Information Bulletin. Fire Pump Battery Failures. Version 1.1 Approved for release August 2011

Similar documents
Vehicle battery BATTERY WARNING SYMBOLS BATTERY CARE

AS/NZS :2016. Grid connection of energy systems via inverters AS/NZS :2016. Part 1: Installation requirements

4. TECHNICAL SPECIFICATIONS

Automatic Battery Charger Switching mode with Micro-controlled Input: Vac / Output: 12Volt DC

Installation & Maintenance Manual

C3 Operating Instructions

Sentry Battery Charger. Installation and Operations Manual Section 75

Automatic Battery Charger Switching mode with Micro-controlled Input: Vac / Output: 12Volt DC

Guardian Battery Charger Series. Installation and Operations Manual Section 75

Australian/New Zealand Standard

The use of batteries in hazardous areas. 1. Type of batteries and technical evolution. March 2018

American National Standard for Lighting Equipment Voltage Surge Requirements

12 VDC Power Sources For Your RV

Automatic Battery Charger Switching mode with Micro-controlled Input: Vac / Output: 12Volt DC

BATTERY CHARGER CHR-1445

110W CARAVAN SOLAR PANEL KIT PLU

Australian/New Zealand Standard

Reference Number PDS 18 - (RIC Standard: EP SP)

Battery. Student booklet

185-40(02) (Head Restraints)

Part Number: DBDC10 / DBDC20 DC to DC Dual Battery Charger Manual

HUNTER PUMPS ELECTRIC FIRE PUMP SET

TECHNICAL BULLETIN Fig #1 - VRLA Battery Components. Intercell Welded Connection Strap joining neg. plates in parallel.

Cruising Charger Series OWNER S MANUAL

2/10/50 AMP 12 VOLT BATTERY CHARGER/ ENGINE STARTER

EUROBAT EUROBAT GUIDE FOR MOTIVE POWER VRLA BATTERIES

CONGRATULATIONS ON YOUR PURCHASE OF YOUR THUNDER BATTERY CHARGER! For your personal safety read, understand and follow the information provided in

Handling Precautions, Prohibitions and General Supply Notices for VARTA Microbattery GmbH CoinPower Lithium-Ion Batteries

SAFETY TRAINING LEAFLET 04 NITROUS OXIDE

Hazardous areas, as found around a service station, are classified into three zones as follow: Table 1: Zone Classification for Vapours

MODEL A97 SERIES. Switchmode Utility Rectifier/Battery Charger ECN/DATE

INTERNATIONAL STANDARD

Turbocharger / VTR..0, VTR..1 Original assembly instructions English

EU Mutual Recognition Technical Requirements

Instructions for use. Fiamm Motive Power energy dry ATEX

Material Safety Data Sheet

INSTRUCTION MANUAL. Maintenance-free Absorbent Glass Mat technology and valve-regulated batteries. (AGM / VRLA)

CONGRATULATIONS ON THE PURCHASE OF YOUR THUNDER DC TO DC BATTERY CHARGER.

INTERNATIONAL STANDARD

STANDARDIZATION ORGANIZATION FOR G.C.C (GSO) GSO 34/2007

Guidelines for Battery Electric Vehicles in the Underground

MODEL 2602A-12 3 STAGE AUTOMATIC BATTERY CHARGER OWNER S MANUAL SAVE THESE INSTRUCTIONS

Propane torch. Model Assembly And Operation Instructions

User s Manual. Automatic Switch-Mode Battery Charger

AS AS Australian Standard. Starter batteries Lead acid. This is a free 6 page sample. Access the full version online.

TRIP OF HORSHAM-REDCLIFFS 220 KV TRANSMISSION LINE AND MURRAYLINK INTERCONNECTOR ON 12 NOVEMBER 2015

FLEX CONNECTOR HEAT SHRINK SLEEVE INSTALLATION GUIDE

CICA HOIST SECTOR FAQs - RELEVANT STANDARDS / REGULATIONS. A. How do I find Australian Standards for cranes?

Marine Recreational Vehicle Batteries Made Simple

12V 1 AMP (1000 ma) Automatic Battery Charger & Maintainer

Caution Wear protective glasses and turn your face away when connecting or disconnecting from the battery.

NATIONAL REGULATOR FOR COMPULSORY SPECIFICATIONS ACT (ACT 5 OF 2008) AS AMENDED THROUGH THE LEGAL METROLOGY ACT (ACT 9 OF 2014)

Operating conditions of VRLA batteries in HVCBS and LVDBS Systems

IMPORTANT SAFETY INSTRUCTIONS

Extended Battery Cabinet for Nfinity

PI1500X Power Inverter User s Manual

What action is expected to take place in the foreseeable future in ADRs with regard to seat belts on school buses?

2020 Sulphur Cap. Challenges and Opportunities. Delivering Maritime Solutions.

BK10 10 CHANNELS BANK CHARGER For 12V lead-acid batteries

SAVE THESE INSTRUCTIONS

IMPORTANT SAFETY NOTICE

Product Guide. An Invensys company

AUTO CHARGE 12 HO MODEL #: MODEL #: MODEL #: AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

INSTALLATION AND OPERATING INSTRUCTIONS FOR FLOODED TUBULAR-HP AND TUBULAR-LM FAST CHARGE MOTIVE POWER BATTERIES

Air Operated Diaphragm Pumps Operating and Maintenance Instructions

Installation and Operating Instructions. Solar System Controller ISC3020

Part Number: DCDC10S / DCDC20S DC to DC Dual Battery Charger Manual

DRAFT TANZANIA STANDARD

MODEL A96 SERIES. 130Vdc Switchmode Utility Rectifier / Battery Charger. Used with LaMarche Power Cage ECN/DATE

777P-PT Battery Charging/Starting System Analyzer with Printer

DIGITAL BATTERY TESTER 12V

CBA Charge Controller

AS/NZS 3112:2004 AS/NZS

12/24 VOLT AUTOMATIC SOLAR CHARGE CONTROLLER

MP V 8A Electronic Smart Charger. Instruction and Information Manual

Korea Eco-label Standards EL764 Revised 19. JUL Ministry of Environment Batteries EL764:2012

DIGITAL BATTERY TORQUE WRENCH (BC-RAD SELECT) USER GUIDE

EU RO Mutual Recognition Technical Requirements

INSTALLATION AND OPERATING INSTRUCTIONS FOR FLOODED TUBULAR-HP MOTIVE POWER BATTERIES

Starting System. Learning Objective/Task (Starting System)

STIHL AP 100, 200, 300. Safety Precautions

ANTI-SYPHON VALVE INSTALLATION GUIDE

Kinsbursky Brothers. Battery Preparation and Packaging

1ZSE en, Rev. 4. On-load tap-changers, type UC User s manual

IEEE IAS Atlanta Chapter

Charging System Diagnosis and Repair 1

Permit Holder. Permitted Equipment

A48 / A48B (base plate) BATTERY CHARGER

Turbocharger / A100-L Original assembly instructions English

Operator s and Maintenance Manual

BAT 135 Battery Tester Operating Instructions

INTERNATIONAL STANDARD

PMA INTAKE FILTER SCREEN INSTALLATION GUIDE

100-30(02) (External Projections)

Installation, Maintenance and Warranty Flat Plate Battery

Safety. After working through this lesson, you should be able to:

STEP-BY-STEP INSTALLATION GUIDE

Managing Electrical Safety on Boats

EnergyCell FLA Series. Owner s Manual

Deep Cycle Battery Safety. First. Battery Handling, Maintenance & Test Procedures

Transcription:

Version 1.1 Approved for release August 21

1.0 Purpose Statement The purpose of this is to raise awareness amongst stakeholders about concerning industry trends associated with batteries supporting fire pump installations that serve fire hydrant and sprinkler systems. 2.0 Audience This is intended for: FPA Australia members Fire pumpset installers 3.0 Background Facilities managers and maintenance contractors Building Surveyors and certifiers. FPA Australia members have reported and recorded faults with batteries supporting fire pumpsets associated with fire hydrant and sprinkler installations. The consistent fault reported has been that flooded-cell lead-acid batteries are exploding. This is thought to be a result of failure and rupture of the battery casing due to internal gas accumulation and in some cases, ignition of this gas. The prescriptive deemed-to-satisfy provisions of the Building Code of Australia as referenced by Federal, State and Territory Governments across Australia, require fire hydrant and sprinkler systems to be installed in accordance with the following standards: AS 2419.1-2005, Fire hydrant installations System design, installation and commissioning AS 2118.1-1999, Automatic fire sprinkler systems General systems AS 2118.4-1995, Automatic fire sprinkler systems Residential AS 2118.6 1995, Automatic fire sprinkler systems Combined sprinkler and hydrant All of these standards require fire compression-ignition (diesel) pumpsets associated with these systems to be installed in accordance with AS 2941-2008, Fixed fire protection installations Pumpset systems. Version 1.1 Page 2

Clause 3.13.6 of AS 2941-2008 requires a warning sign to be fixed adjacent to batteries serving fire pumpsets, as follows: WARNING BATTERIES MUST COMPLY WITH AS 4029. NON-COMPLYING BATTERIES MAY EXPLODE 4.0 Issue AS 2941-2008 references AS 4029, which consists of three parts: AS 4029.1-1994, Stationary batteries Lead-acid Vented type This covers flooded-cell lead-acid type batteries similar to automotive starter batteries. AS 4029.2-2000, Stationary batteries Lead-acid Valve-regulated type AS 4029.3-1993, Stationary batteries Lead-acid Pure lead positive pasted plate type In the first instance, failure or rupture of the battery casing due to internal gas accumulation is a significant occupational health and safety issue. The corrosive substances contained within the battery casing are particularly harmful to clothing, skin and eyes and can be fatal if ingested. This is particularly concerning as typically there is no prior warning that failure or rupture is imminent when gases are ignited. Such failures may also render the diesel fire pumpset inoperable, which may also affect the performance of the fire hydrant or sprinkler system it serves. FPA Australia is aware that reported failures or ruptures are likely to be the result of incorrect charging of flooded-cell lead-acid automotive batteries that have been poorly maintained. Incorrect charging can cause electrolysis of the electrolyte fluid (sulphuric acid and water) that surrounds the lead plates within the battery. Electrolysis produces hydrogen and oxygen gases and depletes the electrolyte of water. Whilst these types of batteries typically have vent holes to allow gases to Version 1.1 Page 3

escape the casing, these are insufficient to expel a high rate of gas production. Gas build-up can swell the casing, which may lead to ruptures and leakage of the fluid. Any spark associated with this build-up of gas will result in an explosion. The use of AS 4029 compliant batteries is required by AS 2941 and should prevent such incidents occurring, provided they are correctly maintained. Industry sources suggest that it is difficult to obtain confirmation from some battery manufacturers that their products are certified to AS 4029. However, FPA Australia is aware that the risk is likely to be significantly reduced, even with batteries that aren t certified to AS 4029.2, if the following conditions are met: The battery is correctly maintained. The battery is of the Absorbed Glass Matt (AGM) type. These batteries do not require maintenance of the electrolyte fluid and are sealed except for the inclusion of a safety pressure relief valve to discharge gas build-up. The technology adopted by AGM batteries produces water as a by-product of the chemical reaction process. This means that there is no requirement to maintain electrolyte levels manually. This eliminates the identified risk of explosion that results from batteries drying out through depletion of electrolyte. The correct float charge voltage is used. Float charge voltage is commonly recommended to be between 13.0 VDC and 13.8 VDC at 26.70C; however, each manufacturer will have a specific charge voltage for their batteries. It is extremely important that the float charge voltage of the battery is set in accordance with the battery manufacturer s requirements to prevent incorrect charging and gas build-up, which may result in an explosion risk. 5.0 Recommendations FPA Australia recommends that stakeholders take the following steps to ensure the safety and integrity of batteries supporting fire pumpsets: 1. Wear eye protection and appropriate personal protective equipment (PPE) when conducting maintenance. 2. Use additional caution at pumpset start up (either manual start up or when automatic start up is expected after instigating pressure drop of fire protection systems). 3. Observe OH&S rules that prevent the introduction of ignition sources within the proximity of batteries. 4. Where possible, determine that installed batteries comply with AS 4029.2. Where batteries have not been marked, check with the supplier of the batteries to ensure their compliance. Version 1.1 Page 4

6.0 Disclaimer 5. Batteries should be of the Absorbed Glass Matt (AGM) type, regardless of compliance with AS 4029.2, to reduce the likelihood of failure or explosion due to gas build-up caused by incorrect charging and depletion of electrolyte. 6. Always make sure the maintenance and the float charge voltage of the battery are in accordance with the manufacturer s requirements. 7. Ensure that any documentation associated with installation of fire pumpsets clearly specifies the use of batteries in accordance with recommendations 1 to 6 above. In particular, when replacing the battery, replace any flooded-cell lead-acid battery with an AGM type battery. This may require the charging voltage to be re-adjusted. 8. Where wet (flooded-cell) batteries with cell caps are fitted, check the electrolyte levels at each service or test before starting the diesel motor. If the electrolyte level is at or below the level of the plates, distilled water must be added before attempting to start the pump. A sufficient quantity of distilled water should be left where batteries are located at each site for battery top up. 9. Consider replacing existing batteries if the system s original installation pre-dates the AS 2941-2008 requirement or if the batteries are older than 2 years. Mark or record the date the battery was installed using an indelible marker or similar method. 10. Install appropriate warning signage. The opinions expressed in this correspondence reflect those of FPA Australia however are subject to change based on receipt of further information regarding the subject matter. You should interpret the technical opinion or information provided carefully and consider the context of how this opinion / information will be used in conjunction with the requirements of regulation (state and/or federal); relevant standards, codes or specifications; certification; accreditation; manufacturer s documentation and advice; and any other relevant requirements, instructions or guidelines. FPA Australia does not accept any responsibility or liability for the accuracy of the opinion / information provided, nor do they accept either directly or indirectly any liabilities, losses and damages arising from the use and application of this opinion / information. 7.0 References Fire Protection Association Australia Technical Advisory Committee 4/8/9. National Construction Code Series Volume 1, Building Code of Australia Published by Australian Building Codes Board, Canberra. Australian Standard AS 2118.1-1999, Automatic fire sprinkler systems General requirements Published by Standards Australia International Ltd. Version 1.1 Page 5

Australian Standard AS 2118.4-1995, Automatic fire sprinkler systems Residential Published by Standards Australia International Ltd. Australian Standard AS 2118.6-1995, Automatic fire sprinkler systems Combined sprinkler and hydrant Published by Standards Australia International Ltd. Australian Standard AS 2419.1-2005, Fire hydrant installations System design, installation and commissioning Published by Standards Australia International Ltd. Australian Standard AS 2941-2008, Fixed fire protection installations Pumpset systems Published by Standards Australia International Ltd. Australian Standard AS 4029.1-1994, Stationary batteries Lead-acid Vented type - Published by Standards Australia International Ltd. Australian Standard AS 4029.2-2000, Stationary batteries Lead-acid Valve-regulated type Published by Standards Australia International Ltd. Australian Standard AS 4029.3-1993, Stationary batteries Lead-acid Pure lead pasted plate type Published by Standards Australia International Ltd. Copyright 21 Fire Protection Association Australia. Material distributed by FPA Australia is subject to copyright. Any information within this publication may not be reproduced in printed or electronic form without permission from FPA Australia. For more information, please see www.fpaa.com.au or contact FPA Australia on: 1300 731 922. Version 1.1 Page 6