OPTIMUM ALLOCATION OF DISTRIBUTED GENERATION BY LOAD FLOW ANALYSIS METHOD: A CASE STUDY

Similar documents
New York Science Journal 2017;10(3)

RECONFIGURATION OF RADIAL DISTRIBUTION SYSTEM ALONG WITH DG ALLOCATION

A Novel Approach for Optimal Location and Size of Distribution Generation Unit in Radial Distribution Systems Based on Load Centroid Method

Power Losses Estimation in Distribution Network (IEEE-69bus) with Distributed Generation Using Second Order Power Flow Sensitivity Method

The Effect Of Distributed Generation On Voltage Profile and Electrical Power Losses Muhammad Waqas 1, Zmarrak Wali Khan 2

Strategic Placement of Distributed Generation in Distribution Networks

DISTRIBUTED GENERATION FROM SMALL HYDRO PLANTS. A CASE STUDY OF THE IMPACTS ON THE POWER DISTRIBUTION NETWORK.

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

Effect of prime mover speed on power factor of Grid Connected low capacity Induction Generator (GCIG)

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

CHAPTER I INTRODUCTION

IMPACT OF THYRISTOR CONTROLLED PHASE ANGLE REGULATOR ON POWER FLOW

Performance Analysis of Transmission Line system under Unsymmetrical Faults with UPFC

TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC)

Computation of Sensitive Node for IEEE- 14 Bus system Subjected to Load Variation

Optimal Placement of Distributed Generation for Voltage Stability Improvement and Loss Reduction in Distribution Network

POWER DISTRIBUTION SYSTEM ANALYSIS OF URBAN ELECTRIFIED RAILWAYS

ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

Adaptive Power Flow Method for Distribution Systems With Dispersed Generation

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

VOLTAGE STABILITY IMPROVEMENT IN POWER SYSTEM BY USING STATCOM

Thermal Analysis of Laptop Battery Using Composite Material

Electric Vehicles Coordinated vs Uncoordinated Charging Impacts on Distribution Systems Performance

Optimal sizing and Placement of Capacitors for Loss Minimization In 33-Bus Radial Distribution System Using Genetic Algorithm in MATLAB Environment

IJRASET 2013: All Rights are Reserved

Optimal placement of SVCs & IPFCs in an Electrical Power System

Reliability Analysis of Radial Distribution Networks with Cost Considerations

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

Management of Congestion in the Deregulated Energy Market

CONTINGENCY ANALYSIS AND RANKING ON 400 KV KARNATAKA NETWORK BY USING MIPOWER

International Journal Of Global Innovations -Vol.2, Issue.I Paper Id: SP-V2-I1-048 ISSN Online:

CONGESTION MANAGEMENT IN DEREGULATED POWER SYSTEM USING FACTS DEVICES

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line

Analysis of Grid Connected Solar Farm in ETAP Software

Reduction of Distribution Losses by combined effect of Feeder Reconfiguration and Optimal Capacitor Placement

Implementation SVC and TCSC to Improvement the Efficacy of Diyala Electric Network (132 kv).

STABILITY ANALYSIS OF DISTRIBUTED GENERATION IN MESH DISTRIBUTION NETWORK IN FREE AND OPEN SOURCE SOFTWARE

IMPROVEMENT OF LOADABILITY IN DISTRIBUTION SYSTEM USING GENETIC ALGORITHM

Okelola, M. O. Department of Electronic & Electrical Engineering, Ladoke Akintola University of Technology, P.M.B. 4000, Ogbomoso, Nigeria

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults

CFD Investigation of Influence of Tube Bundle Cross-Section over Pressure Drop and Heat Transfer Rate

Novel planning techniques for the optimal allocation of DSOs owned energy storage

Use of STATCOM for Improving Dynamic Performance of Wind Farms Connected in Power Grid

Voltage Control Strategies for Distributed Generation

ECONOMIC EXTENSION OF TRANSMISSION LINE IN DEREGULATED POWER SYSTEM FOR CONGESTION MANAGEMENT Pravin Kumar Address:

*Author for Correspondence

OPTIMAL Placement of FACTS Devices by Genetic Algorithm for the Increased Load Ability of a Power System

Targeted Application of STATCOM Technology in the Distribution Zone

Power Consump-on Management and Control for Peak Load Reduc-on in Smart Grids Using UPFC

Network Reconfiguration for Loss Reduction and Voltage Profile Improvement of 110-Bus Radial Distribution System Using Exhaustive Search Techniques

Review paper on Fault analysis and its Limiting Techniques.

Control Scheme for Grid Connected WECS Using SEIG

APPLICATION OF STATCOM FOR STABILITY ENHANCEMENT OF FSIG BASED GRID CONNECTED WIND FARM

COMPARISON OF DIFFERENT SOFTWARE PACKAGES IN POWER FLOW AND SHORT-CIRCUIT SIMULATION STUDIES. A Project

Load Frequency Control of a Two Area Power System with Electric Vehicle and PI Controller

SMART MICRO GRID IMPLEMENTATION

Grid Stability Analysis for High Penetration Solar Photovoltaics

Control Application of PV Solar Farm as PV- STATCOM for Reactive Power Compensation during Day and Night in a Transmission Network

Performance of Low Power Wind-Driven Wound Rotor Induction Generators using Matlab

Voltage Index Method for Optimal Allocation of DG Units in a Distribution system to improve the Voltage Stability Margin

Power System Analysis for a Utility with Localized Wind Generation: Southern Negros Oriental Case

Implementation of FC-TCR for Reactive Power Control

A Method for Determining the Generators Share in a Consumer Load

DESIGN AND ANALYSIS OF CONVERTER FED BRUSHLESS DC (BLDC) MOTOR

International Conference on Advances in Energy and Environmental Science (ICAEES 2015)

Complex Power Flow and Loss Calculation for Transmission System Nilam H. Patel 1 A.G.Patel 2 Jay Thakar 3

Analysis of Low Tension Agricultural Distribution Systems

By: Ibrahim Anwar Ibrahim Ihsan Abd Alfattah Omareya. The supervisor: Dr. Maher Khammash

Simulation Analysis of Closed Loop Dual Inductor Current-Fed Push-Pull Converter by using Soft Switching

Impact of Distributed Generation on Reliability of Distribution System

Maximization of Net Profit by optimal placement and Sizing of DG in Distribution System

LOCAL VERSUS CENTRALIZED CHARGING STRATEGIES FOR ELECTRIC VEHICLES IN LOW VOLTAGE DISTRIBUTION SYSTEMS

TRANSNATIONAL ACCESS USER PROJECT FACT SHEET

An Approach for Formation of Voltage Control Areas based on Voltage Stability Criterion

JCHPS Special Issue 1: February Page 275

Impacts of distributed photovoltaic generation on Jenin distribution network: voltage level, power losses, power factor and power quality

A SIMPLE CONTROL TECHNIQUE FOR UNIFIED POWER FLOW CONTROLLER (UPFC)

Power Flow Management and Control of Hybrid Wind / PV/ Fuel Cell and Battery Power System using Intelligent Control

Performance Analysis of Transient Stability on a Power System Network

CASE STUDY OF POWER QUALITY IMPROVEMENT IN DISTRIBUTION NETWORK USING RENEWABLE ENERGY SYSTEM

CONNECTION OF NEW GENERATORS IN THE ELECTRICAL POWER SYSTEM OF KOSOVO. Rexhep Shaqiri 1, Bogdanov Dimitar 2.

A.Arun 1, M.Porkodi 2 1 PG student, 2 Associate Professor. Department of Electrical Engineering, Sona College of Technology, Salem, India

Transmission Coordination and Planning Committee 2016 Q4 Stakeholder Meeting

Fuzzy Based Unified Power Flow Controller to Control Reactive Power and Voltage for a Utility System in India

Experimental Resultsofa Wind Energy Conversion Systemwith STATCOM Using Fuzzy Logic Controller

GTG MW GTG MW STG 2 36 MW CB11 CB9 GEN TRAFO-4. GEN TRAFO-5 50 MVA 11/34.5 kv %Z. GEN TRAFO-2 50 MVA 11/34.5 kv 15.

Behaviour of battery energy storage system with PV

Design Modeling and Simulation of Supervisor Control for Hybrid Power System

Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device

Characterization of Voltage Rise Issue due to Distributed Solar PV Penetration

Determination of the Optimal Location of Superconductive Fault Current Limiter in a Power System with Grid Connection

Implementation of Steady-State Power System Visualizations Using PowerWorld Simulator. Dr. Jung-Uk Lim, Department of Electrical Engineering

Field Verification and Data Analysis of High PV Penetration Impacts on Distribution Systems

SOLAR PHOTOVOLTAIC ARRAY FED WATER PUMP RIVEN BY BRUSHLESS DC MOTOR USING KY CONVERTER

Electric Power Research Institute, USA 2 ABB, USA

Impact Analysis of Fast Charging to Voltage Profile in PEA Distribution System by Monte Carlo Simulation

COMPARISON OF ANALYTICAL & FEA OF CONTACT ANALYSIS OF SPUR GEAR DRIVE

Transcription:

OPTIMUM ALLOCATION OF DISTRIBUTED GENERATION BY LOAD FLOW ANALYSIS METHOD: A CASE STUDY Wasim Nidgundi 1, Dinesh Ballullaya 2, Mohammad Yunus M Hakim 3 1 PG student, Department of Electrical & Electronics, SDM College of Engineering and Technology Dharwad, Karnataka, India 2 Professor, Department of Electrical & Electronics, SDM College of Engineering and Technology Dharwad, Karnataka, India 3 PG student, Department of Electrical & Electronics, SDM College of Engineering and Technology Dharwad, Karnataka, India Abstract DG is nothing but a small scale generation element connected directly to the distribution network or near customer load center. DG affects the flow of power and voltage conditions at customers and utility equipment. These impacts may manifest themselves either positively or negatively depending on the distribution system operating characteristics and the DG characteristics. DG has a limited size of 10MW or less especially when DG is used in a distribution network. DG is installed at the place where it becomes unfeasible to build a central generation plant. DG is installed to improve the voltage profile as well as minimize losses. DG allocation is a crucial factor. Optimum DG allocation provides a variety of benefits. But inappropriate DG allocation can cause low or over voltage in the network. In this paper a case study is carried out for the Dharwad region, Karnataka. Load flow based method and ETAP software is used to determine the optimum location & optimum size of DG for voltage profile improvement & loss reduction. Keywords: Distributed Generation, Load flow Analysis, ETAP, optimum location, voltage profile improvement. ----------------------------------------------------------------------***---------------------------------------------------------------------- 1. INTRODUCTION Distributed generation is related to the use of small generation units installed in strategic points of the electric power system and mainly, close to load centers. DG can be used in an isolated way, supplying the consumer s local demand or in an integrated way, supplying energy to the remaining of the electric system. In distribution systems, DG can provide benefits for the consumers as well as for the utilities, especially in sites where the central generation is impracticable or where there are deficiencies in the transmission system. A distributed power element can be connected directly to a utility s transmission or distribution system or to consumer s terminal. Distributed generation is not centrally planned, today not centrally dispatched; it is usually connected to the distribution network & its size may be smaller than 50 or 100MW [1]. DG must be reliable, transmittable of the proper size and strategically placed to give the following system benefits: grid reinforcement, voltage support and improved power quality, loss reductions, transmission and distribution capacity release, improved utility system reliability, congestion control, Reduction in fuel and operating costs, Enhanced productivity, reduce reserve requirement, increase system security. The optimal placement and sizing of generation units on the distribution network has been continuously studied in order to achieve different aims. The objective can be the minimization of the active losses of the feeder [2], or the minimization of the total network supply costs, which includes generators operation and losses compensation [3], [4],or even the best utilization of the available generation capacity [5]. As a contribution to the methodology for DG allocation, in this paper it is presented an algorithm for the allocation of generators in distribution networks, in order to voltage profile improvement and loss reduction in distribution network. This paper represents a novel approach to analyze the power system network by using ETAP with the help of one line diagram. This diagram is implemented in ETAP to perform load flow study. The system is analyzed under steady state by using load flow analyses method; the data which is taken for the case is peak load data. Section 2 is the complete single line diagram of the system under consideration; this diagram is implemented based upon practical data in ETAP for simulation purpose in Section 3 describes about load flow methodology. Section 4 and 5 consists of ETAP simulation techniques and algorithm for the case study and contains analysis which include load flow. Section 6 deals with Conclusion of this research work. Volume: 03 Issue: 05 May-2014, Available @ http://www.ijret.org 288

2 SINGLE LINE DIAGRAM OF CASE UNDER STUDY Fig. 1 shows the single line diagram of the complete power system of the Dharwad, Karnataka region which is under study. It is clear from the Fig. 1 that there are two incoming lines of 110 kv supplying power to seven substations and these substations are connected with 11 kv power distribution network (11 kv feeders). The load connected with the system is industrial load, offices load, plazas, shops and domestic load. The load can also be classified as lights, fans, air conditioners, room coolers, water coolers, printers, computers, induction motors, irrigation pumps and the other industrial equipment etc. Comprehensive load modelling is performed in ETAP based upon original system data. Fig -2: Single line diagram of Belur Substation Monitoring Points are also marked on the same single line diagram. The buses are named according to the substation name. Different power transformers with ratings are shown in the single line diagram to step down the voltage level. Single line diagram of the different composite network is also shown Fig -3: Single line diagram of Substation Fig -1: Single line diagram of Dharwad Area Fig -4: Single line diagram of lakmanahalli Substation Volume: 03 Issue: 05 May-2014, Available @ http://www.ijret.org 289

Fig -5: Single line diagram of Mrutyunjaya Substation Fig -7: Single line diagram of Tadasinkoppa Substation Fig -6: Single line diagram of Navnagar Substation Fig -8: Single line diagram of Tarihal Substation 3. POWER FLOW ANALYSIS Power flow analysis is one of the most common computational procedures used in power system analysis. Power flow calculation presents state of the system for a given load and generation. These studies help to analyze the steady state performance of the power system under various operating Volume: 03 Issue: 05 May-2014, Available @ http://www.ijret.org 290

BUS-1 BUS-2 BUS-3 BUS-4 BUS-5 BUS-1 BUS-2 BUS-3 BUS-1 BUS-2 BUS-3 BUS-4 BUS-5 MR BUS-1 MR BUS-2 MR BUS-3 MR BUS-4 NARENDRA BUS BUS-1 BUS-2 PGCL BUS SRS BUS1 SRS BUS2 TAD BUS1 TAD BUS2 BUS-1 BUS-2 BUS-3 BUS-4 IJRET: International Journal of Research in Engineering and Technology eissn: 2319-1163 pissn: 2321-7308 conditions. They are used to determine the circuit loading, voltages at the various buses, reactive power flow, system losses, and branch losses. The studies also helps to identify critical conditions such as over voltages, under voltages, operation near rated value etc. and desired transformer tap settings. Power flow studies and analysis of the continuous process plant with CPP was performed to ensure the security of the power system with respect to available generation capacity and voltage profiles at various buses for various operating conditions. 4. SIMULATION TECHNIQUES The paper presents a method using load flow analysis to allocate a DG at optimum place to improve the system voltage profile also another method to select the size of Discrete Generation to maintain the a minimum loss and voltage profile 4.1 Proposed Methodology To find the proper DG allocation in a distribution system for voltage profile improvement is the main aim of this procedure. The method is based on load flow. The sensitive buses to voltage (the buses that have a low voltage scale) are considered and ranked in the first step, the aim of this step is to install the DG unit for voltage control and the DG is placed in all buses & the voltage profile of the entire system in each installation is considered in the second step. After DG installation in each bus, the voltage profiles of all states are ranked from the best state to worst. Finally, two lists are considered to choose the best place to install the DG distribution system to provide a good voltage profile. 4.2 Computational Procedure Run the base case load flow The graph of voltage v/s bus ID is plotted From the graph (voltage v/s ), the priority list is formed: the sensitive buses (that should have a voltage control) in highest rank. DG is placed in each bus Run the load flow of the system after DG installation in each bus. Then the graphs of voltage profile of the system after placement of DG in each bus is drawn. Then another priority list is formed in this format: after comparing the graphs, it is required to rank them from the best profile to the worst one. The proper place of DG is chosen by comparing the priority list of Simulation Results i.e. the s with the highest ranking : The load flow is done on the distribution system and the voltages are shown in table 1. Table -1: The voltage of the buses after load flow Before DG installation BUS-1 0.968845455 MR BUS-3 0.934363636 BUS-2 0.93830303 MR BUS-4 0.954393939 BUS-3 0.921181818 BUS-4 0.921181818 BUS-5 0.921181818 BUS-1 0.968581818 BUS-2 0.954636364 SRS BUS1 1 BUS-3 0.954636364 SRS BUS2 0.9746 BUS-1 0.969190909 BUS-2 0.944090909 BUS-3 0.944090909 BUS-4 0.927454545 BUS-5 0.927454545 MR BUS-1 0.969372727 MR BUS-2 0.934363636 V O L T A G E ( P. U ) 1.02 1 0.98 0.96 0.94 0.92 0.9 0.88 NAREND RA BUS 0.969881818 BUS-1 0.970172727 BUS-2 0.944181818 PGCL BUS 1 TAD BUS1 0.970318182 TAD BUS2 0.951272727 BUS-1 0.9746 BUS-2 0.954909091 BUS-3 0.952848485 BUS-4 0.942272727 VOLTAGE PROFILE BEFORE DG ALLOCATION Fig -9: The voltage profile of the system before DG allocation Now according to the algorithm, the buses should be ranked from the minimum value of the voltage to the maximum one. Volume: 03 Issue: 05 May-2014, Available @ http://www.ijret.org 291

Table -2: The buses are ranked from minimum value to maximum value (before DG installation) P.U Rank BUS-3, BUS-4, BUS-5, BUS- 4, BUS-5 0.92-0.93 1 MR BUS-2,MR BUS-3, BUS-2 0.93-0.94 2 BUS-4, BUS-2, BUS-3, BUS-2 0.94-0.95 3 TAD BUS2, BUS-3,MR BUS-4, BUS-2, BUS- 3, BUS-2 0.95-0.96 4 BUS-1, BUS- 1, BUS-1,MR BUS- 1,NARENDRA BUS 0.96-0.97 5 BUS-1,TAD BUS1,SRS BUS2, BUS-1 0.97-0.98 6 ---------- 0.98-0.99 7 PGCL BUS,SRS BUS1 0.99-1.0 8 The voltage profile of each state is found after DG installation on each bus. The voltage profiles are ranked from the best profile to worst one. Table 4 shows the ranking of voltage profile of buses after DG installation. Table -3: The voltage of the buses after load flow after dg allocation at all buses. BUS-1 1 MR BUS-3 1 BUS-2 0.994333 MR BUS-4 1 BUS-3 1 NARENDRA BUS 1.0001 BUS-4 1 BUS-1 1.004 BUS-5 1 BUS-2 1 BUS-1 1.002591 PGCL BUS 1 BUS-2 1 SRS BUS1 1 BUS-3 1 SRS BUS2 1.000745 BUS-1 1.005091 TAD BUS1 1.0002 BUS-2 1 TAD BUS2 1 BUS-3 1 BUS-1 1.000745 BUS-4 1 BUS-2 1 BUS-5 1 BUS-3 1 MR BUS-1 1.000164 BUS-4 1 MR BUS-2 1 Table -4: The buses are ranked from best voltage profile to worst voltage profile after DG installation. Rank BUS-1, BUS- 1, BUS-1,SRS BUS2, BUS-1,TAD BUS1,MR BUS- 1,NARENDRA BUS 1.0002-1.0051 1 BUS-1, BUS- 3, BUS-4, BUS-5, BUS-2, BUS-3, BUS-2, BUS-3, BUS-4, BUS-5,MR BUS-2,MR BUS- 3,MR BUS-4, BUS- 2,PGCL BUS,SRS BUS1,TAD BUS2, BUS-2, BUS- 3, BUS-4. 0.9951-1.00000 2 BUS-2 0.9902-0.9951 3 Comparing table 2 & 4, it is necessary to rank the best buses for DG installation. Table 5 shows the best locations for 7.5 MW DG installation to improve the voltage profile and voltage stability. The important point that can be already considered from the table V is that the optimum DG locations are the bus ID BUS-3, BUS-4 and MR BUS-2. The other ranking in the table are not very important because it is not necessary to locate the best place. The voltage profiles of the distribution system in the presence of DG in buses BUS-3, BUS-4 and MR BUS-2 are shown below. It shows the voltage profile improvement. Table -5: Optimum bus ID s for dg allocation BUS ID RANK BUS-3, BUS-4 1 MR BUS-2 2 BUS-2 3 BUS-4, BUS-2, BUS-2 4 TAD BUS2, BUS-3,MR BUS-4, 5 BUS-2, BUS-3, BUS-2 BUS-1, BUS-1,MR BUS-1, 6 NARENDRA BUS BUS-1 7 BUS-1,TAD BUS1,SRS BUS2, 8 BUS-1 PGCL BUS,SRS BUS1 9 Volume: 03 Issue: 05 May-2014, Available @ http://www.ijret.org 292

BUS-1 BUS-2 BUS-3 BUS-1 BUS-2 BUS-3 BUS-4 BUS-5 MR BUS-1 MR BUS-2 MR BUS-3 MR BUS-4 NAREND PGCL BUS SRS BUS1 SRS BUS2 TAD BUS1 TAD BUS2 BUS-1 BUS-2 BUS-3 BUS-4 IJRET: International Journal of Research in Engineering and Technology eissn: 2319-1163 pissn: 2321-7308 Table -6: voltage profile display after 7.5MW DG installation at 3 buses (MR BUS-2, BUS-3, and BUS-4) BUS-1 0.9805 MR BUS-3 0.971545455 BUS-2 0.950212121 MR BUS-4 0.966151515 BUS-3 0.951 NARENDR A BUS 0.981290909 BUS-4 0.951 BUS-1 0.982063636 BUS-5 0.951 BUS-2 0.956272727 BUS-1 0.980681818 PGCL BUS 1 BUS-2 0.967363636 SRS BUS1 1 BUS-3 0.967363636 SRS BUS2 0.984036364 BUS-1 0.981890909 TAD BUS1 0.9815 BUS-2 0.957030303 TAD BUS2 0.962636364 BUS-3 0.957030303 BUS-4 0.966363636 BUS-5 0.966363636 MR BUS-1 0.981009091 MR BUS-2 0.971545455 V o l t a g e ( P. U ) 1.02 0.98 1 0.96 0.94 0.92 BUS-1 0.984036364 BUS-2 0.964545455 BUS-3 0.962424242 BUS-4 0.951909091 Profile after DG allocation interconnected at transmission voltage where the system is designed to accommodate many generators. 5.1 Proposed Methodology To find the optimum size of a DG unit in order to decrease the power loss as well as to maintain a good voltage profile of the distribution system is the aim of this procedure. To determine the optimum size it is necessary to install different sizes of DGs at optimum place (the place where total system loss is minimum) 5.2 Computational Procedure After determining optimum DG location for voltage profile improvement, the following steps are followed for finding optimum DG size. In this procedure different size of DG is placed at the optimum location (i.e. at MR BUS-2, BUS-3, and BUS-4 of the power system). It is also necessary to study the voltage profile& total loss of the system after installing DG of different size. The DG which provides a good voltage range with a minimum total power loss, acceptable as an optimum size. Table -7: Comparison of voltage & total loss for different dg size at 3 buses (MR BUS-2, BUS-3, and BUS- 4) DG size Total losses MW MW MVAR 1 0.82 12.149 No 2 0.776 11.381 No 3 0.734 10.652 No 4 0.703 10.074 No 5 0.659 9.307 No 6 0.624 8.691 Yes 7 0.592 8.113 Yes 8 0.562 7.571 Yes 9 0.535 7.066 Yes within limits Fig -10: The voltage profile of the system after DG allocation at 3 buses 5. OPTIMUM DG SIZING The size of DG depends upon the type of the load, power quality and secondary distribution system, for these reasons the size of DG which is considered is less than 10MW. Distributed generator larger than this is typically The marginal under voltage range is 0.95-0.98 P.U, bus voltage below this range is known as critical under voltage. The power system under study has a total loss of 0.958 MW & a voltage range of 0.923-1.0 P.U without DG. Bus voltage of 0.923 P.U is below the lower limit of marginal under voltage, called critical under voltage. So the voltage profile (0.923-1.0 P.U) of power system under study without DG provides a worse voltage profile & the total loss of the system is high. It is necessary to install DG of optimum size at optimum location to improve the voltage profile as well as to minimize loss. The optimum size of DG is 7MW for the power system Volume: 03 Issue: 05 May-2014, Available @ http://www.ijret.org 293

BUS-1 BUS-2 BUS-3 BUS-1 BUS-2 BUS-3 BUS-4 BUS-5 MR BUS-1 MR BUS-2 MR BUS-3 MR BUS-4 NARENDR PGCL BUS SRS BUS1 SRS BUS2 TAD BUS1 TAD BUS2 BUS-1 BUS-2 BUS-3 BUS-4 IJRET: International Journal of Research in Engineering and Technology eissn: 2319-1163 pissn: 2321-7308 under study, it is concluded after studying the table VII. The voltage profile for DG with 7MW capacity is shown below. V o l t a g e ( P. U ) 1.02 1 0.98 0.96 0.94 0.92 Fig -11: The voltage profile of the system after DG allocation at 3 places with 7MW capacity. 6. CONCLUSIONS profile for 7MW DG The size & location of DGs are crucial factors in the application of DG for loss minimization & voltage improvement respectively. This paper deals with a load flow based simulation using ETAP to find out the optimum location & optimum size of DG unit for voltage profile improvement & minimizing power losses in the Power System Under study. The installation of DG unit at non optimal places can result in an increase in system losses; implying in an increase in costs & resulting low or over voltages in the network, having an effect opposite to the desired. For that reason, the use of a methodology capable of analyzing the influence on some system characteristics of DG allocation can be very useful for the system planning engineer when dealing with the increase of DG penetration that is happening nowadays. The proposed algorithm is already discussed in this paper, more accurate & can identify the best location for single DG placement in order to improve the voltage profile & to minimize total power losses. The proposed method has also used to determine the optimum size & location of DG unit. Results prove that the optimum size & location of a DG can save a huge amount of power. Power system deregulation and shortage of transmission capacities have led to an increase interest in Distributed generations (DGs) sources. The optimal location of DGs in power systems is very important for obtaining their maximum potential benefits. In this paper, only optimum location of DG has been determined for loss reduction and voltage improvement in the distribution system. For proper allocation of DG, size of DG also plays an important role. Size of DG effects losses and voltage profile of the distribution system. Also a comparative study can be done between different techniques like Analytical method, Optimum power flow method, Evolutionary techniques like Genetic Algorithm(GA), Fuzzy logic etc. for finding optimum size and location of DG for loss minimization and voltage improvement of the power system. REFERENCES [1] F.Gonzalez-Longatt,C.Fortoul Review Of The Distributed Generation Concept. Attempt Of Unification. [2] K. Nara, Y. Hayashi, K. Ikeda,and T. Ashizawa,"Application of tabu search to optimal placement of distributed generators," in Proc. 2001IEEE Power Engineering Society Winter Meeting, pp. 918-923 [3] G. Celli, and F. Pilo, "Optimal distributed generation allocation in MV distribution networks," in Proc.2001 IEEE PICA Conference, pp. 81-86. [4] W. El-Khattam, K. Bhattacharya, Y. Hegazy, and M. M. A. Salama, "Optimal investment planning for distributed generation in a competitive electricity market," IEEE Trans. Power Systems, vol. 19, pp. 1674-1684, Aug.2004. [5] A. Keane, and M. O'Malley, "Optimal allocation of embedded generation on distribution networks," IEEE Trans. Power Systems, vol. 20, pp. 1640-1646, Aug. 2005. [6] B.Kuri, M.Redfern, F.LI, Optimization of rating and positioning of dispersed generation with minimum network disruption,2004 IEEE power engineering society general meeting, 6-10 June 2004, vol. 2,pp. 2074-2078. [7] Nibedita Ghosh, Sharmistha Sharma, Subhadeep Bhattacharjee A Load Flow based Approach for Optimum Allocation of Distributed Generation Units in the Distribution Network for Improvement and Loss Minimization, International Journal of Computer Applications (0975 8887) Volume 50 No.15, July 2012 [8] A.Cano, F.Jurado, Optimum location of biomassfuelled gas turbines in an electric systems,2006 IEEE power Engineering Society General Meeting, 18-22 June 2006. BIOGRAPHIES Wasim Nidgundi Currently pursuing M.Tech in Power system Engineering at SDMCET Dharwad. Obtained B.E from SDMCET Dharwad.Area of interest are power system planning, power system reliability studies, real time power system studies. Prof.Dinesh Ballullaya currently working as a professor in SDMCET Dharwad. Obtained his B.E and M.Tech from SJCE mysore.he has 31 years of experience in teaching. Areas of Expertise Electrical machines. Volume: 03 Issue: 05 May-2014, Available @ http://www.ijret.org 294

Mohammad Yunus M Hakim Currently pursuing M.Tech in Power system Engineering at SDMCET Dharwad. Obtained B.E from BLDE bijapur.area of interest is power quality study, electrical machines. Volume: 03 Issue: 05 May-2014, Available @ http://www.ijret.org 295