White Paper. Application of Resistive/Reactive Load Banks for kva Testing

Similar documents
White Paper Load Banks for Power System Testing

White Paper. Direct Current Load Banks for Battery Capacity Testing

White Paper. Load Banks for Regenerative Braking Applications

ASCO Power Technologies - Avtron Load Banks ASCO LOAD BANKS ASCO Power Technologies - Froment Load Banks

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

Load Bank. Fundamental of Load Bank TYPES OF LOAD BANKS LOAD TEST CAPACITY LOAD BANK OVERVIEW

Alternator as a voltage Generating source and its response to the leading power factor loads

Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less)

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

Legal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:

Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kva to 10 MVA or less)

GENERATOR INTERCONNECTION APPLICATION

TECHNICAL TERMS AND ABBREVIATIONS

CUSTOMER / ACCOUNT INFORMATION Electric Utility Customer Information (As shown on utility bill)

Electric Utility Contact Information Indiana Michigan Power

Is Uncorrected Power Factor Costing You Money?

Power Quality and Energy Management

PPHVC Power Quality Solutions. ABB PQC-STATCON Benefits and advantages

American Journal of Science, Engineering and Technology

Electrical Power Electric power electrical electric power Electric power electric electric

CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

CHAPTER 6 DESIGN AND DEVELOPMENT OF DOUBLE WINDING INDUCTION GENERATOR

Power Factor Correction

Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)

Standby Power Systems

MIPSYCON 2014 Can a Grid be Smart without Communications? A Look at an Integrated Volt Var Control (IVVC) Implementation

Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)

HVAC OPTIMIZATION DON T LET THE SAVINGS SLIP. Kevan N Dean CEM, CEP Mike G. Lovan LEED AP

HOKKIM. Control & Protection Relays. giving you control. Utilization: Power Factor Regulator : 14-STEP CYCLIC POWER FACTOR REGULATOR.

Power System Solutions (PSS)

Automatic DC Power Supply/Battery Charger

NORTH CAROLINA INTERCONNECTION REQUEST APPLICATION FORM. Utility: Duke Energy Progress

Form G5-1 PACIFIC GAS AND ELECTRIC COMPANY GENERATION PRE-PARALLEL INSPECTION

Table of Contents. CHAPTER 1 BASIC ELECTRICAL THEORY (Essential for Journeyman and Master s Licensing Exams)... 1

PQC - STATCON The ultra fast Power Quality Compensator

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

4-Day Power System Analysis, Coordination, System Studies

Technical brochure. The Vector series The ABB comprehensive solution for automatic power factor correction

DRAFT. Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

Modular Standardized Electrical and Control Solutions for Fast Track Projects

Est DCM Double Conversion Module 400kVA - 800kVA

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

LUNERA BALLASTLED TECHNOLOGY AND POWER FACTOR

Power Solutions Manager Generac Power Systems, Inc.

Technologies for ToT & Power Electronics Test Facility. under NaMPET-II CDAC, Thiruvananthapuram

S C ELECTRIC EUROPE LTD. Excellence Through Innovation. Harnessing the Wind. November 2011 Descriptive Bulletin E

Southern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management

Illuminator Series CR NEMA 3R

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

Electric Networks/Ina Lehto Updated Original 12/2011

LUNERA BALLASTLED TM TECHNOLOGY AND POWER FACTOR

Solid-State Relays. Solid-State Relays. Features. Description. Overview

Interconnection System Impact Study Report Request # GI

Solid-State Relays. Solid-State Relays. Features. Description. Overview

Power Systems Trainer

Power Quality. Static Var Generator (SVG) SVG Wallmount & SVG Cabinet Mount

International Journal of Advance Engineering and Research Development. Automatic Power Factor Correction in EHV System

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

Three-Phase Power Conversion in a Single Step

The Status of Energy Storage Renewable Energy Depends on It. Pedro C. Elizondo Flex Energy Orlando, FL July 21, 2016

Welcome. Power Survey International

PSNH INTERCONNECTION REQUEST

TABLE OF CONTENTS. About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1

D Series: UPS UPTO - 300KVA - Three / Three Phase

ABB n.v Power Quality in LV installations

Power Protection Discrete Automation & Motion South Africa

Review paper on Fault analysis and its Limiting Techniques.

Optimizing Emergency Power Systems for Health Care Applications

Table of Contents. CHAPTER 1 ElECTRiCAl THEoRY Mike Holt enterprises, inc neC.Code ( )

Ensuring the Safety Of Medical Electronics

Distinctive Features: Bidirectional solar PCU Hybrid inverter (Solar/ Grid/BATT) Vector Modulated Inverter Control Multiple DSP control operation

GENERATING FACILITY INTERCONNECTION APPLICATION. Part 1 Introduction and Overview

Electrical Power Systems 2014/15

Microgrid solutions Delivering resilient power anywhere at any time

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System

Chapter 3.1: Electrical System

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

ABB Wind Care Service Offering

Is Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics

ABB Microgrids and Energy Storage. Nathan Adams, Director, Technology and Business Development

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

EH2741 Communication and Control in Electric Power Systems Lecture 3. Lars Nordström Course map

Synchronous motor control. 8/15/2007 Powerflow Technologies Inc 1

Emergency Back-up Power Generation for Water & Wastewater Facilities

Power Conditioning of Microgrids and Co-Generation Systems

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

Power Factor Correction

MITSUBISHI STAMFORD P CM control system. This generator set is manufactured in facilities certified to ISO 9001.

Distinctive Features: Bidirectional solar PCU Hybrid inverter (Solar/ Grid/BATT) Vector Modulated Inverter Control Multiple DSP control operation

Using the Phoenix MultiPlus to reduce operating cost of a generator

UPS Ratings-Not so Apparent

ICT TRANSFORMERS. Industrial Control Transformers provide a low and safe control voltage for the operation of many electromagnetic devices

Pump ED 101. Power Factor (Part 2) - - Electricity Behaving Better

Final User Smart Grid Trainer AEL-FUSG

Surabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality

Grid Management Voltage Control Distribution Grid Voltage Regulation with DER. Michael Sheehan, P.E. IREC Pacific Northwest Solar Partnership

Transcription:

White Paper Application of Resistive/Reactive Load Banks for kva Testing

Application of Resistive/Reactive Load Banks for kva Testing Resistive load banks are the most commonly used load banks for the testing of generator sets and power systems. They provide full kw loading to the power source and help evaluate the generator sets engine cooling, exhaust, and fuel systems. However, due to its design a resistive load bank will not load to full nameplate kva capacity. To achieve full kva load testing a reactive load bank will be required. Resistive Load Banks The kw of a resistive load bank is real power in electrical terms. When a resistive load bank is used to test an engine generator set the engine will produce its full horsepower rating, dissipate engine exhaust gases, and produce thermal energy into the engine cooling system. The resistive load bank in fact, will completely test the engine and its various systems. It is important to understand that the generator or power system will not be loaded to its full kva rating. Resistive load banks utilize resistors, which only provide kw loading at 1.0 (unity) power factor. Reactive Load Banks Reactive load banks are designed to simulate either an inductive, or a capacitive load depending on the type of load expected on the power system. Reactive/Inductive Load Measured in kvar (Kilo Volt Amperes Reactive), a reactive/ inductive load converts current into a magnetic field. Inductive reactance resists the change to current, causing the circuit current to lag voltage. The inductive power factor is the most common reactive load. Examples of devices producing reactive/inductive loads include motors, transformers and chokes. Reactive/inductive load bank testing is routinely required in OEM Test Cells, Acceptance Testing, Health Care Facilities, Federal & State Agencies and off-shore maritime applications. Reactive/Capacitive Load Measured in kvarc (capacitor kvar rating at the system voltage), a capacitive load charges and releases energy. Capacitive reactance resists the change to voltage, causing the circuit current to lead voltage. A reactive/capacitive load bank is similar to a reactive/inductive load bank in rating and purpose. However, with leading power factor loads reactive power is applied to the system which results in an improvement in overall power factor. The electronic and non-linear loads Current (I) Figure 1: Power Factor Chart I (Leading Current: Capacitive + Resistive) Voltage (V) Current (I cos( )) in phase with V I (Lagging Current: Inductive + Resistive) 2

Photo courtesy of ASCO Power Technologies simulated by capacitive load banks are typical of the Telecommunications, Computer or Uninterruptible Power Supply (UPS) Industries. Reactive/capacitive load testing is also used in applications requiring heavy inductive loads and/or power factor correction, such as in the Manufacturing and Mining industries. Resistive/Reactive Load Banks Typically, facilities require motor-driven devices, transformers and capacitors. If this is the case, then the load banks used for testing require reactive power compensation. The ideal solution is a combination of both resistive and reactive elements in one load bank package. Resistive/reactive loads are able to mimic motor loads and electromagnetic devices within a power system, as well as provide purely resistive loads. Many backup generators and turbines need to be commissioned at nameplate capacity using a combination of resistive and reactive load to fully qualify their operating capability. Using a resistive/reactive load bank enables comprehensive testing from a single unit. A range of resistive/reactive load banks are available to simulate these types of loads on a power source and the transformers, relays and switches which will distribute the power throughout the facility. Resistive/reactive load banks are great choices for testing turbines, switchgear, rotary UPS, generators and UPS systems. They can also be used for integrated system testing of utility substation protection systems, particularly for more complex relays like distance, directional overcurrent, power directional and others. A resistive/reactive inductive and/or capacitive load is often required to test solar inverters to ensure solar panels can be stopped from producing electricity in the event of a power outage. The resistive/reactive combination load banks are used to test the engine generator set at its rated power factor. In most cases this is 0.8 power factor. Using Resistive/Inductive Load Banks to Test to ISO 8528 (BS7698) Part 6. ISO 8528 (BS7698) part 6 is the standard for testing engine-driven generating sets. It sets out general test requirements and defines a functional and an acceptance load bank test. Functional tests must always be performed and usually occur at the manufacturer s test cell. Acceptance tests are optional, they may be done on site and are often witnessed by the customer or a representative. ISO 8528 (BS7698) part 6 defines three performance classes - G1, G2, and G3. A further class, G4, is reserved for performance criteria which are agreed upon between the supplier and the buyer. Each performance class has different criteria for a range of characteristics of the generating set. G1 is the least stringent and generally applies to small, simple generating sets, intended to supply unsophisticated loads. G2 is broadly equivalent to commercially available power. G3 is intended for sets which are powering strategically critical loads or those which particularly require a stable and accurate power supply. 3

Typically resistive/reactive load banks are used in the manufacturer s facility to class a gen-set to G1, G2, or G3 rating and to ensure 0.8pf kva nameplate ratings are met. Power testing and maintenance companies use resistive/reactive load banks on site to ensure ISO 8528 standards are met in gen-sets during operation. The resistive/reactive load ensures full gen-set testing takes place and allow ISO 8528 standard to be met. Load Control and Monitoring Resistive/Reactive load banks require sophisticated load control and monitoring so operator is aware of the various responses in testing. Controls should allow for individual resistive, reactive, or combined (kva) loading along with ability to preset loads on a percentage basis. The ideal platform is software control where operator can set up and store load profiles, capture transient responses, and data log, so test results can be analyzed. Besides the standard Volt, Amp, Frequency and kw monitoring, combined units need to monitor Power Factor and kva. Automatic testing ensures the same load test parameters are met every time a test is performed. ISO 8528 standards (as mentioned earlier in this paper) are provided in market leading load bank controls, and present a pass or fail report. Original manufacturers classes (G1, G2, or G3) are able to be referred back to ensure the health of the genset over time and kva ratings are met. Today most reputable load bank manufacturers offer sophisticated control software. If not, there are many third party software packages that could facilitate load control. Parallel Systems This is a screen shot of software showing power factor rating. (Photo courtesy of ASCO Power Technologies.) When testing installations with multiple generator sets operating in parallel the use of resistive/reactive load banks is justified. Having the ability to fully load the generator with the reactive component is usually required to calibrate the load sharing and voltage regulating systems of parallel generator systems. The load bank system can be connected to the common paralleling bus and be used for testing individual engine generators or any combination of engine generators operating in parallel. A 3000 kw load bank could be used to test a single 1500 kw generator set at full kw or two 1500 kw generators in parallel at full nameplate kw load. If the 1500 kw generator sets were on line in parallel, the operator could load them to two-thirds of their combined or individual kva rating. Summary The correct selection and installation of a load bank is important to effectively determine the operating capability of the power source. The use of a combined Resistive/Reactive Load Bank is an essential tool for power source verification where leading or lagging power factors are required. ASCO Power Technologies has the product depth and breadth to provide practical solutions along with the support to assure your power system will provide many years of safe operation. 4

ASCO Power Technologies Avtron 6255 Halle Drive Cleveland, OH 44125 Tel: 216.573.7600 LBsales@ascopower.com ASCO Power Technologies NJ Froment & Co. Ltd Easton-on-the-Hill Stamford, PE9 3NP United Kingdom Tel: +44 1780 480033 froment.sales@ascopower.com loadbanks.ascopower.com whitepapers.ascopower.com customercare@ascopower.com The ASCO and ASCO Power Technologies marks are owned by Emerson Electric Co. or its affiliates and utilized herein under license. 2017 ASCO Power Technologies. All Rights Reserved. ASCO. Innovative Solutions.