Metasys Zoning Package Overview

Similar documents
Metasys Zoning Package Installation

Metasys Zoning Package

RD-2000 Round Control Dampers

Appendix A: Inputs, Outputs, and Parameters

RA-2000 Airflow Measuring System

Discharge Air Control

Commerical Comfort System (CCS) Variable Air Volume (VAV) Zone Pressure Independent Damper Controller

CCS Zone/Bypass Damper Assembly

Introduction to Johnson Controls Dampers

AD-1251 Probe with Differential Pressure Transducer

Dual Duct Variable Air Volume Terminal (Model TDS)

AD-1250 Airflow Measuring Station

SD-1250 and SD-1600 Series Smoke Dampers

YCCS Zone/Bypass Damper Assembly

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

YCCS Zone/Bypass Damper Assembly

RM-1200 Slim Round Control Damper

PC-125x Counter-Balanced Backdraft Damper

ATP-2040 Electric Damper Actuator/Transmitter

RETROFIT TERMINAL UNITS

Variable Air Volume Dampers

Variable Air Volume (VAV) Pressure Independent Control

VAV TERMINAL UNITS. VVD VAV Diffusers

SECTION CONTROL DAMPERS

ULTRA-ZONE FORCED AIR ZONE CONTROLS EWC

VAV TERMINAL UNIT KYODO-ALLIED TECHNOLOGY PTE LTD

R-317 Air Flow Controller

System 350 P352AB Electronic Pressure Control Series

Operating the Network Control Module (NCM) Battery Charger/Tester

Engineering Bulletin. IntelliPak RTM (Rooftop Module, 1U48) Subject: Generic Building Automation System (GBAS, UCM Module, 1U51)

System 350 S350P Proportional Plus Integral Temperature Stage Module

VAV terminal units. Type TVM. For dual duct systems PD TVM 1

TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

TSS Single-Duct VAV Terminals

FOR USE IN SOLUTION AIR HANDLING UNITS

VA-7450 Series. Electric Valve Actuators

VA-4233-GGx Series Electric Valve Actuators

TM-9100 Series Room Command Module

BD-1600 Balancing/Zone Control Damper

RA-1250 Thermal Dispersion Fan Inlet Sensors Airflow Measuring System

Description. functions including single duct pressure dependent or pressure independent systems.

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

STR Circular VAV Terminal Units

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS

ID-141x 12-Gauge Hat Channel Industrial Damper

PIM Pressure Independent Module

Silver Series Thermal Dispersion Airflow Measurement Technology

M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications

M9216 Series Electric Spring Return Actuators

SECTION AIR TERMINAL UNITS

ELECTRIC POWER REGULATION TEMPERATURE CONTROLLERS. room C

VA2202-xxx-2 Series Electric Spring Return Valve Actuators

M9116, M9124, and M9132 Series Electric Non-spring Return Actuators

22 POINT FULLY PROGRAMMABLE HVAC CONTROLLER

D2-2. Table of Contents RETROFIT/BYPASS TERMINAL UNITS

Multi-Path RTU-TYPE 9 (RTU-1) CES-MPU-025-RE-VAV9

Product Data. Features/Benefits. 45J,M,K,N,Q,R Standard, Quiet, and Low Profile Fan Powered Variable Air Volume Terminals

DRUM LOUVERS DRUM LOUVERS 45DL SERIES. Models: 45DL1 Single Vanes 45DL2 Split Vanes G151 HIGH CAPACITY LONG THROW ALUMINUM CONSTRUCTION

M9210-xxx-3 Electric Spring Return Actuators

500-YVI PARALLEL FAN-POWERED AIR TERMINAL UNIT FORM EG3 (404)

VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators

Laboratory Exhaust Systems

Product Data. 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems. 40 to 3700 cfm

NMQB24-MFT, NMQX24-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

University of Delaware

VAV RETROFIT/BYPASS TERMINAL UNITS TABLE OF CONTENTS RETROFIT/BYPASS TERMINAL UNITS. E-2 Excellence in Air Distribution MODEL RVE MODEL KLB MODEL SVE

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN. Rev.

M9220-xxx-3 Electric Spring Return Actuators

Air Quality Solutions

Horizontal and Vertical Belt Drive Blower Coil Units (Models AHI and AVI)

Metal Enclosure. Application Note: Metal Enclosure Page 3

PIM Pressure Independence Module

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

Form: Rev. A (0802) Supersedes: Nothing. Zoning Tec. echnical Guide

AMD-42-TD. Thermal Dispersion Air Measuring Station with VCD-42 Control Damper. Application and Design. Ratings. Features and Control Options

Installation Guide. DigiTract 4. Two Stage Heat/Cool Comfort Control System. Zoning Systems. That s all we do. Part #DT4MAN Rev.

LF Series Spring Return Direct Coupled Actuator

OE326-23I-OR VAV/Zone Controller

500-YCI SERIES FAN-POWERED AIR TERMINAL UNIT FORM EG2 (404)

AV-8020 Series Floating Control Actuated Valve

Air Measuring Products. AMS Thermal Dispersion Pressure Differential

LINEAR DIFFUSERS AND BAR GRILLES

DPT-2015 Differential Pressure Transmitter for VAV Box Applications

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment

JC-VSD FP Series II Drives Product Bulletin 1

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc.

AIR VOLUME TRANSMITTER / CONTROLLER IML

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

Installation, Service, and Troubleshooting Instructions

NMB (X) 24-MFT. Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

Operations Manual OM

M9208-xxx-x Series Electric Spring Return Actuators

AMD-42V Air Measuring Station with VCD-42V Control Damper

AMD-42 Air Measuring Station with VCD-42 Control Damper

VSD Series II Variable Speed Open Drives

Accutrol, LLC Product Sheet AVC6000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare

AMD-23-TD. Thermal Dispersion Air Measuring Station with VCD-23 Control Damper. Application. Ratings. Features and Options

Installation Instructions

Transcription:

Technical Bulletin Issue Date August 26, 2002 Metasys Zoning Package Overview Metasys Zoning Package Overview...2 Introduction... 2 Key Concepts... 3 Related Information... 3 Metasys Zoning Package Components... 3 Accessories... 6 Metasys Zoning Package Operation... 7 Design Guidelines... 8 Examples... 9 Ordering Information... 11 Metasys Zoning Package Components... 11 Round Dampers... 12 Rectangular Dampers... 14 Shipping Weights... 15 Pressure Drop Curves... 16 2002 Johnson Controls, Inc. www.johnsoncontrols.com Code No. LIT-639100

2 Metasys Zoning Package Overview Technical Bulletin Metasys Zoning Package Overview Introduction The Metasys Zoning Package (MZP) is a Heating, Ventilating, and Air Conditioning (HVAC) system that provides reliable zoning control of standard packaged rooftop units. This technical bulletin describes: related information Metasys Zoning Package components accessories Metasys Zoning Package operation design guidelines examples ordering information

Metasys Zoning Package Overview Technical Bulletin 3 Key Concepts Related Information Table 1 lists the location of literature related to the Metasys Zoning Package. Table 1: Related Information Documentation HVAC PRO User s Guide M9100 Series Electric Non-spring Return Actuators Installation Bulletin N30 Supervisory Controller Protocol Implementation Conformance Statement Technical Bulletin N30 Supervisory Controller Quick Start Technical Bulletin N30 Supervisory Controller Installation Technical Bulletin N30 Supervisory Controller Networking Technical Bulletin N30 Supervisory Controller Point Mapping Technical Bulletin Direct Connect and Dial-Up on Windows 98 Application Note Direct Connect and Dial-Up on Windows NT Application Note Direct Connect and Dial-Up on Windows 2000 Application Note N30 Supervisory Controller User s Manual Operator Workstation Technical Bulletin Operator Workstation Configurations Technical Bulletin Operator Workstation User s Manual Unitary Controller (UNT) Technical Bulletin Unitary (UNT) Controller 1100 Series User s Guide Variable Air Volume Modular Assembly (VMA) 1400 Series Overview and Engineering Guidelines Technical Bulletin Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series Controllers Technical Bulletin Object Dictionary M-Tool Overview and Installation Technical Bulletin Project Builder s User s Guide Site Book User s Guide Code Number LIT-2681060 LIT-6891460 LIT-6891200 LIT-6891100 LIT-6891300 LIT-6891400 LIT-6893350 LIT-6893400 LIT-6893450 LIT-636013 LIT-636013D LIT-6363081 LIT-6363083 LIT-6363120 LIT-6363125 LIT-693100 LIT-6893100 Metasys Zoning Package Components The MZP components include: Building Automation System Building Automation System (BAS) is a generic term that refers to the Metasys Network Control Module (NCM), N30 Series supervisory systems, and associated operator workstations. The specific system names are used when referring to system-specific applications.

4 Metasys Zoning Package Overview Technical Bulletin The Metasys Zoning Package controls any standard, constant volume packaged Rooftop Unit (RTU) which uses select Johnson Controls BAS, digital controllers, and sensors. Unitary (UNT) Controller The UNT controller controls the rooftop unit to regulate the temperature of the supply air according to the zone with the highest demand. The AS-UNT121-1 or the AS-UNT1126-0 Unitary controllers can be used in the Metasys Zoning Package. These are low ambient temperature rated controllers that must be installed in a weatherproof enclosure, unless they are mounted within the enclosed, low voltage electrical compartment of the rooftop unit. Refer to the Unitary Controller (UNT) Technical Bulletin (LIT-6363081) for the AS-UNT121-1 or to the Unitary (UNT) Controller 1100 Series User s Guide (LIT-6363083) for the AS-UNT1126-0 for more information. Zone Damper Assembly One zone damper assembly is required for each zone. The Variable Air Volume (VAV) Modular Assembly (VMA) 1440 controller on the zone damper monitors zone temperature to determine a demand for heating or cooling, and reports this demand to the rooftop UNT controller via the BAS. The VMA1440 also monitors supply air temperature at the discharge of the RTU. As the temperature of the supply air changes, the VMA1440 modulates the zone damper to regulate its flow into the zone and satisfy its heating or cooling needs. The zone damper assembly can be ordered as a round or rectangular damper: RZGddEDx (metal controller cover is optional) ZOVSE-wwwxhhhx (metal controller cover is optional)

Metasys Zoning Package Overview Technical Bulletin 5 Bypass Damper Assembly An actuator controls the bypass damper. The actuator of the bypass is controlled by the VMA1440 controller on a zone damper assembly. The bypass damper regulates air volume and static pressure through the MZP system. As building load is satisfied and the zone dampers in the system begin to modulate closed, static pressure increases in the ductwork. If system static pressure becomes excessive, the static pressure transducer sends a signal to the VMA1440 controller on the master zone damper. In response, the VMA1440 drives the bypass damper partially open, allowing excess air to flow from the supply side to the return side of the rooftop unit. This eliminates excessive system static pressure, prevents the generation of noise at the diffusers, and prevents the erratic loss of temperature control in the zones. The bypass damper assembly requires the following components: RCGddEDx or BOVAE-wwwxhhhx (metal actuator cover is optional) AS-DPTKIT-1 static pressure transducer kit (DPT-2015 static pressure sensor mounted in separate metal enclosure with Dwyer A-303 static pressure tip) Slave Damper Applications The slave applications must be installed with one of the following: RCGddEDx BOVAE-wwwxhhhx VMA1420 Controller The VMA1420 controller can also be used with the MZP application, but the internal Differential Pressure Transducer (DPT) sensor is only used for monitoring purposes. The VMA1420 is not available as a factory-mounted option and must be field installed. Refer to the Metasys Zoning Package Commissioning Technical Bulletin (LIT-639250). Zone Temperature Sensor The recommended zone temperature sensor is the TE-67Nx-1BOO or the AP-TMZ1600-0. Each zone damper assembly supports only one sensor. Split-Bobbin Transformer The recommended split-bobbin transformers are the Johnson Controls Y63, Y64, or Y65 Series transformers.

6 Metasys Zoning Package Overview Technical Bulletin Accessories Required Accessories The following accessory is required and must be ordered separately: Static pressure transducer kit for use with the VMA1440 (AS-DPTKIT-1). This kit is needed for bypass applications and provides input to the VMA1440 zone damper to activate bypass control. Optional Accessories The following optional MZP accessories are also available: M3 Workstation M-Graphics software Zone Terminal (UNT controller only) carbon dioxide (CO 2 ) sensor room sensor (TE-6700 or TMZ1600) humidity sensor

Metasys Zoning Package Overview Technical Bulletin 7 Metasys Zoning Package Operation A commercial zoning package provides cooling and heating to zones served by a single constant-volume rooftop unit. The rooftop unit delivers warm supply air for heating and cold supply air for cooling. If zones on a single rooftop simultaneously require heating and cooling, and cooling is the priority, the rooftop unit delivers enough cold supply air to satisfy all cooling demands. The zone then switches over to warm supply air for the zones calling for heating. The zone dampers regulate the introduction of this supply air into the zones. The volume of the supply air varies with the zone loads. Optional baseboard or other supplemental zone heating is also available. Unitary (UNT) Controller Building Automation System Bypass Damper Assembly Static Pressure Transducer Slave Zone Damper (Wired to VMA Controller on Zone Damper) Zone Damper Assembly Zone Sensor Zone 3 Zone 2 Zone 1 Zones1 Figure 1: Metasys Zoning Package System Overview Note: The VMA1440 analog output supports 10 ma.

8 Metasys Zoning Package Overview Technical Bulletin Design Guidelines Effective zoning depends upon proper system design. Good temperature control is easiest to maintain if the zones have similar temperature needs. For this reason, proper zone selection and tuning is essential. Follow these guidelines when designing a Metasys Zoning Package system: Follow the best engineering practices for all mechanical equipment being installed or controlled. Design the system with sufficient capacity to promptly satisfy heating and cooling needs. Select a supply fan with sufficient capacity to meet design loads while minimizing bypass flow. Lay out each rooftop unit so that: - all zones have similar thermal loads (either all internal or all external zones) - adequate ventilation (minimum flow) is provided to all zones during occupied mode Lay out each zone so that: - all rooms have similar occupancy schedules - all rooms have similar internal and external thermal gains - all rooms have a similar exposure or window area - all rooms have similar HVAC requirements Carefully consider the placement of the static pressure sensor. To minimize turbulence, the recommended location is two-thirds of the distance from the supply fan discharge to the last terminal unit on the farthest run. Use with 0-10 VDC proportional actuators. Contact Johnson Controls before using other actuators. Do not exceed 20 slaves per VMA controller. Do not exceed 5 UNT controllers per supervisory controller. Do not exceed 800 objects per Metasys Zoning system. Do not exceed 50 N2 devices per supervisory controller. Note: The above maximum values do not include special applications. For example, trending may require more memory resulting in fewer supported points.

Metasys Zoning Package Overview Technical Bulletin 9 Economic decisions are important, but occupant comfort and safety should be the primary consideration when making zoning decisions. Examples * DPR-O * CO2-L D * D-1 NC D-2 D-4 DPR-O NO BYP-DPR NO C Mount at 2/3 the distance from the Supply Fan in the longest main duct run. A DPR-O D-3 NC FILTER-S H L * C C SF H PS-1 L EH C DA-T L SA-SP H SPT-1 Static Pressure Tip B A OA-T OA-H * * A = Outside Air B = Discharge Air to Zone Dampers C = Return Air D = Relief Air = Optional Sensors/Devices * ZN-T Ductdiag Figure 2: Metasys Zoning Package System (Rooftop Application) Table 2: Metasys Zoning Package Component Descriptions and Examples Description Abbreviation Part Number Example Bypass Damper Assembly BYP-DPR RCGddEDx or BOVAE-wwwxhhhx Carbon Dioxide Sensor CO2-L CD-Pxx-0-0 (duct mounted) Discharge Air Temperature Sensor DA-T TE-6316P-1 Damper with Actuator DPR-O M9206-GGA-2 or M9216-GGA-2 Filter Switch FILTER-S P32AC-2C Outdoor Air Humidity/Temperature Sensor OA-H or OA-T Proof-of-Airflow Switch PS-1 AFS-460-DSS Supply Fan Status SF-S H-908 ±3% Accuracy HE-67N3-ONOOP or ±2% Accuracy HE-67N2-ONOOP Supply Air Static Pressure Sensor SA-SP AS-DPTKIT-1 with Dwyer A-303 Static Pressure Tip Zone Sensor ZN-T TE-67Nx-1BOO or AP-TMZ1600-0 Note: The items listed in Table 2 are provided as typical components required for the rooftop application and are not included in the bypass and zone damper assemblies.

10 Metasys Zoning Package Overview Technical Bulletin Actuator VMA SA-T Zone A B Zone Sensor with Warm/Cool Adjust Zone Damper A = Primary Air from Rooftop Unit B = To Zone ZN-T One Per Master Controller EH C Electric Duct Heater Control Panel AUX-HTG H C H C1 C2 AUX-HTG1 AUX-HTG2 Auxiliary Heating in the Zone HWR C NO N C HWS Mount Relays AUX-HTG1 and AUX-HTG2 in Heater Control Panel The auxiliary heating valve can be proportional using AO1 or may be an incremental actuator using BO3 and BO4. ductdiag2 Figure 3: Zone Damper Assembly Table 3: Metasys Zoning Package Component Descriptions and Examples Description Abbreviation Part Number Example Supply Air Temperature Sensor SA-T TE-6300-601 Zone Sensor ZN-T TE-67Nx-1BOO or AP-TMZ1600-0 Auxiliary Heating RLY 1SPDT, 10-30 VAC/DC or 120 VAC, Light-Emitting Diode (LED) @ LEC Note: AUX-HTG1 and AUX-HTG2 CVR-11C-0 The items listed in Table 3 are provided as typical components required for the rooftop application and are not included in the bypass and zone damper assemblies

Metasys Zoning Package Overview Technical Bulletin 11 Ordering Information Metasys Zoning Package Components Table 4 lists the required Metasys Zoning Package components: Table 4: Metasys Zoning Package Components Item Building Automation System (BAS) Metasys Network Metasys N30 Supervisory Controller with N2 Field Bus and Ethernet Peer Bus Metasys N30 Supervisory Controller with N2 Field Bus Rooftop Controller (UNT) Bypass Damper Assembly Zone Damper Assembly Zone Temperature Sensor Part Number Only one of the following is required: NU-NCM300 Series MS-N301310-1 MS-N301010-1 AS-UNT121-1 or AS-UNT1126-0 Refer to Table 8 and Table 10 to select part numbers. Refer to Table 7 and Table 9 to select part numbers. TE-67Nx-1BOO or AP-TMZ1600-0 Split-Bobbin Transformer Y6xxx-x Refer to the Series Y63, Y64, Y65, Y66, Y69 Transformers Product Bulletin (LIT-125755). Note: For Zone Applications, order the appropriate damper (for example, round, rectangular, size) with a VMA1440 controller. For bypass or slave applications, order the appropriate damper (for example, round, rectangular, size) with an M9106-GGA-2 actuator. Table 5 lists the optional Metasys Zoning Package components: Table 5: Metasys Zoning Package Optional Components Item Part Number Operator Workstation WS-SWOPMI-0 and WS-SWOGPL-0 M3 Workstation Carbon Dioxide Sensor Outdoor Air Humidity/Temperature Sensor Discharge Air Temperature Sensor MW-M3WHCI-0 and MW-MGRAPH-0 CD-WOO-OO-O (wall mounted) or CD-Pxx-0-0 (duct mounted) ±3% Accuracy HE-67N3-ONOOP or ±2% Accuracy HE-67N2-ONOOP TE-6316T-1

12 Metasys Zoning Package Overview Technical Bulletin Table 6 lists the Metasys Zoning Package replacement parts: Table 6: Metasys Zoning Package Replacement Parts Item Part Number Bypass and Slave Damper Assemblies Proportional Actuator M9106-GGA-2 Static Pressure Kit AS-DPTKIT-1 (includes DPT-2015-1 with Dwyer A-303 static pressure tip) Zone Damper Assembly VMA1440 Controller AP-VMA1440-0 Supply Air Sensor TE-6300-601 Round Dampers Use Table 7 to select the ordering code for the round zone damper or Table 8 for the round control dampers for bypass/slave applications. See Figure 4 for the dimensions of the round damper and the optional metal cover. Length (L) 171mm (6.75 in.) Airflow Diameter (D) Round Damper 140 mm (5.5 in.) Rd_diag Figure 4: Round Damper with Optional Metal Cover

Metasys Zoning Package Overview Technical Bulletin 13 Table 7: Round Zone Damper Selector Damper Actuator Code Number R Z G dd E D NO C Product Family R = Round Dampers Application Z = Zone Control Material Diameter (dd) Actuator/ Controller Control Signal Operation Factory-Installed Options Notes: G = Galvanized 06 to 22 inches (1-inch increments) with Actuator E = VMA1440 Controller D = Default Control Signal NO = Normally Open C = Steel Actuator Cover The RZG round zone damper is a master which includes the TE6300-601 SA Sensor and VMA1440 controller. The code RZG08EDNO specifies a round zone damper with 8-in. diameter, VMA1440 controller, default control signal, normally open actuator operation, and no metal actuator cover. Table 8: Round Control Damper Selector for Bypass/Slave Applications Damper Actuator Code Number R C G dd E D NC C Product Family R = Round Dampers Application C = Control Damper for Bypass/Slave Material G = Galvanized Diameter (dd) 06 to 22 inches (1-inch increments) with Actuator Actuator E = Electric Actuator Non-spring Return M9106-GGA-2 (no controller) Control Signal D = Proportional Operation Factory-Installed Options NC = Normally Closed C = Steel Actuator Cover

14 Metasys Zoning Package Overview Technical Bulletin Rectangular Dampers Use Table 9 to select the ordering code for the rectangular zone damper or Table 10 for the rectangular damper for bypass/slave applications. See Figure 5 for the dimensions of the rectangular damper and the optional steel cover. 171 mm (6.75 in.) Airflow Height (H) 165 mm (6.5 in.) 140 mm (5.5 in.) Rectangular Damper 305 mm (12 in.) Width (W) Rct_diag Figure 5: Rectangular Damper with Optional Steel Cover Note: The recommended duct slot width for installing the damper is 101.6 mm (4 in.). Table 9: Rectangular Zone Damper Selector Code Number Z O V S E - 0 w w x 0 h h C Application Z = Zone Blade Operation O = Opposed Blade Type Bearings/Seals Actuator/ Controller Width Dimensions Height Dimensions Factory-Installed Options Notes: V = One-piece Blade S = Standard Temperature- Acetal Bearings/No Seals E = VMA1440 Controller 008 to 030 inches (1-inch increments) 006 to 030 inches (1-inch increments) C = Steel Actuator or Controller Cover The ZOVSE rectangular damper is a master which includes the TE6300-601 SA Sensor and VMA1440 controller. The code ZOVSE-008x012C specifies a rectangular zone damper with opposed blade operation, one-piece blade, standard temperature acetal bearings without seals using a VMA1440 controller, 8-inch wide x 12-inch high, complete with steel cover. Rectangular damper assemblies are shipped with a 305 mm (12-inch) wide side plate that inserts into a sheet metal shroud supplied by installation contractor.

Metasys Zoning Package Overview Technical Bulletin 15 Table 10: Rectangular Damper Selector for Bypass/Slave Applications Code Number B O V A E - 0 w w x 0 h h C Application B = Bypass/Slave Blade Operation O = Opposed Blade Type Bearings/ Seals Actuator Width Dimensions Height Dimensions Factory-Installed Options Notes: V = One-piece Blade A = Acetal Bearings/No Seals E = Electric Actuator M9106-GGA-2 (no controller) 008 to 030 inches (1-inch increments) 006 to 030 inches (1-inch increments) C = Steel Actuator Cover The BOVAE rectangular damper for Bypass/Slave applications includes a factory-installed actuator without sensors. Rectangular damper assemblies are shipped with a 305 mm (12-inch) wide side plate that inserts into a sheet metal shroud supplied by installation contractor. Shipping Weights Table 11 lists the approximate shipping weights for round and rectangular dampers. Table 11: Approximate Shipping Weights in lb (kg) Height (inches) Width (inches) 12 18 24 30 6 11 (5.0) 14 (6.4) 15 (6.8) 17 (7.7) Notes: 12 15 (6.8) 18 (8.2) 19 (8.6) 21 (9.5) 18 19 (8.6) 25 (11.3) 27 (12.2) 29 (13.2) 24 24 (10.9) 27 (12.2) 32 (14.5) 37 (16.8) 30 25 (11.3) 29 (13.2) 36 (16.3) 42 (19.1) Length for all rectangular dampers is 305 mm (12-inch). Weights do not include packaging.

16 Metasys Zoning Package Overview Technical Bulletin Pressure Drop Curves Figure 6 shows the pressure drop curves for round dampers. 10,000 1,000 Flow (cfm) 22 Inch 16 Inch 14 Inch 10 Inch 12 Inch 8 Inch 6 Inch 100 4 Inch 10 0.00 0.01 0.10 1.00 Static Pressure (inches WG) Rd_curves Figure 6: Round Damper Pressure Drop Figure 7 shows the pressure drop curves for rectangular dampers. 1.00 48 x 48 24 x 24 12 x 12 0.70 Pressure Drop = inches WG 0.40 0.30 0.20 0.07 0.05 0.04 0.03 0.20 0.01 0.2 0.3 0.5 0.7 1 2 3 4 5 7 Approach Velocity = fpm x 1000 Rct_curves Figure 7: Rectangular Damper Pressure Drop Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 www.johnsoncontrols.com Published U.S.A.