GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

Similar documents
Low Voltage. EasyPact CVS. Moulded-case circuit breakers from 16 to 100 A

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

DPX Thermal magnetic and trip-free switches DPX 3 -I 250

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

DPX earth leakage DPX 3 -I earth leakage

DPX Magnetic only

C60H-DC C curve. Catalogue numbers

DPX Thermal magnetic and trip-free switches DPX 3 -I 160

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

DPX Thermal magnetic and trip-free switches DPX 3 -I 630

PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ)

DPX 630 Thermal magnetic and trip-free switches DPX-I 630

cor Long Run Experience

UTS400 SELECTION GUIDE CATALOG NUMBERING [PRODUCT SELECTION] UTS400 NT ATU 400A 3P LL LSIS UL MCCB

DPX 1600 Electronic release

DRX 125 Circuit breaker (not adjustable)

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

DPX 630 Electronic release

Compact NR630. NR100F to NR630F

DRX 250 B/N/H Circuit breaker (not adjustable)

DPX 160 Thermal magnetic and trip-free switches DPX-I 160

DRX 100 B/N/H Circuit breaker (not adjustable)

DPX Electronic + earth leakage

LV switch-disconnectors. Interpact Merlin Gerin 40 to 2500 A. Catalogue. We do more with electricity

Vistop TM isolating switches 63 to 160A

Low Voltage. Interpact. Switch-disconnectors INS/INV40 to 2500 A. Catalogue 2011

Manual Motor Starters. Meta-MEC

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction

DPX moulded case circuit breakers

C 1. SPECTRONIC SP - Air circuit breakers. Summary. C2. General characteristics. C3. Fixed circuit breaker. C4. Withdrawable circuit breakers

3 - Protection components Motor circuit-breakers

AF40... AF96 3-pole contactors Technical data

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

Technical Information

Product Line Overview. The Most Logically Designed Contact Assembly

DX³ RCCBs - ID 4P up to 100 A

DX³ 4-pole RCBO 6000 A/10 ka

DPX Electronic. Fiche technique : F01362EN/02 Mise à jour le : 15/12/2011 Créé le : 15/06/2011

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

PRICING. Multi 9, Compact, Masterpact, Interpact, and Vigirex Circuit Protection Products. Class 600. October 2004

Technical data for manual motor starters Type MS325

PVGard 600 and 1000 Vdc solar photovoltaic circuit breakers

Thermal magnetic and trip-free switches

RX 3 MCB 4500 A Phase + Neutral, neutral on left side

Multi 9 TM. Catalogue 2017 Multistandard protection for OEM. schneider-electric.com

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

Control Circuit Protection

AF series contactors (9 2650)

TX³ RCCBs 2P up to 100 A

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail

General data 5/37. Overview

PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers

Overview of Low voltage equipment - Moulded-case & Air circuit-breakers

DX³ RCBO 4500/6 ka Phase + Neutral, neutral on left

Selection Guide Motor Control Device Solutions

Phase + Neutral, neutral on left side

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427

The breakers offer thermal-magnetic trip protection according to Z and K characteristics.

PD-Series Ground Fault Circuit Protection

Molded Case Circuit Breaker

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

Siemens AG Price groups PG 14O, 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J

Protection components

Series L9 UL489 Miniature Circuit Breakers

Cutler-Hammer. January 2001

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866)

AF series contactors (9 2650)

Cutler-Hammer Molded Case Circuit Breakers Amperes. January 2001 Vol. 1, Ref. No. [0477] G-Frame

Non-fusible. Non-fusible disconnect switches 16A 3150A, 600VAC A, 1000VDC. International acceptance. Disconnect switches.

Series KTU7 UL489 Molded Case Circuit Breakers

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals

up to 63 A (1 module per pole)

Data Sheet Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches. Ex9 Series - M. na.noark-electric.

Phase + Neutral, neutral on right side

1489-M Circuit Breakers

Molded Case Circuit Breakers Amperes LSIA. LSIG Catalog Number 3-Pole Standard Interrupting Capacity 600V AC Rated V AC 13,950.

Description. Positive safety relays

PowerPact B. Molded case circuit breakers and switches from A

F-Series. Circuit Breaker

Table Type FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1.

Extract of the technical catalogue SACE Tmax XT New low voltage molded-case circuit breakers up to 250A

Product index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4.

F-Series. Circuit Breaker

ACW Molded-Case Circuit Breaker UL 489 Listed

Low voltage moulded case circuit breaker EB2

Product index. 4 - Manual motor protectors. Phone: Fax: Web: -

KT4 Manual Motor Starter

Interrupting Capacity (Symmetrical Amperes) Volts ac (50/60 Hz) Y/ ,000 25,000. Frame Only E2L3600F

Protection Equipment

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489

DMX 3 -I 2500 switch disconnectors

Switchboards Instant Service

Circuit breakers for power distribution A1 Ordering information

New DMX 3. Efficient protection up to A AIR CIRCUIT BREAKERS PRODUCT GUIDE

3. Coils shall be of molded construction

C60H-DC. C curve IEC Direct current (DC) Breaking capacity (Icu) according to IEC Type 1P 110 V 220 V 250 V 440 V 500 V

Transcription:

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics................................... Page 2 Circuit Breakers......................................... Page 4 Motor Circuit Protectors................................... Page 5 Installation and Connections............................... Page 6 Accessories............................................ Page 6 Dimensions............................................ Page 11 Connections........................................... Page 13 Wiring Diagrams........................................ Page 13 Trip Curves........................................... Page 14

General Characteristics General Characteristics Compliance with Standards 600Y/347 Vac 480 Vac Series I 30A LR 69561 Wire #14 #I/0 AWG Cu #8 #I/0 Al 60 PowerPact GJL36030M04 Instantaneous-trip Circuit Breaker 3-Pole Unit o Use 75 C Wire Only Made in France E113389 Torque 50 lb-in 50 lb-in IEC 947-2 50/60 HZ UTE BS VDE CEI UNE EN 60 947-2 Ue 240 V~ 415 V~ 690 V~ Ui 750V Ics 100kA 65kA 6kA Uimp Wire 2 2.5 50 mm Cu 10 50 mm 2 AL Icu 100kA 65kA 6kA 8kV Torque 5,5 N m 5,5 N m G1004A.0 THERMAL-MAG. CIRCUIT BREAKER GJL36050 Series I 600Y/347 Vac 480 Vac 50A Wire #14 #1/0 AWG Cu #8 #1/0 Al 60 40 o C UL/NEMA 50/60 Hz Volts AIR 240 ac 100kA 480 ac 65kA 600Y/347 ac 18kA o Use 75 C Wire Only Made in France Torque 50 lb-in 50 lb-in IEC 947-2 50/60 HZ UTE BS VDE CEI UNE EN 60 947-2 Ue 240 V~ 415 V~ 690 V~ Ui 750V Ics 100kA 65kA 6kA Uimp Wire 2 2.5 50 mm Cu 2 10 50 mm AL Icu 100kA 65kA 6kA 8kV Torque 5,5 N m 5,5 N m Compliance with North American Standards GJL circuit breakers are built and tested in accordance with Underwriters Laboratories Inc. UL 489 Standard. Circuit breakers and their accessories, except where noted, are Listed or Recognized under UL files E63335, E103740, E103955 and E113389. Compliance with International Standards GJL circuit breakers and their accessories comply also with the following international standards: IEC 947-1: general rules IEC 947-2: circuit breakers; In that these standards are applied in most countries, GJL circuit breakers and their accessories comply with European (EN 60947-1 and EN 60947-2) and the corresponding national standards France NF Germany VDE U.K. BS Australia AS Italy CEI Compliance with the Specifications of Marine Classification Organizations GJL circuit breakers have been approved for marine application by the American Bureau of Shipping, Bureau Veritas, Lloyd s Register of Shipping, Registro Italiano Navale, Germanischer Lloyd s and Det Norske Veritas. They comply with the following standards: UL 489 Supplement SA (marine use on vessels over 65 feet in length) US Coast Guard specifications IEC 92-504 and marine specifications: inclination, vibrations, insulation resistance IEC 803 Electromagnetic Disturbance Immunity 2

General Characteristics Tropicalization GJL circuit breakers comply with NF C 63-100 standard level 2 conditions (95% relative humidity at 45 C or 80% at 55 C, hot and humid climate conditions). They also comply with the following standards: IEC 68-2-30 damp heat IEC 68-2-2 dry heat IEC 68-2-11 salt spray IEC 68-2-1 low temperatures Pollution Degree GJL circuit breakers are certified for operation in pollution degree III environments as defined by IEC standard 947 (industrial environments). Environmental Protection GJL circuit breakers take into account concerns for environmental protection. Most components are recyclable and parts are marked as specified in applicable standards. Suitability for Isolation/Positive Contact Indication All GJL circuit breakers are suitable for isolation as defined in the IEC 947-2 Standard: The isolation position corresponds to the O (OFF position) The operating handle cannot indicate the OFF position unless the contacts are open Padlocks may not be installed unless the contacts are open. Installation of a rotary handle or a motor mechanism does not alter the functionality of the position indication system. The isolation function is certified by tests guaranteeing The mechanical reliability of the position indication system The absence of leakage currents Overvoltage withstand capacity between upstream and downstream connections Circuit Breaker Marking Installation in Class II Switchboards All GJL circuit breakers, even when fitted with a rotary handle or a motor mechanism, can be installed through the door of Class II IEC switchboards (as per IEC 664 Standard). Refer to circuit breaker installation instructions prior to installing circuit breaker. Installation requires no special insulation because GJL circuit breakers provide Class II insulation between the front face and all internal circuits. 3

Circuit Breakers Circuit Breakers Table 1: GJL Circuit Breaker Ratings and Interrupting Ratings UL 489 Listed Ratings 1 GJL Circuit Breaker Number of Poles 3 Rated Voltage AC 50/60 Hz 480 V 600Y/347 V Rated Current 40 C 15 100 A 240 Vac 100 ka Interrupting Ratings 480 Vac 65 ka 600Y/347 Vac 18 ka IEC 947-2 and EN 60947-2 Ratings Number of Poles 3 Rated Insulation Voltage Ui 750 V Rated Impulse Withstand Voltage Uimp 8 kv Rated Operational Voltage Ue AC 50/60 Hz 690 V DC 250 V Rated Current (A) In 40 C 15 100 A 220/240 V 100 ka AC 50/60 Hz 380/415 V 65 ka Ultimate Breaking Capacity Icu 660/690 V 6 ka DC 125 V (1 pole) 10 ka 250 V (2 poles in series) 10 ka Service Breaking Capacity Ics (% icu) 50 Utilization Category A 1 Circuit breaker is Listed under UL file E63335 Table 2: Protection Characteristics Protection against overloads and short circuits with a built-in thermal-magnetic trip unit (fixed thresholds). Ratings 40 C 15 A 20 A 30 A 40 A 50 A 60 A 70 A 80 A 90 A Overload Protection Thermal Non-Adjustable Short-Circuit Protection Magnetic Non-Adjustable Hold 600 600 600 600 800 800 800 800 800 Trip 1200 1200 1200 1200 1400 1400 1400 1400 1400 4

Motor Circuit Protectors GJL Circuit Breaker and Motor Circuit Protector Motor Circuit Protectors \ Table 3: GJL Motor Circuit Protector Ratings and Interrupting Ratings UL 489 Recognized Component 1 GJL Motor Circuit Protector Number of Poles 3 Rated Voltage 600Y/347 V Rated Current In 40 C 3 75 A Interrupting Ratings In combination with Telemecanique LC1 contactors and LR2 overload relays IEC 947-2 and EN 60947-2 Ratings Number of Poles 3 Rated Insulation Voltage Ui 750 V Rated Impulse Withstand Voltage Uimp 8 kv Rated Operational Voltage Ue AC 50/60 Hz 690 V Rated Current (A) In 40 C 3 75 A 220/240 V 100 ka Ultimate Breaking Capacity Icu AC 50/60 Hz 380/415 V 65 ka 660/690 V 6 ka Service Breaking Capacity Ics (% icu) 50 Utilization Category A 1 Motor circuit protector is Recognized under UL file E113389 and Certified under CSA file LR 69561. Table 4: Motor Circuit Protector Trip Ranges Ampere Rating Adjustable Trip Range 3 9 33 A 7 21 77 A 15 45 165 A 30 90 330 A 50 150 330 A 70 225 825 A Mag-Loc Feature The Mag-Loc adjustment range limiter allows a user to limit the adjustment of the instantaneous-trip setting within the range of 3 11 times the rated current. Once the range has been set, replace the cover and install a cover seal to prevent tampering. This feature allows adjustment within a predefined, customized range of short-circuit protection. 5

push to trip push to trip push to trip GJL Circuit Breaker and Motor Circuit Protector Installation and Connections Installation and Connections Refer to circuit breaker installation instructions before installing circuit breaker, accessories or wiring. Fixed Mounting Mounting on Backplate Mounting on Rails Mounting on DIN Rail E28475 E28476 E28477 O FF O F F OFF Cable Connections See page 13. Terminal covers are optional (see page 10). Accessories NOTE: Molded case circuit breakers contain factory-sealed and calibrated elements. The seal (hologram) must not be broken and the circuit breaker must not be tampered with. Molded case circuit breakers should not be field adjusted or repaired. In the case of a malfunction, the circuit breaker should be replaced or inspected at the factory or by an authorized representative. Location Internal accessories comply with requirements of Underwriters Laboratories Inc. UL 489 and Canadian Standards Association CSA C22.2 No. 5.1 Standards. All internal accessories are Listed for field installation per UL file E103955 and Certified under CSA file LR69561. 6

Accessories Connections Each electrical accessory is fitted with numbered terminal blocks for wires, Maximum wire size for auxiliary switches, shunt trip or undervoltage release is 18 14 AWG (0.75 2.5 mm 2 ). Auxiliary circuits exit the device through a knock-out in the front cover. Auxiliary and Alarm Switches Auxiliary switch (open/closed) indicates the position of the circuit breaker contacts and can thus be used for indications, electrical locking, relays, etc. Alarm switch (trip indication) indicates that the circuit breaker has tripped due to: An overload; A short circuit; The operation of shunt trip or undervoltage trip or the push-to-trip button which resets when the circuit breaker is reset. All of the above auxiliary switches are also available in low-level versions capable of switching very low loads (e.g., for the control of PLCs or electronic circuits). Auxiliary switches comply with UL 489 and IEC 947-5 Standards. Installation Auxiliary switch and alarm switch snap into cavities under the front accessory cover of the circuit breaker. One model serves both indication functions depending on where it is fitted in the circuit breaker. Electrical Ratings Low-Level Switches Regular Switches UL 489 and CSA C22.2 No. 5.1 Ratings Minimum Rating 1 ma 4 V 10 ma 24 V 240 V 5 6 50/60 Hz 480 V 5 6 Maximum Rating 600 V 3 48 V 2.5 2.5 DC 125 V 0.8 0.8 250 V 0.3 0.3 IEC 947 Ratings Rated Thermal Current 5 6 Minimum Rating 1 ma 4 V 10 ma 24 V Utilization Category (IEC 947-4) AC12 AC15 DC12 DC14 AC12 AC15 DC12 DC14 24 V 5 A 3 A 5 A 1 A 6 A 6 A 2.5 A 1 A 48 V 5 A 3 A 2.5 A 0.2 A 6 A 6 A 2.5 A 0.2 A 110 V 5 A 2.5 A 0.8 A 0.05 A 6 A 5 A 0.8 A 0.05 A Operational Current 220/240 V 5 A 2 A 6 A 4 A 250 V 0.3 A 0.03 A 0.3 A 0.03 A 380/415 V 5 A 1.5 A 6 A 3 A 440 V 5 A 1.5 A 6 A 3 A 660/690 V 6 A 0.1 A 7

Accessories Shunt Trip and Undervoltage Trip A voltage release can be used to trip the circuit breaker via a control signal. Undervoltage Trip Trips the circuit breaker when the control voltage drops below a tripping threshold Drops out between 35% and 70% of the rated voltage Circuit breaker closing is possible only if the voltage exceeds 85% of the rated voltage Permanent type When an overvoltage condition exists, operation of the closing mechanism of the circuit breaker will not permit the main contacts to touch, even momentarily Shunt Trip Trips the circuit breaker when the control voltage rises above 70% of its rated voltage Impulse type 20 ms or maintained control signals AC shunt trips can be operated at 55% of their rated voltage, making them suitable for ground-fault protection when combined with a Class I ground-fault sensing element. Operation The circuit breaker must be reset locally after being tripped by a shunt trip or undervoltage trip Undervoltage or shunt-trip tripping has priority over manual closing. In the presence of a standing trip order, such an action does not result in any closing, even temporarily, of the main contacts Endurance 50% of the rated mechanical endurance of the circuit breaker Installation and Connection Accessories are located within the circuit breaker behind the front accessory cover Each terminal can be connected by one stranded copper wire 8 14 AWG (0.75 2.5 mm 2 ). Electrical Characteristics Rated Voltage 42 48 110/130 208 Vac 1 220/140 277 380/415 440/480 Pickup (Shunt Trip) < 10 VA < 5 W Consumption Seal-in (Undervoltage Trip) < 5 VA < 5 W Clearing Time < 50 ms < 50 ms 1 42 Vac rating not available on undervoltage trip. 24 48 Vdc 110/125 250 8

Operating Mechanisms GJL Circuit Breaker and Motor Circuit Protector Accessories Class 9422 Flange-Mounted Handle Cable Operating Mechanism The cable operator maintains: Suitability for isolation Indication of three positions O (Off), I (On) and tripped Access to push-to-test button The circuit breaker may be locked in the off position by one to three padlocks Door can be locked closed due to interlocking features of the handle operator Installation Handle is mounted on flange of enclosure using specified mounting dimensions while circuit breaker and operating mechanism are mounted to inside of enclosure using two screws. Cable lengths available in 3, 5 or 10 ft. lengths to accommodate a variety of mounting locations. Handles available in painted NEMA 1, 3, 3R, 4 (sheet steel) and 12 ratings or chrome NEMA 4, 4x. Class 9421 Type L Circuit Breaker Operating Mechanisms The Type L door-mounted, variable-depth operating mechanisms are component parts kits featuring heavy-duty, all metal construction with trip indication: All of the operating mechanisms can be padlocked in the OFF position when the enclosure door is open. The handle assemblies can be locked OFF with up to three padlocks which also lock the door shut. The 3-inch handle accepts one padlock. A door drilling template is supplied with each kit to ease installation. The component parts kits are rated for installation into NEMA 1, 3, 3R, 4, and 12 enclosures. All NEMA 1, 3, 3R, 4, and 12 handle assemblies are painted. The handle is flat black and the base ring is silver. Complete installation instructions are included with each kit. 9

Accessories Locking and Interlocking Systems Locking Systems Padlocking systems can receive up to three padlocks with diameters ranging from 0.19 to 0.31 in. (5 to 8 mm) (padlocks are not supplied). Terminal Covers Terminal covers provide protection against contact with live parts. Internal interphase barriers provide additional electrical clearances between poles. Terminal covers are sealable. Terminal covers provide protection against contact with live parts. Internal interphase barriers provide additional electrical clearances between poles. Terminal covers are sealable. 10

Dimensions Dimensions GJL Circuit Breaker Dimensions Mounting on Backplate or on Rail E28842 Z 2.53 64.5 2.75 70 3.14 80 3.30 84 3.93 100 2.36 60 4.72 120 4.05 103 8.11 206 E28482 Y 1.77 3.54 45 90 (a) 3.93 100 1.9 48.5 E28843 Ø 0.15 Ø 4 1.18 30 0.59 15 Y 3.93 100 1.9 48.5 1.25 32 Ø 0.15 Ø 4 E28844 1.18 30 Y 0.59 15 Mounting on DIN Rail Electrical Clearances E28483 3.87 98.5 E28497 13.8 35 3.54 90 2.53 64.5 4.72 120 8.11 206 0.4 10 E36865 0.4 10 (a) 0.59 15 2.85 72.5 3.24 82.5 3.4 86.5 4.03 102.5 Z 3.54 90 Y 1.77 45 (a) Terminal shields. 13.8 35 Front Panel Cutouts E28847 A E28848 Cutout A Cutout B Cutout C E28849 E28850 2.38 60.5 1.02 26 2.69 68.5 1.18 30 2.69 68.5 1.18 30 B/C Z 2.79 71 3.18 81 Y 1.14 29 0.57 14.5 Y 1.81 3.62 46 92 Y 11

Dimensions Cable Operating Handle 9.50 241 E36867 4.25 108 4.31 109 9.38 238 12.13 308 E36868 4.75 121 27 1.06 7.01 178 Dimensions: inch mm 12

Connections Connections Front Connections E28484 E28846 E28845 0.75 19 3.81 97 E28485 1.90 48.5 O F F push to trip 14 1/0 AWG Cu 8 1/0 AWG Al 1.5 to 70 mm 2 Cu/Al 1.25 32 Z Y 1.14 29.2 1.14 29.2 Mounting on DIN Rail E28486 1.14 29.2 1.14 29.2 1.73 44 E28487 1.35 34.5 2.08 53 Y 3.54 90 1.77 45 1.35 34.5 Z 3.26 83 Dimensions: inch mm Wiring Diagrams Auxiliary Switches, Shunt Trip and Undervoltage Trip E36866 D1 C1 92 94 12 14 D Symbols A. Undervoltage trip B. Shunt trip C. Alarm switch D. Auxiliary switch trip unit A (1) Legend (1) : Undervoltage or shunt trip B C D4 C2 91 11 13

Trip Curves Trip Curves Effect of High Temperatures When the ambient temperature is greater than 40 C, overload protection characteristics are slightly modified. When determining tripping times using time/current curves, the Ir values corresponding to the thermal setting on the circuit breaker must be reduced using the coefficients below: 45 C 50 C 55 C 60 C 65 C 705 C 0.975 0.95 0.925 0.90 0.875 0.85 14

Trip Curves 15

Trip Curves 16

Trip Curves 17

Trip Curves 18

Trip Curves 19

Schneider Electric USA 3700 Sixth St. SW Cedar Rapids, IA 52404 USA 1-888-Square D 1-888-778-2733 www.schneider-electric.us 0500CT9702R409 Replaces 0500CT9702 03/1998