V5822 / 5823,C SMLL LINER VLVES PN16 FOR MODULTING ND ON/OFFCONTROL V5822 V5823 SPECIFICTION DT FETURES Small size allows installation where space is limited Range of fittings available for different connections (compression, soldered, threaded) Long stroke results in a highquality characteristic Soft seat provides low leakage rate and high rangeability Reduced k VS values in the bypass to facilitate hydronic balancing djustment cap for manual operation Valve inserts changeable without draining by using insert replacement tool WV 108 Compatible with twopiece conex compression fittings Conical sealing connections Flat surfaces on body to fit installation tools 40 mm distance between ports / and the bypass (V5823C, only) GENERL V5823C These small linear valves are used in combination with small electric linear valve actuators and thermoelectric actuators for the control of hot and/or chilled water for fan coil units and small reheaters/recoolers in electric/electronic temperature control systems. SPECIFICTIONS Models Operation Nominal pressure rating Twoway V5822 Threeway V5823 Threeway with bypass V5823C Twoway stem up to open, port to ; Threeway stem up to close, port to PN16 Capacity index (k VS ) see tables on page 2 and 3 Leakage rate 0.02% of k VS Valve body Material rass Size DN (1/2 ), DN (3/4 ) Trim Stem Plug Suitable medium Controlled water temperature Stainless steel rass Water, with max. 50% glycol 2...1 C U.S. Registered Trademark EN00307GE51 R0316 Copyright 16 Honeywell Inc. ll rights reserved
Modulating valves Rangeability Twoway valves 100:1 Threeway valves Flow characteristic Stroke 100:1 for controlled port Equal percentage port, n gl =3.4, linear for bypass port 6.5 mm On/Off valves Stroke 2.5 mm Dimensions see Fig. 4 on page 5 FLOW CPCITIES ND CLOSE OFF PRESSURE RTINGS TWOWY VLVES Valve DN k VS M6410C,L / M7410C,E (180 N) CloseOff Pressure (kpa) with ctuators MT8 MT4 / M7410 0.16 V58221006 1600 600 0.25 V58221014 1600 600 0.40 V58221022 1600 600 0.63 V58221030 1600 600 1.00 V58221048 10 180 1.60 V58221055 10 180 2.50 V58221063 400 50* 4.00 V58221071 400 50* 1.60 V58224000** 10 180 180 2.50 V58224018** 400 50* 50* *Up to 1000kPa system pressure. **In the case of on/off control, the stroke amounts to 2.5 mm. THREEWY VLVES Valve DN k VS M6410C,L / M7410C,E (180 N) CloseOff Pressure (kpa) with ctuators MT8 MT4 / M7410 0.25 V582303 800 500 0.40 V582311 800 500 0.63 V582329 800 500 1.00 V582337 250 0 1.60 V582345 250 0 2.50 V582321 240 2.50 V582352 100 50 4.00 V58232169 240 4.00 V582360 100 50 1.60 V58234009* 250 0 0 2.50 V58234017* 100 50 50 *In the case of on/off control, the stroke amounts to 2.5 mm. EN00307GE51 R0316 2
THREEWY VLVES WITH YPSS Valve CloseOff Pressure (kpa) with ctuators DN k VS k VS M6410C,L / M7410C,E MT8 MT4 / M7410 (180 N) 0.25 0.16 V5823C09 800 500 0.40 0.25 V5823C17 800 500 0.63 0.40 V5823C25 800 500 1.00 0.63 V5823C33 250 0 1.60 1.00 V5823C41 250 0 2.50 1.60 V5823C58 100 50 2.50 1.60 V5823C27 240 4.00 2.50 V5823C66 100 50 4.00 2.50 V5823C2165 240 1.60 1.60 V5823C4005* 250 0 0 2.50 2.50 V5823C4013* 100 50 50 *In the case of on/off control, the stroke amounts to 2.5 mm. OPERTION builtin return spring in the twoway valve produces an opening force. In the threeway valve and the threeway valve with bypass, the spring produces a closing force on the to ports. The valves are supplied with a screwedon adjustment cap for manual operation and for protection of the stem. This allows the stem to be set up for filling or initial heating/cooling during the building construction phase without the use of a controller or actuator. The small electric valve actuators as well as the thermoelectric actuators provide automatic control over the opening and closing movement of the valve stem. TYPICL OPERTION ll types of valves should be mounted in the return flow. If the pvalues exceed 60 kpa, attention should be paid to the development of noise. TwoWay Valves Direction of flow always from port to port Port : Outlet ThreeWay Valves These valves are preferably used as mixing valves, this means: Port : Total flow outlet Port : Controlled flow Port : ypass Fig. 2. Threeway valve operation ThreeWay Valves with ypass These valves simplify the installation, which is depending on the layout of the pipework, as the bypass pipe is part of the valve. The information for the normal threeway valves is also valid for this type. outlet outlet Fig. 1. Twoway valve operation Fig. 3. Threeway valve with bypass 3 EN00307GE51 R0316
MOUNTING When installing the valve, care must be taken that the flow direction is correct (see section "Typical Operation"). The valve must not be mounted with the stem pointing downward. The adjustment cap must be removed from the valve only when the actuator is fitted. The valve should be installed as stressfree as possible with a tightening torque of 25 to 30 Nm. The valve is supplied complete with mounting instructions. The water quality must meet VDI 35 requirements. CCESSORIES For valves V5822, two connection sets are necessary; for valves V5823, three connection sets are necessary; for valves V5823C, four connection sets are necessary. Connection Pipe Size DN Connection Set Description Compression mm 22 mm CNC CNC Consisting of 1 union nut and 1 ferrule Soldering 12 mm mm CNS CNS Consisting of 1 union nut and 1 solder bush External Thread R3/8" R1/2" CNT CNT Consisting of 1 union nut and 1 tailpiece Compression (Conex) mm 22 mm 63* 65* Capnut and compression ring *Cannot be purchased from Honeywell Dimensions of Connection Sets a b c d G1/2 11/8 x 14 S 84 mm 22 mm CNC CNC G1/2 11/8 x 14 S 84 12mm mm CNS CNS G1/2 11/8 x 14 S 84 R3/8" R1/2" CNT CNT EN00307GE51 R0316 4
DIMENSIONS Twoway valve 6. 5 Str ok e * 6.5 Stroke* 18 M30x1.5 llow 130mm for the actuator and clearance for removal a b b d d DN DN 56 56 GG1/2 34 34 DN 6 11/8" x 14 S 84 33 DN 66 11/8 x14s 84 33 Threeway valve 6. 5 Str ok e* 6.5 Stroke* 18 M30x1.5 llow 130mm for the actuator and clearance for removal a a b d c d DN DN 56 56 G1/2 34 26 34 DN DN 66 66 11/8" 11/8 x14s x 14 S 84 84 33 33 c a Threeway valve with bypass 6. 5 Str ok e * 6.5 Stroke* 18 M30x1.5 llow 130mm for the actuator and clearance for removal a a b c d d DN 56 G1/2 40 34 DN 56 G1/2 40 34 DN 66 11/8" x 14 S 84 40 33 DN 66 11/8 x14s 84 40 33 * Modulating valves, only (in the case of on/off valves, the stroke amounts to 2.5 mm and the closure distance to 14 mm). Fig. 4. Dimensions V5822 / V5823,C in mm 5 EN00307GE51 R0316
SPRE PRTS Valve inserts are provided as spare parts for the V5822 and V5823,C small linear valves. When the tool WV 108 is used, the valve inserts can be changed without draining the system. * For on/off control DN k VS Valve Insert V58221006 0.16 0902812 V58221014 0.25 0902811 V58221022 0.40 0902810 V58221030 0.63 0902809 V58221048 1.00 0902808 V58221055 1.60 0902807 V58221063 2.50 0902814 V58221071 4.00 09028 V58224000* 1.60 0902813 V58224018* 2.50 0902816 * For on/off control DN k VS Valve Insert V582303 / V5823C09 0.25 0902821 V582314 / V5823C17 0.40 0902822 V582329 / V5823C25 0.63 0902823 V582337 / V5823C33 1.00 0902824 V582345 / V5823C41 1.60 0902825 V582321 / V5823C58 2.50 0902826 V582352 / V5823C27 2.50 0902818 V58232169 / V5823C66 4.00 0902827 V582360 / V5823C2165 4.00 0902819 V58234009* / V5823C4005* 1.60 0902817 V58234017* / V5823C4013* 2.50 09028 The following valve inserts are interchangeable Twoway valves: k VS 0.16, 0.25, 0.40, and 0.63 k VS 1.0 and 1.6 k VS 2.5 and 4.0 Threeway valves: k VS 0.25, 0.40, 0.63, and 1.0 k VS 2.5 and 4.0 Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.. La Pièce 16, Switzerland by its uthorized Representative: utomation and Control Solutions Honeywell GmbH öblinger Strasse 17 71101 Schönaich, Germany Phone 49 (0) 7031 637 01 Fax 49 (0) 7031 637 740 http://ecc.emea.honeywell.com EN00307GE51 R0316 Subject to change without notice