Earth-Rite II RTR Static Earthing System

Similar documents
Earth-Rite MGV. IECEx SIL 2. Leading the way in hazardous area static control. Mobile Ground Verification System

The Earth-Rite MGV is designed to enable operators establish safe grounding of their vehicle in accordance with these recommended practices.

Cen. -Stat Static Grounding clamps, cables and reels. Leading the way in hazardous area static control

Static Discharge Ignition of Combustible Atmospheres. White Paper. Author Details:

INSTRUCTION MANUAL (ATEX / IECEx)

INSTRUCTION MANUAL (ATEX / IECEx)

Flameproof Level Sensor (Flameproof F/S FP)

11mm Slot Label S1 = 162, S2 = 170, S3 = 250, S4 = 305, S5 = 330, S6 = 410, S7 = 490, S8 = 570, S9 = 650. Maximum Power Dissipation (Watts) T** T**

Operating Instructions

Operating Instructions

Operating Instructions

Zone 1 Linear Range - Installation Guide

Floodlight Range Installation Guide

Position Switches Series 8074/2

Technical Data. Dimensions

GuaRdboX - Gd series IOM (Installation, Operation & Maintenance Manual) 0100-ENG rev.4

Solenoid Valves Type 3963

INSTALLATION AND SERVICE INSTRUCTIONS FOR 2000 SERIES FLAMEPROOF XENON AND FLUORESCENT BEACONS

Earth-Rite MGV Mobile Grounding Verification. White Paper. Author Details: Page 1 of 5

YFC. Limit switch. Ex d. 24 operating head types

Static Discharge Ignition of Combustible Atmospheres. White Paper. Author Details: ungrounded vacuum tankers and road tankers.

Flameproof Alternators

ANKERSMID Temperature controller ATC 510/520/525 for wall-mounting. Application

Operating Instructions

Ex m Solenoid Operator Type 0519

2000 Series Flameproof Xenon and Fluorescent Beacons Installation and Service Instructions

ABG Cable Glands Installation Procedure

Explosion Protected Group IIB Zone 1 Ex d Ring Enclosure Ex e Terminal Boxes Hollow Shaft Option OPERATING SPECIFICATION TECHNICAL DETAILS

Clarius EP PLUS LED FLOODLIGHT Installation Guide

Light Fitting for Fluorescent Lamps Series ECOLUX 6600

OPERATING INSTRUCTIONS

ILED Aquarius Illuminated Windsock. User Manual

Position Switches Series 8060/2

Segurança. Segurança. PSB Heating System Cold applied connection technology. Compulsório. Compulsório. Operation Manual and Installation Instructions

Dimensions shown apply to both Stainless Steel and Mild Steel S1, SF*1 = 162, S2, SF*2, S2L, SF*2L = 170, S3, SF*3 = 250,

Linear Luminaire for Fluorescent Lamps Series ECOLUX 6600

INSTALLATION and MAINTENANCE INSTRUCTIONS SHO SERIES ELECTRIC CABLE REELS

EVZ Series (Small body) Explosion protected luminaire Operating Instructions

Operating Instructions

Flameproof Alternator

Linear Luminaire for Fluorescent Lamps Series EXLUX 6401

Cable Glands - American Series - NEC/IEC

EStrong-series Emergency Stop

GRD Electronic earthing system. Ex d. Polyester coating RAL7035. LED indicators

Self-Exciting Flameproof Alternator

With regards to safety it is not necessary to check for correct operation.

M-0. M-0... series control, monitoring and signalling devices. Ex e

PTB 14 ATEX 2023 X, EPS 16 ATEX 1046 X. Operating Instructions. Solenoid coil Type AC10 Magnetspule Typ AC10 Bobine magnétique Type AC10

Instruction Manual. for Heating Cables and Cold Leads Type and Catalogue no and Hemstedt GmbH.

EWE. Ex de. Cooling fins

Load disconnect switch Series 8146/5-V11

ZB0050 / ZB0051 ZB0070 / ZB0071

Load and Motor Switches, Load-Break Switches Series 8549

ILED Dorado. User Manual

Static Discharge Ignition of Combustible Atmospheres

IECEx Certificate of Conformity

CCAI, CCAIF, CCAIF..H

Flameproof Alternator

BMRX Series ROTARY LEVEL CONTROL

Linear Luminaire for Fluorescent Lamps Series ECOLUX METAL 6010/1

Position Switches Series 8070/2

EX Series User Manual

Solenoid Operator 0516 / 1216

Rosemount Product Data Sheet , Rev GA Catalog FIELDBUS PROTOCOL. Hazardous Locations Certifications

SPOOL VALVES solenoid air operated 1/4 to 1/2 tapped body and NAMUR for integrated pilot

POWER CONNECTOR TERMINATION / HOOK UP PROCEDURE

OPERATION AND MAINTENANCE INSTRUCTIONS

Ground Fault Cable Retractor GR1000L Service Manual

Compact Sheet-Steel Light Fittings Series 6114/1

Thermocouple For additional thermowell, flameproof enclosure (Ex d) Model TC10-L

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Emergency Light Fitting for Fluorescent Lamps Series 6009

Compact Sheet-steel Emergency Light Fitting Series 6118/1

Linear Luminaire with LED Series EXLUX 6002

Cable Reel 0951, 200, 300, 400, 228BH Series Service Manual

Installation Instructions for Appleton Mercmaster LED Luminaire

Resistance thermometer For additional thermowell, flameproof enclosure (Ex d) Model TR10-L

Linear luminaire with LED Series EXLUX 6002

Ground Fault Cable Retractor GR900 Series Service Manual

Easytork Solenoid Valve IOM

CIVACON GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT

Installation, Operating & Maintenance Instructions. Norbro J-Switch FM 00707

PTB 14 ATEX 2023 X, IECEx PTB X. Operating Instructions. Solenoid coil Type AC10 Magnetspule Typ AC10 Bobine magnétique Type AC10

LIVE DEMATEABLE CONNECTOR TERMINATION / HOOK UP PROCEDURE

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004

EWE. Cooling fins. Ex de

K Series 3 Way Direct Acting Balanced Poppet Solenoid Valve

DIAMOND POINT VIBRATING PROBES

Spring Cable Reels EXEL

Load and Motor Switches, Load-Break Switches Series 8544

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

Plugs and Sockets SolConeX & CES Series 8570, 8571, 8575, 8581

Terminal Boxes in Stainless Steel SLS**.T

24V 3A EN54 Ancillary Power Supply

Pendant Light Fitting IEC

LIMIT SWITCH Hawkeye - HX Magnetic Solid State Proximity Sensors Installation, Maintenance and Operating Instructions (HX )

Load and Motor Switches, Load-Break Switches Series 8544

7 Lighting Technology

Type 4-20mA Absolute Shaft Encoder & Optional Dragon Flow Sensor DLS-00X User Manual. hohner OPTICAL ENCODERS

Ex e, ia Junction boxes TNCN. Features

Transcription:

READ MANUAL BEFORE COMMENCING WITH INSTALLATION Earth-Rite II RTR Static Earthing System For use on 110-10 Volt and 0-40 Volt AC Supplies with VESM0 Cable Reel Installation & Operating Instructions II (1) GD Model: ERII - June 11 The safety of any system incorporating the equipment referred to in this manual is the responsibility of the installer of the system. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Any warranty is made void if the equipment is not installed, or used, in accordance with the manufacturers instructions. www.newson-gale.com

Earth-Rite II Static Earth Monitoring System System using an Exd IIC Control Unit Tri-Mode The Earth-Rite II RTR system operates using Tri-Mode technology which uses the electrical capacitance of the road tanker to ensure the presence of an affective Static Earth Point to which the road tanker is connected. It also monitors that the clamp is connected to a road tanker rather than directly to earthed structures or isolated items of metal. Once permissive, the system continues to monitor the resistive loop circuit from tanker to the Static Earth Point. The Earth-Rite II RTR is a Tri-Mode system (capacitive / resistive monitoring), it is intended for use with Road Tankers. It is set to show permissive only when the system detects the presence of a road tanker and when the connection to earth is less than 10 Ohms nominal resistance. Until this condition is achieved, the system remains non-permissive. For correct operation, the cable between the Junction Box (or Cable Reel) and the Monitoring Unit must not exceed 3m in length. If the cable is to be less than 3m in length, an approved barrier (compound-filled) gland shall be used. Refer to the latest edition of IEC 60079-14 or EN 60079-14 for more information. Note: It is recommended that the transfer operation is interlocked with the contacts of the Earth-Rite II unit. This will ensure that the operation is stopped if the earth connection is inadvertently lost. Maintenance: Periodically check exterior of enclosure for damage. IF YOU ARE IN ANY QUERIES REGARDING THE ABOVE POINTS THEN PLEASE CONTACT NEWSON GALE, OR THEIR APPROVED DISTRIBUTOR, WITHOUT DELAY Certification Label Detail Newson Gale Ltd Nottingham NG4 JX UK Earth-Rite II A device known as the RTR Tester is available to allow the Earth-Rite II RTR to switch to permissive for test purposes when a road tanker is not present. Installation 0518 Sira 09ATEX047 Ex d[ia] IIC T6 Gb(Ga) Ex tb IIIC T80 C IP66 Db Ta = -40 C to +55 C IECEx SIR 09.0018 II (1) GD The installation shall be carried out by suitably trained personnel in accordance with the relevant sections of IEC 60079 and EN 60079. All cables entering the monitoring unit must be connected through approved cable glands in accordance with EN 60079-14 The glands should be fitted in such a way as to maintain the ingress protection rating of the enclosure. The system should be connected as per the enclosed installation drawings. The Earth-Rite II system should be powered from 110-10 Volts or 0-40 Volts 50Hz. The system should be protected using a A fast blow fuse mounted in the distribution board / fuse box. The monitoring unit should be mounted, with the indicator window facing away from direct sunlight, at a convenient location, visible to the operator. The lid of the Monitoring Unit enclosure is removed by rotating it in an anti-clockwise direction. A pair of tools, which locate in the two holes in the lid, are provided to assist in this operation. This label is fitted behind the window of the Earth-Rite II Exd enclosure Other Approvals Functional Safety DO NOT OPEN WHEN AN EXPLOSIVE GAS AND/OR DUST ATMOSPHERE MAY BE PRESENT Um = vvvvv Model Number mmmmm Serial Number: YY/XXXXX The Earth-Rite II has been given a SIL (Safety Integrity Level) rating of. Electromagnetic Compatibility The Earth-Rite II has been tested and shown conformity to European Directive 004/108/EC, and FCC Part 15 Emissions. Conformity has been proven to BS EN 61000-6-3 and BS EN 61000-6-. After installation of wiring, secure the cover to the body making sure it is tight. www.newson-gale.com

Customer Supplied Cable Specification Recommended Specification Cable from ERII Unit to Pump Starter 1.0mm core cable + Earth Cable from Supply to the ERII Unit 1.0mm core cable + Earth Cables from ERII Unit to Site Static Earthing Point 4mm single core cable with green sheath. Cable from ERII Unit to optional Mode Selector Key Switch 1.0mm core cable (IS circuit). Length: 3m or more. NOTE: Cables must be secured close to the enclosure in order to prevent them being accidentally pulled out. Cable Glands Please refer to the latest edition of IEC 60079-14 or EN 60079-14 for more information on suitable cable glands and acceptable cable lengths. IF YOU ARE IN ANY DOUBT REGARDING THE INSTALLATION THEN PLEASE CONTACT NEWSON GALE, OR THEIR APPROVED DISTRIBUTOR, WITHOUT DELAY. Optional Mode Selector Key Switch The switch allows the ERII system to be used for grounding both road tanker and other items of plant. Key Switch Positions In the normal OFF position (with key removed) the system is designed to operate with road tankers only. This is the safest option for road tankers as it monitors the capacitance and resistance of the road tanker with respect to ground. In the ON position (with key held in the switch unit) the system is designed to operate with any item of conductive metal plant, e.g. railcars, drums and IBCs, and other items of low conductivity plant (<10 ohms). This option monitors the resistance of the plant item with respect to the site static bonding bar / tape. RTR (TRI-MODE) Operation In the normal quiescent state, with clamp stowed on the insulated pin, the Red Negative Ground Connection LED will show. Attach the earthing clamp onto the tanker, at a suitable position, and ensure that both of the pointed contacts are positively located. If the connection is healthy then the Green Positive Ground Connection LEDs will flash and the interlock contacts will close. The product transfer operation can now take place. If the earth connection is broken during the transfer operation then the Red Negative Ground Connection LED will show and the interlock contacts will open. On completion the earthing clamp should be removed from the tanker and stowed on the insulated pin on the front of the junction box. The Red Negative Ground Connection LED will show. Important Note - The earthing clamp should be fitted prior to any other operation as per the recommendations of IEC 60079-3, NFPA 77 and API RP 003. It is important that the clamp is fitted before hoses are connected to the road tanker and before articulated trailer legs are deployed. Advanced Safety Feature The Earth-Rite II RTR has a System Reboot facility in response to Power Outages. This safety feature is designed to maintain high site safety during interlocked transfer operations using hoses. Should the mains supply be lost during the transfer process, the system will become nonpermissive and the transfer operation will stop. The following procedure will ensure that the system can safely continue to monitor the clamp connection following a Power Outage situation: 1 Attach the clamp to the tanker in the same position as it was originally attached. Turn OFF the supply to the ERII system. 3 Wait 10 seconds. 4 Turn ON the supply to the ERII system. The system should become permissive as indicated by the green flashing LEDs. The benefits of the System Reboot facility also apply to the situation where the clamp is accidentally removed during the transfer process and the system goes non-permissive. If this happens, the above procedure should be used to allow the transfer operation to continue safely. www.newson-gale.com 3

Exd Monitoring Unit Copper-free Cast-aluminium Enclosure Installation & Maintenance Instructions The lid of the enclosure is removed by rotating it in an anticlockwise direction. A pair of tools, which locate in the two holes in the lid, can be provided to assist in this operation. After installation of wiring, secure the cover to the body making sure it is fully tightened. Periodically check exterior of enclosure for damage or deterioration. Troubleshooting at the time of Installation Earth-Rite II - RTR Tri-Mode System Before contacting Newson Gale please check the following points:- Symptom: Red and/or Green LEDs are NOT showing Check that the system is installed in accordance with the supplied manual. Check that there is power to the monitoring unit, and that it is the correct voltage. Caution - Ensure all Health & Safety precautions are taken during the above procedures. IF YOU HAVE ANY QUERIES REGARDING THE ABOVE POINTS THEN PLEASE CONTACT NEWSON GALE, OR THEIR APPROVED DISTRIBUTOR, WITHOUT DELAY. Symptom: System is NOT switching to permissive state when clamp is fitted to road tanker (RED LED continues to show). Check that the system is installed in accordance with the supplied manual. Check that a hose is not connected to the road tanker and that there is no accidental contact between the tanker and ground with items such as loading arms, ladders, railings, gates etc. Ensure that the trailer (where applicable) does not have support legs deployed. Check correct operation using the RTR Tester. Check That the grounding clamp is in good condition: that the contacts are level with each other, sharp and not loose. Caution - Ensure all Health & Safety precautions are taken during the above procedures. If the system still does not switch to permissive state when clamp is fitted to road tanker please contact Newson Gale and confirm the following:- Serial number Company which ordered the system Date of order Any other information Please contact Newson Gale Ltd if you require a translation of this manual. 4 www.newson-gale.com

Component Identification EARTH-RITE II SYSTEM Earth-Rite II RTR MONITORING PCB VAC - FORM INSULATING COVER AC POWER SUPPLY PCB www.newson-gale.com 5

Earth-Rite II RTR & VESM0 Cable Reel VESM0 ZONE 1, 1,, AREA Earth-Rite II RTR PL1 PL PL3 Upper (Monitoring) PCB PL4 ZONE 0, 0, 1, 1,, AREA 6 www.newson-gale.com

Earth-Rite II RTR Cable Connections - AC Version 0-40V 50/60Hz Live and Neutral Supply ZONE 1, 1,, AREA Exd Enclosure VESM0 Reel Earth-Rite II +v 0v sw S1 S G1 G C1 C PL1 PL PL3 PL4 Upper (Monitoring) PCB 1 Lower (Power Supply) PCB Crimp Connector Crimp Connector PL PL3 PL1 nc c no no c nc 10V N 40V L Pillar for Protective Earth (PE) Conductor Non-Intrinsically Safe Wiring Earthing Clamp Protective Earth (PE) Conductor 1 Customer Interlock Circuits N 0-40V 50/60Hz Supply L ZONE 0, 0, 1, 1,, AREA CUSTOMER S STATIC BONDING BAR / TAPE Static Earth Point (Resistance to Earth must be <10 ohm) Verification of the Static Earth Point The system monitors the static dissipation path, from the object to which the Static Earth Clamp or lead is connected to, as far as the Static Earth Point. It is the responsibility of the end user to provide the Static Earth Point and ensure that it is suitable for dissipating electrostatic charges. www.newson-gale.com 7

Earth-Rite II RTR Cable Connections - AC Version 110-10V 50/60Hz Live and Neutral Supply ZONE 1, 1,, AREA Exd Enclosure VESM0 Reel Earth-Rite II +v 0v sw S1 S G1 G C1 C PL1 PL PL3 PL4 Upper (Monitoring) PCB 1 Lower (Power Supply) PCB Crimp Connector Crimp Connector PL PL3 PL1 nc c no no c nc 10V N 40V L Pillar for Protective Earth (PE) Conductor Non-Intrinsically Safe Wiring Earthing Clamp ZONE 0, 0, 1, 1,, AREA Protective Earth (PE) Conductor 1 Customer Interlock Circuits L N 110-10V 50/60Hz Supply CUSTOMER S STATIC BONDING BAR / TAPE Static Earth Point (Resistance to Earth must be <10 ohm) Verification of the Static Earth Point The system monitors the static dissipation path, from the object to which the Static Earth Clamp or lead is connected to, as far as the Static Earth Point. It is the responsibility of the end user to provide the Static Earth Point and ensure that it is suitable for dissipating electrostatic charges. 8 www.newson-gale.com

Intrinsically Safe PCB Connections Monitoring PCB Upper (Monitoring) RTR PCB INTERNAL CONNECTIONS TO LOWER (PSU) PCB OPTIONAL MODE SELECTOR SWITCH STATIC DISSIPATION GROUND CABLE REEL VESM0 +v 0v sw S1 S G1 G C1 C PL1 PL PL3 PL4 POWER SUPPLY PCB Lower (PSU) PCB - AC INTERNAL CONNECTIONS TO UPPER (MONITORING) PCB +v 0v sw PL4 1 PL PL3 PL1 nc c no no c nc 10V N 40V L www.newson-gale.com 9

Internal Component Assembly XXXXXXXXXXXXXXXXX XXXXXXXXXXXXX XXXXXXXXXXXXXXXXX XXXXXXXXXXXXXXX XXXXXXXXXXX XXXXXXXXXXXXXXXXX XXXXXXXXXXX XXXXXXXXXXXXX XX XXXXXXXXXXXX XXXXX XXXXXXXX XXXXXXXXXXXXX XX XXXXXXXXXXX XXXXXXXXXXXXX XXXX XXXXXXXX 1 XXXXXXXXXXXXXXXXX XXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXX XXXXXXXXXXXXX XXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXX 3 4 5 6 XX X XX X X Metal Pillars XX X Insulated Pillar Internal Component Assembly XXXXXXXXXXXXXXXX X XXXXXXXXXXXXX XXXXXXXXXXXXXXXX XXXXXXXXXXXXXXXX XXXXXXXXXXX XXXXXXXXXXXXXXXX XXXXXXXXXXXX XXXXXXXXXXXXXXX XX XXXXXXXXXXXXX XXXXXXXXXXXXXXX XXXXXXXXXXXXXXX XX XXXXXXXXXXX XXXXXXXXXXXXXXX XXXXXXXXXXXXX Always observe precautions against damage to the PCB s from electrostatic discharge. 7 XXXXXXXXXXXXXXXXX XXXXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX XXXXXXXXXXX XXXXXXXXXXXXXXXXXXXXXXXXXXXX 1. Remove the lid of the enclosure and remove the blue approval label. This can be achieved by unscrewing the left-hand screws 4 revolutions anticlockwise and removing the right-hand screw completely.. Disconnect the three wires, of the ribbon cable, from the terminal block. Remove the monitoring PCB by unscrewing the three hexagonal metal pillars. Place the PCB in the anti-static bag provided and keep it safe. 3. Remove the vac-form insulating cover. 4. Install the various cables into the enclosure using suitable glands. Make the connections to the Power Supply PCB. 5. Replace the vac-form insulating cover. 6. Replace the monitoring PCB and secure using the three hexagonal metal pillars. Re-connect the ribbon cable and make the external I.S. wiring connections into the Terminal block. 7. Replace the blue approval label and secure using the screws provided. Replace the lid of the enclosure securely. 10 www.newson-gale.com

Operation - RTR Tri-Mode Note: The Earthing Clamp should be fitted prior to fitting hoses, or any other operation. ERII Newson Gale NewsonGale Reel A. In the normal "rest" state, with the Earthing Clamp not attached and the clamp-cable wound onto the reel, the Red Negative Earth Condition LED will be showing. Clamp Newson Gale Newson Gale B. Attach the Earthing Clamp onto the Road Tanker at a suitable point which is in contact with the tank/frame and ensure that the pointed contacts are positively located. If the connection to the Road Tanker and Earth is good, then the Green Positive Earth Condition LEDs will flash and the interlock contacts will close. The product transfer operation can now take place. Newson Gale Newson Gale X C. If the connection between the Road Tanker and Earth is broken during the transfer operation, then the Red Negative Earth Condition LED will show and the interlock contacts will open. ERII Newson Gale NewsonGale Reel D. On completion the Earthing Clamp should be removed from the road tanker and the clamp-cable should be carefully rewound onto the reel. The Red Negative Earth Condition LED will show. Clamp www.newson-gale.com 11

Operation With system switched to Single-Mode using the Mode Selector Key Switch Note: The Earthing Clamp should be fitted prior to fitting hoses, or any other operation. ERII Newson Gale NewsonGale Reel A. In the normal "rest" state, with the Earthing Clamp not attached and the clamp-cable wound onto the reel, the Red Negative Earth Condition LED will be showing. Clamp Newson Gale Newson Gale B. Attach the Earthing Clamp onto the conductive plant item at a suitable point and ensure that the pointed contacts are positively located. If the connection to the plant item and Earth is good, then the Green Positive Earth Condition LEDs will flash and the interlock contacts will close. The product transfer / mixing operation can now take place. Newson Gale Newson Gale X C. If the connection between the plant item and Earth is broken during the transfer operation, then the Red Negative Earth Condition LED will show and the interlock contacts will open. ERII Newson Gale NewsonGale Reel D. On completion the Earthing Clamp should be removed from the plant item and the clamp-cable should be carefully rewound onto the reel. The Earth Condition LED will show. Red Negative Clamp 1 www.newson-gale.com

Earth-Rite ERII Dimensions Earth-Rite II Exd Controller FIXING HOLE DIAMETER D = 7 mm E - 140 mm A - 19 mm F - 140 mm with window C - 13 mm B - 155 mm PRODUCT DESCRIPTION MAIN DIMENSIONS A mm B mm C mm FIXING DIMENSIONS EARTH / GROUND CABLE TERMINAL 140mm 83mm 8mm 114mm 57mm D mm E mm F mm Exd Earth-Rite II Controller 19 155 13 7 140 140 FIXING SLOTS = 10mm x 0mm CLEARANCE 300mm www.newson-gale.com 13

Earth-Rite II - AC Technical Specification Monitoring Unit Power supply 30/40V 50Hz system (Supply voltage range: 16V to 50V) 110/10V 50Hz system (Supply voltage range: 108V to 15V) Power rating 10 watt Ambient temperature range o o -40 C to +55 C Ingress protection IP66 Weight 4.5 kgs (nett) Construction Copper-free cast-alloy Certification Ex d[ia] IIC T6 Gb(Ga) Ex tb IIIC T80 C IP66 Db Ta = -40 C to +55 C Monitoring circuit Intrinsically safe Minimum tanker capacitance 1000 pf Operational series ground resistance </= 10 Ohm Output Relay contact rating off voltage free change-over switch contacts, 50Vac, 5A, 500VA max resistive 30Vdc, A, 60W max resistive Cable entries 7 x M0 ( x plugged) VESM0 Cable Reel Enclosure Electrical Transfer Method Cable Conductors Clamp Cable Connection Earthing Clamp Clamp design Body Painted Steel Silvered Slip-Rings x 1.0 mm copper 15.m -Core Cable terminated in Quick Connect pole with tungsten carbide contacts Stainless steel NB: In line with our policy of continual product development, we reserve the right to alter specifications at any time. 14 www.newson-gale.com

User instructions in compliance with IEC 60079-0:007 clause 30 The following instructions apply to the Earth-Rite II Earth Monitoring Unit, Ex d[ia], covered by certificate numbers IECEx SIR 09.0018 and Sira 09ATEX047. Certification Label Detail Instructions for safe selection, installation, use, maintenance and repair The equipment may be used in zones 1,, 1 and with flammable gases and dusts. The equipment may be used in the presence of flammable gases and vapours with apparatus groups IIC or IIB or IIA and with temperature classes T1 or T or T3 or T4 or T5 or T6. The equipment may be used in the presence of flammable dusts, powders and flyings, conductive or non-conductive, the only limitation being the maximum external surface o temperature of 80 C. The equipment is certified for use in ambient temperatures in o o the range of 40 C to +55 C and should not be used outside this range. The equipment is to be installed by suitably trained personnel in accordance with the applicable code of practice (typically IEC/EN 60079-14). Protective insulated plugs are fitted to help prevent the supply cables from being connected to the wrong terminals. Check which supply voltage is required and remove the plug from that terminal only. No user adjustment is required. Regular periodic inspection of the equipment should be performed by suitably trained personnel in accordance with the applicable code of practice (typically IEC/EN 60079-17) to ensure it is maintained in a satisfactory condition. The equipment is not intended to be repaired by the user. Repair of the equipment is to be carried out by the manufacturer, or their approved agents, in accordance with the applicable code of practice. The equipment contains no user-replaceable parts. nnnn Newson Gale Ltd Nottingham NG4 JX UK Earth Rite ER II II (1) GD DO NOT OPEN WHEN AN EXPLOSIVE GAS AND/OR DUST ATMOSPHERE MAY BE PRESENT Um = vvvvv Model Number: mmmmm dddd Serial Number: YY/XXXXX Control Drg. CCCCCC Intrinsically safe output at PL3/PL4 combined: Tri-Mode: Uo = 8.61V, Io = 0.060A, Po = 0.19W, Co = 1.0µF, Lo = 9868µH NOTE: vvvvv = UM = 15/50Vac mmmmm = RTRMEA ddddd = RTR YY = Year of Manufacture XXXXX = Specific Serial Number CCCCC = ERII-Q-0946- Al Sira 09ATEX047 Ex d[ia] IIC T6 Gb(Ga) Ex tb IIIC T80 o C IP66 Db Ta = -40 o C to +55 o C IECEx SIR 09.0018 Verification of the Static Earthing Point The system monitors the static dissipation path, from the object to which the Static Earthing Clamp or lead is connected to, as far as the Static Earthing Point. It is the responsibility of the end user to provide the Static Earthing Point and ensure that it is suitable for dissipating electrostatic charges. Reference to ATEX 95, ATEX 137, EN 60079-14, IEC 60079-3, or other equivalent international standard, will give guidance on the installation of a suitable Static Earthing Point. The above does not apply to any system used to monitor a bond connection only. IF YOU HAVE ANY QUERIES REGARDING THE ABOVE POINTS THEN PLEASE CONTACT NEWSON GALE WITHOUT DELAY. www.newson-gale.com 15

Ex scheduled drawing: DO NOT modify without approval from Sira Certification, Approved on behalf of Sira Certification by D W Holton, 05 October 011 16 www.newson-gale.com

READ MANUAL BEFORE COMMENCING WITH INSTALLATION Earth-Rite II VESM0 Static Discharge Grounding Reel Installation & Operating Instructions Model: VESM0 Newson Gale Static Discharge Grounding Reels are used to prevent the build-up of electrostatic charges on plant items during the transfer, mixing and handling operations involving flammable liquids and powders. The VESM0 reel is a spring operated automatic retrieve reel containing a - core Hytrel sheathed cable and silver coated slip-rings. The reel is constructed of steel, with a hard-wearing painted finish. A ratchet lock provides operator control over cable pay-out. The cable is fitted with a spring dampened bump stop. The weight of the reel, including clamp and 15m cable, is 11.5kg (5lb). The VESM0 Grounding Reel is approved, under ATEX, for use in Zones 1, 1 and (CAT and 3), and may be connected to any Earth-Rite Grounding System with certified Intrinsically Safe monitoring circuit output. The unit is also suitable for use in conjunction with Earth-Rite systems with certified Intrinsically Safe monitoring circuit outputs according to North American NEC Class/Division approvals. Operation Engage the ratchet lock by pulling cable out to the required length and letting it retract SLOWLY until the ratchet lock engages. To release the lock, pull cable out a short distance and allow it to slowly retract. DO NOT allow the cable to retract in an uncontrolled manner. Always guide cable back to reel. Failure to do so could result in damage to the reel, or personal injury. Always operate the reel within the cable size and length and spring tensioning limits for which it was intended. Two wraps of cable should remain on the reel at maximum extension to avoid excessive tension on the cable entrance watertight grommet. The spring should not be wound to its last two turns at maximum payout to avoid overstressing the spring, thus reducing its life or damaging the reel. Keep the reel and cable clean to avoid excessive wear and damage. Arrange for maintenance service if damage is found on the cable or reel. Cable should be fully retracted when not in service to maximize spring life. EARTH / GROUND CABLE TERMINAL 140mm 83mm 8mm 114mm 57mm FIXING SLOTS = 10mm x 0mm CLEARANCE 300mm www.newson-gale.com 17

INSTALLATION Mount the reel securely, in the vertical plane as per sketch. To minimise wear on cable and cable guide, and for best results, reel should be mounted in direct line with work so that the cable is pulled out as straight as possible during use avoid pulling the cable out of the reel at an angle. For best operation mount the reel at eye level. Mounting The Reel Standard Mounting The reel may be mounted by bolting the base to any flat surface which is structurally sound enough to support it and the forces of winding and unwinding the cable. The spool drum must rotate on a horizontal axis. The reel should be oriented so that the cable extends perpendicular to the rotation of the spool. The total cable deflection should not exceed 30 degrees. If deflection is constant to either side of the reel and operation is impaired, re-mount the reel. If the angle of deflection exceeds 30 degrees a Pivot Base should be used, otherwise excessive cable wear and unreliable operation will result. GROUNDING Ensure reel housing is securely connected to Earth / Ground using a 4mm (# 1 ga) cable and the screw and crimp connector provided. MONITORING CONNECTIONS MAINTENANCE All springs and bearings are lubricated for life at the factory. Additional lubrication should not be required. Do not apply any lubricants or solvent cleaning agents to slip ring, brush or insulator surfaces. The slip-rings should be inspected and cleaned as part of the planned routine maintenance schedule. Periodically check the cable for wear. Planned Maintenance Periodically check the reel for any loose or missing fasteners. Tighten or replace as necessary. NOTE: Do not over tighten, this will cause fasteners to snap. Inspect cable for damage or wear which could make it unsafe to use. Top-up the static dissipative coating on the cable guide rollers using Techspray 1756 Licron Crystal spray. The slip ring assembly should be checked periodically as follows: 1 - Clean to remove dust and dirt from the slip ring housing area and all slip ring assembly and brush surfaces. - Brushes should be centered on slip rings and brush springs should be seated in the terminal grooves. Terminal screw connections should be tight. Check for excessive brush wear. The reel is supplied with a 3m length of -core Hytrel sheathed cable for connection to the Newson Gale intrinsically safe monitoring circuit. The reel may be connected to any Newson Gale monitoring device in accordance with the monitoring unit installation manual and any supplementary instructions. EARTH / GROUND CABLE TERMINAL THE BODY OF THE REEL MUST BE CONNECTED TO EARTH / GROUND IN ORDER TO PREVENT THE REEL BODY BECOMING ELECTROSTATICALLY CHARGED 18 www.newson-gale.com

EXPLODED VIEW Feeder Cable Water Tight Seal Hex Head Cap Screw Lock Washer Shaft Coupling Ratchet Pawl Assembly Guide Arm Base Assembly Roller Guides Spring Motor Housing Inner Gasket Electrical Connections Slip Ring Assembly Bump Stop Water Tight Seal Drum Outer Gasket Flange Screws (10-3 x 3½ in.) & Lockwasher (#10 Int. Tooth) 4 Req. Ea. Outer Flange www.newson-gale.com 19

PIVOT BASE MOUNTING (Optional Accessory) The VESM0 Reel can be furnished with a pivot base to allow the reel to rotate and keep the extended cable perpendicular to the application. The Pivot Base will rotate up to 345 degrees. Travel can be limited to 90 degrees, 180 degrees, or 70 degrees by installing an additional roll pin in the appropriate available hole. When a pivot base is used the reel must be mounted horizontally ("ceiling" or "floor" mounted). The Roller Guide should be mounted to require the cable to travel perpendicular to the axis of rotation. This will guard against cable twisting and ensure effective swivel action from the pivot base. The safety of any system incorporating the equipment referred to in this manual is the responsibility of the installer of the system. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Any warranty is made void if the equipment is not installed, or used, in accordance with the manufacturers instructions. "Warning: Do not disassemble the spring motor, or spring housing, for any reason. Serious personal injury could result. This cable reel is equipped with springs under tension." United States Newson Gale Inc 460 Faraday Avenue Bldg C Jackson, NJ 0857 USA +1 73 961 7610 groundit@newson-gale.com United Kingdom Newson Gale Ltd Omega House Private Road 8 Colwick, Nottingham NG4 JX, UK +44 (0)115 940 7500 groundit@newson-gale.co.uk Deutschland Newson Gale GmbH Ruhrallee 185 45136 Essen Deutschland +49 (0)01 89 45 45 erdung@newson-gale.de South East Asia Newson Gale S.E.A. Pte Ltd 136 Joo Seng Road, #03-01 Singapore 368360 +65 6704 9461 ngsea@newson-gale.com www.newson-gale.co.uk NG UK ATEX RTR Exd AC + VESM0 ISM 1116 R1