Protector Series ISO. PROTECTOR SERIES Standby Generators Liquid-Cooled Gas Engine FEATURES INCLUDES:

Similar documents
Protector Series ISO FEATURES. Standby Generators Liquid-Cooled Gas Engine INCLUDES:

Protector Series ISO. PROTECTOR SERIES Standby Generators Liquid-Cooled Gaseous Engine FEATURES INCLUDES:

Protector QS Series ISO. PROTECTOR QS SERIES Standby Generators Liquid-Cooled Gaseous Engine FEATURES INCLUDES:

Protector Series ISO. PROTECTOR SERIES Standby Generators Liquid-Cooled Gaseous Engine FEATURES INCLUDES: Protector Series

Standby Generators ISO FEATURES. Standby Generators Liquid-Cooled Gaseous Engine. Standby Generators INCLUDES:

Protector QS Series ISO. PROTECTOR QS SERIES Standby Generators Liquid-Cooled Gaseous Engine FEATURES INCLUDES: Protector QS Series

Centurion Series. CENTURION SERIES Standby Generators Liquid-Cooled Gas Engine FEATURES. Centurion Series INCLUDES:

Guardian Series. GUARDIAN SERIES Standby Generators Liquid-Cooled Gas Engine FEATURES. Guardian Series INCLUDES:

Quietsource Series ISO. QUIETSOURCE SERIES Standby Generators Liquid-Cooled Gas Engine FEATURES. Quietsource Series INCLUDES:

GENERAC GUARDIAN SERIES STANDBY GENERATORS

GENERAC QUIETSOURCE SERIES STANDBY GENERATORS

GENERAC GUARDIAN SERIES STANDBY GENERATORS

70 kw GENERAC STANDBY GENERATORS. Liquid-Cooled Engine Generator Sets FEATURES INCLUDES: Standby Power Rating Model QT070 (Bisque) - 70 kw 60Hz

GENERAC GUARDIAN SERIES STANDBY GENERATORS

GENERAC GUARDIAN SERIES STANDBY GENERATORS

22 kva GENERAC STANDBY GENERATORS ISO. Liquid-Cooled Engine Generator Sets FEATURES INCLUDES:

22 / 27 / 32 / 38 / 48 kw

GENERAC GUARDIAN SERIES STANDBY GENERATORS

GENERAC GUARDIAN SERIES STANDBY GENERATORS

GENERAC QUIETSOURCE SERIES STANDBY GENERATORS

STANDBY GENERATOR 25 kw LIQUID-COOLED GENERATOR SET INCLUDES FEATURES. Standby Power Rating Model HT kw 60Hz

STANDBY GENERATOR 130 kw LIQUID-COOLED GENERATOR SET INCLUDES FEATURES. Standby Power Rating Model HT kw 60Hz

STANDBY GENERATOR 100 kw LIQUID-COOLED GENERATOR SET INCLUDES FEATURES. Standby Power Rating Model HT kw 60Hz

STANDBY GENERATOR 80 kw LIQUID-COOLED GENERATOR SET INCLUDES FEATURES. Standby Power Rating Model HT kw 60Hz

Siemens Liquid Cooled Standby Generators

Protector Series ISO FEATURES. Diesel Generator Set INCLUDES:

Standby Generators. 70kW - Liquid Cooled Gas Engine. Meets 2010 EPA emissions regulations.

Siemens Liquid Cooled Standby Generators

Protector Series ISO FEATURES. Diesel Generator Set. Protector Series INCLUDES:

GENERAC GUARDIAN SERIES STANDBY GENERATORS

20 kw GENERAC GUARDIAN SERIES STANDBY GENERATORS - PREPACKAGED. Air-Cooled Gas Engine Generator Sets FEATURES

GENERAC GUARDIAN SERIES STANDBY GENERATORS

16 kw CENTURION STANDBY GENERATOR. Air-Cooled Gas Engine Generator Sets FEATURES. INCLUDES: True Power Electrical Technology

1P 120/240V, 3600 RPM,

7kW. 7kW. CorePower System Residential Standby Generators Air-Cooled Gas Engine FEATURES. Power Rating Model (Composite Polymer) - 7 kw 60Hz

17 kw GENERAC GUARDIAN SERIES STANDBY GENERATORS - PREPACKAGED. Air-Cooled Gas Engine Generator Sets FEATURES

16 kw CENTURION STANDBY GENERATOR. Air-Cooled Gas Engine Generator Sets FEATURES. Standby Power Rating Model (Steel - Gray) - 16 kw 60Hz

QT025A 2.4L 25 kw INDUSTRIAL SPARK-IGNITED GENERATOR SET EPA Certified Stationary Emergency

STANDBY GENERATORS 17 kw AIR-COOLED GENERATOR SETS

17/20kW. 17/20kW. GUARDIAN SERIES Residential Standby Generators Air-Cooled Gas Engine FEATURES. Includes: Standby Power Rating

STANDBY GENERATOR 20 kw AIR-COOLED GENERATOR SET INCLUDES FEATURES. Standby Power Rating Model (Steel - Dark Gray) - 20 kw 60 Hz - US

*Only if located away from doors, windows and fresh air intakes, and unless otherwise directed by local codes.

SPECIFICATIONS. Stationary Emergency Generator Specifications STATIONARY EMERGENCY GENERATOR COOLING SYSTEM FUEL SYSTEM ENGINE ELECTRICAL SYSTEM

8/10/14kW. 8/10/14kW. GUARDIAN SERIES Residential Standby Generators Air-Cooled Gas Engine FEATURES INCLUDES:

16/20/22 kw CENTURION SERIES

Standby Rated Generators. Standby SG kva / 28 kw. Prime PG kva / 22 kw

Optimus Residential Standby Generators

Power Ratings. Standby SG kva / 240 kw. Prime PG kva / 192 kw

Spark-ignited generator set

Standby Rated Generators. Standby SG kva / 184 kw. Prime PG kva / 147 kw

Power Ratings. Standby SG kva / 160 kw. Prime and standby ratings based on 3-Phase voltages. Model number based on kw rating.

Power Ratings. Standby SG kva / 320 kw. Prime PG kva / 288 kw

9/11 kw. 9/11 kw. GUARDIAN SERIES Residential Standby Generators Air-Cooled Gas Engine FEATURES

INDUSTRIAL SPARK-IGNITED GENERATOR SET EPA Certified Stationary Emergency CODES AND STANDARDS POWERING AHEAD

SG L. Industrial Spark-Ignited Generator Set. Powering Ahead. Codes and Standards. SG kw. Standby Power Rating 80 kw 100 kva 60 Hz

Spark-ignited generator set

Diesel generator set. QSB5 series engine Hz EPA Tier 3 emissions. Specification sheet. Description. Features

Diesel generator set. 20 kw EPA emissions stationary Standby. Specification sheet. Description. Features

SG L. Industrial Spark-Ignited Generator Set. Powering Ahead. Codes and Standards. SG kw. Standby Power Rating 70 kw 88 kva 60 Hz

INDUSTRIAL SPARK-IGNITED GENERATOR SET EPA Certified Stationary Emergency CODES AND STANDARDS POWERING AHEAD

SG L 300 kw INDUSTRIAL SPARK-IGNITED GENERATOR SET EPA Certified Stationary Emergency

INDUSTRIAL SPARK-IGNITED GENERATOR SET EPA Certified Stationary Emergency POWERING AHEAD CODES AND STANDARDS

SG L. Industrial Spark-Ignited Generator Set. Powering Ahead. Codes and Standards. SG kw. Standby Power Rating 130 kw 163 kva 60 Hz

8/11/13kW. 8/11/13kW. CENTURION SERIES Residential Standby Generators Air-Cooled Gas Engine FEATURES. Includes: Standby Power Rating

SG L. Industrial Spark-Ignited Generator Set. Powering Ahead. Codes and Standards. SG kw. Standby Power Rating 150 kw 188 kva 60 Hz

Diesel generator set. 50 kw - 60 kw EPA emissions stationary Standby. Specification sheet. Description. Features

100 KW(NG) / 100 KW(LP) LIQUID COOLED POWERED by

SG L 250 kw INDUSTRIAL SPARK-IGNITED GENERATOR SET EPA Certified Stationary Emergency

SG L 35 kw INDUSTRIAL SPARK-IGNITED GENERATOR SET EPA Certified Stationary Emergency

MG L. MG Series Paralleling Unit. Industrial Spark-Ignited Generator Set. Powering Ahead. Codes and Standards. MG kw

SG L 50 kw INDUSTRIAL SPARK-IGNITED GENERATOR SET EPA Certified Stationary Emergency

MG L. MG Series Paralleling Unit. Industrial Spark-Ignited Generator Set. Powering Ahead. Codes and Standards. MG kw

8/11/14kW. 8/11/14kW. GUARDIAN SERIES Residential Standby Generators Air-Cooled Gas Engine FEATURES. Includes: Standby Power Rating

16/20/22 kw. 16/20/22 kw GUARDIAN SERIES FEATURES. Residential Standby Generators Air-Cooled Gas Engine. Standby Power Rating INCLUDES: 1 of 6

DIESEL GENERATOR SETS

Diesel generator set QSK23 series engine

Diesel generator set QSX15 series engine

Diesel generator set 6BT5.9 series engine

Power Connect RX50. Series. Specification sheet. Features and benefits. Weight, size and sound level

Diesel generator set QSK23 series engine

DIESEL GENERATOR SET. 60 Hz FEATURES

Power Connect TM Series RX60

60 Hz FEATURES. Exclusively from your Caterpillar dealer

Diesel generator set QSX15 series engine

Quiet Connect TM Series - RS13A, RS17A, RS20A, & RS20AC

Diesel generator set QSB7 series engine

Quiet Connect TM Series - RS13A, RS17A, RS20A, & RS20AC

Rental Power 800 kw. Specification sheet. Description. Features. Options

Diesel generator set 4BT3.3 series engine

MG L 150 kw INDUSTRIAL SPARK-IGNITED GENERATOR SET EPA Certified Stationary Emergency

Residential standby system RS12000

48kW ¹ STANDBY GENERATOR

20 KW / 25 KVA LIQUID COOLED POWERED by

STANDBY 400 ekw 500 kva 50 Hz 1500 rpm 400 Volts

Residential standby system RS12000

G50U MODEL STANDARD FEATURES GENERATOR RATINGS CONDITIONS OF SALE. General features :

8/11 kw. 8/11 kw. CENTURION SERIES Residential Standby Generators Air-Cooled Gas Engine FEATURES INCLUDES: Standby Power Rating

SD L. Industrial Diesel Generator Set. SD kw. Powering Ahead. Codes and Standards. Standby Power Rating 20 kw 25 kva 60 Hz

Diesel generator set QSL9-G7 series engine

8/11 kw. 8/11 kw. GUARDIAN SERIES Residential Standby Generators Air-Cooled Gas Engine FEATURES

Transcription:

Protector Series PROTECTOR SERIES Standby Generators Liquid-Cooled Gas Engine 1 of 9 INCLUDES: Two Line LCD Multilingual Digital Evolution Controller (English/Spanish/ French/Portuguese) with external viewing window for easy indication of generator status and breaker position. True Power Electrical Technology Isochronous Electronic Governor Sound Attenuated Enclosure Closed Coolant Recovery System Smart Battery Charger UV/Ozone Resistant Hoses ±1% Voltage Regulation Natural Gas or LP Operation 5 Year Limited Warranty Standby Power Rating Model RG025 (Steel - Bisque or Aluminum - Gray) - 25 kw 60 Hz Model RG030 (Steel - Bisque or Aluminum - Gray) - 30 kw 60 Hz Model RG036 (Steel - Bisque or Aluminum - Gray) - 36 kw 60 Hz Model RG045 (Steel - Bisque or Aluminum - Gray) - 45 kw 60 Hz Model RG060 (Steel - Bisque or Aluminum - Gray) - 60 kw 60 Hz UL 2200 Listed * Note: 25-45 kw units are field convertible between natural gas or LP. 60 kw units are built per fuel requirement and are not convertible. *Built in the USA using domestic and foreign parts Meets EPA Emission Regulations 25, 30 & 45 kw CA/MA emissions compliant 36 & 60 kw not for sale in CA/MA FEATURES INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of GENERAC S success in IMPROVING POWER BY DESIGN. But it doesn t stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, allows you to choose GENERAC POWER SYSTEMS with the confidence that these systems will provide superior performance. TEST CRITERIA: PROTOTYPE TESTED SYSTEM TORSIONAL TESTED NEMA MG1-22 EVALUATION MOTOR STARTING ABILITY SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION. This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine. Digital voltage regulation at ±1%. SINGLE SOURCE SERVICE RESPONSE from Generac s extensive dealer network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component. GENERAC TRANSFER SWITCHES. Long life and reliability are synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is that the GENERAC product line includes its own transfer systems and controls for total system compatibility. ISO 9001: 2008

2 of 9 25 30 36 45 60 kw application & engineering data GENERATOR SPECIFICATIONS Type Synchronous Rotor Insulation Class H Stator Insulation Class H Telephone Interference Factor (TIF) <50 Alternator Output Leads 1-Phase 4 wire Alternator Output Leads 3-Phase 6 wire Bearings Sealed Ball Coupling Flexible Disc Excitation System Direct ENGINE SPECIFICATIONS: 25 & 30 kw Make Generac Model In-line Cylinders 4 Displacement (Liters) 1.5 Bore (in/mm) 3.05/77.4 Stroke (in/mm) 3.13/79.5 Compression Ratio 11:1 Intake Air System Naturally Aspirated Lifter Type Hydraulic VOLTAGE REGULATION Type Sensing Electronic Single Phase Regulation ± 1% GOVERNOR SPECIFICATIONS Type Frequency Regulation Electronic Isochronous Steady State Regulation ± 0.25% ELECTRICAL SYSTEM Battery Charge Alternator Static Battery Charger Recommended Battery System Voltage GENERATOR FEATURES Revolving field heavy duty generator Directly connected to the engine Operating temperature rise 120 C above a 40 C ambient Class H insulation is rated at 150 C rise at 25 C ambient All models fully prototyped tested ENCLOSURE FEATURES Steel weather protective enclosure with aluminum roof (all models) or aluminum weather protective enclosure (available on 60 kw only) Enclosed critical grade muffler Small, compact, attractive SAE 12 Volt 15 Amp - 25 & 30 kw 12 Volt 30 Amp - 36, 45 & 60 kw 2 Amp Group 26, 525CCA 12 Volts Ensures protection against mother nature. Electrostatically applied textured epoxy paint for added durability. Quiet, critical grade muffler is mounted inside the unit to prevent injuries. Makes for an easy, eye appealing installation. Sound attenuated enclosure ensures quiet operation. ENGINE SPECIFICATIONS: 36, 45 & 60 kw Make Generac Model In-line Cylinders 4 Displacement (Liters) 2.4 Bore (in/mm) 3.41/86.5 Stroke (in/mm) 3.94/100 Compression Ratio 9.5:1 Intake Air System Naturally Aspirated (36 & 45 kw) or Turbocharged/Aftercooled (60 kw) Lifter Type Hydraulic ENGINE LUBRICATION SYSTEM Oil Pump Type Gear Oil Filter Type Full flow spin-on cartridge Crankcase Capacity (qt/l) 4/3.8-25, 30, 36 & 45 kw 5.25/4.96-60 kw ENGINE COOLING SYSTEM Type Closed Water Pump Belt driven 2484-25 & 30 kw Fan Speed (rpm) 1865-36 & 45 kw 2100-60 kw Fan Diameter (in/mm) 17.7/449.6 (25 & 30 kw) or 22/558.8 (36, 45 & 60 kw) Fan Mode Pusher (25 & 30 kw) or Puller (36, 45 & 60 kw) FUEL SYSTEM Fuel Type Natural gas, propane vapor Carburetor Down Draft Secondary Fuel Regulator Standard Fuel Shut Off Solenoid Standard Operating Fuel Pressure 5-14" water column/9-26 mm HG (All ratings in accordance with BS5514, ISO3046, ISO8528, SAE J1349 and DIN6271)

25 30 36 45 60 kw operating data GENERATOR OUTPUT VOLTAGE/kW - 60 Hz kw LPG Amp LPG kw Nat. Gas Amp Nat. Gas CB Size (Both) 120/240 V, 1Ø, 1.0 pf 25 104 25 104 125 RG025 120/208 V, 3Ø, 0.8 pf 25 87 25 87 100 120/240 V, 3Ø, 0.8 pf 25 75 25 75 90 120/240 V, 1Ø, 1.0 pf 30 125 30 125 150 RG030 120/208 V, 3Ø, 0.8 pf 30 104 30 104 125 120/240 V, 3Ø, 0.8 pf 30 90 30 90 100 120/240 V, 1Ø, 1.0 pf 36 150 36 150 175 RG036 120/208 V, 3Ø, 0.8 pf 36 125 36 125 150 120/240 V, 3Ø, 0.8 pf 36 108 36 108 125 277/480 V, 3Ø, 0.8 pf 36 54 36 54 60 120/240 V, 1Ø, 1.0 pf 45 188 45 188 200 RG045 120/208 V, 3Ø, 0.8 pf 45 156 45 156 175 120/240 V, 3Ø, 0.8 pf 45 135 45 135 150 277/480 V, 3Ø, 0.8 pf 45 68 45 68 80 120/240 V, 1Ø, 1.0 pf 60 250 60 250 300 RG060 120/208 V, 3Ø, 0.8 pf 60 208 60 208 250 120/240 V, 3Ø, 0.8 pf 60 180 60 180 200 277/480 V, 3Ø, 0.8 pf 60 90 60 90 100 3 of 9 SURGE CAPACITY IN AMPS RG025 RG030 RG036 RG045 RG060 Voltage Dip @ <.4 pf 15% 30% 120/240 V, 1Ø 65 170 120/208 V, 3Ø 80 130 120/240 V, 3Ø 69 112 120/240 V, 1Ø 75 180 120/208 V, 3Ø 96 155 120/240 V, 3Ø 83 134 120/240 V, 1Ø 105 240 120/208 V, 3Ø 44 130 120/240 V, 3Ø 38 115 277/480 V, 3Ø 20 60 120/240 V, 1Ø 105 240 120/208 V, 3Ø 44 130 120/240 V, 3Ø 38 115 277/480 V, 3Ø 20 60 120/240 V, 1Ø 140 320 120/208 V, 3Ø 70 210 120/240 V, 3Ø 61 182 277/480 V, 3Ø 30 91 Note: Fuel pipe must be sized for full load. For Btu content, multiply ft³/hr x 2520 (LP) or ft³/hr x 1000 (NG) For megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG) Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes. ENGINE FUEL CONSUMPTION Natural Gas Propane (ft³/hr) (m³ /hr) (gal/hr) (l/hr) (ft³/hr) Exercise cycle 60 1.7 0.7 2.5 24 25% of rated load 220 6.3 2.9 9.1 88 RG025 50% of rated load 297 8.4 3.3 12.3 119 75% of rated load 362 10.3 4 15 145 100% of rated load 430 12.2 4.7 17.8 172 Exercise cycle 60 1.7 0.7 2.5 24 25% of rated load 240 6.8 2.6 10 96 RG030 50% of rated load 320 9.1 3.5 13.3 128 75% of rated load 400 11.4 4.4 16.6 160 100% of rated load 492 14 5.4 20.4 197 Exercise cycle 65 108 0.7 2.6 25 25% of rated load 210 6 2.3 8.6 83 RG036 50% of rated load 380 10.8 4.2 15.7 151 75% of rated load 545 15.5 5.9 22.4 216 100% of rated load 730 20.7 8 30.1 290 Exercise cycle 65 1.8 0.7 2.6 25 25% of rated load 210 6 2.3 8.6 83 RG045 50% of rated load 380 10.8 4.2 15.7 151 75% of rated load 545 15.5 5.9 22.4 216 100% of rated load 730 20.7 8 30.1 290 Exercise cycle 123 3.5 1.34 5.1 49.3 25% of rated load 267 7.6 2.7 10.5 101 RG060 50% of rated load 483 13.7 5 19 183 75% of rated load 672 19.1 7 26.5 255 100% of rated load 862 24.5 9 33.9 327 STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.

4 of 9 25 30 36 45 60 kw operating data ENGINE COOLING 25 kw 30 kw 36 kw 45 kw 60 kw Air flow (inlet air including alternator and combustion air in cfm/cmm) 2490/70.5 2490/70.5 2725/77.2 2725/77.2 3280/92.9 System coolant capacity (gal/liters) 2/7.6 2/7.6 2.5/9.5 2.5/9.5 2.5/9.5 Heat rejection to coolant (BTU per hr/mj per hr) 112,000/118.2 135,000/142.4 193,000/203.6 193,000/203.6 270,000/284.9 Maximum operation air temperature on radiator ( C/ F) 60/150 Maximum ambient temperature ( C/ F) 50/140 COMBUSTION REQUIREMENTS Flow at rated power (cfm/cmm) 62/1.8 72/2 144/4.1 144/4.1 180/5.1 SOUND EMISSIONS Sound output in db(a) at 23 ft (7 m) with generator in exercise mode* 59 59 61 61 65 Sound output in db(a) at 23 ft (7 m) with generator operating at normal load* 72 73 70 73 72 *Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters. EXHAUST Exhaust flow at rated output (cfm/cmm) 203/5.7 237/6.7 300/8.5 420/11.9 494/14 Exhaust temperature at muffler outlet ( C/ F) 593/1100 610/1130 579/1075 593/1100 566/1050 ENGINE PARAMETERS Rated Synchronous rpm 3600 POWER ADJUSTMENT FOR AMBIENT CONDITIONS Temperature Deration...3% for every 10 C above 25 C or 1.65% for every 10 F above 77 F Altitude Deration (25, 30, 36 & 45 kw)...1% for every 100 m above 183 m or 3% for every 1000 ft above 600 ft Altitude Deration (60 kw)... 1% for every 100 m above 915 m or 3% for every 1000 ft above 3000 ft CONTROLLER FEATURES 2-Line Plain Text LCD Display...Simple user interface for ease of operation. Mode Switch: Auto...Automatic Start on Utility failure. 7 day exerciser Off...Stops unit. Power is removed. Control and charger still operate. Manual... Start with starter control, unit stays on. If utility fails, transfer to load takes place. Programmable start delay between 10-30 seconds... Standard Engine Start Sequence... Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration) Engine Warm-up... 5 sec Engine Cool-Down...1 min Starter Lock-out...Starter cannot re-engage until 5 sec after engine has stopped. Smart Battery Charger... Standard Automatic Voltage Regulation with Over and Under Voltage Protection... Standard Automatic Low Oil Pressure Shutdown... Standard Overspeed Shutdown... Standard, 72 Hz High Temperature Shutdown... Standard Overcrank Protection... Standard Safety Fused... Standard Failure to Transfer Protection... Standard Low Battery Protection... Standard 50 Event Run Log... Standard Future Set Capable Exerciser... Standard Incorrect Wiring Protection... Standard Internal Fault Protection... Standard Common External Fault Capability... Standard Governor Failure Protection... Standard

25 30 36 45 60 kw available accessories Model # Product Description 006463-3 Mobile Link Generac's Mobile Link allows you to check the status of your generator from anywhere that you have access to an Internet connection from a PC or with any smart device. You will even be notified when a change in the generator s status occurs via e-mail or text message. Note: Harness Adapter Kit required. 5 of 9 006478-0 Harness Adapter Kit The Harness Adapter Kit is required to make liquid-cooled units compatible with Mobile Link. 006175-0 - 25 & 30 kw 005630-1 - 36, 45 & 60 kw 006174-0 - 25 & 30 kw 005616-0 - 36, 45 & 60 kw Cold Weather Kit Extreme Cold Weather Kit If the temperature regularly falls below 32 F (0 C), install a cold weather kit to maintain optimal battery temperature. Kit consists of battery warmer with thermostat built into the wrap. Recommended where the temperature regularly falls below 32 F (0 C) for extended periods of time. For liquid cooled units only. 005651-0 Base Plug Kit Add base plugs to the base of the generator to keep out debris. 005703-0 - Bisque 005704-0 - Gray 006176-0 - 25 & 30 kw 006172-0 - 36 & 45 kw 006171-0 - 60 kw Paint Kit* Scheduled Maintenance Kit If the generator enclosure is scratched or damaged, it is important to touch-up the paint to protect from future corrosion. The paint kit includes the necessary paint to properly maintain or touch-up a generator enclosure. The Liquid-Cooled Scheduled Maintenance Kits offer all the hardware necessary to perform complete maintenance on Generac liquid-cooled generators. 005928-0 Wireless Remote Completely wireless and battery powered, Generac's wireless remote monitor provides you with instant status information without ever leaving the house. 006665-0 006710-0 Wireless Remote Extension Harness Smart Management Module (50 Amps) Recommended for use with the Wireless Remote on units up to 60 kw, required for use on units 70 kw or greater. Smart Management Modules are used in conjunction with the Automatic Transfer Switch to increase its power management capabilities. It provides additional power management flexibility not found in any other power management system. 006510-0 E-Stop E-stop allows for immediate fuel shutoff and generator shutdown in the event of an emergency. * Note: Bisque kits are used in conjunction with steel enclosures. Gray kits are used in conjunction with aluminum enclosures.

6 of 9 25 & 30 kw installation layout Drawing #0K8420-A (1 of 2) BATTERY 12V GROUP 26 NEGATIVE GROUND P/N: 077483 NOTES: SERVICE ITEM 1.5L OIL FILL CAP EITHER DOOR 1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1092 (43") WIDE X 1887 (74.3") LONG. REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES. 2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL, STATE, AND LOCAL CODES. 3. CONTROL PANEL / INFORMATION: - SEE SPECIFICATION SHEET OR OWNERS MANUAL - ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR. 4. REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS THE STUB-UP AREAS AS FOLLOWS: - HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION. - LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES. 5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS. 6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW. 7. EXHAUST SYSTEM MAXIMUM BACK PRESSURE: 24 INCHES H2O. 8. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS. 9. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5 (USE STANDARD SAE TORQUE SPECS) 10. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS. 11. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED. 12. EXHAUST MUFFLER ENCLOSED WITHIN GENERATOR ENCLOSURE, REMOVE ENCLOSURE TO ACCESS EXHAUST MUFFLER. OIL DIP STICK RIGHT DOOR AIR INTAKE (BOTH SIDES) OIL FILTER RIGHT DOOR RADIATOR/EXHAUST DISCHARGE AIR (BOTH SIDES) REMOVE COVER FOR ACCESS TO RADIATOR FILL CAP OIL DRAIN HOSE RIGHT DOOR RADIATOR DRAIN HOSE RIGHT DOOR AIR CLEANER ELEMENT RIGHT DOOR SPARK PLUGS RIGHT DOOR 665.5 [26.2"] CENTER OF GRAVITY (SEE NOTE 5) MUFFLER SEE NOTE 12 FAN BELT EITHER DOOR BATTERY RIGHT DOOR REFERENCE OWNERS MANUAL FOR PERIODIC REPLACEMENT PART LISTINGS. NEUTRAL AND CUSTOMER CONNECTION OPENING 630 (24.8) DOOR TYP VISE ACTION LATCH, ONE PER DOOR, ONE LIFT-OFF DOOR PER SIDE OF GENERATOR. REAR ENCLOSURE COVER PANEL SEE NOTE 4 SEE NOTE 3 978 (38.5) OVERALL HEIGHT 48 (1.8) CUSTOMER ACCESS ASSEMBLY, CONTROL PANEL ACCESS, BATTERY CHARGER LOCATED WITHIN SEE NOTE 4 783 (30.7) 44 (1.7) 1490 (57.6) 47.6 (2.9) WEIGHT DATA SHIPPING WEIGHT WEIGHT SHIPPING SKID WEIGHT GENSET ONLY ENGINE/KW ENCLOSURE MATERIAL 1.5L/25KW ST 392 [865] 30 [66] 422 [931] 1.5L/30KW ST 406 [895] 30 [66] 436 [961] 1.5L/25KW AL 352 [777] 30 [66] 382 [843] 1.5L/30KW AL 366 [807] 30 [66] 396 [873] LEFT SIDE VIEW REAR VIEW FUEL LINE CONNECTION 3/4" NPT FEMALE COUPLING RIGHT SIDE VIEW EXHAUST MUFFLER ENCLOSED WITHIN GENERATOR ENCLOSURE LIFTING PROVISION (4 PLACES) SEE NOTES 5, 8 AND CENTER OF GRAVITY DIMENSIONS. TOP VIEW RADIATOR/EXHAUST DISCHARGE AIR DIMENSIONS: MM [INCH]

25 & 30 kw installation layout REMOVABLE STUB-UP COVER 96 (3.8) Drawing #0K8420-A (2 of 2) 7 of 9 45 (1.8) TYP 13.5 X 29.5 MOUNTING SLOTS 4X 1380 (54.3) TYP MOUNTING SLOT CENTERS HIGH AND LOW VOLTAGE STUB-UP AREA NEUTRAL AND CUSTOMER CONNECTION OPENING 674 (26.5) STUB-UP AREA 104.5 (4.1) TOP VIEW 50 (1.9) 9 (.4) 51 (2.0) 100 (3.9) 1345 (60.8) 226 (8.9) STUB-UP AREA 735 (28.9) 1580 (62.2) 27 (1.0) TYP 723 (28.5) TYP MOUNTING SLOT CENTERS 776 (30.6) LEFT SIDE VIEW REAR VIEW DIMENSIONS: MM [INCH]

8 of 9 36, 45 & 60 kw installation layout Drawing #0K8636-A (1 of 2) NOTES: 1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1194MM (47") WIDE X 2256MM (88.8") LONG. REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES. 2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL, STATE, AND LOCAL CODES. 3. CONTROL PANEL / INFORMATION: - SEE SPECIFICATION SHEET OR OWNERS MANUAL - ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR. 4. REMOVE THE REAR ENCLOSURE COVER PANEL TO ACCESS THE STUB-UP AREAS AS FOLLOWS: - HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION. - LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES. 5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS. 6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW. 7. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS. 8. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5 (USE STANDARD SAE TORQUE SPECS) 9. MUST ALLOW FREE FLOW OF INTAKE AIR, DISCHARGE AIR AND EXHAUST. SEE SPEC SHEET FOR MINIMUM AIR FLOW AND MAXIMUM RESTRICTION REQUIREMENTS. 10. GENERATOR MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE AND THAT DISCHARGE AIR FROM RADIATOR IS NOT RECIRCULATED. 11. EXHAUST MUFFLER AND FAN BELT ENCLOSED WITHIN GENERATOR ENCLOSURE, REMOVE FRONT PANEL TO ACCESS. SERVICE ITEM 2.4L OIL FILL CAP EITHER SIDE OIL DIP STICK RIGHT SIDE OIL FILTER RIGHT SIDE OIL DRAIN HOSE RIGHT SIDE RADIATOR DRAIN HOSE LEFT SIDE COOLANT RECOVERY BOTTLE LEFT SIDE RADIATOR FILL CAP ROOF TOP AIR CLEANER ELEMENT LEFT SIDE SPARK PLUGS LEFT SIDE MUFFLER SEE NOTE 11 DRIVE BELT EITHER SIDE FAN BELT SEE NOTE 11 BATTERY LEFT SIDE LUBE OIL MAINTAINER ROOF TOP SUPPLY TANK FILL CAP REFERENCE OWNERS MANUAL FOR PERIODIC REPLACEMENT PART LISTINGS. RADIATOR/EXHAUST DISCHARGE AIR (BOTH SIDES) AIR INTAKE (BOTH SIDES) 758 [29.8] DOOR TYP REMOVE COVER FOR ACCESS TO RADIATOR FILL CAP 443 [17.5] 187 [7.4] 50 [2.0] 749.3 [29.5] CENTER OF GRAVITY (SEE NOTE 5) VICE ACTION LATCH, ONE PER DOOR, ONE LIFT OFF DOOR PER SIDE OF GENERATOR BATTERY 12V GROUP 26 NEGATIVE GROUND P/N: 077483 SEE NOTE 3 REAR ENCLOSURE COVER PANEL SEE NOTE 4 1170 [46.1] OVERALL HEIGHT 58 [2.3] TYP 1857 [73.1] TYP 46.5 [1.83] CUSTOMER ACCESS ASSEMBLY, CONTROL PANEL ACCESS, BATTERY CHARGER LOCATED WITHIN SEE NOTE 4 888 [35.0] OVERALL WIDTH 1000 [39.4] 1950 [76.8] OVERALL LENGTH WEIGHT DATA WEIGHT WEIGHT GENSET ONLY SHIPPING SKID ENGINE/KW ENCLOSURE SHIPPING WEIGHT MATERIAL 2.4L 36KW ST 569 [1255] 44 [98] 613 [1353] 2.4L 36KW AL 545 [1202] 44 [98] 590 [1300] 2.4L 45KW ST 596 [1313] 44 [98] 640 [1411] 2.4L 45KW AL 572 [1260] 44 [98] 616 [1358] RADIATOR/EXHAUST DISCHARGE AIR REAR VIEW FUEL LINE CONNECTION 3/4" NPT FEMALE COUPLING RIGHT SIDE VIEW DIMENSIONS: MM [INCH] LEFT SIDE VIEW TOP VIEW EXHAUST MUFFLER ENCLOSED WITHIN GENERATOR ENCLOSURE REMOVE COVER FOR ACCESS TO LUBE OIL MAINTAINER SUPPLY TANK REFERENCE OWNERS MANUAL

36, 45 & 60 kw installation layout REMOVABLE STUB-UP COVER 9 of 9 50 [2.0] TYP 13.5 X 29.5 MOUNTING SLOTS 4X 1733 [68.2] 1750 [68.9] TYP MOUNTING SLOT CENTERS 1950 [76.8] 162 [6.4] 217 [8.5] STUB-UP AREA 786 [30.9] STUB-UP AREA 162 [6.4] 9 [.4] 51 [2.0] 850 [33.5] 116 [4.6] TOP VIEW LEFT SIDE VIEW 12 [.5] HIGH AND LOW VOLTAGE STUB-UP AREA NEUTRAL AND CUSTOMER CONNECTION OPENING 25 [1.0] TYP 838 [33.0] TYP MOUNTING SLOT CENTERS 888 [35.0] REAR VIEW DIMENSIONS: MM [INCH] Drawing #0K8636-A (2 of 2) Generac Power Systems, Inc. S45 W29290 HWY. 59, Waukesha, WI 53189 generac.com 2015 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0L0037SBY-A Printed in U.S.A. 02/27/15