MATRIX LLC LEVEL CONTROL PANEL

Similar documents
QUANTUM LX CONTROL PANEL

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Signet Temperature Transmitter

Signet Pressure Transmitter

INTECH Micro 2300-RTD6

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide

USERS MANUAL MCD REMOTE OPERATOR

SIGNET Temperature Transmitter

OPERATION MANUAL Variable Speed Pump Controller Dated: 06/04/2013 Pump Down Application. Document No.: LMSII_V100_OM Page 1 of 8 Model-V100 LMS II

Signet Pressure Transmitter

Description. functions including single duct pressure dependent or pressure independent systems.

Heating Cable. Description

R & D SPECIALTIES ROTROL I USER'S MANUAL

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING

PowerView PV380-R2 Mechanical Configuration

Spartan Controls Millennium Compressor Control Panel Operating Philosophy

RVS-DN Digital Reduced Voltage Motor Starter

RVS-DX Digital Reduced Voltage Motor Starter

ECCII to ECCIII Upgrade Kit

Application Engineering

PCT-3001 plus. Display LCD

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

TTM MODEL TTM TRANSFORMER TEMPERATURE MONITOR AND COOLING CONTROL SYSTEM. BCI Bulletin BCI-TTM-01 Revision 12/03/02

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION

Product Manual. Part Number: MVP-193 Mefi-6 ECU Revision: 1.0

Cascade CD101 Auto-Start Controller. Installation and Operations Manual Sections 40 & 75

Vission 20/20 micro-controller. Operation and service manual

Vission 20/20 micro-controller. Operation and service manual Version 2.6

Application Engineering

Flight Systems. Replacement for KASSEC DESCRIPTION

User manual. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS.

Product Information Page

GENERAL INFORMATION. H-1649, H-1650, H-1651 H-1653, H-1654 Easy-Count. uline.com. that may hurt accuracy:

Harris IRT Enterprises Digital Resistance Tester Model XP

HBLT-C1 Controller. Instruction Manual. For pump control of levels in industrial refrigeration systems

Digital Fan Coil Thermostats with 0(2)-10 VDC Fan Output

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n Revision 0

INSTALLATION/OPERATING INSTRUCTIONS TSC


Model H30 Operation Manual

Positive displacement batch controller

P445 Series Electronic Lube Oil Control

Quick Setup Guide for IntelliAg Model YP40 20 Air Pro

Te 803 Electronic Controller. Service, Operation & Technical Information Manual

STRA-24 for chilled beams

Loadcell Tension Control

ECONOMISER SERIES E2T USER MANUAL

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp

SE7200 Series Installation Guide

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, P/N: , Revision 1

ICL Three Pump Controller

Application Engineering Europe

Operations Manual *Products covered in this document comply with European Council electromagnetic compatibility directive 2004/108/EC and electrical

PowerCommand 2100 digital generator set control

Drive Electronics \ Drive Automation \ System integration \ Services MOVITRAC LTP. Catalog. Edition 03/ / EN

Quick Setup Guide for IntelliAg Model YP Air Pro

Modbus Integration Integration for Modbus Functionality for VT8600 Series

FVC2100/2200 TEK-AIR TECHNICAL PRODUCT DATA SHEET FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER. Application. General Description

ICON 2 1. FEATURES AND CHARACTEIRICS

Generator Sets Controller 210. Operation Manual. Ver1.0

Power Switching Devices

BERMAD Waterworks. Insertion Flow Meter Device (IFM)

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

SmartVFD HVAC FEATURES APPLICATION SPECIFICATION DATA

Supersedes CL2 (512) Form CL2 (615) STARTUP CHECKLIST PHONE: CUSTOMER ORDER NO: JCI TEL NO: JCI ORDER NO: JCI CONTRACT NO:

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016

DIESEL Engine Fire Pump Controllers Features

Issue 2.0 December EPAS Midi User Manual EPAS35

TOUCH PLS TOUCHSCREEN PLS A NEW HORIZON IN PROGRAMMABLE LIMIT SWITCHES

Owner s Manual. MG2000 Speedometer IS0211. for use with SmartCraft Tachometer

Section 55 Chapter 6

OPERATING INSTRUCTIONS

Digital Room Thermostats with Touch Screen LCD

Control Panel. Operation and Service Manual

Low Pressure Sensor. Overview. Specifications. Installation and Operation

201A-9 INSTALLATION INSTRUCTIONS. Revision A1 Rapid City, SD, USA, 01/2010

Vantage 6000 Portable Ultrasonic Flow Meter

AMI. American Magnetics, Inc. Excellence in Magnetics and Cryogenics

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

DX330 L/M/V. Safer. Faster. Easier SERIES DOTECH, INC. Universal Intelligent Controller for Screw Air Compressor

Power Flame Incorporated

AIR VOLUME TRANSMITTER / CONTROLLER IML

FRICK QUANTUM HD COMPRESSOR CONTROL PANEL

AQUATIC INTELLIGENCE FILTER CONTROL GUIDE

PRESSURE GOVERNOR, ENGINE MONITORING, AND MASTER PRESSURE DISPLAY MODEL TCA200

GENERAL INFORMATION MECHANICAL INSTALLATION PRESSURE INDEPENDENT VALVES 2-1/2"-10" MVP INSTALLATION & OPERATION INSTRUCTIONS UNION CONNECTIONS

INSTALLATION AND OPERATION INSTRUCTION

MANUAL FOR MODEL FD4 FIRE PUMP CONTROLLERS

Model DS5000 Dewpoint Monitor

DKG-317 MANUAL AND REMOTE START UNIT

Accutrol, LLC Product Sheet AVC6000. US Patents 6,991,177 & 7,543,759. Laboratories, Life Sciences, Healthcare

Stepping Motor and Driver Package. High-Efficiency AR Series. DC Power-Supply Input. Built-in Controller Type Pulse Input Type

EGT-100 Operations and Installation Manual

OPERATING INSTRUCTIONS ECON-M

PowerCommand 1.1 control system

SE8300 Series Installation Guide 24 Vac Low Voltage

ESV. Electronic Steam Valve Control Modulates One or Two Actuators. Installation and Operation Manual ESV. Control Module

Operating Instructions incl. Declaration of Conformity. Controller RVC 300 BG BE / C ( ) 1

Transcription:

MATRIX LLC LEVEL CONTROL PANEL Installation Operation Maintenance Manual 1-26-09 REV-0.3 1

INDEX Introduction. 3 Product Configurations..... 4 I/O Descriptions. 8 Operation o Intercooler, Accumulator, Surge Drum & Recirculator...... 8 o Transfer System...13 Keypad.. 16 Display Screens o Intercooler, Accumulator, Surge Drum & Recirculator 17 o Transfer System.... 42 Set-point Table 48 Specifications.... 51 2

INTRODUCTION The RVS Matrix-LLC control is a cost-effective, total packaged solution for vessel control. The dual colored level bar graph makes it easy to see the level in the vessel from a distance. Settings are simple and easy to understand. Everything is automated in the software, so there are no complicated adjustments that need to be made. Figure #1 illustrates the basic system configuration: DO1 2 X 20 LCD DISPLAY DO2 DO3 DO4 DO5 MICRO D06 AI AO1 KEYPAD AO2 AO3 LEVEL BAR GRAPH HI-LEVEL DI RS485 DO7 3

PRODUCT CONFIGURATIONS The controller can be configured to control five basic products: o Intercoolers o Accumulators o Surge Drums o Transfer systems o Recirculators The following tables illustrate the I/O configurations of each of these products: D-I/O# INTERCOOLERS & ACCUMULATORS DI DO AI AO Level Probe 1 1 7 High Level shutdown 1 1 6 High level alarm 1 5 Liquid transfer 1 4 Liquid Feed #1 1 1 3 Liquid Feed #2 1 1 2 1 Alarm horn 1 Totals 1 6 1 3 D-I/O# SURGE DRUMS DI DO AI AO Level Probe 1 1 7 High Level shutdown 1 1 6 High level alarm 1 5 4 Liquid Feed #1 1 1 3 Liquid Feed #2 1 1 2 1 Alarm horn 1 Totals 1 5 1 3 DI = Digital Input DO = Digital Output AI = Analog Input AO = Analog Output 4

D-I/O# TRANSFER SYSTEM DI DO AI AO Level Probe 1 1 7 6 5 Liquid transfer 1 4 Hot gas solenoid 1 3 Vent solenoid 1 2 1 Alarm horn 1 Totals 0 5 1 1 D-I/O# RECIRCULATOR DI DO AI AO Level Probe 1 1 7 High Level shutdown 1 1 6 High level alarm 1 5 Liquid transfer 1 4 Liquid Feed #1 1 1 3 Liquid Feed #2 1 1 2 Low level shutdown 1 1 Alarm horn 1 Totals 1 7 1 3 DIGITAL OUTPUT CONFIGURATION TABLE D-OUT-7 D-OUT-6 D-OUT-5 D-OUT-4 D-OUT-3 D-OUT-2 D-OUT-1 INTERCOOLER ACCUMULATOR HI-LEVEL SHUTDOWN HI-LEVEL ALARM LIQUID TRANSFER LIQ-SOL #1 LIQ-SOL #2 ALARM HORN SURGE DRUM HI-LEVEL SHUTDOWN HI-LEVEL ALARM LIQ-SOL #1 LIQ-SOL #2 ALARM HORN TRANSFER SYSTEM LIQUID TRANSFER HOT GAS SOL VENT SOL ALARM HORN RECIRCULATOR HI-LEVEL SHUTDOWN HI-LEVEL ALARM LIQUID TRANSFER LIQ-SOL #1 LIQ-SOL #2 LO-LEVEL SHUTDOWN ALARM HORN 5

I/O DESCRIPTIONS Analog Input #1: Analog Input #1 reads the 4-20 ma signal from the level probe. Analog Output #1: Analog Output #1 is a 4-20 ma output signal that is equivalent to the input level signal. This output is used to interface to PLC plant control systems. Analog Output #1 is an electronically repeated level input signal. It does not have direct interface to the microprocessor and therefore cannot be calibrated. Analog Output #2: Analog Output #2 is a 4-20 ma output that controls motorized liquid feed valve #1. Analog Output #3: Analog Output #3 is a 4-20 ma output that controls motorized liquid feed valve #2. Digital Input #1: Switched input, connected to the high level shutdown float switch or to an electronic level switch. If this input is energized, it is OK to run. If this input is de-energized, a high level shutdown is indicated on the screen and Digital Output #7 is de-energized. Digital Output #1: Alarm output When an alarm condition occurs, the alarm output is turned off. On in normal mode. Digital Output #2: Low level alarm output. When in the recirculator mode, this output is energized on low level alarm. Off in normal mode. Digital Output #3: Liquid feed solenoid #2 when in the following modes: Intercooler. Accumulator. Surge Drum. Recirculator. Vent solenoid when in the transfer system mode. Energized when feeding liquid or venting. Off when not feeding liquid or venting. 6

Digital Output #4: Liquid feed solenoid #1 when in the following modes: Intercooler. Accumulator. Surge Drum. Recirculator. Hot gas solenoid when in the transfer system mode. Energized when feeding liquid or hot gas. Off when not feeding liquid or hot gas. Digital Output #5: Liquid transfer solenoid/pump output. Energized when transferring. Off in normal mode. Digital Output #6: High level alarm. Energized when in alarm. Off in normal mode. Digital Output #7: High level shutdown. This output is wired directly to Digital Input #1 and is not controlled by the microprocessor. Therefore if the high level shutdown float switch trips, this output trips immediately. An external timer is required to prevent false trips to the compressors. 7

INTERCOOLER, ACCUMULATOR, SURGE DRUM & RECIRCULATOR OPERATION LEVEL CONTROL: The diagram below shows a vessel with liquid in it. A level probe reads the level and transmits the signal to the controller. The controller determines the level in comparison to the desired set-point, and if lower than set-point, energizes the liquid solenoid until the liquid level reaches the set-point. Once set-point is reached, the liquid solenoid is turned off. The signal from the level probe needs to have offset calibration so that the indicated level is the same as the actual level. A calibration screen allows the operator to input a (+/-) variable to correct the level input signal. The level value is then displayed on the operator interface and is also made available on Analog Output #1 as a 4-20mA signal and transmitted through the serial communications port. Level probe Solenoid Liquid The control algorithm is a simple servo feedback loop incorporating Proportional control as shown in the following diagram. 8

Level probe Liquid make-up Solenoid Analog in Controller Digital out The analog value is read from the level probe and compared to the set-point entered by the operator. If the level is at set-point or higher, the output remains off and the solenoid is closed. If the level drops below the set-point plus dead band, the output is turned on and the solenoid is opened. The output remains open until the level reached the set-point. A small dead-band is placed at set-point (1%) so that the solenoid cannot chatter. An example would be if the operator set the desired level at 40%. The solenoid would close at 40% and open at 39%. If there is a High Level Alarm, the liquid feed solenoid is de-energized. The liquid feed solenoid stays closed after a High Level Alarm until the level drops below the operating level. Once below the operating level, the liquid feed solenoid is re-energized under control of the liquid level control set-point. When the OFF mode is selected, the liquid feed solenoid is closed and remains closed until the ON is selected and the level is below set-point. When there is a Low Level Alarm the liquid feed solenoid continues to operate to get the vessel level back to normal operating level. Dual liquid make-up solenoids can be employed to optimize for full load and part load conditions. The two solenoids can be the same size or one larger than the other. The software would be configured so that the solenoids would be energized in a two-stage configuration. Using the previous example, where the set-point is at 40%, solenoid #1 would open when the level drops to 39%. Solenoid #2 would open when the level dropped to 34%. At this point, both solenoids are open and feeding liquid to the vessel. When the level begins to rise, the #2 solenoid would shut off at 35% and the #1 solenoid would shut off at 40%. If there is a High Level Alarm, the liquid feed solenoids are de-energized. The liquid feed solenoids stay closed after a High Level Alarm until the level drops below the operating level. Once below the operating level, the liquid feed solenoids are re-energized under control of the liquid level control set-point. 9

When the OFF mode is selected, the liquid feed solenoids are closed and remains closed until the AUTO mode is selected and the level is below set-point. When there is a Low Level Alarm, the liquid feed solenoids continue to operate to get the vessel level back to normal operating level.. Level probe 2 Solenoids Liquid MOTORIZD LIQUID FEED VALVES A variable motorized valve can be substituted for a liquid make-up solenoid. The variable valve has the advantage of feeding liquid at full flow or part load. Motorized valves eliminate the liquid hammer effect from solenoids. True P-I-D control can be used with the motorized valve where only the proportional part of the P-I-D control can be used with the solenoid. The microprocessor controller outputs a 4-20mA signal to drive the valve. Level probe P-I-D Liquid make-up motorized valve Analog in Controller Analog out 10

The analog value is read from the level probe and compared to the set-point entered by the operator. The software is configured so that the valve opens proportional to the difference in level from set-point. An example would be if the operator set the desired level set-point at 40%, the valve closed set-point at 0% difference and fully open set-point at 10% difference. If the level is at set-point or higher, the analog output remains at 4 ma which drives the motorized valve closed. If the level drops below set-point, each 1% drop, opens the valve 10%. When the vessel level drops to 30%, the valve is at 20 ma and is fully open. Level probe Motorized valve Solenoid Liquid A solenoid must be included with the motorized valve. The reason for the solenoid is that it acts as a back-up safety device in case the motorized valve sticks open or fails operate. The controller will close the solenoid when the level reaches the SOL OFF DIFF set-point, regardless of the motorized valve position. In addition, some valves may not close during a power failure, allowing liquid to continue to flow into the vessel, possibly over filling it. The solenoid assures liquid shutoff. The software, under normal operation, would energize the solenoid when the AUTO mode is selected and de-energized when the OFF mode is selected. If there is a high level alarm the solenoid is de-energized. If there is a High Level Alarm, the liquid feed solenoid is de-energized. The liquid feed solenoid stays closed after a High Level Alarm until the level drops below the operating level. Once below the operating level, the liquid feed solenoid is re-energized. The motorized valve then takes over control of the liquid level. When the OFF mode is selected, the liquid feed solenoid is closed and remains closed until the AUTO mode is selected. The motorized valve is also driven closed when the OFF mode is selected and remains closed until the AUTO mode is selected. 11

When there is a Low Level Alarm, the liquid feed solenoid and motorized valve continue to operate to get the vessel level back to normal operating level. When the vessel level rises to the Liquid Transfer ON set-point, the transfer pump/solenoid output is energized. When the vessel level drops to the Liquid Transfer OFF set-point, the transfer pump/solenoid output is de-energized. Two motorized valves can be incorporated where they can be set up as a two stage system. Level probe motorized valves Liquid Operation is similar to the previous example, except that valve #1 operates from 0 to 10% deviation from set-point. Valve #2 would operate from 10% to 20% deviation from set-point. 12

TRANSFER SYSTEM OPERATION LEVEL CONTROL: The diagram below shows a transfer vessel with liquid in it. A level probe reads the level and transmits the signal to the controller. The controller determines the level in comparison to the transfer set-points and decides whether to begin liquid transfer, end liquid transfer or wait. The signal from the level probe needs to have offset calibration so that the indicated level is the same as the actual level. A calibration screen allows the operator to input a (+/-) variable to correct the level input signal. The level value is then displayed on the operator interface and is also made available to be transmitted through the serial communications port. Vent Solenoid Level probe Hot Gas Solenoid Transfer Solenoid Liquid When the vessel is not in the transfer mode, the outputs are in the following states: o Vent solenoid = open o Hot Gas solenoid = closed o Transfer pump/solenoid = off/closed When the level in the vessel rises to the Liquid Transfer ON set-point, the following sequence occurs: o Close Vent solenoid o Time delay = 3-5 seconds o Open Hot Gas solenoid o Time delay = 5-10 seconds o Energize transfer pump/solenoid. 13

When the level in the vessel drops to the Liquid Transfer OFF set-point, the following sequence occurs: o De-energize transfer pump/solenoid. o Time delay = 5-10 seconds o Close Hot Gas solenoid o Time delay = 3-5 seconds o Open Vent solenoid. When the OFF mode is selected, the vent solenoid remains open and the Hot gas and transfer outputs are turned off. 14

Matrix LEVEL = 48% LEVEL 100 90 80 70 ENTER 60 50 40 PREV NEXT 30 20 10 15

KEYPAD Screen navigation is accomplished with seven keys: In the normal operating mode, the PREV and NEXT keys select the category of the information viewed. Pressing the NEXT key steps between: Home Data Setpoint Communications Factory Setup Program Version Info Continuing to press the NEXT key will wrap-around back to the Home screen. Either PREV or NEXT keys will rotate through the screen categories and continue to wrap around as many times as the key is pressed. When in the Factory Setup mode the following screen categories are displayed while pressing the PREV and NEXT keys: Home Data Setpoint Communications Factory Setup Password Change Calibration Program Version Info The LEFT and RIGHT arrow keys step through each of the screen categories sub menus. Pressing the RIGHT arrow key steps down into the sub menus, while the LEFT arrow key steps back out of the sub menus. There is no wrap-around with these keys. The UP and DOWN arrow keys change the setting within the sub menus. Once the setting is changed, the ENTER must be pressed to make the change valid, otherwise, the present value is retained. If an UP or DOWN key is held in, the entry selection will scroll slowly at first, then rapidly change the longer the key is held down. This feature allows for quick access to larger values within the setpoint. DISPLAY SCREENS The display is a 2 line X 20 character, alphanumeric LCD device. Operator displays are organized into categories as follows: Home Data Setpoint Communications Factory Setup Password Calibration Program Version Info 16

RECIRCULATOR INTERCOOLER ACCUMULATOR & SURGE DRUM SCREENS 17

RECIRCULATOR SCREEN MAP HOME LEVEL & ALARM LEFT ARROW RIGHT ARROW DATA % LEVEL SOLENOID #1 SOLENOID #2 MOTOR VALVE #1 MOTOR VALVE #2 LIQUID TRANSFER SETPOINT LEVEL #1 SETPOINT SOLENOID #1 MODE #1 DEAD BAND VALVE #1 MODE RESP #1 RATE #1 SOL OFF DIFF #1 LEVEL #2 SETPOINT SOLENOID #2 MODE #2 DEAD BAND VALVE #2 MODE RESP #2 PREV RATE #2 SOL OFF DIFF #2 LIQ TRANS MODE TRANSFER ON % TRANSFER ON DELAY TRANSFER OFF % NEXT TRANSFER OFF DLY HI LEVEL ALARM % HI LEVEL ALRM DLY LO LEVEL ALARM % LO LEVEL ALRM DLY HI LEVEL SHDN DLY COMM DEVICE ADDRESS BAUD RATE DATA BITS PARITY STOP BITS FACTORY SETUP INTER- COOLER ACCUM- ULATOR SURGE DRUM TRANSFER SYSTEM RECIRC SYSTEM # SOL VALVES SOL #1 NORM/REV SOL #2 NORM/REV # MOTOR VALVES VLV #1 NORM/REV VLV #2 NORM/REV PASS WORD CHANGE PASS-WRD CAL LEVEL IN LOW-CAL LEVEL IN HI-CAL MTR VAL 1 LOW-CAL MTR VAL 1 HI-CAL MTR VAL 2 LOW-CAL MTR VAL 2 HI-CAL PROGRAM VERSION VERSION # REL-DATE UP ARROW CHANGE SETPOINT DOWN ARROW SCREEN CATEGORY STANDARD KEY OPTION FACTORY SETUP 18

INTERCOOLER/ACCUMULATOR SCREEN MAP HOME LEVEL & ALARM LEFT ARROW RIGHT ARROW DATA % LEVEL SOLENOID #1 SOLENOID #2 MOTOR VALVE #1 MOTOR VALVE #2 LIQUID TRANSFER SETPOINT LEVEL #1 SETPOINT SOLENOID #1 MODE #1 DEAD BAND VALVE #1 MODE RESP #1 RATE #1 SOL OFF DIFF #1 LEVEL #2 SETPOINT SOLENO ID #2 MODE #2 DEAD BAND VALVE #2 MODE RES P #2 PREV RATE #2 SOL OFF DIFF #2 LIQ TRANS MODE TRANSFER ON % TRANSFER ON DELAY TRANSFER OFF % NEXT TRANSFER OFF DLY HI LEVEL ALARM % HI LEVEL ALRM DLY HI LEVEL SHDN DLY COMM DEVICE ADDRESS BAUD RATE DATA BITS PARITY STOP BITS FACTORY SETUP INTER- COOLER ACCUM- ULATOR SURGE DRUM TRANSFER SYSTEM RECIRC SYSTEM # SOL VALVES SOL #1 NORM/REV SOL #2 NORM/REV # MOTOR VALVES VLV #1 NORM/REV VLV #2 NORM/REV PASS WORD CHANGE PASS-WRD CAL LEVEL IN LOW-CAL LEVEL IN HI-CAL MTR VAL 1 LOW-CAL MTR VAL 1 HI-CAL MTR VAL 2 LOW-CAL MTR VAL 2 HI-CAL PROGRAM VERSION VERSION # REL-DATE UP ARROW CHANGE SETPOINT DOWN ARROW SCREEN CATEGORY STANDARD KEY OPTION FACTORY SETUP 19

SURGE DRUM SCREEN MAP HOME LEVEL & ALARM LEFT ARROW RIGHT ARROW DATA % LEVEL SOLENOID #1 SOLENOID #2 MOTOR VALVE #1 MOTOR VALVE #2 SETPOINT LEVEL #1 SETPOINT SOLENOID #1 MODE #1 DEAD BAND VALVE #1 MODE RESP #1 RATE #1 SOL OFF DIFF #1 LEVEL #2 SETPOINT SOLENOID #2 MODE #2 DEAD BAND VALVE #2 MODE RESP #2 PREV RATE #2 SOL OFF DIFF #2 HI LEVEL ALARM % HI LEVEL ALRM DLY HI LEVEL SHDN DLY NEXT COMM DEVICE ADDRESS BAUD RATE DATA BITS PARITY STOP BITS FACTORY SETUP INTER- COOLER ACCUM- ULATOR SURGE DRUM TRANSFER SYSTEM RECIRC SYSTEM # SOL VALVES SOL #1 NORM/REV SOL #2 NORM/REV # MOTOR VALVES VLV #1 NORM/REV VLV #2 NORM/REV PASS WORD CHANGE PASS-WRD CAL LEVEL IN LOW-CAL LEVEL IN HI-CAL MTR VAL 1 LOW-CAL MTR VAL 1 HI-CAL MTR VAL 2 LOW-CAL MTR VAL 2 HI-CAL PROGRAM VERSION VERSION # REL-DATE UP ARROW CHANGE SETPOINT DOWN ARROW SCREEN CATEGORY STANDARD KEY OPTION FACTORY SETUP 20

Home Screen: LEVEL = 48% Normal operation LEVEL = 48% COMM With communications port active LEVEL = 78% HI LEV ALARM With alarm. HI LEV SHTDN (Shuts off liquid solenoids until the alarm is cleared. If the HI LEV SHDN is still active after clearing, the alarm wull be re-issued and the liquid solenoids will be turned off.) HI LEV ALRM LO LEV ALARM Once the alarm condition is corrected, the operator can press the ENTER key to clear the alarm(s). Alarms can only be cleared on the Home screen. 21

Data Screens: DATA LEVEL 48% DATA LEVEL 48% LIQ SOL #1: AUTO ON Liquid Solenoid #1 can be selected as AUTO or MANUAL in the Setpoints screen. In the AUTO mode, Liquid Solenoid #1 is turned on when the level is below LEV 1 SETPOINT, and is turned off when above LEV 1 SETPOINT. In the MANUAL mode, Liquid Solenoid #1 can be set to the OFF position in the setpoint screen LIQ SOL #1 MODE. In this position, the Liquid Solenoid #1 stays off regardless of the vessel level. In the MANUAL mode, Liquid Solenoid #1 can be set to the ON position in the setpoint screen LIQ SOL #1 MODE. In this position, the Liquid Solenoid #1 stays off and only energizes when the UP arrow is pressed while on this screen. When Motorized Valve #1 is enabled, Liquid Solenoid #1reverts to a safety valve mode where the motorized valve controls on LEV 1 SETPOINT, and the solenoid closes only if the level rises above SOL OFF DIFF #1 setpoint. 22

DATA LEVEL 48% LIQ SOL #2: AUTO ON OPTION: DISPLAYED ONLY WHEN LIQ SOL #2 OR WHEN MOTORIZED VALVE #2 IS ENABLED IN FACTORY SETUP. LIQ SOL #2 is automatically enabled when VALVE #2 is enabled in Factory Setup Liquid Solenoid #2 can be selected as AUTO or MANUAL in the Setpoints screen. In the AUTO mode, Liquid Solenoid #2 is turned on when the level is below LEV 2 SETPOINT, and is turned off when above LEV 2 SETPOINT. In the MANUAL mode, Liquid Solenoid #2 can be set to the OFF position in the setpoint screen LIQ SOL #2 MODE. In this position, the Liquid Solenoid #2 stays off regardless of the vessel level. In the MANUAL mode, Liquid Solenoid #2 can be set to the ON position in the setpoint screen LIQ SOL #2 MODE. In this position, the Liquid Solenoid #2 stays off and only energizes when the UP arrow is pressed while on this screen. When Motorized Valve #2 is enabled, Liquid Solenoid #2 reverts to a safety valve mode where the motorized valve controls on LEV 2 SETPOINT, and the solenoid closes only if the level rises above SOL OFF DIFF #2 setpoint. DATA LEVEL 48% VALVE #1: AUTO 50% OPTION: DISPLAYED ONLY WHEN MOTORIZED VALVE #1 IS ENABLED IN FACTORY SETUP. Liquid Motorized Valve #1 can be selected as AUTO or MANUAL in the Setpoints screen. In the AUTO mode, Liquid Motorized Valve #1 modulates open via. PID loop control when the level is below LEV 1 SETPOINT, and modulates closed when above LEV 1 SETPOINT. Liquid Motorized Valve #1 can be set to the MANUAL position in the setpoint screen VLV #1 MODE. In this position, the Liquid Motorized Valve #1 stays at it s present position and only moves open or closed by pressing the UP or DOWN arrows while on this screen. 23

DATA LEVEL 48% VALVE #2: AUTO 100% OPTION: DISPLAYED ONLY WHEN MOTORIZED VALVE #2 IS ENABLED IN FACTORY SETUP. LIQ SOL #2 is automatically enabled when VALVE #2 is enabled in Factory Setup Liquid Motorized Valve #2 can be selected as AUTO or MANUAL in the Setpoints screen. In the AUTO mode, Liquid Motorized Valve #2 modulates open via. PID loop control when the level is below LEV 2 SETPOINT, and modulates closed when above LEV 2 SETPOINT. Liquid Motorized Valve #2 can be set to the MANUAL position in the setpoint screen VLV #2 MODE. In this position, the Liquid Motorized Valve #2 stays at it s present position and only moves open or closed by pressing the UP or DOWN arrows while on this screen. DATA LEVEL 48% LIQ TRANS: AUTO OFF NOT DISPLAYED WHEN SURGE DRUM IS SELECTED. Liquid Transfer can be selected as AUTO or MANUAL in the Setpoints screen. In the AUTO mode, Liquid Transfer output is turned on when the level is at or above the TRANSFER ON setpoint for the time delay, and is turned off when the level is below the TRANSFER OFF setpoint for the time delay. In the MANUAL mode, Liquid Transfer can be set to the OFF position in the setpoint screen LIQ TRANS MODE. In this position, the Liquid Transfer output stays off regardless of the vessel level. In the MANUAL mode, Liquid Transfer can be set to the ON position in the setpoint screen LIQ TRANS MODE. In this position, the Liquid Transfer output stays off and only energizes when the UP arrow is pressed while on this screen. 24

Setpoint Screens: SETPOINTS LEV 1 SETPOINT 48% Setpoint for Level #1. If solenoid control, the solenoid closes when the vessel level is above this setpoint and opens when the vessel level is below this setpoint. If motorized valve control, the valve modulates open when the vessel level is below this setpoint and modulates closed when the vessel level is above this setpoint. SETPOINTS LIQ SOL #1 MODE: AUTO Selects the Liquid Solenoid #1 control mode. Off The liquid solenoid #1 output remains off regardless of the vessel level. On The Liquid Solenoid #1 remains off regardless of the vessel level. When on the Data Screen at LIQ SOL #1: MAN OFF, the operator can press the UP arrow to energize the Liquid #1 solenoid output. Releasing the UP arrow de-energizes the output. Auto The Liquid Solenoid #1 output energized when the level is below the LEV 1 SETPOINT and is below the DEAD BAND #1 setpoint. The Liquid Solenoid #1 output de-energized when the level is above the LEV 1 SETPOINT and is above the DEAD BAND #1 setpoint. 25

SETPOINTS DEAD BAND #1 2% Percent dead band above and below LEV 1 SETPOINT. This is the area where no action is taken until the level deviates beyond the dead band from setpoint. SETPOINTS VLV #1 MODE: AUTO OPTION: DISPLAYED ONLY WHEN MOTORIZED VALVE #1 IS ENABLED IN FACTORY SETUP. Selects the motorized valve #1 control mode. Manual The motorized valve #1 remains in its present position, regardless of the vessel level. When on the Data Screen at VLV #1 MODE: MANUAL, the operator can press the UP arrow to modulate the valve open. Pressing the DOWN arrow modulates the valve closed. The liquid solenoid will close when the vessel level reaches the SOL OFF DIFF #1 setpoint which protects the vessel from overfilling. There are no back-ups for draining and therefore the vessel could be drained in manual operation. CAUTION THIS MODE CAN ALLOW A VESSEL TO BE DRAINED! If the level reaches the SOL OFF DIFF #1 setpoint, the #1 liquid feed solenoid will turn off preventing accidental overfilling of the vessel. Auto The Motorized Valve #1 will modulate open and closed to maintain level based on LEV 1 SETPOINT. 26

SETPOINTS RESPONSE #1 5 OPTION: DISPLAYED ONLY WHEN MOTORIZED VALVE #1 IS ENABLED IN FACTORY SETUP. Selects the Motorized Valve #1 response which determines how fast to respond when deviated from setpoint. The range is 1 to 30. 1 = small 30 = large Same as the Proportional setting in a PID loop control. SETPOINTS RATE #1 5 OPTION: DISPLAYED ONLY WHEN MOTORIZED VALVE #1 IS ENABLED IN FACTORY SETUP. Selects the Motorized Valve #1 rate which determines the amount of valve movement per cycle. The range is 1 to 100. 1 = slow 100 = fast Same as the Integral setting in a PID loop control. SETPOINTS SOL OFF DIFF #1 10% OPTION: DISPLAYED ONLY WHEN MOTORIZED VALVE #1 IS ENABLED IN FACTORY SETUP. Selects the percent deviation above LEV 1 SETPOINT Where the Liquid #1 solenoid will close when in motorized valve control. This setpoint prevents the vessel from over filling if the motorized valve does not respond. 27

SETPOINTS LEV 2 SETPOINT 38% OPTION: DISPLAYED ONLY WHEN LIQ SOL #2 OR WHEN MOTORIZED VALVE #2 IS ENABLED IN FACTORY SETUP. LIQ SOL #2 is automatically enabled when VALVE #2 is enabled in Factory Setup Setpoint for Level #2. If solenoid control, the solenoid closes when the vessel level is above this setpoint and opens when the vessel level is below this setpoint. If motorized valve control, the valve modulates open when the vessel level is below this setpoint and modulates closed when the vessel level is above this setpoint. SETPOINTS LIQ SOL #2 MODE: AUTO OPTION: DISPLAYED ONLY WHEN LIQ SOL #2 OR WHEN MOTORIZED VALVE #2 IS ENABLED IN FACTORY SETUP. Selects the Liquid Solenoid #2 control mode. Off The Liquid Solenoid #2 output remains off regardless of the vessel level. On The Liquid Solenoid #2 remains off regardless of the vessel level. When on the Data Screen at LIQ SOL #2: MAN OFF, the operator can press the UP arrow to energize the Liquid #2 solenoid output. Releasing the UP arrow de-energizes the output. Auto The Liquid Solenoid #2 output energized when the level is below the LEV 2 SETPOINT and is below the DEAD BAND #2 setpoint. The Liquid Solenoid #2 output de-energized when the level is above the LEV 2 SETPOINT and is above the DEAD BAND #1 setpoint. 28

SETPOINTS DEAD BAND #2 2% OPTION: DISPLAYED ONLY WHEN LIQ SOL #2 OR WHEN MOTORIZED VALVE #2 IS ENABLED IN FACTORY SETUP. Percent dead band above and below LEV 2 SETPOINT. This is the area where no action is taken until the level deviates beyond the dead band from setpoint. SETPOINTS VLV #2 MODE: AUTO OPTION: DISPLAYED ONLY WHEN MOTORIZED VALVE #2 IS ENABLED IN FACTORY SETUP. LIQ SOL #2 is automatically enabled when VALVE #2 is enabled in Factory Setup Selects the Motorized Valve #2 control mode. Manual The Motorized Valve #2 remains in its present position, regardless of the vessel level. When on the Data Screen at VLV #2 MODE: MANUAL, the operator can press the UP arrow to modulate the valve open. Pressing the DOWN arrow modulates the valve closed. The liquid solenoid will close when the vessel level reaches the SOL OFF DIFF #2 setpoint which protects the vessel from overfilling. There are no back-ups for draining and therefore the vessel could be drained in manual operation. CAUTION THIS MODE CAN ALLOW A VESSEL TO BE DRAINED! If the level reaches the SOL OFF DIFF #2 setpoint, the #2 liquid feed solenoid will turn off preventing accidental overfilling of the vessel. Auto The Motorized Valve #2 will modulate open and closed to maintain level based on LEV 2 SETPOINT. 29

SETPOINTS RESPONSE #2 5 OPTION: DISPLAYED ONLY WHEN MOTORIZED VALVE #2 IS ENABLED IN FACTORY SETUP. Selects the Motorized Valve #2 response which determines how fast to respond when deviated from setpoint. The range is 1 to 30. 1 = small 30 = large Same as the Proportional setting in a PID loop control. LEVEL SETPOINTS RATE #2 5 OPTION: DISPLAYED ONLY WHEN MOTORIZED VALVE #2 IS ENABLED IN FACTORY SETUP. Selects the Motorized Valve #2 rate which determines the amount of valve movement per cycle. The range is 1 to 100. 1 = slow 100 = fast Same as the Integral setting in a PID loop control. SETPOINTS SOL OFF DIFF #2 10% OPTION: DISPLAYED ONLY WHEN MOTORIZED VALVE #2 IS ENABLED IN FACTORY SETUP. Selects the percent deviation above LEV 2 SETPOINT Where the Liquid #2 solenoid will close when in motorized valve control. This setpoint prevents the vessel from over filling if the motorized valve does not respond. 30

SETPOINTS LIQ TRANS MODE: AUTO NOT DISPLAYED WHEN SURGE DRUM IS SELECTED. Selects the liquid transfer control mode. Off The liquid transfer output remains off regardless of the vessel level. On The liquid transfer output remains off regardless of the vessel level. When on the Data Screen at LIQ TRANS: MAN OFF, the operator can press the UP arrow to energize the liquid transfer output. Releasing the UP arrow de-energizes the output. Auto The liquid transfer output is energized when the level is at or above the TRANSFER ON setpoint for the TRANSFER ON time delay. The liquid transfer output is de-energized when the level is at or below the TRANSFER OFF setpoint for the TRANSFER OFF time delay. SETPOINTS TRANSFER ON 70% NOT DISPLAYED WHEN SURGE DRUM IS SELECTED. The liquid transfer output is energized when the level is at or above the TRANSFER ON setpoint for the TRANSFER ON time delay. SETPOINTS TRANSFER ON 2 SEC NOT DISPLAYED WHEN SURGE DRUM IS SELECTED. Once the level reaches the TRANSFER ON setpoint, this time delay must time out before the liquid transfer output is energized. 31

SETPOINTS TRANSFER OFF 60% NOT DISPLAYED WHEN SURGE DRUM IS SELECTED. The liquid transfer output is de-energized when the level is at or below the TRANSFER OFF setpoint for the TRANSFER OFF time delay. SETPOINTS TRANSFER OFF 2 SEC NOT DISPLAYED WHEN SURGE DRUM IS SELECTED. Once the level reaches the TRANSFER OFF setpoint, this time delay must time out before the liquid transfer output is de-energized. SETPOINTS HI LEV ALARM 80% If the level reaches the HI LEV ALARM setpoint, and after the HI LEV ALARM time delay, the high level alarm output will be energized and an alarm issued on the Home screen. SETPOINTS HI LEV ALARM 2 SEC Once the level reaches the HI LEV ALARM setpoint, this timer must time out before the liquid transfer output is energized. 32

SETPOINTS LO LEV ALARM 2 SEC DISPLAYED ONLY WHEN RECIRCULATOR IS SELECTED. If the level drops to the LO LEV ALARM setpoint, and after the LO LEV ALARM time delay, the low level alarm output will be energized and an alarm issued on the Home screen. SETPOINTS LO LEV ALARM 2 SEC DISPLAYED ONLY WHEN RECIRCULATOR IS SELECTED. Once the level reaches the LO LEV ALARM setpoint, this timer must time out before the low level alarm output is energized. SETPOINTS HI LVL SD DLY 60 S If the level reaches the HI LEV SHDN float switch or electronic high level switch, and after the HI LEV SHDN time delay, a high level shutdown will be displayed on the Home screen. This delay works only for the alarm message to the home screen and the communications port. Since the HI level shutdown float switch input is tied directly to the HI level shutdown output, the output relay does not have a time delay. If a time delay is required, a separate electronic timer must be installed in line with the timer output. 33

Communications Screens: COMMUNICATIONS DEVICE ADDRESS 255 The communications protocol is MODBUS-RTU over RS-485. This screen selects the device address on the network for this panel. Device address range is 0 to 255. COMMUNICATIONS BAUD RATE: 19200 Baud Rate Selects the data transfer rate. 2400, 4800, 9600, 19200 baud. COMMUNICATIONS DATA BITS: 8 BITS Data bits Selects the number of data bits. 8 bits. COMMUNICATIONS PARITY: NONE Parity Error checking based on parity. None 34

COMMUNICATIONS STOP BITS: 1 BITS Stop Bits Number of stop bits. 1 Factory Setup Screens: * FACTORY SETUP * PASSWORD 0000 In order to enter the Factory settings, a password entry is required. Pressing the UP and DOWN arrows, scrolls to the password setting. Holding the UP or DOWN arrow keys causes the scrolling function to speed up. Once the desired password number is reached, press the ENTER KEY. Factory Setup will remain enabled for 15 minutes. Once this time has elapsed, you will have to re-enter the password. Lost password: If the password is lost the following procedure can be used to gain access to the factory setup where a new password can be assigned: Press and hold the LEFT and RIGHT arrows simultaneously for 5 seconds. Release the LEFT and RIGHT arrow keys. Press the ENTER key. Press the PREV key. Factory setup should now be accessible. If not, repeat the above procedure. Once into the Factory setup Change Password screen, re-enter a new password. 35

* FACTORY SETUP * MODE: INTERCOOLER Matrix LLC has five basic control modes Intercooler Accumulator Surge Drum Transfer System Recirculator Pressing the UP or DOWN arrows selects the desired control mode. Press the ENTER key to confirm selection. * FACTORY SETUP * MODE: ACCUMULATOR * FACTORY SETUP * MODE: SURGE DRUM * FACTORY SETUP * MODE: TRANSFER SYS * FACTORY SETUP * MODE: RECIRC SYS 36

* FACTORY SETUP * # SOL VALVES: 2 Selects the number if liquid feed solenoid valves. One is standard, with a maximum of two. If Motorized Valve #1 is selected, Liquid Feed Valve #1 becomes a back-up safety valve for the motorized valve. If Motorized Valve #2 is selected, Liquid Feed Valve#2 is automatically enabled as a back-up safety valve. * FACTORY SETUP * SOL #1 MODE: NORMAL Selects the solenoid mode for either normal acting or reverse acting. If motorized #1 valve is selected, then solenoid #1 is automatically configured as normal or reverse based on the motorized #1 valve mode of normal or reverse. * FACTORY SETUP * SOL #2 MODE: REVERSE Selects the solenoid mode for either normal acting or reverse acting. If motorized #2 valve is selected, then solenoid #2 is automatically configured as normal or reverse based on the motorized #2 valve mode of normal or reverse. 37

* FACTORY SETUP * # MTR VALVES: 2 Selects the number if liquid feed motorized valves. No motorized valve is standard, with a maximum of two. If Motorized Valve #1 is selected, Liquid Feed Valve #1 becomes a back-up safety valve for the motorized valve. If Motorized Valve #2 is selected, Liquid Feed Valve #2 is automatically enabled as a back-up safety valve. * FACTORY SETUP * VLV #1 MODE: NORMAL Selects the motorized valve mode for either normal acting or reverse acting. If motorized #1 valve is selected, then solenoid #1 is automatically configured as normal or reverse based on the motorized #1 valve mode of normal or reverse. * FACTORY SETUP * VLV #2 MODE: REVERSE Selects the motorized valve mode for either normal acting or reverse acting. If motorized #2 valve is selected, then solenoid #2 is automatically configured as normal or reverse based on the motorized #2 valve mode of normal or reverse. 38

Password Screen: CHANGE PASSWORD PASSWORD 0001 Selects the password that enables access to factory setup. To change the password, use the UP or DOWN arrow keys to scroll to the desired password number. Press ENTER to accept. Lost password: If the password is lost the following procedure can be used to gain access to the factory setup where a new password can be assigned. This must be entered on the Factory Setup Password Entry screen: Press and hold the LEFT and RIGHT arrows simultaneously for 5 seconds. Release the LEFT and RIGHT arrow keys. Press the ENTER key. Press the PREV key. Factory setup should now be accessible. If not, repeat the above procedure. Once into the Factory setup Change Password screen, re-enter a new password. Calibration Screens: A quality digital voltmeter is required in order to properly calibrate the Matrix LLC analog inputs and outputs. There is one analog input and three analog outputs. Analog Input #1 Level input from vessel level probe. The incoming signal is 4-20Ma Analog Output #1 Level output. This output is used to feed the vessel level signal to other systems such as plant supervisory systems. This analog output is a repeater of the analog input and has no calibration. Analog Output #2 Motorized valve #1. Analog Output #3 Motorized valve #2 39

CALIBRATE LEVEL 48% INPUT LOWER CAL -3 With the digital meter in line with the level probe signal, verify that the level is at its lowest position which is 4 ma. Press the UP or DOWN arrow keys until the display shows 0%. Press ENTER. An offset is now entered into the unit for the low end of the level probe. CALIBRATE LEVEL 48% INPUT HIGH CAL 2 With the digital meter in line with the level probe signal, verify that the level is at its highest position which is 20 ma. Press the UP or DOWN arrow keys until the display shows 100%. Press ENTER. An offset is now entered into the unit for the high end of the level probe. CALIBRATE VLV#1 0% VALVE LOW CAL 0 To calibrate the Motorized Valve #1 put the valve in the Manual On mode in the setpoint screen. On the data screen, press the DOWN arrow until the valve is at its minimum position. With the digital meter in line with the motorized valve signal, verify that the level is at its lowest position which is 4 ma. Press the UP or DOWN arrow keys until the display shows 0%. Press ENTER. An offset is now entered into the unit for the low end of Motorized Valve #1. 40

CALIBRATE VLV#1 100% VALVE HIGH CAL -2 On the data screen, press the UP arrow until the valve is at its maximum position. With the digital meter in line with the motorized valve signal, verify that the level is at its highest position which is 20 ma. Press the UP or DOWN arrow keys until the display shows 0%. Press ENTER. An offset is now entered into the unit for the high end of Motorized Valve #1. CALIBRATE VLV#2 0% VALVE LOW CAL 1 To calibrate the Motorized Valve #2 put the valve in the Manual On mode in the setpoint screen. On the data screen, press the DOWN arrow until the valve is at its minimum position. With the digital meter in line with the motorized valve signal, verify that the level is at its lowest position which is 4 ma. Press the UP or DOWN arrow keys until the display shows 0%. Press ENTER. An offset is now entered into the unit for the low end of Motorized Valve #2. CALIBRATE VLV#2 100% VALVE HIGH CAL 3 On the data screen, press the UP arrow until the valve is at its maximum position. With the digital meter in line with the motorized valve signal, verify that the level is at its highest position which is 20 ma. Press the UP or DOWN arrow keys until the display shows 0%. Press ENTER. An offset is now entered into the unit for the high end of Motorized Valve #2. 41

Program Version Screen: PROG VERSION 2.1 REL DATE 10-04-07 Indicated the current program version and release date. Be sure to record this information when requesting assistance from the Service Department. 42

TRANSFER SYSTEM SCREENS 43

TRANSFER SYSTEM SCREEN MAP HOME LEVEL & ALARM LEFT ARROW RIGHT ARROW DATA HOT GAS VENT LIQUID TRANSFER SETPOINT TRANSFER MODE TRANSFER ON % TRANSFER OFF % VENT-HG DELAY HG-TRANS DELAY HI LEVEL SHDN DLY PREV NEXT COMM DEVICE ADDRESS BAUD RATE DATA BITS PARITY STOP BITS FACTORY SETUP INTER- COOLER ACCUM- ULATOR SURGE DRUM TRANSFER SYSTEM RECIRC SYSTEM PASS WORD CHANGE PASS-WRD UP ARROW CHANGE SETPOINT DOWN ARROW CAL LEVEL IN LOW-CAL LEVEL IN HI-CAL MTR VAL 1 LOW-CAL MTR VAL 1 HI-CAL MTR VAL 2 LOW-CAL MTR VAL 2 HI-CAL PROGRAM VERSION VERSION # REL-DATE SCREEN CATEGORY STANDARD OPTION FACTORY SETUP KEY 44

Data Screens: DATA LEVEL 48% DATA LEVEL 48% HOT GAS SOL: OFF Hot gas solenoid status: On / Off DATA LEVEL 48% VENT SOLENOID: OFF Vent solenoid status: On / Off DATA LEVEL 48% LIQ TRANS: MAN OFF Liquid Transfer can be selected as AUTO or MANUAL in the Setpoints screen. In the AUTO mode, Liquid Transfer sequence is initiated at or above the TRANSFER ON setpoint. The sequence is as follows: The vent solenoid output is turned off. Time delay TRANS VNT-HG times out The hot gas solenoid output is turned on. Time delay TRANS HG-TRN times out The transfer output is turned on. When the level drops to the TRANSFER OFF setpoint, the sequence is as follows: The transfer output is turned off. Time delay TRANS HG-TRN times out 45

The hot gas solenoid output is turned off. Time delay TRANS VNT-HG times out The vent solenoid output is turned on. In the MANUAL mode, Liquid Transfer can be set to the OFF position in the setpoint screen LIQ TRANS MODE. In this position, the Liquid Transfer output stays off regardless of the vessel level. In the MANUAL mode, Liquid Transfer can be set to the ON position in the setpoint screen LIQ TRANS MODE. In this position, the Liquid Transfer output stays off. When on the Data screen LIQ TRANS: MAN OFF, the UP arrow is pressed while on this screen, the liquid transfer sequence initiates. As long as the UP arrow is held in, the transfer will sequence on from vent off, hot gas, transfer. If the key is released, the transfer will sequence off, from transfer, hot gas, vent. 46

Setpoint Screens: SETPOINTS LIQ TRANS MODE: AUTO Selects the liquid transfer control mode. Off The liquid transfer output remains off regardless of the vessel level. On The liquid transfer output remains off regardless of the vessel level. When on the Data Screen at LIQ TRANS: MAN OFF, the operator can press the UP arrow to initiate the liquid transfer sequence. In the MANUAL mode, Liquid Transfer can be set to the ON position in the setpoint screen LIQ TRANS MODE. In this position, the Liquid Transfer output stays off. When on the Data screen LIQ TRANS: MAN OFF, the UP arrow is pressed while on this screen, the liquid transfer sequence initiates. As long as the UP arrow is held in, the transfer will sequence on from vent off, hot gas, transfer. If the key is released, the transfer will sequence off, from transfer, hot gas, vent. Auto The liquid transfer sequence is energized when the level is at or above the TRANSFER ON setpoint. The liquid transfer output is de-energized when the level is at or below the TRANSFER OFF setpoint for the TRANSFER OFF time delay. 47

SETPOINTS TRANSFER ON 70% Setpoint to initiate transfer in the automatic mode. SETPOINTS TRANSFER OFF 60% Setpoint to terminate transfer in the automatic mode. SETPOINTS TRANS VNT-HG 3 SEC Transfer time delay, vent to hot gas and hot gas to vent. SETPOINTS TRANS HG-TRN 5 SEC Transfer time delay, hot gas to transfer and transfer to hot gas. 48

SETPOINTS HI LVL SD DLY 60 S If the level reaches the HI LEV SHDN float switch or electronic high level switch, and after the HI LEV SHDN time delay, a high level shutdown will be displayed on the Home screen. This delay works only for the alarm message to the home screen and the communications port. Since the HI level shutdown float switch input is tied directly to the HI level shutdown output, the output relay does not have a time delay. If a time delay is required, a separate electronic timer must be installed in line with the timer output. 49

SET-POINT TABLE MODE Set-point Description X Default Setting Range Intercooler, LEV 1 SETPOINT 40% 0-100% Accumulator Surge Drum Recirculator Intercooler, LIQ SOL #1 MODE AUTO AUTO, OFF, ON Accumulator Surge Drum Recirculator Intercooler, DEAD BAND #1 2% 0-10% Accumulator Surge Drum Recirculator Intercooler, VLV #1 MODE AUTO AUTO MANUAL Accumulator Surge Drum Recirculator Intercooler, RESPONSE #1 5 1-30 Accumulator Surge Drum Recirculator Intercooler, RATE #1 5 1-100 Accumulator Surge Drum Recirculator Intercooler, SOL OFF DIFF #1 10% 0-15% Accumulator Surge Drum Recirculator Intercooler, LEV 2 SETPOINT 50% 0-100% Accumulator Surge Drum Recirculator Intercooler, Accumulator Surge Drum Recirculator LIQ SOL #2 MODE AUTO AUTO, OFF, ON 50

Intercooler, Accumulator Surge Drum Recirculator Intercooler, Accumulator Surge Drum Recirculator Intercooler, Accumulator Surge Drum Recirculator Intercooler, Accumulator Surge Drum Recirculator Intercooler, Accumulator Surge Drum Recirculator Intercooler Accumulator Recirculator Intercooler, Accumulator Recirculator Transfer System Intercooler Accumulator Recirculator Intercooler Accumulator Recirculator Transfer System Intercooler Accumulator Recirculator Intercooler Accumulator Surge Drum Recirculator DEAD BAND #2 2% 0-10% VLV #2 MODE AUTO AUTO MANUAL RESPONSE #2 5 1-30 RATE #2 5 1-100 SOL OFF DIFF #2 10% 0-15% LIQ TRANS MODE AUTO AUTO, OFF, ON TRANSFER ON 60% 0-100% TRANSFER ON DELAY 2 SEC 0-50 SEC TRANSFER OFF 50% 0-100% TRANSFER OFF DELAY 2 SEC 0-50 SEC HI LEV ALARM 70% 0-100% 51

Intercooler HI LEV ALARM DELAY 5 SEC 0-50 SEC Accumulator Surge Drum Recirculator Recirculator LO LEV ALARM 10% 0-100% Recirculator LO LEV ALARM DELAY 5 SEC 0-50 SEC Intercooler HI LEV SHDN DELAY 2 SEC 0-250 SEC Accumulator Surge Drum Recirculator Transfer System Transfer System LIQ TRANS MODE AUTO AUTO, OFF, ON Transfer System TRANS VNT-HG 3 SEC 0-50 SEC DELAY Transfer System TRANS HG-TRN 5 SEC 0-50 SEC DELAY All DEVICE ADDRESS 1 0-255 BAUD RATE 19200 2400 4800 9600 19200 All DATA BITS 8 BITS 8 BITS All PARITY NONE NONE All STOP BITS 1BITS 1 BIT All FACTORY SETUP MODE X INTERCOOLER ACCUMULATOR SURGE DRUM TRANSFER SYS RECIRCULATOR All CHANGE PASSWORD X 1 0-9999 All INPUT LOWER CAL X 0-25 to +25 All INPUT HIGH CAL X 0-25 to +25 All VALVE #1 LOW CAL X 0-25 to +25 All VALVE #1 HIGH CAL X 0-25 to +25 All VALVE #2 LOW CAL X 0-25 to +25 All VALVE #2 HIGH CAL X 0-25 to +25 NOTE: X indicates password protected set-points 52

SPECIFICATIONS INPUT POWER o 105 125 VAC 47 63 Hz * Standard o 185 250 VAC 47 63 Hz *Optional (Contact factory) DC OUTPUT POWER o 5 VDC @ 2A (10 Watts) o 24 VDC @ 1A (24 Watts) AC OUTPUT POWER o 24 VAC @ 7.5A (180 Watts) ENVIRONMENTAL o Operating temperature -4ºF to 131ºF (-20ºC to 55ºC) o Storage temperature -13ºF to 140ºF (-25ºC to 60ºC) o Humidity (non condensing) 0% to 95% o Vibration 2.0g s (19.61m/s 2 ) o Shock 100g s (980m/s 2 ) o RFI Immunity 15v/m (15MHz to 1.5gHz) o EMI Immunity Complies with CE EMC directive DISPLAY o Dot format (2 line x 20) char. alphanumeric LCD o Display mode FSTN, Positive, Transflective o Backlight Yellow LED o Brightness 28 cd/m 2 KEYPAD o Material o Switches Polycarbonate Stainless steel snap-domes CERTIFICATIONS o UL 508A o cul STAND-ALONE PANEL o Dimensions (H x W x D) 16 x 8 x 6 (40.6 x 20.3 x 15.2 cm) o Weight 17 LBS o Design NEMA 4 o Material Painted steel o Finish RVS blue paint 53

OUTPUT MODULES o Relay output 10A @ 125 VAC 6 A @ 250 VAC 5A @ 30 VDC Form C SENSORS o Level o Technology o Range o Output o Accuracy o Excitation voltage o Temperature range Capacitance probe 20 to 168 @9 sizes (50.8 to 426.7 cm) 4-20 ma +/- 1% of full scale 24 VAC or VDC -76ºF to 212ºF (-60ºC to 100ºC) COMMUNICATIONS o Serial port o Type o Protocol o Baud rate RS-485 MODBUS RTU 2.4K to 19.2K baud 54

MATRIX LLC CONTROL PANEL COMMUNICATIONS ADDENDUM 1-26-09 REV- 0.4 1

INDEX Introduction. 3 Display Screen.. 4 Digital I/O.. 5 Analog I/O.... 6 Status 6 Set-points.. 7 2

INTRODUCTION The RVS Matrix LLC Microprocessor Control utilizes a communications format, based on Modbus protocol, to interface to supervisory control systems. The physical interface is RS-485 which utilizes Modbus RTU protocol The following pages will describe the communications functionality and the code sets related to the data and set-points within the Matrix LLC Micro. 3

Communications Screens: COMMUNICATIONS DEVICE ADDRESS 255 The communications protocol is MODBUS-RTU over RS-485. This screen selects the device address on the network for this panel. Device address range is 0 to 255. COMMUNICATIONS BAUD RATE: 19200 Baud Rate Selects the data transfer rate. 2400, 4800, 9600, 19200 baud. COMMUNICATIONS DATA BITS: 8 BITS Data bits Selects the number of data bits. 8 bits. COMMUNICATIONS PARITY: NONE Parity Error checking based on parity. None COMMUNICATIONS STOP BITS: 1 BIT Stop Bits Number of stop bits. 1 4

DIGITAL I/O (Read Only) INTERCOOLER TRANSFER SYSTEM ACCUMULATOR SURGE DRUM RECIRCULATOR MODBUS DESCRIPTION TYPE DESCRIPTION TYPE VALUE ADDRESS 43001 High level shutdown Input High level shutdown Input 0 = Off 1 = On 43002 Alarm horn Output Alarm horn Output 0 = Off 1 = On 43003 Lo level shutdown (Recirculator only) Output 0 = Off 1 = On 43004 Liquid solenoid #2 Output Vent solenoid Output 0 = Off 1 = On 43005 Liquid solenoid #1 Output Hot gas solenoid Output 0 = Off 1 = On 43006 Liquid transfer (Not available on surge drum) Output Liquid transfer Output 0 = Off 1 = On 43007 High level alarm Output 0 = Off 1 = On 43008 High level shutdown Output High level shutdown Output 0 = Off 1 = On 43009 Future Input Future Input 0 = Off 1 = On 43010 Future Input Future Input 0 = Off 1 = On 43011 Future Input Future Input 0 = Off 1 = On 43012 Future Input Future Input 0 = Off 1 = On 43013 Future Input Future Input 0 = Off 1 = On 43014 Future Input Future Input 0 = Off 1 = On 43015 Future Input Future Input 0 = Off 1 = On 43016 Future Input Future Input 0 = Off 1 = On 5

ANALOG I/O (Read Only) MODBUS ADDRESS DESCRIPTION TYPE VALUE RANGE 43017 Vessel level Input 0-100% 43018 Motorized feed valve #1 Output 0-100% 43019 Motorized feed valve #2 Output 0-100% 43020 Future Input 43021 Future Input 43022 Future Input 43023 Future Input 43024 Future Input 43025 Future Input 43026 Future Input STATUS MODBUS DESCRIPTION TYPE VALUE RANGE ADDRESS 43027 Future Read Only 43028 Future Read Only 43029 Future Read Only 43030 Future Read Only 43031 Future Read Only 43032 Future Read Only 6

SET-POINTS (Read / Write) and (Read Only) MODBUS DESCRIPTION TYPE VALUE RANGE ADDRESS 43033 Level #1 setpoint Read/Write 0-100% 43034 Liquid Solenoid #1 mode Read/Write 0 = Auto. 1 = Off 2 = On 43035 Dead band #1 Read/Write 0-10% 43036 Motorized valve #1 mode Read/Write 0 = Auto 1 = manual 43037 Response #1 Read/Write 1-30 43038 Rate #1 Read/Write 1-100 43039 Solenoid off differential #1 Read/Write 0-15% 43040 Level #2 setpoint Read/Write 0-100% 43041 Liquid Solenoid #2 mode Read/Write 0 = Auto 1 = Off 2 = On 43042 Dead band #2 Read/Write 0-10% 43043 Motorized valve #2 mode Read/Write 0 = Auto 1 = manual 43044 Response #2 Read/Write 1-30 43045 Rate #2 Read/Write 1-100 43046 Solenoid off differential #2 Read/Write 0-15% 43047 Liquid transfer mode Read/Write 0 = Auto 1 = Off 2 = On 43048 Liquid Transfer on setpoint Read/Write 0-100% 43049 Liquid Transfer on delay Read/Write 0-50 Sec. 43050 Liquid Transfer off setpoint Read/Write 0-100% 43051 Liquid Transfer off delay Read/Write 0-50 Sec. 43052 Transfer System on setpoint Read/Write 0-100% 43053 Transfer System off setpoint Read/Write 0-100% 43054 Transfer System Vent-HG delay Read/Write 0-60 Sec. 43055 Transfer System HG-Transfer Read/Write 0-60 Sec. delay 43056 High level alarm setpoint Read/Write 0-100% 43057 High level alarm delay Read/Write 0-50 Sec. 43058 Low level alarm setpoint Read/Write 0-100% 43059 Lo level alarm delay Read/Write 0-50 Sec. 43060 High level shutdown delay Read/Write 0-250 Sec. 7