Fixed, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

Similar documents
Automatic, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

C1000 Series Automatic Cap Bank

MEDIUM VOLTAGE METAL ENCLOSED CAPACITOR BANKS

Technical Specification For Outdoor Substation Harmonic Filter Banks

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

Technical Specification for Pole Mounted Capacitor Rack

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

Specification for Medium Voltage Automatic Metal-Enclosed Capacitor Banks. - Solar Plant Application -

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Metal-enclosed medium-voltage power factor correction system

35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. Submit manufacturer's literature and technical data before starting work.

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

Medium Voltage Metal-Enclosed Switches

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

Design Standard. Capacitor Bank. Detailed specifications follow. PART 1 - GENERAL

SWITCHED POWER FACTOR AND *********HARMONIC CORRECTION EQUIPMENT MEDIUM VOLTAGE SECTION 16280E

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

Design Standard. Purpose: Design Standard:

Typical Specification

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

Medium Voltage Metal-Enclosed Switches

15-kV Safefront 200 Amp Primary Capacitor Station Pad-Mounted Outdoor

STANDARD SPECIFICATION FOR PAD-MOUNTED CAPACITOR BANKS FOR 15kV or 25kV APPLICATIONS

Underground Distribution Switchgear

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Indoor or Outdoor 2400 to 14,400 Volts 600 to 14,400 Kvac, 3 Phase, 60 Hz

Metal-enclosed medium voltage power factor correction system

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.

TYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

SECTION PADMOUNT TRANSFORMER - OIL FILLED

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

STANDARD SPECIFICATION FOR TYPE PLD LIVE-FRONT/DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV A. General

DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV

35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses

Horizontal Circuit Switchers

EMPAC Metal enclosed capacitor bank for wind applications

Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks

Three-Phase Pole Mounted Recloser

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

15-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 140 Amp (Max) Clip-Mounted Current-Limiting Fuses

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

Design Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak

Underground Distribution Switchgear

Solar Power Switchgear & Energy Storage Renewable Energy Systems

35-kV Safefront 200 Amp SuperWell Primary Metering Station Pad-Mounted Outdoor

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

University of Houston Master Construction Specifications Insert Project Name

MATERIAL SPECIFICATION ELECTRIC OPERATIONS ORGANIZATION. M3902 ****Supercedes BECo Standard E and ComElectric Spec ****

Horizontal Circuit Switchers

University of Houston Master Construction Specifications Insert Project Name

Specification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION

SWITCHGEAR DIVISION PRODUCT PROFILES

SWITCHGEAR DIVISION PRODUCT PROFILES

Product Specifications for Aluminum Vertical Break Switches

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

S&C Manual PME Pad-Mounted Gear

15-kV Live Terminal Primary Metering Station Pad-Mounted Outdoor

Publication No.: PSG

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

MATERIAL STANDARD ELECTRIC OPERATIONS ORGANIZATION. ****Supercedes BECo Standard E and ComElectric Spec ****

100 / 110 DRYWELL FUSE SPECIFICATION

C. System Design and Performance Requirements

Volt Instrument Transformers

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

Underground Distribution Switchgear

Kuhlman Electric Corporation Volt Instrument Transformers

35-kV Safefront 200 Amp Primary Metering Station Pad-Mounted Outdoor

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

INDEX Welcome 1.2 Contacting Powergrid Solutions, Inc. 1.3 Terms Of Usage 1.4 Product Codes and Descriptions

CITY OF MARYVILLE ELECRIC DEPARTMENT Maryville, Tennessee SPECIFICATIONS FOR 15KV POWER CIRCUIT BREAKERS. September 2018

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

SECTION MOTOR CONTROL

Guide Form Specification for Medium Voltage Automatic Metal-Enclosed Harmonic Filter System. - Mining Application -

15-kV Safefront 200 Amp Source Isolated Cable Switching Station Pad-Mounted Non-Fusible

Introduction. Features. Intelligent Technologies Motor Control Center Structures

GE 8000-Line Motor Control Centers

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Climas y Proyectos Leyco, S.A. de C.V.

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

SECTION PANELBOARDS

STANDARD SPECIFICATION FOR LIVE-FRONT 15KV AND 25KV PSI/II PAD-MOUNTED SWITCHGEAR

Transcription:

Fixed, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification 1. General 1.1 This specification is for a fixed, medium-voltage, padmounted, three-phase power capacitor bank consisting one (1) step of kvar at kv RMS and Hertz. 1.2 All of the power capacitor bank components are to be housed in a compartmentalized steel enclosure. The power capacitor bank shall come fully assembled and ready for use. All exceptions to this specification shall be clearly stated in your bid. If no exceptions are taken, the bid should include the phrase No Exceptions Have Been Taken! 1.3 The electrical ratings for the power capacitor shall be compatible with the following power system parameters. Basic Lightning Impulse Insulation Level (BIL) Maximum System Voltage Nominal System Voltage kv crest kv RMS kv RMS Symmetrical Short Circuit Current Available at the Harmonic Filter Bank Line-to-Ground Three-Phase 2. Codes and Standards ka RMS ka RMS The power capacitor bank shall meet or exceed the applicable requirements of the latest editions of the following codes and standards. ANSI Standard C57.12.28-1988, Pad Mounted Equipment Enclosure Integrity ANSI Standard Z535.4-01 July 2002, Product Safety Label Standard Applicable portions of ANSI Standard C57.21-1990 IEEE Standard Requirements, Terminology and Test Code for Shunt Reactors Rated Over 500 kva Applicable portions of Article 710 in the National Electrical Code Article 460 of the National Electrical Code NESC Standards UL-347, High Voltage Industrial Control Equipment UL-508, Industrial Control Panels, Issue Number 2, October 1993 UL-50, Standard for Enclosures for Electrical Equipment 3. Enclosure Construction 3.1 The assembler of the power capacitor bank must also be the manufacturer of the enclosure. This will ensure the highest degree of control with respect to critical enclosure manufacturing processes such as cleaning, painting, priming, surface preparation and welding. 3.2 The enclosure shall be a single compartmentalized unit meeting the requirements of NEMA type. All components shall be accessible and removable from "the front or rear of the enclosure. The front of the enclosure shall have a dead-front compartment and a control system compartment. The rear of the enclosure shall be a live-front design. Equipment layout and access shall be as follows: Control System Compartment This compartment contains the control system components and the equipment nameplate. The compartment shall be accessible from the front without having to open the deadfront compartment. The compartment shall be completely isolated from the dead-front and live-front compartments. The compartment shall be equipped with a floor. Dead-Front Compartment This compartment shall be equipped with a hinged window that allows for inspection of the blown fuse indicators and when opened, provides access to the fuses. The window shall be fabricated from an impact resistant, ultraviolet resistant material. This compartment shall not be equipped with a floor. Loop Design: Contains a full-width, tin-plated copper ground bus; six (6) bushing wells and six (6) stainless steel parking stands. CP-1 NEMA Standard on Shunt Capacitors IEEE Standard 1036-1992, IEEE Guide for Application of Shunt Power Capacitors

Radial Design: Contains a full-width, tinplated copper ground bus; three (3) bushing wells and three (3) stainless steel parking stands. would permit entry of a wire into the enclosure. Bifolding doors may be fastened with a single padlock and penta-head bolt. Access, however, shall be such that a positive and separate action must be taken to open the second door only after the first access door has been opened. Live-Front Compartment This compartment contains a full-width, tinplated copper ground bus, arresters, control power transformer, main fuses, power capacitor units, stage switches and transient inrush reactors. These components shall be removable from this compartment. This compartment shall be equipped with a floor. 3.3 The enclosure shall be fabricated from twelve (12) gauge, hot-rolled steel, pickled and oiled, ASTM A569 Type 1010. The roof shall be cross-kinked or gabled to allow for watershed. 3.4 The doors shall be flush and removable in the open position. They shall be equipped with stainless steel hinges, stainless steel hinge pins, stainless steel penta-head bolts, stainless steel penta-head threaded inserts and three-point latching handles. The handles shall be pad lockable. All doors shall be equipped with stays to hold doors in the open position. 3.5 The dead-front and live-front compartment doors shall be fastened with a device that requires a pentahead tool to permit unlatching the door only after the padlock has been removed. The penta-head bolt shall be coordinated such that the padlock may not be inserted into the hasp until the door is fully latched and the penta-head device is secured. A minimum of one (1) penta-head bolt and padlocking means shall be provided for each of the front-compartment and rear-compartment doors. The penta-head bolt shall be surrounded by a non-rotating guard or shall be recessed such that the penta-head bolt can be engaged only with the proper tools. The dimensions of the penta-head bolt and non-rotating recess shall comply with ANSI Standard C57.12.28. The pentahead bolt shall not be readily removable during normal operation of the doors and if removed or disengaged there shall be no holes remaining that 3.6 Removable steel lifting plates shall be located at each corner of the enclosure base. 3.7 Ventilation louvers shall be located on the sides of the enclosure and shall be backed with a screen. Air filters shall have washable, aluminum mesh elements and they shall be serviceable from outside of the enclosure. 3.8 All fasteners and associated hardware shall be stainless steel. Externally accessible hardware that is used to support electrical components or switchoperating mechanisms that are housed in the enclosure shall be tamper-proof. 3.9 All non-ventilated compartments shall be equipped with strip heaters. The strip heaters shall be controlled with a thermostat. 3.10 If required, a fan or ventilator shall be supplied. The fan or ventilator shall be controlled with a thermostat. 3.11 Each door of the enclosure shall be equipped with self-adhesive vinyl warning signs that comply with ANSI Z535.4 Product Safety Label Standard dated July 1, 2002. The incoming compartment sign shall include signs that state the following information: Electric arc flash hazard. Will cause severe injury or death. Wear proper protective equipment before opening or performing diagnostic measurements while energized. (See NFPA 70E) 2

3.12 The power capacitor bank shall have a corrosion-resistant nameplate that contains the following information: Basic Lightning Impulse Insulation Level (BIL) Bank Configuration Effective Capacitive Reactive Power Hazardous Flash Boundary PPE Requirements and Incident Energy (calories per cm 2 ) at eighteen (18) inches Maximum System Voltage Nominal System Voltage System Frequency The nameplate shall be secured to the enclosure with rivets or screws. 3.13 The enclosure shall be prepared and painted with a polyester powder coating using the procedure specified below. The paint color shall be either ANSI 61 or Munsell Number 8.3G 6.10/0.54 (gray), ANSI 70 or Munsell Number 5BG 7.0/0.4 (gray) or Munsell Number 7GY 3.29/1.5 (green). Surface Preparation The following five-stage washer and pre-treatment procedure shall be used. Stage One: HAZARDOUS VOLTAGE. Contact may cause electric shock or burn. Turn off and lock out system power before servicing. A heated heavy-duty alkaline cleaner shall be applied to the substrate to remove dirt, oils and other contaminates. Stage Three: Stage Four: Stage Five: Paint Coating Primer: Top Coat: alkali that is remaining on the substrate after stage one. The rinse shall be continuously monitored for water quality. Additional overflow water shall be automatically added if the conductivity exceeds a specified value. This surface shall be converted to an iron phosphate coating. The iron phosphate coating improves paint adhesion and also increases the corrosion resistance of the substrate. An ambient temperature city water rinse shall be used to stop the iron phosphate conversion process and remove excess iron phosphate from the surface of the substrate. The final rinse in this stage shall apply fresh city water to the substrate before it enters the final stage. This stage shall apply a polymeric coating, which seals the iron phosphate coating and provides additional corrosion protection. A zinc rich epoxy coating shall be applied to maximize corrosion resistance. The minimum thickness of this coating shall be 2 mils. A polyester triglycidal isocyanurate (TGIC) topcoat shall be applied. The minimum thickness of this coating shall also be 2 mils. Weathering of the polyester TGIC is comparable to polyurethane. However, the TGIC coating provides superior edge coverage and maintains excellent mechanical properties with respect to film thickness. The result is excellent performance with respect to both mechanical stability and weathering. Stage Two: An ambient temperature city water rinse shall be used to remove any 3

3.14 The manufacturer shall supply written documentation that the applied coating meets or exceeds the tests specified in ANSI Standard C57.12.28-1988. 4. Main Fuses 4.1 The power capacitor bank shall be equipped with current-limiting fuses. The main fuses shall have a short circuit current interrupting capacity that meets or exceeds the available short circuit current at the point where the power capacitor bank is connected to the electrical system. 4.2 The main fuses shall be equipped with blown fuse indicators. The blown fuse indicators shall be visible through a hinged window located in the dead front compartment. The window shall be fabricated from an impact resistant, ultra violet resistant material. The window shall allow for hot-stick replacement of the fuses after the power connectors have been disconnected and placed on the parking stands. 5. Arresters 5.1 The power capacitor bank shall be shall be equipped with heavy-duty distribution arresters. The maximum continuous operating voltage capability (MCOV) of the arrester shall be specified by the power capacitor bank manufacturer. 6. Transient Insrush Reactors, Optional 6.1 Each power capacitor stage shall be equipped with air-core, single-phase, transient inrush reactors. The transient inrush reactor shall limit the rate-of-rise of the power capacitor stage inrush current (di/dt) to 3.6 x 107 amperes per second. Calculations shall be provided to confirm the manufacturer claims. 6.2 The transient inrush reactor shall have a minimum continuous current rating of 135% of the nominal current rating for the power capacitor stage. When expansion capability is offered, the minimum continuous current rating for the transient inrush reactor shall be 135% of the nominal current rating for the maximum capacity of the stage. 6.3 The manufacturer of the power capacitor bank shall certify that the maximum average winding temperature rise in an ambient temperature of 46 C does not exceed the limiting temperature for the insulation system used in the transient inrush reactor. The certification shall be obtained from heat run data for the transient inrush reactor. The heat run shall be witnessed by a nationally recognized testing laboratory (NRTL). 6.4 The manufacturer of the power capacitor bank shall certify that the basic lightning impulse insulation level (BIL) for the transient inrush reactor is consistent with the basic lightning impulse insulation level (BIL) for the power capacitor bank. The certification shall be obtained from impulse tests made on the actual transient inrush reactor or from impulse tests on a transient inrush reactor of similar construction. 7. Stage Switch 7.1 The power capacitor bank shall be controlled by either three (3) single-phase vacuum switches or one (1) three-phase vacuum switch that has been designed and tested for power capacitor switching. The stage switch shall be tested in accordance with ANSI Standard C37.66. 7.2 The stage switch shall be equipped with either motordriven or solenoid-driven operators. 7.3 The stage switch shall be controlled by an OFF/ON/ REMOTE selector switch. In the REMOTE position, a remotely located operator will control the stage switch. In the OFF or ON position, the stage switch will be either OFF or ON, regardless of the state of the remotely located operator. 7.4 The control system shall prevent the stage switch from operating more than once in a five (5) minute period. 8. Power Capacitor Units 8.1 The bank shall be equipped with all-film, low-loss power capacitor units manufactured by Asea Brown Boveri, Cooper Power Systems or the General Electric Company. Depending on the system requirements, power capacitor units can be one-bushing singlephase, two-bushing single-phase or thee-bushing three-phase units. The power capacitor units shall be designed, manufactured and tested to meet or exceed all applicable ANSI/IEEE and NEMA standards. 4

8.2 Each power capacitor unit shall be equipped with internal discharge resistors that will reduce the residual voltage to fifty (50) volts or less five (5) minutes after the power is removed from the unit. 8.3 When the bank has more than one power capacitor unit connected in parallel per phase in a single ungrounded wye configuration then the power capacitor units shall be protected from sustained over-voltages due to a power capacitor unit failure and/or system ground faults by a neutral unbalance detection system. 10.2 The control compartment shall be an integral part of the enclosure, no externally mounted control compartments shall be allowed. The control compartment shall allow for bottom entry of customer control wires without having to enter the medium-voltage compartment. The control compartment shall be equipped with a swing out panel to allow access to the low-voltage control components. The panel shall be equipped with stainless steel hinges and stainless steel hinge pins. 8.4 The power capacitor unit shall be located in a separate compartment from the air disconnect switch and the main fuses. 8.5 The power capacitor units shall be mounted horizontally. Flat Washer Copper Bus Bars Flat Washer Hex Head Bolt 9. Ground and Power Bus 9.1 The ground and power bus shall be silver-plated, round-edge, electrolytic-tough-pitch (ETP) copper, alloy CDA110, hard temper as specified in ASTM B-152 and ASTM B-187. Hex Nut Split-Ring Lock Washer 9.2 The current density in the power bus shall not exceed one thousand (1,000) amperes RMS per square inch. Where expansion capability is required, the power bus shall be rated for the maximum capacity of the power capacitor bank. 9.3 Bolted copper-to-copper connections shall be made with stainless steel hardware. The bolted connections shall be made as shown in the figure to the right. 9.4 The bus shall be braced to withstand the forces that can be developed by the available short-circuit current at the point where the power capacitor bank is connected to the electrical system. 10. Control System 10.1 The low-voltage control system, where practical, shall be isolated from the medium-voltage compartments. The low-voltage control system, where practical, shall be accessible while the power capacitor bank is energized. The control system shall be listed under UL 508A for Industrial Control Panels. 10.3 All low-voltage control wiring that connects to components inside a medium-voltage compartment shall be enclosed in metal conduit or wire troughs that are an integral part of the power capacitor bank enclosure. 10.4 The power capacitor bank shall be equipped with a maintenance interval timer that can be set to alert plant personnel of a maintenance requirement. 5

10.5 The power capacitor bank shall be equipped with a control power transformer. The primary winding of the control power transformer shall be connected between phase B and phase C. The primary winding of the control power transformer shall be equipped with two (2) current-limiting fuses. The secondary winding of the control power transformer shall be equipped with a circuit breaker. 10.6 The power capacitor bank shall be equipped an OFF/ ON/REMOTE selector switch, BANK ON indicator (green lens) and BANK OFF indicator (red lens). A delay-on-operate time of five (5) minutes shall be provided for the stage switch. The manufacturer of the power capacitor bank shall confirm that when switching from the ON position to the REMOTE position, that the stage switch will not be energized in less than five (5) minutes. 10.7 A GFI convenience outlet rated for 15 amperes RMS shall be provided in the control compartment. 11. Quality System 11.1 The manufacturer shall be ISO-9001 certified. 11.2 The manufacturer s quality system shall meet all applicable industry standards. 11.3 The manufacturer shall have on staff a professional engineer with a Bachelors of Science in Electrical Engineering and a minimum of ten (10) years of experience in medium-voltage power systems. 12. Submittals 12.1 The manufacturer of the power capacitor bank shall provide: bill of materials material safety data sheets (MSDS) for all of the dielectric fluids used in the power capacitor bank outline drawings pad drawing power circuit schematic protective relay settings when required short circuit coordination study 13. Bid Requirements 13.1 The manufacturer of the power capacitor bank shall state all exceptions taken to this specification in its bid. If no exceptions are taken, the manufacturer must state that no exceptions have been taken. 13.2 The equipment is to be shipped free on board from the factory. 14. Manufacturer s Requirements 14.1 The manufacturer must offer a minimum warranty period of twelve (12) months from first use or eighteen (18) months from date of shipment. 14.2 The manufacturer must show that they are a regular supplier of fixed, medium-voltage, pad-mounted, three-phase power capacitor banks. Product literature and a list of customers that have purchased similar products shall be supplied upon request. 14.3 The manufacturer shall provide a performance guarantee with respect to harmonic resonance and power factor. 14.4 The manufacturer shall be responsible for control cable and power cable coordination. component data sheets control circuit schematic installation instructions internal layout drawings maintenance instructions 2013 Hubbell Power Systems. All rights reserved. Hubbell, the Hubbell logo are registered trademarks or trademarks of Hubbell Power Systems. All other trademarks are the property of their respective owners. GF_01_023_E_0113