AccuTrak Rotary Position Monitors Explosionproof NEC Fully integrated and encapsulated rotary valve position monitors that are certified for use in explosive atmospheres Features Touch set cams are hand adjustable, spring loaded and self-locking providing quick calibration of position switches and sensors. Terminal strips are pre-wired and numbered with generous working space for ease of use. Strong durable Beacon TM offers 360 visual indication in a choice of styles and colors. Additional conduit for easy field wiring and mounting accessories as standard. Standardized mounting pattern for easy adaptation to common bracketry. NAMUR shaft output compliant to VDI/VDE 3845 available. Analog position transmitter option. Eliminator option for easy integration of external solenoid valve. Aluminum enclosures with ultra-low copper content (0.2% maximum) ensure robust performance in corrosive environments. Rugged stainless steel enclosures. Technical Data Agency approvals Area classification (NEC 500) Models 2007/5050/9479 Class I, Division 1, Groups C & D/ T6 Ta = 60 C Class II, Division 1, Groups E, F & G/ T6 Ta = 60 C Model 9479 Class I, Division 2, Groups A,B,C & D/T4 Ta = 60 C Model 5050 Class II, Division 2, Groups E, F & G/T6 Ta = 50 C Model 360/366 Class I, Division 1, Groups A,B, C & D [1] Class II, Division 1, Groups E, F & G [2] Enclosure standards (ANSI/NEMA 250) All enclosures Type 4, 4X Switches Model 2007 V3 (SPDT) & DPDT mechanical / GO Model 5050 Pepperl + Fuchs model NJ2-V3-N Model 9479 Magnum / MagPAC Models 360/366 V3 (SPDT) & DPDT mechanical / Magnum Enclosures Models 2007/5050/9479/360 Aluminum Models 2007/9479/366 Stainless steel General Application AccuTrak position monitors are ideal for manual and automated rotary valves. They provide consistent and accurate valve monitoring in a compact unit which can be mounted directly or via a valve actuator. [1] Groups C & D only with eliminator conduit option [2] Groups F & G only with eliminator conduit option www.westlockcontrols.com Copyright Westlock. All rights reserved. VCTDS-02702-EN 16/08
33 [ 1.2 9 7 ] 2 8. 5 5 [ 1.1 2 4 ] 13.9 [ 0. 5 4 6 ] 6. 3 5 [ 0. 2 50] 15 7.7 3 [ 6.2 10 ] 8. 8 9 [ 0.350] 4.98 [ 0. 19 6 ] 25.7 [ 1. 0 1 1 ] 1 5 5.40 [ 6. 1 18 ] 3 5.36 [1. 3 9 2 ] 77.70 [3. 059 ] 25.7 [ 1. 0 1 1 ] 17.67 [ 0.6 9 6 ] AccuTrak Rotary Position Monitors Explosionproof NEC Models 2007/5050/9479 dimensions 98.85 [3.892 ] 162.62 [6.402] Conduit entry x4 max See options table on housing machining drawing for details 57.15 [2.250 ] 28.56 [1.124 ] External earth (M5) View on underside Ø64 [2.523] 4 holes 5/16-18 UNC x 0.50 deep or M8 x 1.25P x 8 deep 6.35 A/F [0.250] Ø 9.525 9.513.3750.3745 [ ] Ø 9.525 9.513.3750.3745 [ ] Ø4.85 [0.191] 3.98 3.93 A/F.1567 [.1547] NAMUR shaft arrangement Standard shaft arrangement 56.11 [2.209] Dimensions in inches, where available metric dimension (mm) in parentheses Technical specifications Materials of construction Enclosure Aluminum with powder coat finish Shaft and hardware Stainless steel Bushing Oil impregnated bronze Beacon visual indicator Co-polyester Drive shaft Westlock standard Double-D with ¼ A/F NAMUR standard NAMUR standard VDI/VDE 3845 Available switches Model 2007 V3 mechanical switches, SPDT DPDT (Form CC) mechanical switches GO switches Model 5050 Pepperl + Fuchs model NJ2-V3-N Model 9479 Magnum (hermetically sealed proximity type) MagPAC bifurcated switch pack Options Models 2007/9479 Stainless steel enclosure Models 2007/9479 4-20 ma position transmitter 1. See selection guide for standard conduit entries 2. See switches & sensors data sheet for further information 3. A specialist eliminator fitting is available for the mounting of an aftermarket solenoid valve 4. Please consult your sales office for any other requirements 2
AccuTrak Rotary Position Monitors Explosionproof NEC Models 360/366 dimensions 3.19 [81.01] Typical 30 Typical Conduit size available: 3/4 NPT Conduits to be specified at time of order 5.00 [127.41] Cover locking screw *5.25 [133.29] *7.44 clearance for Cover removal.29 [7.27].54 [13.75] 3.07 [77.92] 2.26 [57.35].3750 Ø.3745.248.246 Across flat Beacon fixing M6 3.15 2.25 [57.15] Sq See detail A 4X M8 x 1.25P thru External earth M6 Conduit B See NAMUR shaft detail.3750 Ø.3747 Conduit A Conduit C.59 [14.99].255 [6.47] 3.10 1.18 [78.33] [29.97] 4.41 5.24 [111.81] [132.90].157 [3.98].35 [8.89].124.123 Detail A Scale 2:1 Standard shaft detail 4X ø.22 thru 1.13 [28.57] 1.57 [39.87] 6.54 [166.16] Ø.191 [4.85] Detail A Scale 2:1.157 [3.98] Detail B Scale 2:1 NAMUR shaft detail.078 [1.98] Dimensions in inches, where available metric dimension (mm) in parentheses Technical specifications Materials of construction Enclosure Model 360 Aluminum with powder coat finish Model 366 Stainless steel with electropolished finish Shaft and hardware Stainless steel Bushing Oil impregnated bronze Beacon visual indicator Co-polyester Drive shaft Westlock standard Double-D with ¼ A/F NAMUR standard NAMUR standard VDI/VDE 3845 Available switches V3 mechanical switches, SPDT DPDT (Form CC) mechanical switches Magnum, SPDT hermetically sealed switches, with tungsten contacts Magnum, SPDT hermetically sealed switches, with rhodium contacts Options Models 360/366 4-20 ma position transmitter 1. See selection guide for standard conduit entries 2. See switches & sensors data sheet for further information 3. A specialist eliminator fitting is available for the mounting of an aftermarket solenoid valve 4. Please consult your sales office for any other requirements 3
AccuTrak Explosionproof Rotary Position Monitors Model 2007 Selection Guide Base model 2007 Aluminum enclosure Shaft output S N Standard (double-d with ¼ Flats) NAMUR Beacon BY RG FE AB AR B1 B3 B5 B7 B9 FC BM2-Y (standard) BM2-RG (Red Closed/Green Open) BM2-Y-FE (French/English) BM2-B BM2-R BM3-1 BM3-3 BM3-5 BM3-7 BM3-9 Flat cover Conduit 2B 4B 2E 4E 4F Two ¾ NPT (F) Four ¾ NPT (F) One ¾ NPT (F) and one ½ NPT (M) eliminator fitting Three ¾ NPT (F) and one ½ NPT (M) eliminator fitting Two ¾ NPT (F) and two ½ NPT (M) eliminator fittings Position switches 2M02 4M02 6M02 2M04 4M04 2M03 4M03 Two SPDT mechanical switches - 8 pt. TS Four SPDT mechanical switches - 16 pt. TS Six SPDT mechanical switches - 24 pt. TS Two DPDT mechanical switches - 16 pt. TS Four DPDT mechanical switches - 24 pt. TS Two SPDT GO switches - 12 pt. TS Four SPDT GO switches - 16 pt. TS Analog position transmitter 2007 N BY 2B 2M02 00 = Model number 2007NBY2B2M0200 00 CS None 4-20 ma position transmitter (not available with 4M04, 6M02, 2M03, 4M03 switch options) 12 pt. TS w/2m02; 16 pt. TS w/2m04 and 4M02 1. Please contact your sales office for guidance on selecting the best possible combination for your control and monitoring requirements. 2. See Hazardous area classification technical bulletin for further information on global standards. 3. For stainless steel enclosure, please add 00124 to the end of your part number built with the selection guide above. 4
AccuTrak Explosionproof Rotary Position Monitors Model 5050 Selection Guide Base model 5050 Aluminum enclosure Shaft output S N Standard (double-d with ¼ Flats) NAMUR Beacon BY RG FE AB AR B1 B3 B5 B7 B9 FC BM2-Y (standard) BM2-RG (Red Closed/Green Open) BM2-Y-FE (French/English) BM2-B BM2-R BM3-1 BM3-3 BM3-5 BM3-7 BM3-9 Flat cover Conduit 2B 4B 2E 4E 4F Two ¾ NPT (F) Four ¾ NPT (F) One ¾ NPT (F) and one ½ NPT (M) eliminator fitting Three ¾ NPT (F) and one ½ NPT (M) eliminator fitting Two ¾ NPT (F) and two ½ NPT (M) eliminator fittings Position switches 2M08 Two P+F sensors model NJ2-V3-N - 8 pt. TS Analog position transmitter 00 Not available 5050 N BY 2E 2M08 00 = Model number 5050NBY2E2M0800 1. Please contact your sales office for guidance on selecting the best possible combination for your control and monitoring requirements. 2. See Hazardous area classification technical bulletin for further information on global standards. 5
AccuTrak Explosionproof Rotary Position Monitors Model 9479 Selection Guide Base model 9479 Aluminum enclosure Shaft output S N Standard (double-d with ¼ Flats) NAMUR Beacon BY RG FE AB AR B1 B3 B5 B7 B9 FC BM2-Y (standard) BM2-RG (Red Closed/Green Open) BM2-Y-FE (French/English) BM2-B BM2-R BM3-1 BM3-3 BM3-5 BM3-7 BM3-9 Flat cover Conduit 2B 4B 2E 4E 4F Two ¾ NPT (F) Four ¾ NPT (F) One ¾ NPT (F) and one ½ NPT (M) eliminator fitting Three ¾ NPT (F) and one ½ NPT (M) eliminator fitting Two ¾ NPT (F) and two ½ NPT (M) eliminator fittings Position switches 2M06 2M12 2M13 4M06 4M12 6M06 6M12 Two SPDT Magnum switches with tungsten contacts - 8 pt. TS Two SPDT Magnum switches with rhodium contacts - 8 pt. TS MagPAC module (SPST bifurcated switches with LEDs) Four SPDT Magnum switches with tungsten contacts - 16 pt. TS Four SPDT Magnum switches with rhodium contacts - 16 pt. TS Six SPDT Magnum switches with tungsten contacts - 24 pt. TS Six SPDT Magnum switches with rhodium contacts - 24 pt. TS Analog position transmitter 00 CS None 4-20 ma position transmitter (not available w/6m06 and 6M12) 12 pt. TS w/2m06 and 2M12 16 pt. TS w/4m06 and 4M12 9479 N BY 2B 2M12 00 = Model number 9479NBY2B2M1200 1. Please contact your sales office for guidance on selecting the best possible combination for your control and monitoring requirements. 2. See Hazardous area classification technical bulletin for further information on global standards. 3. For stainless steel enclosure, please add 00124 to the end of your part number built with the selection guide above. 6
AccuTrak Explosionproof Rotary Position Monitors Model 360/366 Selection Guide Base model 360 366 Aluminum enclosure Stainless steel enclosure Shaft output S N Standard (double-d with ¼ Flats) NAMUR Beacon BY RG BM2-Y (standard) BM2-RG (Red Closed/Green Open) Conduit 2B 3B 2E 3E Two ¾ NPT (F) Three ¾ NPT (F) (360/366 only) One ¾ NPT (F) and one ½ NPT (M) eliminator fitting Two ¾ NPT (F) and one ½ NPT (M) eliminator fitting Position switches 2M02 2M04 2M06 2M12 4M02 4M06 4M12 Two SPDT mechanical switches - 10 pt. TS Two DPDT mechanical switches - 14 pt. TS Two SPDT Magnum switches - 10 pt. TS Two SPDT Magnum switches with rhodium contacts - 10 pt. TS Four SPDT mechanical switches - 14 pt. TS Four SPDT Magnum switches - 14 pt. TS Four SPDT Magnum switches with rhodium contacts - 14 pt. TS Analog position transmitter 360 N BY 2B 2M12 00 = Model number 360NBY2B2M1200 00 CS None 4-20 ma position transmitter - 10 pt. TS (only available with 2M02, 2M06, 2M12 switch options) 1. Please contact your sales office for guidance on selecting the best possible combination for your control and monitoring requirements. 2. See Hazardous area classification technical bulletin for further information on global standards. 7
www.westlockcontrols.com Westlock. We reserve the right to change designs and specifications without notice. 8