515.16-TG1Y (499) TECHNICAL SPECIFICATIONS SPLIT SYSTEM HEAT PUMPS Models 018-060 1Ø 036, 048 3Ø ERA Series 10 SEER Single and Three Phase Models ERA 018 thru ERA090 Nominal Capacity: 18 thru 90 MBH Models 060, 090 3Ø DESCRIPTION The ERA series heat pumps are designed for use with a variety of YORK evaporator sections to suit any need for both single and three phase applications. A full line of matching Add-On Coils are available for use with upflow, downflow or horizontal furnaces. Matching Air Handlers are also available for upflow, downflow or horizontal installation to provide a complete system. 1 & 3Ø electric heat may be installed in both single piece and modular air handlers. All units are factory charged to assure easy installation. FEATURES DURABLE CONSTRUCTION - The outdoor unit is constructed of pre-painted steel that offers tough protection against corrosion and resists fading when exposed to sunlight. Drain holes are incorporated into the base pan to permit free drainage of moisture. PROTECTED COMPRESSOR - The hermetic compressor is internally protected against high pressure and temperature by the simultaneous operation of a high pressure relief valve, high pressure cutout control and temperature sensors which stop the compressor if operating temperatures go too high. All protectors reset automatically. The heat pump control locks the compressor out. QUALITY COIL - The coil is constructed of copper tube and hardened black coated aluminum fins for durability and long lasting efficient operation. Coil guard provides additional protection when installed in a heavy traffic area. TIME TEMPERATURE DEFROST CONTROL - Provides defrost including field selectable time periods between cycles (30, 60, 90 minutes). LED lockout indicator, anti-short cycle timer protection are also provided. LOW OPERATING SOUND LEVEL - The compressor is mounted on rubber isolators to reduce operating sounds. The slow moving condenser fan keeps air turbulence and sound to a low level. EASY SERVICE ACCESS - Fully exposed refrigerant connections, a single panel covering the electrical controls and the molex plug in the control box connecting the condenser fan, make for easy servicing of the unit. SECURED SERVICE VALVES - Secured re-usable service valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging. FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
515.16-TG1Y COOLING CAPACITY - With Air Handler Coils AIR HANDLER COOLING COIL 2 ELECTRIC4,5 RATED NET MBH W KW SEER SEER/ HEAT KW CFM TOTAL SENS. TXV 1 EER 1 Phase ERA / NAH E1RA01806 N1AHB0806 2,5,8,10 G2FD024S 850.8 12.8 2.00 0 -- 8.95 E1RA02406 N1AHB0806 5,8,10,15,18 G2FD030S 850 22.6 16.3 2.43 0 -- E1RA03006 N1AHB1206 5,8,10,15,18 G2FD030S 1025 28.0 20.7 3.08 0 -- N1AHB1206 5,8,10,15,18 G2FD036S 1025 28.4.0 3.09 0 -- 9.20 E1RA03606 N1AHB1206 5,8,10,15,18 G2FD036S 1250 33.6 24.9 0 -- 8.80 N1AHB1206 5,8,10,15,18 G2FD046S 1250 34.6 25.6 0 -- 9.05 E1RA04206 N1AHC1606 5,8,10,15,20 G2FD042S 1400 39.0 28.9 4.31 0 -- 9.05 N1AHC1606 5,8,10,15,20 G2FD048S 1450 40.0 29.6 4.37 0 -- 9.15 N1AHC1606 5,8,10,15,20 G2FD048S 1600 33.7 4.84 0 -- 9.40 E1RA04806 N1AHD2006 8,10,15,20,25,30 24 G2FD048S24 1650 32.8 4.80 0 -- 9.40 N1AHD2006 8,10,15,20,25,30 24 G2FD060S24 1650 46.0 34.0 4.79 0 -- 9.60 E1RA06006 N1AHD2006 8,10,15,20,25,30 24 G2FD060S24 1825 54.5 40.3 6.09 -- 0 8.95 3 Phase ERA / NAH E1RA036S25,46 N1AHC1606,46 5,8,10,15,20 G2FD042S 1400 34.2 24.6 3.80 0 -- 8.95 N1AHC1606,46 5,8,10,15,20 G2FD048S 1650 32.8 4.80 0 -- 9.40 E1RA048S25,46 N1AHD2006,46 8,10,15,20,25,(29),30 24 G2FD048S24 1650 32.8 4.80 0 -- 9.40 E1RA060S25,46 N1AHD2006,46 8,10,15,20,25,(29),30 24 G2FD060S24 1850 57.0 41.0 5.80 0 -- 9.80 AIR HANDLER COOLING COIL 2 ELECTRIC4,5 HEAT KW W RATED NET MBH KW SEER SEER/ EER CFM TOTAL SENS. TXV1 1 Phase ERA / FRP / FFP E1RA018 F2RP018 5, 7.5, 10 -- 650.0 12.3 1.92 -- 8.9 18 F2RP024 5, 7.5, 10 -- 650.2 12.4 1.93 -- 8.9 E1RA024 F2RP024 5, 7.5, 10 -- 850 22.0 16.5 2.41 -- 9.3 18 F2RP030 5, 7.5, 10, 15 -- 850 22.5.0 2.42 -- 9.4 E1RA030 F2RP030 5, 7.5, 10, 15 18 -- 1000 28.4.0 3.09 -- 9.2 F2RP036 5, 7.5, 10, 15 -- 1000 29.0 20.9 3.09 -- 9.4 E1RA036 F2RP036 5, 7.5, 10, 15 -- 1200 33.7 24.9 3.62 -- 9.3 F2RP042 5, 7.5, 10, 15 -- 1250 34.0 25.6 3.77 -- 9.0 E1RA042 F2RP042 5, 7.5, 10, 15 -- 1400 39.0 28.8 4.38 -- 8.9 F2FP048 5, 7.5, 10, 15 24 -- 1400 39.5 28.8 4.32 -- 9.15 E1RA048 F2FP048 -- 1600 33.6 4.97 -- 9.15 5,7.5,10,15,20,25 24 F2FP060 -- 1600 46.5 33.9 5.05 -- 9.20 E1RA060 F2FP060 5,7.5,10,15,20,25 24 -- 1850 54.0 40.5 6.28 -- 8.60 3 Phase ERA / FRP/FFP F2RP036 10,15 -- 1200 33.7 24.9 3.62 0 -- E1RA036S25,46 F2RP042 10,15 -- 1250 34.0 25.6 3.77 0 -- 9.00 F2FP048 10,15 24 -- 1600 33.6 4.97 0 -- 9.15 E1RA048S25,46 F2FP060 10,15 24 -- 1600 46.5 33.9 5.05 0 -- 9.20 E1RA060S25,46 F2FP060 10,15 24 -- 1850 54.0 41.0 6.28 0 -- 8.60 3 Phase ERA / FEH E1RA090S25,46 F3EH090 10,16, 26, 36 25-1/8 -- 3000 91.2 87.4 9.60 -- -- 9.50 Rated in accordance with DOE test procedures (Federal Register 12-27-79 + 3-18-88) and ARI Standards 240. Cooling MBH based on 80 F entering air temperature, 50% RH, and rated air flow. KW includes compressor, outdoor fan and indoor blower motor watts. Add-on coils include 365 watts/1000 CFM for blower motor. EER (Energy Efficiency Ratio) is the total cooling output in BTU s at a 95 F outdoor ambient divided by the total electric power in watthours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period. 1 TXV = Thermal Expansion Valve kit required. Use 1TV700 series kit. Must be used with Hard Start Assist kit. (Hard Start not required on units with scroll compressors.) 2 To meet R=4.2 insulation requirements, substitute F2FP FOR F2RP models. All ratings remain the same. 3 P3HU, P3DN, P3UR furnaces and F2RP air handlers have B.O.D. standard. 4 Single phase units require single phase 2HK heaters Three phase units require three phase 2HK heaters. (29) indicates 460 volt use only. 5 2HS045 series electric heatersd must be used for F3EH090 fan coil unit. Field transition may be required. = Not Applicable. 2 Unitary Products Group
COOLING CAPACITY - 1 & 3 Ø ERA / Upflow, Downflow and Horizontal Furnaces and Coils FURNACE CFM RANGE W E1RA018 800 1200 E1RA024 800 1200 E1RA030 1000 1400 E1RA036 1200 1600 E1RA042 1400 2000 E1RA048 1600 2000 E1RA060 1850 2000 14, 14 14 14 14 COIL G1UA024S14, G1UA030S14 G2FD024S14, G1HD024 G1UA030S14 G1UA036S G1UA036S G1NA030SH G2FD035S14 G2FD030S G1NF024SOF G1HD024 G1UA036S G1UA036S G1NA030SK G2FD035S14 G2FD036S G2FD036S G1NF036SOF G1HD036 14, G1UA036S14, G1UA036S,24 G1UA048S,24 G1NA036SC G2FD036S G2FD036S G2FD042S G2FD046S G1NF036SOF G1HD036 G1HD048,24 24 24 24 G1UA048S,24 G1UA060S24 G1NA048SD G2FD046S G2FD042S G2FD048S G2FD048S24 G2FD060S24 G1NF048SOF G1HD048,24 G1UA048S,24,24 G1UA060S,24 G1NA048SD G2FD048S 24 G2FD048S24 24 G2FD060S24 G1NF048SOF G1HD048 G1HD060,24 24 G1UA060S,24 G2FD060S24 G1NF060SOF G1HD060 RATED CFM 650 850 1025 1250 1400 1600 1850 NET MBH TOTAL SENS..6 12.7.8 12.8.8 12.8 18.0 12.9 22.2 22.6 22.6 23.6 22.6 22.6 23.0 22.2 29.0 29.0 29.0 28.0 28.4 28.6 29.0 28.4 33.4 33.4 34.4 35.0 33.6 34.0 34.2 34.6 34.0 33.4 35.2 39.5 42.0 40.5 39.5 39.0 40.0 40.0 40.0 41.5 44.5 46.0 46.5 46.0 45.0 44.5 54.5 54.5 53.5 16.4 16.2 16.2 16.1 18.2 16.2.0 16.4 20.2 20.2 20.4 19.6.0 20.6.4.0 24.2 24.2 24.7 25.7 24.9 24.5 25.3 25.6 25.1 24.7 26.0 28.4 32.4 28.6 28.4 28.9 29.6 28.8 29.6 30.7 32.9 32.7 33.1 30.7 33.7 32.8 34.0 33.3 32.9 33.6 39.2 40.3 39.6 33.9 COOLING KW 1.96 1.98 1.98 2.00 2.40 2.43 2.43 2.62 2.43 2.43 2.55 2.37 3.07 3.07 3.07 3.07 3.09 3.10 3.15 3.08 3.80 3.85 3.80 3.46 3.77 3.86 4.29 4.44 4.43 4.30 4.30 4.37 4.40 4.30 4.36 4.75 4.89 4.84 4.89 4.84 4.80 4.79 4.73 4.75 4.76 6.12 6.09 5.87 4.76 SEER 10.5 10.5 SEER/ TXV 1 515.16-TG1Y E1RA090 2500 3000 35 G2FD090S35 3000 91.2 67.5 9.60 9.50 See Notes on Page 2 EER 8.85 8.95 8.95 9.00 9.25 9.00 9.00 9.35 9.45 9.45 9.45 9.20 9.25 9.20 9.20 8.75 8.75 9.05 8.80 9.05 8.95 9.05 9.00 8.85 9.20 9.45 9.15 9.15 9.15 9.50 9.35 9.50 9.50 9.40 9.40 9.60 9.50 9.35 9.55 8.90 8.95 9.55 SOUND RATINGS ERA SOUND RATINGS BELS ERA SOUND RATINGS BELS 018 8.0 042 8.2 024 8.0 048 8.4 030 8.0 060 8.2 036 8.2 090 CERTIFICATION APPLIES ONLY WHEN USED WITH PROPER COMPONENTS AS LISTED WITH ARI Unitary Products Group 3
515.16-TG1Y HEATING PERFORMANCE - 1 & 3 Ø ERA / With Air Handler & Multi-Position Coils COIL 1 ARI HEATING 2 OUTDOOR TEMP 3 47 F F HSPF -3 F 7 F F 27 F 37 F 47 F 57 F MBH COP MBH COP STD MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW G2FD024S.0 3.02 10.6 2.06 7.0 6.4 1.41 8.5 1.46 10.6 1.51 12.7 1.56 14.8 1.60.0 1.65 20.3 1.69 F2RP018 6.2 1.43 7.4 1.46 9.1 1.50 11.2 1.61 14.0 1.62.0 1.68 18.2 1.75.0 2.96 9.1 1.78 6.8 E1RA018 F2FP018 6.2 1.43 7.4 1.46 9.1 1.50 11.2 1.61 14.0 1.62.0 1.68 18.2 1.75 F2RP024 7.2 1.44 8.6 1.47 10.6 1.52 13.0 1.63 14.0 1.59.0 1.66 18.2 1.73.0 3.00 10.6 2.05 7.0 F2FP024 7.2 1.44 8.6 1.47 10.6 1.52 13.0 1.63 14.0 1.59.0 1.66 18.2 1.73 G2FD030S 22.6 3.28 11.9 2.00 7.3 4.7 1.55 8.3 1.65 11.9 1.74 15.5 1.84 19.1 1.93 22.6 2.02 27.3 2.18 F2RP024 7.5 1.56 9.3 1.66 11.5 1.78 13.0 1.87 19.4 1.91 22.0 2.00 24.8 2.08 22.0 3.20 11.5 1.89 7.0 E1RA024 F2FP024 7.5 1.56 9.3 1.66 11.5 1.78 13.0 1.87 19.4 1.91 22.0 2.00 24.8 2.08 F2RP030 7.7 1.52 9.6 1.62 11.9 1.74 13.4 1.83 19.8 1.90 22.5 2.00 25.4 2.07 22.6 3.30 11.9 2.00 7.3 F2FP030 7.7 1.52 9.6 1.62 11.9 1.74 13.4 1.83 19.8 1.90 22.5 2.00 25.4 2.07 G2FD030S 29.0 3.08 18.0 2.20 7.4 9.4 2.08 13.7 2.24 18.0 2.40 22.3 2.56 26.9 2.71 29.0 2.76 34.6 2.98 G2FD036S 29.2 3.12 18.2 2.22 7.4 9.5 2.10 13.9 2.25 18.2 2.40 22.5 2.55 27.2 2.70 29.2 2.74 34.8 2.95 E1RA030 F2RP030 10.5 1.99 13.5 2.19 16.2 2.26 19.6 2.46 25.3 2.59 28.8 2.72 33.0 2.86 28.8 3.10 16.2 2.0 7.2 F2FP030 10.5 1.99 13.5 2.19 16.2 2.26 19.6 2.46 25.3 2.59 28.8 2.72 33.0 2.86 F2RP036 11.6 2.11 15.0 2.32 18.0 2.39 19.8 2.47 25.5 2.61 29.0 2.74 33.2 2.88 29.0 3.10 18.0 2. 7.4 F2FP036 11.6 2.11 15.0 2.32 18.0 2.39 19.8 2.47 25.5 2.61 29.0 2.74 33.2 2.88 G2FD036S 34.0 3.02 20.2 2.16 7.2 11.3 2.37 15.7 2.55 20.2 2.74 24.7 2.93 29.5 3.13 34.0 3.30 40.5 3.48 G2FD042S 34.0 3.00 20.2 2.14 7.2 11.3 2.40 15.7 2.58 20.2 2.77 24.7 2.95 29.5 3.15 34.0 3.32 40.5 3.50 E1RA036 F2RP036 15.5 2.40 15.6 2.54 20.4 2.80 24.9 3.03 29.9 3.20 34.0 3.32 38.5 3.50 34.0 3.0 20.4 2.15 7.2 F2FP036 15.5 2.40 15.6 2.54 20.4 2.80 24.9 3.03 29.9 3.20 34.0 3.32 38.5 3.50 F2RP042 34.0 3.0 20.4 2.14 7.2 11.3 2.42 15.9 2.61 20.4 2.79 24.9 2.98 28.2 3.11 34.0 3.32 40.2 3.54 F2FP042 34.0 3.0 20.4 2.14 7.2 11.3 2.42 15.9 2.61 20.4 2.79 24.9 2.98 28.2 3.11 34.0 3.32 40.2 3.54 G2FD042S 39.0 3.22 23.4 2.08 7.4 11.9 3.00.6 3.15 23.4 3.30 29.2 3.45 35.5 3.56 39.0 3.55 47.5 3.84 G2FD048S 39.5 3.34 23.4 2.10 7.5 12.4 3.04.9 3.15 23.4 3.27 28.9 3.38 34.9 3.46 39.5 3.47 46.8 3.66 E1RA042 F2RP042 38.8 3.25 23.2 2.10 7.4 11.8 2.95.5 3.09 23.2 3.24 28.9 3.38 35.2 3.50 38.8 3.50 47.3 3.78 F2FP042 38.8 3.25 23.2 2.10 7.4 11.8 2.95.5 3.09 23.2 3.24 28.9 3.38 35.2 3.50 38.8 3.50 47.3 3.78 F2FP048 39.5 3.30 23.4 2.12 7.4 12.4 2.97.9 3.10 23.4 3.23 28.9 3.37 32.5 3.39 39.5 3.51 47.5 3.64 F2FP048 47.0 3.08 31.4 2.32 7.5 20.8 3.64 26.1 3.80 31.4 3.97 36.7 4.13 40.1 4.27 47.0 4.47 54.6 4.71 G2FD048S 47.0 3.02 31.2 2.32 7.5.0 3.56 26.1 3.75 31.2 3.94 36.3 4.13 40.1 4.32 47.0 4.56 54.1 4.59 E1RA048 G2FD048S24 47.0 3.02 31.2 2.32 7.5.0 3.56 26.1 3.75 31.2 3.94 36.3 4.13 40.1 4.32 47.0 4.56 54.1 4.59 G2FD060S24 47.0 3.00 31.2 2.30 7.5.0 3.60 26.1 3.79 31.2 3.98 36.3 4. 42.0 4.39 47.0 4.59 54.1 4.61 F2FP060 47.5 3.04 31.4 2.30 7.5 22.0 3.64 26.1 3.85 31.4 3.97 36.7 4.13 40.1 4.27 47.0 4.47 54.6 4.71 G2FD060S24 56.5 3.10 37.0 2.30 7.5 24.1 4.30 30.6 4.51 37.0 4.71 43.4 4.92 48.2 5.09 56.5 5.34 65.9 5.59 E1RA060 F2FP060 57.0 3.04 37.4 2.22 7.5 24.3 4.59 30.9 4.76 37.4 4.94 44.0 5.11 48.6 5.25 57.0 5.50 67.0 5.79 E1RA090 F3HE090 83.3 2.79 54.0 2.05 -- 38.0 6.55 45.1 1.73 54.0 2.05 58.5 2.10 62.9 2.40 83.3 2.79 85.8 2.90 1 Rated CFM same as for cooling. 2 Heating MBH based on ARI standards of 70 DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no supplemental electric heat operation. 3 Integrated heating capacities include the effect of defrost cycles in the temperature range where they occur. COP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period. = Not Applicable. 4 Unitary Products Group
HEATING CAPACITY - With Furnace Coils COIL 1 ARI HEATING 2 OUTDOOR TEMP 3 515.16-TG1Y 47 F F -3 F 7 F F 27 F 37 F 47 F 57 F HSPF MBH COP MBH COP MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW G1UA024S14 16.8 2.95 10.6 2.02 7.0 6.4 1.44 8.5 1.49 10.6 1.54 12.7 1.59 14.8 1.64 16.8 1.67 20.3 1.80 G1UA024S 16.8 2.95 10.6 2.02 7.0 6.4 1.44 8.5 1.49 10.6 1.54 12.7 1.59 14.8 1.64 16.8 1.67 20.3 1.80 E1RA018 G1UA030S14.0 3.02 10.6 2.06 7.0 6.4 1.41 8.5 1.46 10.6 1.51 12.7 1.56 14.8 1.60.0 1.65 20.3 1.69 G2FD024S14.0 3.02 10.6 2.06 7.0 6.4 1.41 8.5 1.46 10.6 1.51 12.7 1.56 14.8 1.60.0 1.65 20.3 1.69 G2FD024S.0 3.02 10.6 2.06 7.0 6.4 1.41 8.5 1.46 10.6 1.51 12.7 1.56 14.8 1.60.0 1.65 20.3 1.69 G1NA030SH.5 3.00 12.6 2.00 7.0 1.50 11.3 1.55 11.9 1.59 15.2 1.62 18.5 1.78 19.8 1.86 22.3 2.00 G1UA030S14 22.4 3. 11.6 2.00 7.1 4.4 1.46 8.0 1.58 11.6 1.70 15.2 1.82 18.8 1.94 22.4 2.05 27.1 2.23 G1UA036S 22.6 3.28 11.9 2.00 7.4 4.7 1.55 8.3 1.65 11.9 1.74 15.5 1.84 19.1 1.93 22.6 2.02 27.3 2.18 G1UA036S 22.6 3.28 11.9 2.00 7.4 4.7 1.55 8.3 1.65 11.9 1.74 15.5 1.84 19.1 1.93 22.6 2.02 27.3 2.18 E1RA024 G2FD035S14 22.6 3.28 11.9 2.00 7.3 4.7 1.55 8.3 1.65 11.9 1.74 15.5 1.84 19.1 1.93 22.6 2.02 27.3 2.18 G2FD030S 22.6 3.28 11.9 2.00 7.3 4.7 1.55 8.3 1.65 11.9 1.74 15.5 1.84 19.1 1.93 22.6 2.02 27.3 2.18 G1NF024SOF 23.4 3.04 13.3 2.00 7.0 11.1 1.57 12.5 1.60 13.3 1.63.8 1.66 22.4 1.91 23.4 1.94 27.4 2.11 G1HD024 22.3 3.24 11.8 2.00 7.1 4.7 1.53 8.2 1.63 11.8 1.73 15.4 1.83 18.9 1.93 22.3 2.02 27.3 2.18 G1NA030SH 23.4 3.04 13.3 2.00-11.1 1.57 12.5 1.60 13.3 1.63.8 1.66 22.4 1.91 23.4 1.94 27.4 2.11 G1UA036S 29.0 3.08 18.0 2.20 7.4 9.4 2.08 13.7 2.24 18.0 2.40 22.3 2.56 26.9 2.71 29.0 2.76 34.6 2.98 G1UA036S 29.0 3.08 18.0 2.20 7.4 9.4 2.08 13.7 2.24 18.0 2.40 22.3 2.56 26.9 2.71 29.0 2.76 34.6 2.98 G2FD035S14 22.6 3.28 11.9 2.00 7.4 4.7 1.55 8.3 1.65 11.9 1.74 15.5 1.84 19.1 1.93 22.6 2.02 27.3 2.18 E1RA030 G2FD036S 29.2 3.12 18.2 2.22 7.4 9.5 2.10 13.9 2.25 18.2 2.40 22.5 2.55 27.2 2.70 29.2 2.74 34.8 2.95 G2FD036S 29.4 3.10 18.0 2.12 7.4 9.1 2.22 13.5 2.35 18.0 2.49 22.5 2.62 27.3 2.76 29.4 2.78 34.8 2.96 G1NF036OF 29.4 3.07 18.5 2.24 7.0 13.9 1.89 16.1 2.00 18.5 2.04 22.1 2.14 26.7 2.29 29.4 2.42 33.8 2.64 G1HD036 29.4 3.10 18.0 2.20 7.4 9.7 2.09 13.8 2.24 18.0 2.40 22.2 2.55 26.7 2.71 29.4 2.78 33.1 2.94 G1NA030SH 29.4 3.07 18.5 2.24-13.9 1.89 16.1 2.00 18.5 2.04 22.1 2.14 26.7 2.29 29.4 2.42 33.8 2.64 G1UA048S 34.0 3.00 20.2 2.14 7.2 11.3 2.40 15.7 2.58 20.2 2.77 24.7 2.95 29.5 3.15 34.0 3.32 40.5 3.50 G1UA048S24 34.0 3.00 20.2 2.14 7.2 11.3 2.40 15.7 2.58 20.2 2.77 24.7 2.95 29.5 3.15 34.0 3.32 40.5 3.50 G2FD036S 34.0 3.02 20.2 2.16 7.2 11.3 2.37 15.7 2.55 20.2 2.74 24.7 2.93 29.5 3.13 34.0 3.30 40.5 3.48 G2FD036S 33.4 2.93 19.8 2.12 7.0 11.0 2.33 15.4 2.53 19.8 2.74 24.2 2.94 28.9 3.16 33.4 3.34 39.8 3.55 E1RA036 G2FD042S 34.0 3.00 20.2 2.14 7.2 11.3 2.40 15.7 2.58 20.2 2.77 24.7 2.94 29.5 3.15 34.0 3.32 40.5 3.50 G2FD046S 33.6 3.00 20.0 2.15 7.2 11.2 2.35 15.6 2.54 20.0 2.73 24.4 2.92 29.1 3.12 33.6 3.28 40.0 3.47 G1NF036SOF 35.2 3.23.0 2.10 7.2 14.2 2.25.9 2.40.0 2.46 26.3 2.57 30.8 2.67 35.2 2.74 41.5 2.98 G1HD036 34.0 3.03 20.2 2.15 7.2 11.2 2.39 15.7 2.57 20.2 2.75 24.7 2.93 29.5 3.12 34.0 3.29 40.5 3.47 G1HD048 34.1 3.07 20.4 2.18 7.2 11.5 2.39 16.0 2.57 20.4 2.74 24.8 2.92 29.6 3.10 34.1 3.26 40.6 3.42 G1NA036SC 35.2 3.23.0 2.10-14.2 2.25.9 2.40.0 2.46 26.3 2.57 30.8 2.67 35.2 2.74 41.5 2.98 G1UA048S 39.0 3.25 23.4 2.10 7.4 11.8 2.97.6 3.12 23.4 3.27 29.2 3.41 35.6 3.53 39.0 3.52 46.1 3.75 G1UA048S24 39.0 3.25 23.4 2.10 7.4 11.8 2.97.6 3.12 23.4 3.27 29.2 3.41 35.6 3.53 39.0 3.52 46.1 3.75 G2FD046S 39.2 3.25 23.4 2.09 7.4 11.8 2.99.6 3.14 23.4 3.28 29.2 3.43 35.6 3.54 39.2 3.54 46.5 3.78 G2FD042S 39.0 3.22 23.4 2.08 7.4 11.9 3.00.6 3.15 23.4 3.30 29.2 3.45 35.5 3.56 39.0 3.55 47.5 3.84 E1RA042 G2FD048S 39.5 3.25 23.4 2.10 7.4 12.4 3.04.9 3.15 23.4 3.27 28.9 3.38 34.9 3.46 39.5 3.47 46.8 3.66 G2FD048S24 39.5 3.25 23.4 2.10 7.4 12.4 3.04.9 3.15 23.4 3.27 28.9 3.38 34.9 3.46 39.5 3.47 46.8 3.66 G2FD060S24 39.0 3.24 23.4 2.10 7.4 12.9 2.99 18.2 3.13 23.4 3.27 28.6 3.41 32.0 3.42 39.0 3.53 45.8 3.75 G1NF048SOF 41.0 3.30 27.7 2.48 7.4 20.4 2.59 24.3 2.74 27.7 2.78 33.7 2.92 37.8 3.05 41.0 3.15 44.9 3.33 G1HD048 39.0 3.25 23.4 2.10 7.4 11.8 2.96.6 3.11 23.4 3.27 29.2 3.42 33.1 3.43 39.0 3.52 47.8 G1NA048SD 41.0 3.30 27.7 2.48-20.4 2.59 24.3 2.74 27.7 2.78 33.7 2.92 37.8 3.05 41.0 3.15 44.9 3.33 G1UA048S 47.0 3.00 31.2 2.30 7.5 20.9 3.60 26.1 3.79 31.2 3.98 36.3 4.16 42.0 4.39 47.0 4.59 54.0 4.61 G1UA048S24 47.0 3.00 31.2 2.30 7.5 20.9 3.60 26.1 3.79 31.2 3.98 36.3 4.16 42.0 4.39 47.0 4.59 54.0 4.61 G1UA060S 47.0 3.00 31.2 2.30 7.5.0 3.60 26.1 3.79 31.2 3.98 36.3 4. 42.0 4.39 47.0 4.59 54.0 4.61 G1UA060S24 47.0 3.00 31.2 2.30 7.5.0 3.60 26.1 3.79 31.2 3.98 36.3 4. 42.0 4.39 47.0 4.59 54.0 4.61 G2FD048S 47.0 3.02 31.2 2.32 7.5.0 3.56 26.1 3.75 31.2 3.94 36.3 4.13 40.1 4.32 47.0 4.56 54.1 4.59 E1RA048 G2FD048S24 47.0 3.02 31.2 2.32 7.5.0 3.56 26.1 3.75 31.2 3.94 36.3 4.13 40.1 4.32 47.0 4.56 54.1 4.59 G2FD060S24 47.0 3.00 31.2 2.30 7.5.0 3.60 26.1 3.79 31.2 3.98 36.3 4. 42.0 4.39 47.0 4.59 54.1 4.61 G1NF048SOF 48.8 2.99 30.8 2.31 7.5 23.4 3.05 27.8 3.30 30.8 3.40 38.3 3.67 44.3 3.98 48.8 4.27 57.2 4.88 G1HD048 47.0 3.00 31.2 2.30 7.5 20.9 3.60 26.1 3.79 31.2 3.98 36.3 4. 42.0 4.41 47.0 4.59 53.9 4.63 G1HD060 47.0 3.00 31.2 2.30 7.5 20.9 3.60 26.1 3.79 31.2 3.98 36.3 4.16 42.0 4.41 47.0 4.59 53.9 4.63 G1NA048SD 48.8 2.99 30.8 2.31-23.4 3.05 27.8 3.30 30.8 3.40 38.3 3.67 44.3 3.98 48.8 4.27 57.2 4.88 G1UA060S 56.5 3.10 37.0 2.30 7.5 24.1 4.30 30.6 4.51 37.0 4.71 43.4 4.92 48.2 5.09 56.5 5.34 65.9 5.59 G1UA060S24 56.5 3.10 37.0 2.30 7.5 24.1 4.30 30.6 4.51 37.0 4.71 43.4 4.92 48.2 5.09 56.5 5.34 65.9 5.59 E1RA060 G2FD060S24 56.5 3.10 37.0 2.30 7.5 24.1 4.30 30.6 4.51 37.0 4.71 43.4 4.92 48.2 5.09 56.5 5.34 65.9 5.59 G1NF060SOF 58.0 3.20 35.0 2.30 7.5 9.2 1.12.6 2.62 35.0 3.85 44.2 4.26 50.1 4.57 58.0 4.70 61.2 5.32 G1HD060 56.8 3.10 37.0 2.30 7.5 24.0 4.30 30.5 4.51 37.0 4.71 43.5 4.92 48.3 5.10 56.8 5.37 66.1 5.55 E1RA090 G2FD090 82.3 2.73 53.0 2.00 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- NOTES: See page 4. Unitary Products Group 5
515.16-TG1Y TYPICAL INSTALLATION 60" OVERHEAD CLEARANCE 18" SERVICE ACCESS CLEARANCE WEATHERPROOF DISCONNECT SWITCH THERMOSTAT TO FURNACE OR AIR HANDLER TERMINAL BLOCK NEC CLASS 1 WIRING NEC CLASS 2 WIRING 10" CLEARANCE COIL AREA TO INDOOR COIL NOTE: ALL OUTDOOR WIRING MUST BE WEATHERPROOF SEAL OPENING(S) WITH PERMAGUM OR EQUIVALENT CONTROL ACCESS PANEL ACCESSORIES Refer to Price Manual for specific model numbers. Compressor Blanket - Designed to further reduce the normal operating sound and is required to meet Canadian sound levels for units of three tons and below. Low Temperature Lockout - 2LT06700224 - Prevents heat pump operation below minus 10 F ambient Temperature. Outdoor Thermostat - 2TD06700124 - Consists of an adjustable outdoor thermostat and relay in a vented enclosure. It provides additional second stage control of the supplemental resistance heat.(balance Point Control) Room Thermostats - One of the following thermostats may be used with these heat pump systems. 6TH104024 - Two stage heat / one stage cool / non-electronic manual changeover thermostat. 6TH104124 - Two stage heat / one stage cool / automatic change over, outdoor compensated, non-electronic thermostat. 3600-367P - Two stage heat / one stage cool / non-programmable non-electronic thermostat. 6 Unitary Products Group
TYPICAL FIELD WIRING - 1 Ø Units (018-060) TYPICAL FIELD WIRING - 3 Ø Units (036, 048, 060) 515.16-TG1Y TYPICAL FIELD WIRING - 3 Ø Units (090) Unitary Products Group 7
MATCHING INDOOR COMPONENTS Add-On Coils - For Furnace Application G1UA Upflow G1HD Horizontal Duct G1NA Upflow G2FD MULTI-POSITION (Upflow, Horizontal, and Downflow) G1NF Outdoor Furnace Coil Available with factory installed horizontal drain pan. Air Handlers - For Non-Furnace Application N1AH or N1VS MODULAR BLOWER (Upflow, Horizontal, and Downflow) F2RP / FP or F2RC / FC Fan Coil Units (Upflow Horizontal) G2FD Coil F3EH Light Commercial Applications Available with factory installed horizontal drain pan. Unitary Products Group 5005 York Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A. Copyright by York International Corporation 1999. All Rights Reserved. Code: EBY, EGY 515.16-TG1Y (499) Supersedes: 515.16-TG1Y (298)