Landmark Rooftop Packaged Units Engineered for superior performance and reliability Exclusively distributed by AUS - 13 23 50 www.lennoxaus.com.au NZ - 0800 653 330 www.lennoxnz.co.nz 1
Landmark Rooftop Packaged Units Introduction & Overview The Lennox Landmark Rooftop reverse cycle (heat pump) Packaged Units has been specifically engineered for superior performance and reliability. Designed with the installer in mind, Landmark incorporates many innovative features which can save time and money on site. Market Segments Retail Offices Industrial Education Civic Light Commercial Features & Benefits The Lennox Landmark Rooftop Packaged Unit offers: Reliable scroll compressor technology with isolated compressor compartment for ease of service. Pre-determined fan motor with slide out blower for simple, fast air flow adjustments and ease of service. TX valves for improved efficiency and refrigerant control. Independent motor mount for ease of service. Control Options Landmark can be configured with the following options: Commercial Touchscreen Thermostat ComfortSense 7 ComfortSense 3000 Commercial ComfortSense 7500 Programmable BMS HLI interface: BACnet, LonWorks. Full perimeter base rail for structural integrity during transport. Rigging holes and forklift slots for ease of handling and transport from multiple angles. Removable corrosion resistant drain pan to minimize risk of water leaks. Nomenclature K = Landmark Major Design Sequence A = 1st generation B = 2nd generation S = Std Efficiency B = Belt Drive Minor Design Sequence 1 = 1st revision 2 = 2nd revision 3 = 3rd revision K H A 120 S 4 B N 1 M H = Packaged Unit Heat Pump Cooling Capacity 036 = 9.31kW 048 = 12.34kW 060 = 15.38kW 072 = 17.93kW 092 = 22.97kW 120 = 31.12kW 150 = 36.23kW 180 = 45.28kW 240 = 58.06kW 4 = R410A Factory Installed Electric Heater N = No Heater M = 380/240V - 3 phase - 50Hz 2 AUS - 13 23 50 www.lennoxaus.com.au NZ - 0800 653 330 www.lennoxnz.co.nz
Flexible Handing Options Standard Vertical Optional Supply Optional Horizontal (On-site panel change) Std Supply Optional Roof Curb Std Return Optional Return Designed for ease of installation, an optional roof curb can save significant time and money on site. Other benefits include improved efficiency and aesthetics compared to external ductwork, with one roof penetration. Heatcraft offers custom-made roof curbs to suit your installation. For replacement units Landmark Rooftop Packaged Units can be connected to your existing roof curb with a custom roof curb adaptor. Optional Accessories MODEL NUMBER (REVERSE CYCLE) KHA036 KHA048 KHA060 KHA072 KHA092 KHA120 KHA150 KHA180 KHA240 DRAIN TRAP - PVC X X X X X X X X X CORROSION PROTECTION O O O O O O O O O LOW AMBIENT KIT X X X X X X X X X COIL GUARDS X X X X X X X X X HAIL GUARDS X X X X X X X X X STANDARD ECONOMIZER WITH OUTDOOR AIR HOOD OX OX OX OX OX OX OX OX OX ENTHALPY CONTROL X X X X X X X X X OUTDOOR AIR DAMPERS - MANUAL OX OX OX OX OX OX OX OX OX OUTDOOR AIR DAMPERS - MOTORIZED OX OX OX OX OX OX OX OX OX POWER EXHAUST FAN X X X X X X X X X BAROMETRIC RELIEF X X X X X X X X X CO2 SENSOR X X X X X X X X X SMOKE DETECTOR - SUPPLY OR RETURN X X X X X X X X X X = Field installed; O = Factory option must be specified at time of order. Lead-times apply; OX = Can be either Field installed or Factory Option Field Information MODEL NUMBER (REVERSE CYCLE) KHA036 KHA048 KHA060 KHA072 KHA092 KHA120 KHA150 KHA180 KHA240 REFRIGERANT (R410A) DRAIN CONNECTION AIR DUCT SPIGOT (STD) NO. OF CIRCUITS 1 1 1 1 2 2 2 2 3 FACTORY CHARGE (kg) 5.67 5.95 7.26 9.30 5.70 6.80 10.00 9.53 11.79 5.40 6.80 10.40 9.53 11.79 SIZE/TYPE (1) 1" NPT (1) 1'' FPT SUPPLY H x W (mm) RETURN H x W (mm) 508 X 457 737 X 279 508 X 495 737 X 279 509 X 457 737 X 279 509 X 495 737 X 279 394 X 762 762 X 394 394 X 762 762 X 394 394 X 762 762 X 394 508 X 711 (2) (V) 381 X 1537 (V) 508 X 711 (2) (V) 381 X 1537 (V) H - Horizontal V - Vertical AUS - 13 23 50 www.lennoxaus.com.au NZ - 0800 653 330 www.lennoxnz.co.nz 3
Landmark Rooftop Packaged Units Technical Data Summary MODEL NUMBER (REVERSE CYCLE) KHA036 KHA048 KHA060 KHA072 KHA092 KHA120 KHA150 KHA180 KHA240 TOTAL CAPACITY AS/NZS 3823.1.2 NETT CAPACITY AS/NZS 3823.1.2 INPUT POWER AS/NZS 3823.1.3 COOLING 1 kw 9.31 12.34 15.38 17.93 22.97 31.12 36.23 45.28 58.06 HEATING 2 kw 9.06 12.47 15.74 17.75 22.60 30.02 35.25 43.35 54.23 COOLING 1 kw 8.88 11.68 14.62 17.20 22.18 29.99 34.00 43.80 54.75 HEATING 2 kw 9.49 13.13 16.49 18.48 23.39 31.13 37.49 44.83 56.65 COOLING kw 2.8 3.7 4.5 5.3 6.4 8.8 10.7 13.8 17.4 HEATING kw 2.4 3.1 3.8 4.9 5.6 7.6 10.1 11.9 14.6 EER AS/NZS 3823.1.2 COOLING 3.23 3.15 3.25 3.27 3.49 3.41 3.19 3.17 3.15 COP AS/NZS 3823.1.2 HEATING 3.97 4.26 4.33 3.81 4.16 4.12 3.73 3.76 3.90 MEPS COMPLIANT YES YES YES YES YES YES YES YES YES HEAT EXCHANGER TYPE COPPER TUBE WITH RIPPLED-EDGE ALUMINUM FINS COMPRESSOR TYPE SCROLL FANS OUTDOOR TYPE INDOOR TYPE DIRECT DRIVE AXIAL BELT DRIVEN, FC DWDI CENTRIFUGAL POWER SUPPLY V / Ø / Hz 380-420 / 3 / 50 COMPRESSOR 1 COMPRESSOR 2 OUTDOOR FAN MOTOR POWER EXHAUST 0.25 kw INDOOR BLOWER MOTOR MAXIMUM OVERCURRENT PROTECTION AIRFLOW (EVAPORATOR) EXTERNAL STATIC PRESSURE RATED LOAD AMPS 5.4 6.1 7.8 9.7 6.1 7.8 9.7 12.2 16.7 LOCKED ROTOR AMPS 38 43 51.5 64 41 51.5 64 101 111 RATED LOAD AMPS 6.1 7.8 9.7 12.2 16.7 LOCKED ROTOR AMPS 41 51.5 64 101 111 NUMBER OF FANS 1 1 1 1 2 2 3 4 4 FULL LOAD AMPS 1.1 1.1 1.3 1.5 1.3 1.5 1.3 1.3 1.3 TOTAL AMPS 1.1 1.1 1.3 1.5 2.6 3.0 3.9 5.2 5.2 NUMBER OF FANS 1 1 1 1 1 1 1 2 2 FULL LOAD AMPS 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 TOTAL AMPS 1.3 1.3 1.3 1.3 1.3 1.3 1.3 2.6 2.6 kw 1.5 1.5 1.5 1.5 1.5 2.2 3.7 1.5 2.2 3.7 1.5 2.2 3.7 2.2 3.7 5.6 3.7 5.6 7.5 FULL LOAD AMPS 3.6 3.6 3.6 3.6 3.6 5.3 8.2 3.6 5.3 8.2 3.6 5.3 8.2 5.3 8.2 11.7 8.2 11.7 16.3 UNIT ONLY 15 15 20 25 25 25 30 30 30 35 35 40 40 50 50 50 60 70 70 WITH (1) 0.25 kw POWER EXHAUST 15 15 20 25 25 25 30 30 30 35 40 40 40 50 50 50 70 70 70 MAXIMUM (L/S) 708 944 1133 1369 2831 2477 2477 4250 4250 NOMINAL (L/S) 545 755 935 970 1415 1700 2124 2830 3540 MINIMUM (L/S) 425 566 755 897 1062 1062 1062 2240 2240 MAXIMUM AIRFLOW (Pa) 25 25 25 25 150 50 50 100 100 MINIMUM AIRFLOW (Pa) 400 400 400 400 600 650 650 650 650 HEIGHT (mm) 987 987 1191 1191 1191 1191 1191 1378 1378 DIMENSIONS (UNIT) WIDTH (mm) 2165 2165 2165 2496 2572 2572 3159 3369 3369 DEPTH (mm) 1194 1194 1194 1194 1527 1527 1527 2315 2315 NET WEIGHT kg 243 253 303 340 477 522 612 885 975 SOUND POWER LEVEL dba 75 75 82 83 88 88 88 93 93 1. Total cooling capacity at AS/NZS 3823.1.3 rating conditions: temperature of air entering on outdoor side 35 C DB / 24 C WB and on indoor side 27 C DB / 19 C WB. 2. Total heating capacity at AS/NZS 3823.1.3 rating conditions: temperature of air entering on outdoor side 7 C DB / 6 C WB and on indoor side 20 C DB / 15 C WB. 4 AUS - 13 23 50 www.lennoxaus.com.au NZ - 0800 653 330 www.lennoxnz.co.nz
Unit Clearances KHA036S4 to KHA072S4 A B C D UNIT CLEARANCE mm mm mm mm Service Clearance 914 914 914 914 Minimum Operation Clearance 914 914 914 914 TOP CLEARANCE Unobstructed NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface. 1 Service Clearance - Required for removal of serviceable parts. Minimum Operation Clearance - Required clearance for proper unit operation. C OUTDOOR AIR HOOD B D A KHA092S4B to KHA150S4B A B C D UNIT CLEARANCE mm mm mm mm Service Clearance 1524 914 914 1524 Minimum Operation Clearance 914 914 914 914 TOP CLEARANCE Unobstructed NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface. 1 Service Clearance - Required for removal of serviceable parts. Minimum Operation Clearance - Required clearance for proper unit operation. C OPTIONAL OUTDOOR AIR HOOD D DB A KHA180S4B to KHA240S4B A B C D UNIT CLEARANCE mm mm mm mm Service Clearance 1524 914 914 1676 Minimum Operation Clearance 1143 914 914 1041 TOP CLEARANCE Unobstructed NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface. 1 Service Clearance - Required for removal of serviceable parts. Minimum Operation Clearance - Required clearance for proper unit operation. OUTDOOR AIR HOOD C D B A AUS - 13 23 50 www.lennoxaus.com.au NZ - 0800 653 330 www.lennoxnz.co.nz 5
Landmark Rooftop Packaged Units Dimensions KHA036S4 to KHA072S4 CORNER WEIGHTS CENTER OF GRAVITY MODEL NUMBER AA BB CC DD EE FF Base Max. Base Max. Base Max. Base Max. Base Max. Base Max. kg kg kg kg kg kg kg kg mm mm mm mm KHA036S4 42 53 51 60 82 96 68 85 978 1016 457 457 KHA048S4 44 55 53 62 86 100 71 88 978 1016 457 457 KHA060S4 52 63 64 71 103 115 84 101 978 1016 457 457 KHA072S4 73 84 82 94 106 122 94 109 1174 1174 521 521 Base Unit - The unit with standard heat exchanger NO OPTIONS. Max. Unit - The unit with ALL OPTIONS Installed (Economizer, etc.). 1143 (45) 143 (5-5/8) AA 737 (29) 1194 (47) DD 279 (11) 413 (16-1/4) 178 (7) BOTTOM RETURN AIR 168 (6-5/8) 673 (26-1/2) BOTTOM SUPPLY AIR 457 (18) 127 (5) 508 (20) FF BOTTOM OUTLET CENTER OF GRAVITY TOP VIEW (Base) 2115 (83-1/4) KHA036 thru 060 2445 (96-1/4) KHA072 654 (25-3/4) KHA036 thru 060 984 (38-3/4) KHA072 241 (9-1/2) EE BOTTOM POWER ENTRY 76 x 203 (3 X 8) BB CC 25 (1) 987 (38-7/8) KHA036 thru 048 1191 (46-7/8) KHA060 / 072 899 (35-3/8) KHA036 thru 048 1102 (43-3/8) KHA060 / 072 89 (3-1/2) OUTLET (EITHER SIDE) 140 (5-1/2) ELECTRICAL INLET 25 (1) 1194 (47) END VIEW 673 (26-1/2) LIFTING HOLES (For rigging) 2165 (85-1/4) KHA036 thru 060 2496 (98-1/4) KHA072 495 (19-1/2) 467 (18-3/8) 279 (11) 51 (2) 508 (20) 737 (29) FORKLIFT SLOTS (Front, Back and Blower End) 140 (5-1/2) BACK VIEW HORIZONTAL SUPPLY AIR HORIZONTAL 140 RETURN AIR (5-1/2) (Without Economizer) 6 AUS - 13 23 50 www.lennoxaus.com.au NZ - 0800 653 330 www.lennoxnz.co.nz
Dimensions KHA092S4B & KHA120S4 CORNER WEIGHTS CENTER OF GRAVITY MODEL NUMBER AA BB CC DD EE FF Base Max. Base Max. Base Max. Base Max. Base Max. Base Max. kg kg kg kg kg kg kg kg mm mm mm mm KHA092S4 120 140 108 123 117 131 133 154 1181 1156 622 648 KHA120S4 129 151 120 135 131 145 143 165 1181 1156 622 648 Base Unit - The unit with NO INTERNAL OPTIONS. Max. Unit - The unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories external to unit or high static power exhaust. AA 156 (6-1/8) 143 (5-5/8) BOTTOM SUPPLY BB 156 (6-1/8) 1527 (60-1/8) BOTTOM POWER ENTRY 140 (5-1/2) Dia. 178 (7) DD 686 (27) 610 (24) BOTTOM RETURN 168 (6-5/8) 178 (7) 886 (34-7/8) EE 273 (10-3/4) 508 (20) 711 (28) BOTTOM 2572 (101-1/4) TOP VIEW CENTER OF GRAVITY FF CC 1476 (58-1/8) OPTIONAL DISCONNECT (FACTORY INSTALLED) 2521 (99-1/4) 1191 (46-7/8) DRAIN (FRONT) 1191 (46-7/8) 1102 (43-3/8) 25 (1) 137 (5-3/8) 1527 (60-1/8) END VIEW 89 (3-1/2) ELECTRIC INLETS 886 (34-7/8) FORKLIFT SLOTS (BOTH SIDES) 2572 (101-1/4) LIFTING HOLES (FOR RIGGING) 394 (15-1/2) 41 (1-5/8) 394 (15-1/2) HORIZONTAL SUPPLY AIR HORIZONTAL RETURN AIR 762 (30) 308 (12-1/8) 156 (6-1/8) 800 (31-1/2) 1686 (66-3/8) DRAIN (BACK) 762 (30) 137 (5-3/8) (Horizontal Openings) AUS - 13 23 50 www.lennoxaus.com.au NZ - 0800 653 330 www.lennoxnz.co.nz 7
Landmark Rooftop Packaged Units Dimensions KHA150S4 CORNER WEIGHTS CENTER OF GRAVITY MODEL NUMBER AA BB CC DD EE FF Base Max. Base Max. Base Max. Base Max. Base Max. Base Max. kg kg kg kg kg kg kg kg mm mm mm mm KHA150S4 158 180 137 153 146 160 171 193 1181 1156 622 648 Base Unit - The unit with NO INTERNAL OPTIONS. Max. Unit - The unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories external to unit or high static power exhaust. AA 156 (6-1/8) 143 (5-5/8) BOTTOM SUPPLY BB 156 (6-1/8) 1527 (60-1/8) BOTTOM POWER ENTRY 140 (5-1/2) Dia. 178 (7) DD 686 (27) 610 (24) BOTTOM RETURN EE 168 (6-5/8) 178 (7) 886 (34-7/8) 273 (10-3/4) 508 (20) CENTER OF GRAVITY 711 (28) BOTTOM FF 3159 (124-3/8) TOP VIEW CC 1476 (58-1/8) OPTIONAL DISCONNECT (FACTORY INSTALLED) 3127 (123-1/8) 1191 (46-7/8) DRAIN (FRONT) 1191 (46-7/8) 1102 (43-3/8) 25 (1) 137 (5-3/8) 1527 (60-1/8) END VIEW 89 (3-1/2) ELECTRIC INLETS 886 (34-7/8) FORKLIFT SLOTS (BOTH SIDES) 3159 (124-3/8) LIFTING HOLES (FOR RIGGING) 394 (15-1/2) 41 (1-5/8) 394 (15-1/2) HORIZONTAL SUPPLY AIR HORIZONTAL RETURN AIR 762 (30) 308 (12-1/8) 1387 (54-5/8) 156 (6-1/8) DRAIN (BACK) 762 (30) 2273 (89-1/2) (Horizontal Openings) 137 (5-3/8) 8 AUS - 13 23 50 www.lennoxaus.com.au NZ - 0800 653 330 www.lennoxnz.co.nz
Dimensions KHA180S4 & KHA240S4 CORNER WEIGHTS CENTER OF GRAVITY MODEL NUMBER AA BB CC DD EE FF Base Max. Base Max. Base Max. Base Max. Base Max. Base Max. kg kg kg kg kg kg kg kg mm mm mm mm KHA180S4 182 232 220 258 284 306 235 275 1499 1441 1010 1060 KHA240S4 199 253 235 274 314 335 267 309 1480 1422 991 1041 Base Unit - The unit with NO INTERNAL OPTIONS. Max. Unit - The unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories external to unit or high static power exhaust. ALTERNATE (THRU THE ) DRAIN LOCATION 41 mm (1-5/8 in.) Diameter AA 108 (4-1/4) 314 1537 (60-1/2) (12-3/8) 721 381 (15) BOTTOM RETURN (28-3/8) BOTTOM SUPPLY S 457 (18) 143 (5-5/8) 314 (12-3/8) 711 (28) 508 (20) 114 (4-1/2) 711 (28) 508 (20) BB EE 102 (4) DD 102 (4) CENTER OF GRAVITY FF BOTTOM POWER ENTRY 127 X 203 mm (5 X 8 inches) TOP VIEW CC 2289 (90-1/8) 3369 (132-5/8) DRAIN 1378 (54-1/4) 1295 (51) 137 (5-3/8) 730 (28-3/4) 2315 (91-1/8) SIDE ELECTRICAL INLETS 83 (3-1/4) LIFTING HOLES (For Rigging Front and Back) FORKLIFT SLOTS (Front and Left Side Only) 2737 (107-3/4) 645 (25-3/8) END VIEW AUS - 13 23 50 www.lennoxaus.com.au NZ - 0800 653 330 www.lennoxnz.co.nz 9
Landmark Rooftop Packaged Units Dimensions - Accessories - KHA180S4 & KHA240S4 Optional Horizontal Roof Curb - Requires Optional Horizontal Return Air Panel Kit 46 (1-13/16) 46 (1-13/16) Frame Opening 2099 (82-5/8) 2594 (102-1/8) 2502 (98-1/2) 46 (1-13/16) 1 660 (26) 2 940 (37) Frame Opening 25 (1) NAILER STRIP (Furnished) 51 (2) SECTION A-A A 46 (1-13/16) A NOTE C1CURB14C-1 is designed for horizontal discharge when unit is mounted on a slab. C1CURB15C-1 is designed for horizontal discharge when unit is mounted on a rooftop. PANEL TO COVER RETURN IN BOTTOM OF UNIT (Furnished With Optional Horizontal Return Air Panel Kit) 2191 (86-1/4) 2502 (98-1/2) 1372 (54) SUPPLY AIR TURNING VANE (Furnished) NOTE Roof deck may be omitted within confines of curb. (Packaged Unit) 46 (1-13/16) TOP VIEW 2594 (102-1/8) 210 (8-1/4) 2191 (86-1/4) NAILER STRIP (Furnished) 140 (5-1/2) 1 660 (26) 2 940 (37) 75 CURB SUPPLY (1905) With 38 mm (1-1/2 in.) FLANGE 356 (14) 1 165 (6-1/2) 2 445 (17-1/2) SUPPLY AIR TURNING VANE (Furnished) SUPPLY DUCT PANELS (Furnished) 2604 (102-1/2) 2200 (86-5/8) FRONT VIEW 1 C1CURB14C-1 2 C1CURB15C-1 HORIZONTAL SUPPLY AND RETURN S WITH HORIZONTAL ROOF CURB 1378 (54-1/4) 1937 (76-1/4) C1CURB14C-1 2216 (87-1/4) C1CURB15C-1 559 (22) C1CURB14C-1 838 (33) C1CURB15C-1 OUTDOOR COILS OPTIONAL RETURN AIR PANEL KIT (Required For Horizontal Applications) 381 (15) 51 (2) HORIZONTAL SUPPLY 1537 (60-1/2) HORIZONTAL RETURN 1905 (75) 356 (14) 314 (12-3/8) 210 (8-1/4) NOTE Top of Roof Curb extends102 mm (4 inch) inside bottom of unit base. See Typical flashing detail. 667 (26-1/4) OPTIONAL HORIZONTAL ROOF CURB (Required For Horizontal Applications) 165 (6-1/2) C1CURB14C-1 445 (17-1/2) C1CURB15C-1 10 AUS - 13 23 50 www.lennoxaus.com.au NZ - 0800 653 330 www.lennoxnz.co.nz
Notes AUS - 13 23 50 www.lennoxaus.com.au NZ - 0800 653 330 www.lennoxnz.co.nz 11
The contents of this brochure are copyright protected and may not be reproduced in any form without the written consent of Heatcraft. Recommendations and advice regarding the use of the products described in this publication are to be taken as a guide only and are given without liability on the part of the company or its employees. As Heatcraft continually improves its product range and processes, Heatcraft reserves the right to change product specifications without any prior notification. Please refer to the Heatcraft website for the latest version of this publication. The purchaser should independently determine the suitability of the product for the intended use and application and that the product complies with relevant standards. Heatcraft accepts no responsibility for loss or damage (direct or indirect and including consequential loss, loss of profits or opportunity and economic loss) however arising which results from any errors or omissions in the information contained in this publication or arising from the use or application of the information contained herein. LENNOXLANDMARK_1116 australia 13 23 50 lennoxaus.com.au new zealand 0800 653 330 lennoxnz.co.nz and Registered Trade Mark and Trade Mark of Heatcraft Australia Pty Ltd Copyright 2016 Heatcraft Australia Pty Ltd 12 AUS - 13 23 50 www.lennoxaus.com.au NZ - 0800 653 330 www.lennoxnz.co.nz