW) (see Fig. 11). -LOW +HIGH Fig. 12. Air flow pick-up connections Fig. 11. Configuring the to open CCW The damper direction has now been reconfigured. IMPORTANT It is recommended that the dampers be left in an "open" position after installation to avoid the possibility of over-pressurizing the ductwork on NOTES: Use 6-mm outside diameter with 1-mm wall thickness plenum-rated 1219 FR (94V-2) pneumatic tubing. Always use a fresh cut on the end of the tubing that connects to the air flow pick-ups and the connectors on the. Connect the high pressure or upstream tube to the plastic restrictor labeled (+ HI) or P1 and the low-pressure or downstream tube to the restrictor labeled (- LO) or P2. See labeling in Fig. 12. NOTE: If controllers are mounted in unusually dusty or dirty environments, a 5-micron disposable air filter is recommended for the high-pressure line (marked as +) connected to the air flow pick-up. When twin tubing is used from the pick-up, split the pick-up tubing a short length to accommodate the connections. NOTES: The tubing from the air flow pick-up to the should not exceed 0.914 m in length. Lengths much longer than this can degrade the flow sensing accuracy. EN1B-0279GE51 R0512C 4

EXCEL 10 SMART VAV ACTUATOR INSTALLATION INSTRUCTIONS To avoid damaging the air flow connectors, use caution when removing tubing from them. Always pull straight away from the connector; never remove by pulling at an angle. 1 2 3 Wiring All wiring must comply with applicable electrical codes and ordinances, or as specified on installation wiring diagrams. NOTES: 24 Vac power connections. Verify that multiple controllers powered by the same transformer are wired with the transformer secondary connected to the same input terminal numbers on each W7751. See Fig. 13. Controller configurations are not necessarily limited to three devices, but the total power draw including accessories cannot exceed 100 VA when powered by the same transformer. For power wiring recommendations, refer to Excel 10 W7751B,D,F,H,J Variable Air Volume Controller Application Guide (Product Literature No.: 74-2949). In the case of multiple units operating from a single transformer, the same side of the transformer secondary must be connected to the same input terminal in each and the ground terminals (terminal 3 of the ) must be connected to a verified earth ground for each controller in the group. See Fig. 14. Controller configurations are not necessarily limited to three devices, but the total power draw including accessories cannot exceed 100 VA when powered by the same transformer. For power wiring recommendations, refer to Excel 10 W7751B,D,F,H,J Variable Air Volume Controller Application Guide (Product Literature No.: 74-2949). All loads on a must be powered by the same transformer that powers the. Keep the earth ground connection (terminal 3) wire run as short as possible. See Fig. 14. Do not connect the analog ground (terminal 5) to the earth ground. See Fig. 15. 50/60 Hz X 1 2 1 2 1 2 1 2 Fig. 13. Wiring multiple W7751 units (with transformer secondary connected to same input terminal numbers) 50/60 Hz Fig. 14. Earth grounding Power The 24 Vac power from an energy-limited Class II Power Source must be provided to each. To conform to Class II restrictions, transformers must not be larger than 100 VA. IMPORTANT Power must be OFF prior to connecting to or disconnecting from output terminals 9 and 10. Use the heaviest gauge wire available, up to 2.0 mm2 with a minimum of 1.0 mm 2, for all power and earth ground wiring. For non-plenum, open areas, run cables exposed (or in conduit, if required). 50/60 Hz 32 W7751D,F 24V 24V 28 W7751B 1 2 3 4 9 10 1 IF THE IS USED IN UL 1995 EQUIPMENT AND THE PRIMARY POWER IS MORE THAN 150 V, ONE SIDE OF TRANS- FORMER SECONDARY. 2 3 Fig. 15. Power wiring for multiple controllers NOTES: Unswitched 24 Vac power wiring can be run in the same conduit as the WORKS network cable. Maintain a 76-mm separation between triac outputs and WORKS network wiring throughout the installation. Communications See Chapter "LonWorks System Engineering" of Excel 50/500 LonWorks Mechanisms Interface Description (Product Literature No.: EN0B-0270GE51) for a complete description of WORKS network topology rules. Pull the cable to each device on the WORKS network and connect to communication terminals 11 and 12 of the. 5 EN1B-0279GE51 R0512C

EXCEL 10 SMART VAV ACTUATOR INSTALLATION INSTRUCTIONS Notes on Communications Wiring: All field wiring must conform to local codes and ordinances (or as specified on the installation drawings). Approved cable types for WORKS network communications wiring is Level IV 0.34 mm 2 plenum or nonplenum rated unshielded, twisted pair, solid conductor wire. For non-plenum areas, US part AK3781 (one pair) or US part AK3782 (two pair) can be used. In plenum areas, US part AK3791 (one pair) or US part AK3792 (two pair) can be used. Only one router is allowed with each Excel 10 Zone Manager, and each network segment can have a maximum of one repeater. Unswitched 24 Vac power wiring or sensor wiring can be run in the same conduit as the WORKS network cable. Do not bundle output wires with sensor, digital input or WORKS network wires. Ensure that neither WORKS bus wire is grounded. In noisy (high EMI) environments, avoid wire runs parallel to noisy power cables, motor control centers, or lines containing lighting dimmer switches, and keep at least 76 mm of separation between noisy lines and the WORKS network cable. Do not use different wire types or gauges on the same WORKS bus segment: Step changes in line impedance characteristics cause unpredictable reflections on the WORKS bus. For WORKS termination, use an XAL-Term. Verify Termination Module Placement The installation wiring diagrams should indicate the locations for placement of termination module(s). See Chapter "LonWorks System Engineering" of Excel 50/500 LonWorks Mechanisms Interface Description (Product Literature No.: EN0B-0270GE51). Correct placement of the termination module(s) is required for proper WORKS network communications. Wiring Details Wire to the terminal blocks as follows: 1. Strip 5 mm insulation from the conductor 2. Insert the wire into the required terminal location and tighten the screw to complete the termination. NOTE: Earth ground wire length should be held to a minimum. Use the heaviest gauge wire available, up to 14 AWG (2.0 mm 2 ), with a minimum of 18 AWG (1.0 mm 2 ). NOTE: With the exception of 2.0 mm 2, if inserting two or more wires into one terminal location, use end sleeves. Deviation from this rule can result in improper electrical connection. Fig. 16 through Fig. 21 provide detailed wiring diagrams for the. See the installation diagrams for specific wiring. NOTE: Ensure that the wall module's Configuration DIP Switch is set as shown in Fig. 19. Switches 1 through 3 set the timing of the valve actuator to match the outputs (minimum of 0.1 s, with a max. time of 25.6 s). Switch 4 determines the action of the actuator (OFF = Direct Acting, ON = Reverse Acting). 1 2 3 4 5 6 7 BYP/FAN T7460E BYP/RTN /RTN NOT OPEN SIGNAL STEM UP M IN CLOSED SIGNAL STEM DOWN VALVE ACTUATOR Fig. 16. modulating reheat valve wiring diagram 1 2 3 4 5 6 7 BYP/FAN T7460E BYP/RTN /RTN NOT LINE POWER M IN STAGE 1 Fig. 17. two-stage reheat wiring diagram STAGE 2 EN1B-0279GE51 R0512C 6

EXCEL 10 SMART VAV ACTUATOR INSTALLATION INSTRUCTIONS 1 2 3 4 5 6 7 BYP/FAN T7460E BYP/RTN /RTN NOT TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION. M IN WIRED FOR MODULATING OR STAGED REHEAT LF20 DUCT TEMPERATURE Fig. 18. discharge air sensing CHECKOUT Step 1. Wiring Connections Inspect all wiring connections at the and the T7460 terminals, and verify compliance with installation diagrams. If any wiring changes are required, first be sure to remove power from the controller before starting work. Pay particular attention to: Controller wiring: Be sure that each is wired (terminal 3 on the ) to a verified earth ground using a wire run as short as possible with the heaviest gauge wire available, up to 2.0 mm 2 with a minimum of 1.0 mm 2 for each controller in the group. See Fig. 15. Verify that triac wiring to external devices uses the proper load power/24 Vac terminal (terminal 1 on the ). NOTE: All wiring must comply with applicable electrical codes and ordinances. See the installation diagrams for specific wiring. Step 2. Startup Broadcasting the Service Message The Service Message contains the device's ID number and can therefore be used to confirm the physical location of a particular in a building's WORKS network. There are two methods for broadcasting the Service Message from the : 1. Operating the service pin on the : Insert a thin rod (e.g., paper clip) into the service pin hole (see Fig. 2) and push briefly; the Service Message will then be broadcast on the network. 2. Using the wall module bypass button: Pressing the wall module's bypass/override button for more than four seconds causes the to broadcast the Service Message (supported in firmware version 1.2.15 and higher). When using this method, the occupancy override state of the changes depending upon how long the bypass/override button is pressed. For example, if the button is pressed for six seconds, the will broadcast the Service Message and also enter into the "continuous unoccupied" mode. To clear the "continuous unoccupied" mode, the button must be pressed briefly. PWM PWM OUTPUT FROM CNTRL PERIPHERAL HEAT VALVE ACTUATOR ML7984B PWM VALVE ACTUATOR T6T5 C B W R NOT PWM PWM OUTPUT FROM CNTRL T6T5 C B W R TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION. M IN REHEAT VALVE ACTUATOR ML7984B PWM VALVE ACTUATOR CONFIGURATION DIP SWITCHES LOCATED ADJACENT TO INPUT TERMINAL BLOCK ON ML7948B ON OFF Fig. 19. to PWM Valve Actuator NOTE: Ensure that all transformer wiring is as shown. Reversing terminations will result in equipment malfunction. CONTACTOR () NOT SERIES OR PARALLEL FAN TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION. 1 2 M IN 3 4 REHEAT VALVE ACTUATOR ML7984B PWM VALVE ACTUATOR PWM PWM OUTPUT FROM CNTRL T6T5 C B W R Fig. 20. to PWM Valve Actuator and series or parallel fan 7 EN1B-0279GE51 R0512C

EXCEL 10 SMART VAV ACTUATOR INSTALLATION INSTRUCTIONS Alarms CARE is used to perform the ID Assignment task. Once ID Assignment has been performed and commissioning has been completed, check the WORKS service to determine if there are any alarms. Possible alarm causes can be determined by viewing the nvoalarm, e.g., in CARE. WORKS Service The WORKS Service on the front of the (see Fig. 2) provides a visual indication of the status of the device. When the receives power, the appears in one of the following allowable states: 1. OFF = no power to the processor. 2. Continuous ON = processor is in initialized state. 3. Slow blink = controlling, normal state. 4. Fast blink = the has an alarm condition. When the has an alarm condition, it reports it to the central node on the WORKS network (typically, the Excel 10 Zone Manager). Also, the variables, AlarmLogX, where X is 1 through 5, that store the last five alarms to occur in the controller, are available. These points can be viewed using XBS or the corresponding LNS plug-in. For a description of Excel 10 Alarms, refer to Table 12 of Excel 10 W7751B,D,F,H,J Variable Air Volume Controller Application Guide (Product Literature No.: 74-2949) T7460 Wall Module Override The remote override located on the T7460 Wall Module, will display the "manual override" mode of the. Possible modes are: 1. = OFF. No override active. 2. = Continuously ON. Bypass mode (timed occupied override). 3. = One flash per second. Continuous unoccupied override. 4. = Two flashes per second. Remote only, continuous occupied override. T7560 Wall Module NOT M IN NOTE: The node can be reset by switching the node to MANUAL and then to the normal operating mode. OPTIONAL WIRING TO NEXT CONTROLLER NOT MMC325 PNEUMATIC TRANSDUCER INCREASE DECREASE M B M M IN PNEUMATIC VALVE USE 1/4 IN. (6 MM) MIN. TUBING. BRANCH LINE MUST BE 6 FT. (1.8 M) OR GER. Fig. 21. to pneumatic transducer NOTE: Reverse wires (INCREASE/DECREASE) to reverse action (DIRECT/REVERSE). 1 2 3 4 5 6 7 8 TEMP. TEMP. NOT USED IN NOT USED T7560A Fig. 22. to T7560A NOTE: The parameter P4 of the T7560A must be set to "2". override mode from controller, US signaling (100 ms pulses); with contr. W7750, W7751, W7753, W7761, and XL12 The supports a reduced command set, only: The "" and the "UNOCCUPIED" commands are supported. The "OCCUPIED" command is not supported; rather, the "OCCUPIED" state is triggered, e.g., by TodEvent schedule. When the is in the state "STANDBY" or "OCCUPIED," this not displayed by the T7560A. Step 3. I/O Tests The must be configured using the LNS plug-in. Once this is done, the can be commanded to the "manual" mode, and each output and input can be EN1B-0279GE51 R0512C 8

EXCEL 10 SMART VAV ACTUATOR INSTALLATION INSTRUCTIONS exercised/viewed to verify proper wiring connections and equipment operation. Checkout To check out the, determine the direction the damper shaft moves to open the damper (CW or CCW). See Fig. 7. Connect the with the laptop PC. To do this, the must be wired, powered, and connected to the portable PC via the LonTalk adapter. The LonTalk Adapter connects to the either directly via the WORKS network or via the T7460-JACK (accessory available with the T7460 and T7560 Wall Modules). Using the WORKS tool, you should then drive the actuator fully open and then closed. Observe the actuator's operation; if the damper is closed, it should begin to open. If the damper is open, it should begin to close. If no movement is observed, check to see if 24 Vac is present at the. With proper wiring, with 24 Vac present, and with proper commands from the LNS plug-in, the actuator should operate properly. Step 4. Verify Sequences of Operation For the detailed descriptions of the sequences of operation, see Excel 10 W7751B,D,F,H,J Variable Air Volume Controller Application Guide (Product Literature No.: 74-2949). Optional Accessories Spare Parts Kit Order no.: A7211.2071. Contains: 1 anti-rotation bracket + screws 2 universal terminal blocks 2 strain-relief clamps 2 grommets 2 adjustable end stops In order to guarantee IP54, only original Honeywell grommets may be used. 9 EN1B-0279GE51 R0512C

41 142 85 105 76 103 Fig. 23. Dimensions (in mm) Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative: Automation and Control Solutions Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://ecc.emea.honeywell.com Subject to change without notice. Printed in Germany EN1B-0279GE51 R0512C