PowerOhm Installation Manual for LG ATV Series Braking Modules

Similar documents
PowerOhm Installation Manual for BM R Series Braking Modules

PowerOhm Installation Manual for BM R Series Braking Modules

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

17429X.00 SERIES MODELS:

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

High Frequency SineWave Guardian TM

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

CDBR-B. Dynamic Braking Unit Instruction Manual. April 2009 Part Number: R1 Copyright 2009 Electromotive Systems

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

CDBR-B. Instruction Manual. Dynamic Braking Unit. March 2013 Part Number: R4 Copyright 2013 Magnetek

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

DYNAMIC BRAKING (DB) OPTION

GP-1000 Inverter. Go Power! Electric Inc. PO Box 6033 Victoria, BC V8P 5L4 Tel: Fax:

CALTRAP INSTALLATION AND OPERATIONS MANUAL

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation

CONTROL FEATURES AVAILABLE OPTIONS

GSL Electronics Modified Sine Wave Power Inverters

SINUS K 13. ACCESSORIES Braking resistors APPLICATION TABLES 78/160 INSTALLATION INSTRUCTIONS

Power Distribution System User s Manual. Model: PDS-100

CDBR-D. Instruction Manual. Dynamic Braking Unit. May 2014 Part Number: R1 Copyright 2014 Magnetek

Braking Unit for Frequency Inverter Serie 3CV V 18,5 bis 55kW

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Go Power! Manual. GP-1750HD Inverter GP-2500 Inverter

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL REV MTE Corporation

MATRIX FILTER USER MANUAL. SERIES D 480 Volts, 60HZ PART NO. INSTR 024 REL REV MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Pure Sine Wave Inverter GP-HS1500. Owner s Manual

MATRIX FILTER USER MANUAL. SERIES D 400 Volts, 50HZ PART NO. INSTR 025 REL REV MTE Corporation

A6Z OPERATING MANUAL

SDC,Inc. SCR-Regenerative Ac Drive

Pure Sine Wave Inverter User Manual

Art. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2

FR-BU2-1.5K to 55K FR-BU2-H7.5K to H280K

Kelly HSR Series Motor Controller with Regen User s Manual V 3.3. Kelly HSR Opto-Isolated Series Motor Controller with Regen.

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

DPD72PG1 BILEVEL STEP MOTOR DRIVER PACK With RAMPING PULSE GENERATOR

1332 TROUBLESHOOTING GUIDE. Remarks: If this function is not appropriate for the application, it can be eliminated by turning off DSWl, switch 3.

INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC.

USERS MANUAL MCD REMOTE OPERATOR

PF Guard Power Factor Capacitor Bank Installation, Operation, and Maintenance Manual

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation

3 Phase Smart Controller

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide

PS-1X Series Power Supply Unit Information & User Manual

Product Overview. Product Identification. Amps One CT Two CTs Three CTs

Battery Power Inverters

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD

Owner s Manual. PowerVerter PV1000HF, PV1800HF & PV3000HF DC-to-AC Inverters. Contents. Reliable AC Power Wherever You Need It!

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL

X100P Load Bank. Read all instructions before using the load bank. Contents

DC TO AC POWER INVERTER

G213V STEP MOTOR DRIVE REV 7: March 25, 2011

Features IN THIS CHAPTER

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation

DIN Rail UPS Model: DIN-UPS Installation/Operation Manual

XLM 62V Energy Storage Module

DO NOT INSTALL, REMOVE, OR REWIRE THIS EQUIPMENT WITH POWER APPLIED.

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

DC3E Non-Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC M/N DC3N-12D AI M/N DC3N-12D-4X-010-AI

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages.

OPERATION INSTRUCTIONS

Operations Manual. Zero Speed Switch Sensor Model ZS09P

Freedom egen System End-of- Line Functional Checklist

A3Z OPERATING MANUAL

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V

ESD5500E Series Speed Control Unit

G203V / G213V MANUAL STEP MOTOR DRIVE

VLT SERIES. True Sine Wave AC Power Inverter. Owner s Manual. Owner s Manual D Rev.B

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

Brushed. Brushed. Brushed Motor

User Manual JS-ICON. 624 ARCH Dimmer Rack. JOHNSON SYSTEMS INC. Spring

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

Special Specification 6058 Battery Back-Up System for Signal Cabinets

Battery Equalizer. Table of Contents Introduction. 2. Specifications.. 3. Theory of Operation Typical Applications... 5

Installation and Operation Guide. Tundra HD 2500 Power Inverter. for the. Webasto BlueCool Truck System

USER S MANUAL

MMA 160S ARC/MMA WELDER OPERATION INSTRUCTIONS

MaxPak Plus Analog DC V S Drive

PHASE PERFECT PHASE CONVERTERS OPERATION & INSTALLATION MANUAL PHASE TECHNOLOGIES, LLC

V 2.0 DC TO AC POWER INVERTER PWRINV500012W PWRINV500024W PWRINV500036W PWRINV500048W. Instruction Manual

GLM SERIES CONTROL Users Manual Rev:

VC-30 / VC-40 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

XLR Energy Storage Module

The Power of Reliability INSTRUCTION MANUAL

Devices Supported: KEB48220 KEB48221 KEB48300 KEB48301 KEB48400 KEB48401 KEB48600 KEB48601 KEB72330 EB KEB72450 KEB EB KEB72600 KEB

PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual

CPS Energy Balancer. Version: 1.0

USER S MANUAL. Variable-frequency drive for 3-phase and single-phase AC motors

USER S MANUAL VFD05-D230-PCM VFDP4X04-D230-PCM VFDA4X04-D230-PCM VFDF4X04-D230-PCM VFDS4X05-D230-PCM

Data Bulletin. ALTIVAR FLEX58 Chassis Drive Controllers Class 8806 INTRODUCTION DESIGN CONCEPT. Bulletin No. 8806DB0102 August 2001 Raleigh, NC, USA

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

Filtered PWM Speed Control for Permanent Magnet DC Motors

XS400 Load Bank. Read all instructions before using the load bank. Contents

Transcription:

PowerOhm Installation Manual for LG ATV Series Braking Modules IMPORTANT: These instructions should be read thoroughly before installation. All warnings and precautions should be observed for both personal safety and for proper equipment performance and longevity. Failure to follow these instructions could result in equipment failure and/or serious injury to personnel. Braking modules contain lethal voltages when connected to the inverter. It is very important to remove power to the inverter before installing or servicing this unit. Always allow adequate time (approximately 5 minutes) after removing power before touching any components. The POWER ON LED must be completely out before servicing the unit.

Table Of Contents Page 2: Table of Contents for HCPMAN0009_R3 (2018-03-05) Page 3: Product Overview Page 4: Inspection and Environmental Conditions Page 5: Electrical Ratings Page 6: Equipment Installation Page 7: Mounting Dimensions and Weight Page 8: Wire Recommendations Page 9: Wire Sizing Page 10: Power Connections for 50 & 115amp models Page 11: Power Connections for 150 amp models Page 12: 115vac Enable & Control Connections Page 13: Module Set Up - Jumper Descriptions & Locations Page 14: Module Set Up - Jumper Positions & Factory Settings Page 15: Module Set Up Voltage, Master & Fault Jumper Descriptions Page 16: System Integration - Drive DC Bus Connections Page 17: System Integration - Single Module Power Connections Page 18: System Integration - Master / Slave Power Connections Page 19: System Integration - Master / Slave Control Connections Page 20: Start Up Page 21: Start Up Page 22: Maintenance Page 23: Troubleshooting Page 24: Troubleshooting Page 25: Troubleshooting Page 26: Troubleshooting Page 27: Note Page Page 28: Back Page 2 a brand of ICD, Inc.

Product Overview AC variable frequency drives are commonly used with various types of motors to form reliable variable speed drive systems. Problems with these drive systems can occur when an application requires a deceleration rate faster than what can be managed by the drive alone, or when motor speeds exceed the synchronous speed set by the output frequency of the drive (which is called an overhauling load condition). Both of these conditions create regenerated power which flows from the motor back into the drive, causing its DC Bus to rise. To manage the regenerated power and avoid shutting the drive down due to an over-voltage trip, this power must be dissipated by an external braking resistor. PowerOhm Series ATV Braking Modules can be used in conjunction with any AC drive to monitor the DC bus of the drive and activate an external braking resistor as needed not only to avoid over-voltage trips, but to greatly improve the performance of the drive system. The use of Braking Modules and resistors increase the braking torque capability of a variable frequency drive, allowing faster and more controlled deceleration times. To accommodate system horsepower requirements beyond the capability of a single Module, the Modules are all Master/Slave programmable. This allows an arrangement of multiple Modules to effectively function as a single higher rated module. The products covered in this manual are intended to be used with Listed inverter drives. The input of the DBU is only to be connected across the DC bus of an inverter drive. Conductors for connection of the DBU shall be according to the NFPA 70 (national Electric Code) and the drives installation instructions. 3 a brand of ICD, Inc.

Inspection upon Receipt Upon receipt of your PowerOhm Braking Module, be sure to carefully unpack the module and inspect the unit carefully for any shipping damage. The module contains electronics that can be damaged by static electricity, so handle in accordance with industry standards. Check for loose, broken or otherwise damaged parts due to shipping. Report any shipping damage immediately to the freight carrier. Be sure to verify that the part number and ratings listed on the nameplate match the order specification and the capabilities of the drive system. The ratings listed on the nameplate are critical installing and energizing the incorrect part number could damage the braking module and/or the drive! Environmental Conditions The PowerOhm Series ATV Braking Module should be installed in an environment protected from moisture and excessive dust. Dust buildup can reduce the electrical insulation characteristics of the unit and moisture can cause arching or shorting. Air must be free of combustible gases and corrosive vapors. Chassis classification: Open type Ambient Temperature Range: -10ºC to 40ºC Maximum Altitude: 3300 feet (1000m) Maximum Vibration: 10 to 20Hz, 32ft/sec/sec; 20 to 50Hz, 6.5 ft/sec/sec 4 a brand of ICD, Inc.

Electrical Ratings The PowerOhm Series ATV Braking Module is available in three different voltage classes including 240, 480 and 600 volts. The continuous current ratings available are 50, 115, and 150 amps. (* note that a cooling fan is used to achieve the 115 & 150 amp ratings). Peak currents up to the maximum are allowed at intermittent duty cycles, as long as the Module RMS Load Current rating is not exceeded (reference Table1). SCHNEIDER Part No. RMS Load Current = Peak Current the square root of duty cycle TABLE 1: General Specifications for ATV Braking Modules Nominal AC Line Voltage Minimum Ohms @ listed Turn ON Turn ON Voltage RMS Cont Current Max Peak Current % Cont Duty Cycle Max Watt Loss HCPATVBM250 240 1.95 390vdc 50 200 6.25 154 HCPATVBM2115 * 240 1.95 390vdc 115 200 33 293 HCPATVBM2150 * 240 1.3 390vdc 150 300 25 369 HCPATVBM450 480 3.88 775vdc 50 200 6.25 163 HCPATVBM4115 * 480 3.88 775vdc 115 200 33 302 HCPATVBM4150 * 480 2.6 775vdc 150 300 25 378 HCPATVBM650 600 4.85 970vdc 50 200 6.25 177 HCPATVBM6115 * 600 4.85 970vdc 115 200 33 316 HCPATVBM6150 * 600 3.3 970vdc 150 300 25 392 * 115 & 150 amp models require external power for fan in order to meet RMS ratings 5 a brand of ICD, Inc.

Equipment Installation The PowerOhm Series ATV Braking Module should be installed on a low vibration surface that is non-flammable. ATTENTION: Installation and removal of this equipment should be done by qualified personnel only. Equipment must be installed in accordance with all applicable national and local electrical codes and regulations. MOUNTING REQUIREMENTS To allow proper cooling, it is very important to install convection cooled PowerOhm braking modules in the vertical position (see Figure 1). A convection cooled model is simply a unit without a factory installed cooling fan. If the braking module includes the optional cooling fan, the chassis can be orientated in any position. A convection cooled braking module requires a minimum of 2 inches of clearance around all sides. A fan cooled module requires a minimum of 4 inches above the fan exhaust face to allow proper cooling. Figure 1: Mounting Position for Convection Cooled Modules 6 a brand of ICD, Inc.

Dimensions and Weight The PowerOhm Series ATV Braking Module shown in Figure 2 includes the details of the fan cooled model (115,150 amp model fan is shown with dashed lines). Note that the height will be 11 inches without the fan kit. Figure 2: Braking Module Dimensions Weight: For 50 amp the weight is approximately 9 lbs; For 115 & 150 amp the weight (with fan) is approximately 11 lbs. 7 a brand of ICD, Inc.

Wiring Recommendations It is recommended that the AC drive manual, braking resistor instructions and any other pertinent documentation be thoroughly reviewed before proceeding. Note that control and power wiring should be separated to avoid electrical noise and interference problems. The wiring between the drive and braking module should not exceed 15 feet and between the braking resistor and braking module should not exceed 30 feet. Use CU conductors only with insulation rated for 75 C minimum or equivalent. Important: Always properly ground each component to Power Earth ground (PE). Ground Brake Module DIRECTLY to AC Drive Module Power ground, and ensure the drive cabinet has a good ground. Figure 3: Wiring Lengths Between Drive System Components WARNING: Never install a braking resistor directly across the DC bus of the drive. Drive damage or failure may occur upon applied power or, the resistor will dissipate power continuously and be subject to overheating and failure. 8 a brand of ICD, Inc.

Wire Sizing Reference Table 2 for suggested minimum wire sizes only. Keep in mind the duty cycle rating greatly affects the minimum wire size needed. TABLE 2: Wire Sizing for Power Interconnections Motor HP at 10% Duty Cycle 240VAC 480VAC 600VAC WIRE SIZE 1HP to 50HP 1HP to 75HP 1HP to 75HP 10 AWG 60HP to 100HP 100HP to 150HP 100HP to 150HP 8 AWG N/A 200HP-250HP 200HP-250HP 6AWG Motor HP at 30% Duty Cycle 240VAC 480VAC 600VAC WIRE SIZE 1HP to 30HP 1HP to 40HP 1HP to 40HP 8 AWG 40HP to 75HP 50HP to 75HP 50HP to 75HP 6 AWG 100HP 100HP to 250HP 100HP to 250HP 4 AWG Note: 18 AWG wire is sufficient for all control and signal wiring ATTENTION: The National Electric Code (NEC) and local regulations govern the installation and wiring of electrical equipment such as braking resistors and modules. DC power wiring, AC power wiring, control wiring and conduit must be installed in accordance with all applicable codes and regulations. 9 a brand of ICD, Inc.

Power Connections The PowerOhm Series ATV Braking Module features a total of four power connections and an earth ground. Terminal location and size is dependent on the current capacity of the model. See reference tables 3a, and 3b for a description of each terminal s function, torque, type of connection and wire size. TABLE 3a: Power Connections for ATV 50 & 115 amp Models Terminal Designation Terminal Description Maximum Torque (lb-in) Connection Type Max Wire Size N [DC -] DC Bus Negative 32 Tubular Clamp 2 awg P [DC+] DC Bus Positive 32 Tubular Clamp 2 awg No Connection No Connection PO [1] Braking Resistor 32 Tubular Clamp 2 awg B [2] Braking Resistor 32 Tubular Clamp 2 awg Power Earth Ground 45 Tubular Clamp 4 awg 50 & 115 amp Power Terminals 10 a brand of ICD, Inc.

Terminal Designation TABLE 3b: Power Connections for ATV 150 amp Models Terminal Description Maximum Torque (lb-in) Connection Type Max Wire Size N [DC -] DC Bus Negative 33 Tubular Clamp 1/0 P [DC+] DC Bus Positive 33 Tubular Clamp 1/0 PO [1] Braking Resistor 33 Tubular Clamp 1/0 B [2] Braking Resistor 33 Tubular Clamp 1/0 Power Earth Ground 45 Tubular Clamp 4 awg 150 amp Power Terminals 11 a brand of ICD, Inc.

Control Connections The PowerOhm Series ATV Braking Module features a 10-position terminal block for all signal and control wiring. All terminations on the block can accept bare wire or fork lugs for a #6 screw. Reference Table 4 for a description of each terminal. Terminal Number TABLE 4: Control Connections for All ATV Models Terminal Description Electrical Ratings Maximum Torque (lb-in) 1 Slave Input Pulse (Positive) 24vdc @ 10ma 7 2 Slave Input Pulse (Negative) 24vdc @ 10ma 7 3 Fault Contact Output (NO or NC) 125vac/24vdc @.5a 7 4 Fault Contact Output (NO or NC) 125vac/24vdc @.5a 7 5 Master Output Pulse (Positive) 24vdc @ 50ma 7 6 Master Output Pulse (Negative) 24vdc @ 50ma 7 7 Non-functioning termination N/A 7 8 Non-functioning termination N/A 7 9 120VAC external Enable & Fan.5a @ 125vac 7 10 120VAC external Enable & Fan.5a @ 125vac 7 Note: 18 AWG wire is sufficient for all control and signal wiring 12 a brand of ICD, Inc.

Module Set Up The PowerOhm Series ATV Braking Module has several jumper settings that are accessible on the main circuit board. The front cover has to be removed to change the jumper settings. Warning: Do not make jumper changes while power is applied! Change as required only after power is removed and the green power indicator is off! Use insulated tools when changing jumper positions. TABLE 5: Description of Jumper Settings Jumpers JP1-JP5 JP6 JP7 JP8 Jumper Description Set to match the actual on site AC line voltage Selects Internal or External Brake Enable Selects a Master or Slave configuration Selects a NC or NO Fault contact. FIGURE 4a: Control Board Jumper Locations 13 a brand of ICD, Inc.

FIGURE 4b: Control Board Jumper Positions Brake Enable Jumper: JP6 selects between internal enable or external enable modes Internal (Automatic): When the JP6 jumper is in the downward position, the Brake is Enabled automatically whenever system DC Bus voltage is applied. External: When the JP6 jumper is in the upward position, the Brake is enabled ONLY when voltage is applied to control terminals 9 and 10. This position is recommended so the Brake can be disabled when the drive is not running. The ATVBMx-115 & ATVBMx-150 models REQUIRE voltage at terminals 9 & 10 to run the cooling fan so JP6 MUST be set to external for brake module to be enabled. TABLE 6: Factory Installed Enable Jumper Settings SCHNEIDER Part No. ATVBMx-050 ATVBMx-115 ATVBMx-150 (JP1-JP5) AC Line Voltages 200-600 JP6 Brake Enable Internal External External JP7 Master Slave Master JP8 Fault Contact NC CAUTION: If the Enable Jumper is set to INTERNAL with power applied to an idle drive, the bus voltage can reach a value high enough to turn on the brake module, potentially causing the brake resistor to over-heat. 14 a brand of ICD, Inc.

Line Voltage Level Jumpers: The voltage ID box in fig 4a indicates which voltage class the control board is set up for and the voltage class determines the DC threshold level expected for each jumper position. ATV series braking modules are calibrated to the DC voltages shown in the JP5 column in table 7, with JP5 ON. Moving the jumper to another position changes the DC turn on thresholds as shown in table 7. TABLE 7: DC Voltage turn on voltages for ATV models Voltage Class JP1 JP2 JP3 JP4 JP5 200vac 322vdc 338vdc 354vdc 374vdc 390vdc 400vac 640vdc 671vdc 703vdc 744vdc 775vdc 600vac 805vdc 844vdc 883vdc 931vdc 970vdc If the actual drive input AC Line voltage differs from the factory default setting considerably, and the external enable command is not used, it may be necessary to change the jumper setting to match the power source. Generally speaking, it is best to operate the module with the highest allowable setting to allow for upward drift of the AC line & DC bus during unloaded conditions Drive over-voltage trip level must be taken into account Removing the enable forces the brake to ignore any over-voltage conditions when the drive is not running Master - Slave Jumper: When the JP7 jumper is in the upward position, the braking module is in the Slave mode. If the JP7 jumper is in the downward position, the braking module is in the Master mode. When a single module is used it must be in the Master mode. If multiple modules are needed, only one unit can be in the Master mode while all other modules are in the Slave mode. Fault Contact Jumper: When the module is operating properly and JP8 is in the upward position the fault contact is Normally Closed (NC). When JP8 is in the downward position the fault contact is Normally Open (NO). Contacts change state only during a fault condition and do not change state when the module is powered ON or OFF. Contacts are rated 125VAC at.5 amps. 15 a brand of ICD, Inc.

System Integration Figure 5: Drive DC BUS Power Connections Internal/External Chopper: In the example above, the internal and external chopper connections are shown. Both should never be used at the same time. An external chopper is needed when a drives internal chopper cannot support the desired duty cycle, or when the drive has no internal chopper transistor. Wiring Notes: All DC power wiring should be connected DIRECTLY to the DC bus caps of the drive as shown in Figure 5. Connecting upstream of contactor or line chokes may cause an overvoltage or high frequency switching condition and possibly damage the brake and drive. 16 a brand of ICD, Inc.

Figure 6: Power Connections for a Single Braking Module Master - Slave Jumper Settings: In the example above, the braking module is set as the Master (JP7 is the downward position). Wiring Notes: All DC power wiring between the drive, braking module and braking resistor should be twisted (if possible) and run separate from all control wiring. 17 a brand of ICD, Inc.

Figure 7: Power Connections for Multiple Braking Modules Master - Slave Jumper Settings: In the example above, the top braking module is set as the Master (JP7 is the downward position) and the lower module is in Slave Mode (JP7 is in the upward position). Wiring Notes: All DC power wiring between the drive, braking module and braking resistor should be twisted (if possible) and run separate from all control wiring. 18 a brand of ICD, Inc.

Figure 8: Control Connections for Multiple Braking Modules Master - Slave Jumper Settings: In the example above, the top braking module is set as the Master (JP7 is the downward position) and the lower module is in Slave Mode (JP7 is in the upward position). Damage may occur if both jumpers are set for master with signal wires connected Wiring Notes: All control wiring must be twisted and run separate from all power wiring. 19 a brand of ICD, Inc.

Start Up PRELIMINARY: Ensure the DC bus connections are proper polarity. Make sure that braking module voltage rating is equivalent to the drive and that all voltage selection jumpers are in the proper positions. Ensure the drive is set up for external brake and that the drives internal braking overvoltage control circuits are disabled. Ensure the Enable / Fan voltage is correct if used. Ensure the enable jumper is set according to your application. JP6 is Factory set for an external enable voltage at control board terminals 9 & 10 for the 115 & 150 amp. THE BRAKE MODULE WILL NOT TURN ON IF THE MODULE IS NOT ENABLED To see the internal LEDs it will be necessary to position yourself directly in front of the module front cover looking into the cover viewing hole. It is good practice to monitor the DC bus under stopped and braking conditions, making sure the braking setpoint is not too close to the nominal unloaded DC bus voltage. In order to best capture the peak voltage use an oscilloscope or a meter with a peak hold function. POWER UP: As the DC bus pre-charges the green POWER ON LED illuminates indicating that DC bus voltage is properly applied to the DC- and DC+ power connections. At this time the braking and fault LEDs should be OFF. Note unloaded DC bus level. BRAKING CYCLE: Start the drive and run the motor unloaded. Stop the drive quickly and monitor the green BRAKE LED. The LED will flash on, the heavier the braking, the more it flashes. Load motor, then start and stop drive and again monitor braking LED. Note DC bus level during the peak of the braking cycle. If the unloaded nominal DC bus is within 10% of the peak DC Bus during braking, consider increasing the braking voltage threshold or using a drive contact to disable the brake while drive is idle. 20 a brand of ICD, Inc.

DECELERATION: While under full load slowly decrease drive decel time while monitoring DC bus level. Decrease decel time as process allows until DC bus rises near the drive high bus trip level. Now increase decel time back to a level allowing a comfortable amount of headroom to prevent nuisance overvoltage trips. (If the drive trips on overvoltage easily or you can t stop the drive fast enough, the brake module may be undersized DUTY CYCLE: While under full load increase the duty cycle while monitoring the DC bus level and module resistors. If the resistors are glowing at the end of each braking cycle the duty cycle should be decreased. (Although the resistors can take extreme temperature they will last longer if they are not stressed to the point of glowing on every cycle) FAULT: With the brake module sized correctly and the proper decel time and duty cycle settings the fault LED should never turn ON. If the fault LED turns on and the brake module is hot simply allow time too cool, and either increase the decel time or decrease the duty cycle. Ensure the cooling fan is operating properly. (115 & 150 amp models) 21 a brand of ICD, Inc.

Maintenance CAUTION: NEVER perform any maintenance while power is present. ALWAYS be sure to double check for safe voltage levels by measuring the DC bus input as well as any external control or status signals before working on equipment. Monthly: Check that the Green power LED is ON, and the Red Fault LED is OFF. If the brake module has an internal fan, check that it is blowing air. Yearly: Check the module circuit boards for buildup of dust, debris, or moisture. Check the cooling fan and heatsink for any buildup. High voltages exist within the module and the buildup of dust, debris, and moisture can contribute to arcing and equipment damage. Take corrective action as necessary to keep the module clean. If cleaning is needed remove power from system and allow time for all voltages too drain to safe levels. Blow the debris out with clean dry air. Blow off any debris that exists on the circuit boards. 22 a brand of ICD, Inc.

Troubleshooting NORMAL LED INDICATORS The PowerOhm Series ATV Braking Module has three LED indicators that allow the user to verify the following: POWER ON: An illuminated green LED indicates that DC bus voltage is applied to the DC- and DC+ power connections. BRAKING: An illuminated or flashing green LED indicates that the module is braking. FAULT: An illuminated red LED indicates that the module has over-heated OR the internal braking transistor has failed shorted. If the module overheated the fault LED will eventually turn off after a cooling period of no less than 2 minutes with fan running and no longer than 30 minutes without fan running. TURN ON LEVEL (ADJ.) The TURN ON LEVEL adjusts at what DC bus voltage the braking module will turn ON and activate the braking resistor. This level is calibrated at the factory and should never be adjusted in the field by non-factory personnel. Generally speaking, it is best to operate the module with the highest allowable setting to allow for upward drift of the AC line during lightly loaded conditions. Control board Jumpers JP1 JP5 are a coarse adjustment and change the setpoint by approximately 4-5% for each position. If changing jumper positions the system power should be turned off and insulated needle nose pliers should be used. 23 a brand of ICD, Inc.

ABNORMAL SYMPTOMS Before removing equipment covers or making any changes in jumper positions or adjustments, power down equipment and wait for DC bus to drop to safe levels. Always use an insulated screwdriver or insulated pliers when making jumper changes or adjustments Follow these steps and make note of indications before calling for help. Have unit model and serial number ready to aid PowerOhm in troubleshooting GREEN POWER LED IS NOT ON Check for DC bus at input of brake chopper module If new installation check for loose wires or connections on control board If DC bus is present and all connections seem to be normal, replace module BRAKING LED NEVER TURNS ON Check for proper voltage rating of control board Check for proper positioning of coarse voltage adjust jumpers Check enable jumper position and enable voltage at TB1-9 & 10 of control board Monitor DC bus and decrease decel time until DC bus rises enough to cause braking If all the above are OK, using insulated needle nose pliers move coarse voltage adjust jumper to the left one position and retry If moving jumper to the left three positions does not result in brake module turning ON, replace module BRAKING LED FLICKERS During light duty braking or at the end of a braking cycle it is normal for the LED to flicker some If the LED flickers when the Drive is idle there may be excessive noise on the DC bus from other equipment, a higher than expected AC line level, or high harmonics on the incoming voltage If the LED flickers when drive is running normal load (not braking) there may be excessive common mode noise on the DC bus and addition DC bus filtering may be needed 24 a brand of ICD, Inc.

BRAKING LED NEVER TURNS OFF / RESISTOR OVERHEATS Check for proper voltage rating of control board and jumper positions Ensure the brake module is connected DIRECTLY to the drive DC bus cap bank. Connecting up stream of the precharge circuits may result in high peak voltages that can turn on the brake module Check actual system AC line voltage for high harmonic content (high peak to RMS ratio) or for excessive noise spikes as this may cause an unusually high DC bus level on an unloaded drive If the above are OK, power down and using insulated needle nose pliers move coarse voltage adjust jumper to the right one position and retry If moving jumper to the right 3 positions does not result in brake module turning off, or the jumper cannot be moved further to the right, continue with next step Using an insulated screwdriver turn the adjustment pot CW. If the control board is working properly, and the DC bus voltage is normal, at some point the braking LED should turn off. This indicates the unit has been tampered with and should be re-calibrated by qualified personnel at the PowerOhm facility If none of the above steps solves the problem, replace module BRAKING MODULE GETS HOT It is normal for brake modules to generate heat during heavy duty operation Check load and duty cycle to make sure module is sized correctly If the module overheats the fault LED will turn on and the output fault contact will change states If IGBT is shorted the electronics module will not get hot, but the resistor will 25 a brand of ICD, Inc.

FAULT LED IS ON Check unit for heatsink overheating and allow time to cool Check for proper sizing of brake module as overheating indicates the module is running beyond its capacity a. Reduce the duty cycle or increase the decel time b. Use a higher rated braking module Confirm the 2 position thermostat plug at top of control board is seated properly If the above are OK, replace module MASTER SLAVE SYSTEM DOES NOT WORK PROPERLY Check position of master slave jumpers on each module. Damage will occur if both jumpers are set for master with signal wires connected. Make sure wiring between master and slaves is correct at TB1 of the control board Ensure the system is sized properly Monitor Braking LED on all modules. If master braking LED turns on but any slave does not, and wiring is correct, replace slave module(s). If master braking LED never turns on follow steps for Braking LED never turns on 26 a brand of ICD, Inc.

Notes 27 a brand of ICD, Inc.

HCPMAN0009_R3 (2018-03-05) 28 a brand of ICD, Inc.