TROUBLESHOOTING GENERATOR UNITS

Similar documents
Portable Generator Familiarization & Troubleshooting Guide Section 3 Generator Diagnostics and Adjustments

Manufacturing of: Vehicle Mounted Generators Hydraulic Generators

INDEX Section Page Number Remarks

C.E. Niehoff & Co. C653/C653A and C625 Alternators Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

C802/C802D/C802TD/C820 Alternators Troubleshooting Guide

C.E. Niehoff & Co. C703/C703A and C706 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

AUT 125 ELECTRICAL II CH 54 & 55 CHARGING SYSTEMS

SERVICE SHOP NOTES. Use ohmmeter to check the resistance between the leads.

C.E. Niehoff & Co. C505, C527, C531, and C534 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING

N1233 Series Troubleshooting Guide for N Alternator

A/C Generator Systems

WARNING This manual should only be used by a qualified Service Technician. FinishPro 390/395 Airless/Air-Assisted Sprayer Repair Electrical Manual

C627, C628, C631, C656, C657, C658, C671 and C680 Alternator Troubleshooting Guide

C.E. Niehoff & Co. N1601, N1602, N1603, and N1604 Alternator Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

C.E. Niehoff & Co. C840D Alternator Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

UNIVERSAL VOLTAGE REGULATOR Manufactured in the USA by

Table No. 1 provides a means of identifying the various alternator systems. Note: All output figures are rated at 3600 RPM. TABLE NO.

Page 1 of 1 ALTERNATORS. Overview. Intek TM V-Twin Cylinder OHV Engine Service Manual Version 1.0. Copyright 1999 by Briggs and Stratton Corporation

EA07. Generator Automatic Voltage Regulator Operation Manual

XR500B Universal Voltage Regulator

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

Alternator, Leece-Neville 15.00

600 Series Troubleshooting Guide for C651 and C654 Alternators

MAGNAMAX DVR DIGITAL VOLTAGE REGULATOR

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

500 Series Troubleshooting Guide for C520 Alternators

ALTERNATOR - HITACHI

RV GENERATOR TROUBLESHOOTING GUIDE

Troubleshooting Guide for N1225-1/N1237-1/N Alternators

N1387 Series Troubleshooting Guide for N Alternators

RigMaster Power Service and Repair Manual Document # S901009

2015 EDITION SUBMERSIBLE MOTORS AIM MANUAL. APPLICATION INSTALLATION MAINTENANCE 60 Hz, Single-Phase and Three-Phase Motors. franklinwater.

CHARGING SYSTEM 7.7 GENERAL TROUBLESHOOTING. Alternator. Voltage Regulator. Battery. Wiring. Voltage Regulator Inspection HOME

Handout Activity: HA773

G 2.1A G 3.3A G 4.6A GS 4.6A GS 5.7A

PAGE Both power cords must be connected & powered to operate the E-TES SD 120 volt unit.

CHARGING SYSTEM 8C - 1 CHARGING SYSTEM CONTENTS

VoltPro VP4 Automatic Voltage Regulator

Maintenance Manual 13 AMPERE POWER SUPPLY 19A704647P1-P3. Mobile Communications LBI-31801C

Contacts The moveable contact, which is the one affected by the armature is sometimes referred to as the hinge contact.

Advanced Troubleshooting Guide Snorkel V Battery Charger Rev 0 3JAN07

ALTERNATOR - CHRYSLER 40/90-AMP & 50/120 AMP

WARRANTY WILL BE VOID If These Steps are Not Performed Before Installing The Control STEPS TO PERFORM BEFORE CONTROL INSTALLATION

AFM500X Automatic Flashing Module

COMPONENT ACCESS. If no voltage is present, check wiring to the board. If voltage is present, and brewer does not power on, replace board.

PM300 VOLTAGE REGULATOR INSTRUCTION MANUAL

ALTERNATOR & REGULATOR - NIPPONDENSO


A/C-HEATER SYSTEM - AUTOMATIC

INSTRUCTION MANUAL FOR

PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual

James Hamilton Electrical Pty Ltd (Inc in Qld) A.C.N trading as. Power Drive Systems. Generator Control Specialists

N1240/N1243 Series Troubleshooting Guide for N1240-3/N Alternators

ELECTRICAL TABLE OF CONTENTS

Diagnostic Repair Manual

MX431 Generator Automatic Voltage Regulator Operation Manual

BASIC ELECTRICAL MEASUREMENTS By David Navone

Questions Section: Do you have questions that aren't covered? Please contact us!

MCC Automatic Start-Stop Microcomputer Charger Control

Caution: This document contains mixed page sizes (8.5 x 11 or 11 x 17), which may affect printing. Please adjust your printer settings according to

ESC2301. Universal Electronic Governor Controller Operation Manual

ELECTRONIC MANUAL VOLTAGE CONTROL Model: MVC 300. Part Number:

Coleman Air C440-HVM 440 Amp Diversion Controller Version 3.2

10.0 Alternator Test

2000 F-150 Workshop Manual

1984 Jeep CJ7. IGNITION SYSTEM - SOLID STATE' 'Distributors & Ignition Systems MOTORCRAFT SOLID STATE IGNITION (SSI)

CHARGING SYSTEM 8C - 1 CHARGING SYSTEM CONTENTS

ALTERNATOR - BOSCH 35/75-AMP & 40/90-AMP

1G SI 34 SI HEAVY DUTY BRUSHLESS ALTERNATOR SERVICE MANUAL Delco Remy International Inc. All Rights Reserved.

OnCommand Troubleshooting Guide Hayward Industries

********SERVICE MANUAL********* MODELS:

STARTING SYSTEMS 8B - 1 STARTING SYSTEMS CONTENTS

SE2000BX Static Exciter

Kwikee IMGL Step Control Testing Procedure #82-ST0500

ALTERNATOR PRECAUTIONS. Some precautions should be taken when working on this, or any other, AC charging system.

G 2.5A G 3.7A G 5.6A GS 5.6A GS 8.5V GS 9.7V

Coleman Air Diversion Controller Model C40

2001 Cougar Workshop Manual

Charging Systems. ATASA 5 th. ATASA 5 TH Study Guide Chapter 19 Pages Charging Systems 42 Points. Please Read The Summary

Just what is an alternator?

Experiment 3. The Direct Current Motor Part II OBJECTIVE. To locate the neutral brush position. To learn the basic motor wiring connections.

POWER SUPPLY MODEL XP-800. TWO AC VARIABLE VOLTAGES; 0-120V and 7A, PLUS UP TO 10A. Instruction Manual. Elenco Electronics, Inc.

EG3000. Generator Electronic Governor Controller Operation Manual

This chapter contains information on DC Generation, External Power, and Electrical Load Distribution.

BLOWER VACUUM SWITCH FAILED OPEN

ONE TOUCH CONTROL BOX

700 Series Troubleshooting Guide for C711/C712 Alternators

M O D E L USER MANUAL. FLIGHT SYSTEMS 207 Hempt Rd. Mechanicsburg PA FLIGHT SYSTEMS 207 Hempt Rd. Mechanicsburg PA 17050

Troubleshooting 3Z8 038 Rev B

ABF40 Automatic Battery Flash Unit

M O D E L USER MANUAL FLIGHT SYSTEMS FLIGHT SYSTEMS

MANUAL. Transmotor generator DCG-56 EVRP

EG1069X. Generator Electronic Governor Controller Operation Manual

Controlled Ferroresonant Ballast (CFB) Generation #3. Manual

Understanding The HA2500's Horiz Driver Test

NOTE: SPECIFICATION TABLES BEGIN ON PAGE 41 OF THIS SECTION.

BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi

Operating Manual OBD Link Connector

Troubleshooting Guide for Stamford Generators

24-00 ELECTRICAL POWER

Transcription:

TROUBLESHOOTING GENERATOR UNITS Figure 3.17 Troubleshooting Flow Chart For Direct Excited (Brush Type) Generators or later. 68

Troubleshooting Direct Excited (Brush Type) Generators Refer to Figure 3.17 Test 1: Check AC Output Voltage & Frequency Connect the test leads of an AC voltmeter or a volt-ohmmillimeter VOM into a generator receptacle. Also connect an (AC) frequency meter. Disconnect any electrical loads. Start the generator engine, let it stabilize and warm up. Read the no-load voltage and frequency, and analyze the results as follows: If zero volts or less than 6VAC is indicated: Go to Test 2. If low voltage is indicated, but reading is above 6VAC and AC frequency is normal: Go to Test 3. If low voltage is indicated, but reading is above 6VAC and AC frequency is low: Engine Governor may need adjustment. (Refer to the appropriate engine manual) Test 2: Flash The Field In normal generator operation, upon startup there is some residual magnetism in the rotor to get the generating process started. Residual magnetism is the magnetism left in the rotor after the unit is shut down. When residual magnetism is lost, the unit will have an output voltage that will remain at zero. If residual magnetism is lost it can usually be restored by flashing the field with a simple process involving a (DC) battery. This usually occurs if the unit is out of use for a long period of time. NOTE: Some units are equipped with FIELD BOOST and should never lose residual magnetism unless a field boost failure has occurred. Field boost current flashes the field on every startup (see Field Boost on Page 45). Refer to the appropriate electric schematic and/or wiring diagram to determine if a unit has field boost. If the unit is equipped with a voltage regulator or a bridge rectifier, flash the field as follows: Obtain a 12VDC battery. Get two jumper leads that can go from the battery to the brushes (wires with alligator clips work well). Find the brushes inside the alternator portion of the unit. Start the engine and get it up to running speed. Connect the battery positive (+), to the positive brush, which will be the brush closest to the rotor bearing. Connect the battery negative (-), to the negative brush, which is the brush farthest away from the rotor bearing. (Refer to Figure 3.18). Figure 3.18 Restoring Residual Magnetism After about five seconds, disconnect the battery wires from the brushes and check for proper (AC) output voltage. Shut the engine down. Restart the unit and check once again for proper (AC) output voltage. 69

If the unit is equipped with a brush/bridge rectifier (refer to Figure 3.19), proceed as follows: Figure 3.19 Brush & Rectifier Combination To test the rotor with a volt-ohm-milliameter VOM, set the VOM to its OHM scale and zero the meter.then, test for an open, shorted or grounded condition as follows: Step 1: Checking Rotor Resistance Remove the brush assembly. Set the VOM to its OHM scale. Connect the test leads to the rotor slip rings (See Figure 3.20). Figure 3.20 Checking Rotor Resistance Locate the brush/bridge rectifier inside the alternator portion of the unit. Remove the DPE wires 2 & 6 (or red and blue) from the rectifier terminals J1 and J2. Start the engine and get it up to running speed. Apply 12VDC across terminals J1 and J2. (Polarity is not important.) After about five seconds, disconnect the 12VDC from the rectifier, and stop the engine. Reconnect the DPE wires to the rectifier terminals. Wire number 2 (blue) connects to J1, and wire number 6 (red) connects to J2. Restart the unit and check once again for proper (AC) output voltage. Test 3: Check Rotor Little or no (AC) output voltage can be caused by a rotor failure. Because of the cramped quarters inside the rear bearing carrier, it is necessary to remove the power cable grommet as shown in Figure 3.21. Figure 3.21 Access To Rotor Slip Rings Grommet Removed For Access NOTE: The voltage surge that occurs at the moment of rotor failure can result in damage to the bridge rectifier or voltage regulator. For that reason, if a rotor has failed, be sure to check the bridge rectifier, voltage regulator, or power regulator board. Before testing the rotor, inspect the brushes and slip rings. Replace brushes if they are worn excessively, or if they are cracked or damaged. Do not use any metallic grit to clean up slip rings. 70

Measure the rotor resistance and compare it to the nominal resistance from the appropriate resistance table (Briggs & Stratton Power Products Portable Generator Rotor/Stator Resistance Tables Pub. #87971 Rev 6 or later). A reading of infinity or a very high resistance indicates an open circuit or a partially open condition in the rotor windings. A very low resistance indicates a shorted rotor. Connect one test lead to the rotor shaft and the other test lead to either rotor slip ring (Figure 3.22). Connect a jumper wire between the negative brush and the negative post on the battery (See Figure 3.23). Figure 3.23 Rotor Current Draw Test Figure 3.22 Checking Rotor Short To Ground A reading of infinity should be measured. A reading other than infinity indicates a rotor winding shorted to the rotor shaft. NOTE: Sometimes a rotor may only fail while it is spinning at rated RPM.This condition is called a Flying Open or Flying Short. To diagnose, use the Rotor Current Draw Test. Step 2: Rotor Current Draw Test Locate the brush wires. (Normally these wires are #4 and #1.) Isolate the brushes from the bridge rectifier or voltage regulator. Connect a (DC) amp meter between the positive brush wire #4, and the positive post on a 12VDC battery. Start the engine and monitor amp draw. It should not change while the unit is running or static.the (DC) amp draw will be determined by the specified resistance of the rotor being tested. To find the desired amp draw, use Ohms Law: Voltage divided by amperage equals resistance. For example: 12VDC divided by a rotor resistance of 24 ohms equals an amp draw of 0.5 amp. NOTE: Amp draw may vary slightly due to exact battery voltage, rotor resistance, and meter calibration etc. Look for extreme differences. Analyze the test results as follows: If the rotor current draw is higher than specified, a flying short exists in the rotor. If current draw is lower than specification, a flying open exists in the rotor. If current draw is within specifications, rotor is OK. Test 4: Check And Adjust Governor Refer to the appropriate engine manual. 71

Test 5: Check Stator Excitation (DPE) Windings NOTE: The excitation wires may be colored or numbered.the numbered wires are #2 and #6.The colored wires are blue and red. Be sure not to confuse the colored excitation wires with the colored power wires.the excitation wires are the wires connected to the bridge rectifier or voltage regulator. Set the VOM to its OHM scale. Connect the test leads to the stator excitation wires (Figure 3.24). Figure 3.25 Testing For Short Between Windings Figure 3.24 Checking DPE Resistance A reading of infinity should be measured. A reading other than infinity indicates a power winding shorted to an excitation winding. Connect one test lead to an excitation wire. Connect the other test lead to a good metal ground. (Figure 3.26) Figure 3.26 Checking DPE Short To Ground resistance from the appropriate table (Briggs & Stratton Power Products Portable Generator Rotor/Stator Resistance Tables Pub. #87971 Rev 6 or later). A reading of infinity or high resistance indicates an opening in the excitation winding. A low reading indicates a shorted stator winding. Connect one test lead to a stator power wire. Connect the other test lead to one of the stator excitation wires (Figure 3.25). A reading of infinity should be measured. A reading other than infinity indicates a winding shorted to ground. 72

Test 6: Testing Stator AC Power Windings Testing Single Voltage Type Power Winding Set a VOM to its OHM scale. Connect the meter test leads across the (AC) power wires. (Wire #11 and wire #22 or blue and red wires (Figure 3.27). Connect one meter test lead to a good ground. Connect the other test lead to the stator power winding (Figure 3.28). Figure 3.28 Testing For Short To Ground Figure 3.27 Checking Power Winding Resistance A reading of infinity should be measured.a reading of other than infinity indicates a stator winding shorted to ground. resistance from the appropriate table (Briggs & Stratton Power Products Portable Generator Rotor/Stator Resistance Tables Pub. #87971 Rev 6 or later). A reading of infinity or high resistance indicates an opening in the stator winding. A low reading indicates a shorted stator winding. Testing Dual Voltage Type Power Windings Set a VOM to the OHM scale. Connect the test leads to the stator wires #11 and #22. resistance from the appropriate table (Briggs & Stratton Power Products Portable Generator Rotor/Stator Resistance Tables Pub. #87971 Rev 6 or later). Connect the test leads to the stator wires #22 and #44. resistance from the appropriate table. Analyze the results the same as in Testing Single Voltage Type Power Winding. Connect one meter test lead to a good ground. Connect the other test lead to the stator power winding. (Refer back to Figure 3.28). A reading of infinity should be measured. A reading other than infinity indicates a stator winding shorted to ground. 73

Testing Battery Charge Windings Set VOM to OHM scale. If a single winding is used: Connect the meter test leads across wires No. 55 and 66. Compare the reading obtained with the resistance value from the Briggs & Stratton Power Products Portable Generator Rotor/Stator Resistance Tables Pub. #87971 Rev 6 or later. If dual Battery Charge Windings are used, take meter readings as follows: Read across Wires No. 55 (black) and 66 (brown). Read across Wires No. 55 (black) and 77 (brown). resistance from the appropriate table. Analyze the results the same as in Testing Single Voltage Type Power Winding. NOTE: The resistance table gives only two resistance values for multi-tap Battery Charge Windings, even though there are actually four (4) windings.the difference in resistance between 55-66A and 55-77A, and 55-66 and 55-77 is minimal and insignificant. Test 7: Bypassing the Voltage Regulator or Bridge Rectifier NOTE: Bypassing the bridge rectifier and voltage regulator are similar tests, the difference being that six wires are unplugged from the voltage regulator where only two or four are removed from the bridge rectifier. During the bridge rectifier test you measure (AC) output at the stator power and excitation windings only, there are no sensing wires on a bridge rectifier system. Start the generator (make sure the remaining wires are not touching each other or the control panel, etc.). Measure (AC) output across sensing wires #11 and #22 (on voltage regulator types only). On bridge rectifier types, measure (AC) output at the 120VAC receptacle. At least 60VAC should be measured, slightly higher is ok (Figure 3.29). Figure 3.29 Testing Power Winding Output Measure (AC) output across excitation winding wires #2 and #6. At least 60VAC should be measured. It can be higher (Figure 3.30). Figure 3.30 Testing Excitation Winding Output Verify that the field flash has taken place (Voltage Regulator types only).watch the light on the Voltage Regulator. If it comes on at all, field flash has occurred. Disconnect all wires from the Voltage Regulator or Bridge Rectifier and keep them completely isolated from the circuit. Apply 12VDC to the brush wires, normally wires #4 (+), and #1 (-). 74

Analyze the test results as follows: If any of the (AC) voltage readings are below 60VAC (slightly higher is ok) and rotor current draw is within specification: The problem is in the stator windings. If the rotor current draw (Test 3) is higher than specified: A flying short exists in the rotor. If current draw (Test 3) is lower than specification: A flying open exists in the rotor. If (AC) output and current draw are within specifications and the rotor and stator are ok: The voltage regulator is defective. 75