PROCESS VFD SAVINGS CALCULATOR USER GUIDE CONTENTS ENERGY EFFICIENCY FOR BUSINESS CUSTOM INCENTIVES CUSTOM-TO-GO

Similar documents
LIGHTING SAVINGS CALCULATOR USER GUIDE CONTENTS SMART $AVER CUSTOM INCENTIVES CUSTOM-TO-GO

Best Practice Variable Speed Pump Systems

Optimizing Airflow on Dust, Mist and Fume Collection Systems

Prescriptive HVAC and Mechanical Equipment Application

Vaneaxial Fans. Series 25 Series 53 Series 53C Series 54 Series 55 HARTZELL. Hartzell Fan, Inc., Piqua, Ohio

MOTOR SAMPLE PROBLEM #1 Low-Slip Drive Belts

DR Hub October 2018 Release Notes

Docket 50-ER-108 Algoma Utilities. Final Form Rate and Rule Tariff Sheets Amendment 78. Filed By: Public Service Commission of Wisconsin

Prescriptive Program Rebate Application

Fiberglass Axial Flow Fans. Series 28 Series 28B. Series 34 Series 35 Series 35V. Series 29 Series 29B HARTZELL

Prescriptive Program Rebate Application

Motor and Drive Efficiency Drive rebate application

Solar*Rewards Frequently asked questions system size and customer usage

Save Thousands of Dollars Per Year!

InvestSmart Business Energy Upgrades HVAC Equipment Catalog 01/01/2017

Impact Evaluation of 2004 Compressed Air Prescriptive Rebates

Pepco & Delmarva Power. Commercial & Industrial Energy Savings Program Grocery and Convenience Stores October 11, 2012

Lighting and Lighting Controls Energy Savings Opportunities Technical Training Series

Revised Cal. P.U.C. Sheet No E Cancelling Original Cal. P.U.C. Sheet No E

ELECTRIC SCHEDULE AG-ICE Sheet 1 AGRICULTURAL INTERNAL COMBUSTION ENGINE CONVERSION INCENTIVE RATE - EXPIRATION TRANSITION RATE

COMMERCIAL MOTORS & VARIABLE SPEED DRIVES REBATE APPLICATION

September 21, Advice No , NEW Schedule 50 Retail Electric Vehicle Charging Rates

INDUSTRIAL EQUIPMENT INCENTIVES FOR OREGON BUSINESS CUSTOMERS

LINEA Low Discharge Roof Exhausters

Sustainability Strategies

APP S 674 pumps APP S / APP S APP S

Centrifugal Utility Fans - SFD/SFB

Series

The Practical Pumping Handbook

General Catalog. A New Vision for Quality Pumps. General Catalog

Prescriptive Program Rebate Application

Fan Efficiency Grades and System Effect and Their Effects on HVAC Systems

Commercial & Industrial Retrofit 2017 Compressed Air Incentive

ENERGY STORAGE. resource guide & user instructions

Steve Schouten. Donna Densmore

Laboratory Exhaust Systems

Southern California Edison Company Demand Response Appendices to SCE-1, Volumes 1-4 ERRATA Replacing Appendix D, Pages D-1 & D-3

ELECTRIC SCHEDULE E-9 EXPERIMENTAL RESIDENTIAL TIME-OF-USE SERVICE FOR LOW EMISSION VEHICLE CUSTOMERS

SERVICE THE GORMAN-RUPP COMPANY P.O. Box 1217 MANSFIELD, OH FX

EXHIBIT A ORDINANCE NO. O CITY OF LAURINBURG, NORTH CAROLINA SCHEDULES OPR RESIDENTIAL TIME-OF-USE SERVICE

West Campus Power Plant

PAHT pump PAHT X

Twin City Fan & Blower

Energy Savings and Incentives with PG&E. Chad Stout Account Manager

Variable Frequency Drives

RATE APPLICATION MANUAL. Kansas City Board of Public Utilities

Cooling Efficiency 2017 Cooling Equipment Rebate Application

APUA TARIFFS ELECTRICITY TARIFFS

WINDOM ELECTRIC UTILITY: RATE STUDY. Tim Miller Manager, Financial Analysis & Rates Missouri River Energy Services December 30, 2015

Xcel Energy s Energy Efficiency Programs. Derek Shockley Trade Relations Manager Commercial and Industrial

Meter Insights for Downtown Store

Introducing Uconnect Rewards via MSER!

PART 2 GUIDELINES. To be eligible to receive a financial incentive, the following conditions must be met:

THE NARRAGANSETT ELECTRIC COMPANY LARGE DEMAND RATE (G-32) RETAIL DELIVERY SERVICE

Airscrew 200+ Vmax Vaneaxial Fans

Realizing Energy Savings in Fan and Pump Systems using Variable Frequency Drives. Schaedler Yesco Expo 2012

Shedding Light on S lar Overview of Solar Finance

Tubular Centrifugal Fans

Benefits of EC Motor Technology for Automotive Air Handling

Rate Schedule Entry User Manual (for the Load Profile) 2003

Energy Saving Solutions Using Variable Frequency Drives

Noble County Rural Electric Membership Corporation

CAMERON HYDRAULIC DATA

Lighting Efficiency Lighting Retrofit Rebate Application

BAC, BAF, BAH Central Station Air Handlers

Pepco & Delmarva Power. Commercial & Industrial Energy Savings Program Small Business Program October 3, 2012

Twin City Fan & Blower

Cyclone Custom Centrifugal Fans

KISSsoft 03/2016 Tutorial 7

FAN PERFORMANCE MODULATION

Centrifugal Inline Fans Models SQ-M and BSQ-M. Direct and Belt Drive

Bulletin BCF 103 DESIGN 10A BACKWARD INCLINED WHEELS

Net Metering & Compensation Seminar

Industry best 5 year fan housing warranty, 1 year motor warranty

KISSsoft 03/2018 Tutorial 7

Fan Powered Terminal Units FPV, FDV Series Variable Volume Parallel Flow

Variable Speed Drives Controlling Centrifugal Pumps Energy Savings

Buy All Sell All Rider for Interconnection of Renewable Generation

PUMP HEART OF PLUMBING SYSTEM V.SRINIVAS

Goulds Lenntech. API th Edition / ISO nd Edition API BB2 Two-Stage, Between-Bearing, Radially Split

Trash- and Solids-Handling Centrifugal Pumps Series 2100 Quality Design Features Assure Long, Trouble-Free Service

It s What s Inside that Counts

Motors and Variable Speed Drives for Pumps and Fans. Reid Hart, PE

Fluid control equipments

M50 L50 Series - 50Hz Metric Edition Multistage Regenerative Turbine Pumps

2019 BQDM Extension Auction Frequently-Asked Questions Updated January 29, 2018

Unitil Energy Demand Response Demonstration Project Proposal October 12, 2016

Series 4600F. HSC Fire Pumps & Packaged Systems

Power Metrics International INC Richmond Terrace Staten Island, NY 10302

North Dakota Commercial and Industrial Electric Prices

EXHAUST FANS CUD & CUB UPBLAST FANS

PAHT pumps / PAHT G pumps / ATEX PAHT G pump

Series 8500 Centrifugal Swingout Fans Design 8510 Centrifugal Airfoil Design 8520 Centrifugal BI

Fristam Powder Mixer. Function Principle

Prescriptive Rebate Program

Energy Design Assistance

multiflow Multistage Heavy Duty Axially

Air Moving Solutions. MODULAR plenum fans

Retro-commissioning for Peak Electric Demand Reduction in New York City. Kim Lenihan , ext.

Appendix G - Danvers Electric

Transcription:

PROCESS VFD SAVINGS CALCULATOR USER GUIDE ENERGY EFFICIENCY FOR BUSINESS CUSTOM INCENTIVES CUSTOM-TO-GO CONTENTS 1. Getting Started... 2 2. Measure Tool Description... 2 2.1. Applicable Types of Equipment and size Covered by the Tool... 4 3. Measure Tool Use... 6 3.1. Select Your Service Territory... 6 3.2. Tool Inputs... 7 3.3. Tool Outputs Savings Summary... 21 3.1. Tool Outputs Notes and Error Messages... 23

1. GETTING STARTED The current version of the Process Variable Frequency Drive (VFD) Savings Calculator can be downloaded from http://duke-energy.com/eebtools. It is included in the Energy Efficiency for Business Custom-To-Go tool suite, which contains a number of useful tools that can help you calculate savings and incentives for various energy saving measures. The ZIP output file from the calculator must be submitted with the Energy Efficiency for Business application (Step 1) in order to receive an incentive payment. For application submissions and questions about the application process, contact us at CustomIncentives@dukeenergy.com. 2. MEASURE TOOL DESCRIPTION Variable Speed Drives (VSD), also referred to as Variable Frequency Drives (VFD), are used for controlling AC motors. The VFD is a solid-state device that controls the frequency and voltage supplying the motor. Many AC motors used for process applications are oversized to accommodate peak loads even though the average loads are lower. The most common applications involve centrifugal pumps and fans which have large savings potential due to their power versus speed curves. Without VFDs the motors are left operating at full speed or are controlled by primitive part-load strategies. Often times the motors cannot be cycled on and off too frequently so the motors remain at full speed. The VFD offers large energy savings for these AC motors that operate at partial loads. This tool was developed to assist customers in identifying and estimating VFD saving opportunities on process pumps and fans. Process VFD Calculator can be used for facilities with the characteristics shown in Table 1. Description Table 1: EMS Savings Calculator Common Features Measure Feature States North Carolina South Carolina Locations All Building Types Office School K-12 College/University Retail/Service Restaurant Hotel/Motel (Guest Rooms) Hotel/Motel (Other) Medical Grocery Warehouse Light Industry Heavy Industry Page 2 of 25 Version 1.0.2 5/17/2016

Parking Garage Operating Hours Monday Friday, 8am 5pm Monday Friday, 7am 7pm Monday Friday, 6am 10pm Monday Friday, 24 hours per day Monday Friday, 6am 8pm, Saturday and Sunday, 8am 6pm Monday Saturday, 8am 5pm Monday Saturday, 10am 9pm Monday Saturday, 7am 7pm, Sunday, 8am 5pm Monday Sunday, 8am 5pm Monday Sunday, 9am 9pm Monday Sunday, 11am 11pm Monday Sunday, 6am 10pm Monday Sunday, 24 hours per day System Types Fan Pump Version 1.0.2 5/17/2016 Page 3 of 25

2.1. Applicable Types of Equipment and size Covered by the Tool Process VFD Calculator covers the pump and fan systems described in Table 2. Table 2: Equipment Coverage Matrix Description Type Control Type Drive Type Centrifugal Fan Airfoil, SISW On/Off Direct Airfoil, DIDW Outlet Dampers V. Belt Backward Inclined Backward Curved, SISW Inlet Vanes Rubber Chain Backward Inclined Backward Curved, DIDW Radial, SISW Radial Tip, SISW Forward Curved, SISW Forward Curved, DIDW Tubular Industrial and Commercial Air Handling Industrial and Commercial Material Handling Industrial and Commercial Long Shavings Centrifugal Centrifugal Exhaust On/Off Direct Exhaust Fan Outlet Dampers V. Belt Rubber Chain Axial Fan Vaneaxial On/Off Tube Axial Outlet Dampers Propeller Axial Exhaust Fan Axial Exhaust On/Off Outlet Dampers Centrifugal Pump End Suction ANSI/API End Suction Slurry End Suction Stock End Suction Sewage Large End Suction API Double Suction Multistage Boiler Feed Axial Double Suction Vertical Turbine On/Off Throttling Recirculating Direct V. Belt Rubber Chain Direct V. Belt Rubber Chain N/A Page 4 of 25 Version 1.0.2 5/17/2016

Positive Displacement Pump N/A Recirculating N/A Version 1.0.2 5/17/2016 Page 5 of 25

3. MEASURE TOOL USE 3.1. Select Your Service Territory In order to properly load the correct utility program the user must first select the service territory associated with their account. To begin, select your state from the list presented in the Select State dialog box. If the State of Indiana, Kentucky, or Ohio is selected the application will open the appropriate service territory version of the software. If one of the Carolinas is selected the application needs a little more information. In these cases, a Select Service Territory dialog box will appear. Please either enter the service address zip code or select the Utility associated with the service account. To return to the state selection dialog box click on the Choose State link. Page 6 of 25 Version 1.0.2 5/17/2016

3.2. Tool Inputs Tool inputs are done either by selecting predefined dropdown options or entering numerical values as prompted by the tool. Version 1.0.2 5/17/2016 Page 7 of 25

Inputs window is divided into tabs. Refer to tables below for input details. Page 8 of 25 Version 1.0.2 5/17/2016

Table 2 Site Inputs Version 1.0.2 5/17/2016 Page 9 of 25

Input Name Duke Electric Account Number Customer Name Site Address State Building Type Operating Hours Square Footage Average Billing Rate ($/kwh) Options System Type Description / Purpose Enter the customer s Duke Energy Progress electric account number. Enter the name of company or facility. Enter address of the facility. Select state from pull down. Select building type from pull down. Select operating hours from pull down. Enter square footage of the facility. Do not enter decimals (whole numbers only). Default can be used or actual average can be entered by user. Check if the project is Federal Owned or New Construction Select Fan or Pump The selection of a system type (Fan or Pump) will determine if the Fan Inputs (Table 4 and Table 5) or the Pump Inputs (Table 6 and Table 7) will be required. Page 10 of 25 Version 1.0.2 5/17/2016

Table 3 Fan System Details Inputs Input Name System Type Exhaust Fan? Average Fan Inlet Air Temperature ( F) Site Elevation (ft) System Design Maximum Flow (CFM) Description / Purpose Select existing fan type from pull down If the existing fan an exhaust fan (Yes/No) Enter the average fan inlet temperature in F. Enter the site elevation of the fan in feet. Enter the system s design maximum design flow per the manufactures fan performance curve in CFM Version 1.0.2 5/17/2016 Page 11 of 25

System Pressure at Max Design Flow (in Wg) Minimum Allowable System Pressure (in Wg) Enter the system s pressure at maximum design flow per the manufactures fan performance curve in inches Wg. If there is a minimum allowable operating pressure for the fan system, enter it here. Otherwise, leave blank. Page 12 of 25 Version 1.0.2 5/17/2016

Table 4 Fan Details Input Name Input Type Fan ID Fan Type Control Type Fan Drive Type Description / Purpose Select advanced if you know the fan efficiency, motor efficiency, motor RPM, motor service factor, and motor enclosure type. Enter an ID for the fan Select existing fan type from pull down Select existing fan control type from pull down Select existing fan drive type from pull down Version 1.0.2 5/17/2016 Page 13 of 25

Actual Fan Speed (RPM) Fan Flow at BEP (CFM) Static Pressure at BEP (in WG) Fan Efficiency at BEP (%) Motor Size (hp) Motor Speed Motor Enclosure Motor Efficiency (%) Motor Service Factor Enter the actual fan speed when a belt drive has been specified. This field is meant to account for differences in the motor and fan gear ratios. Enter fan flow at the best efficiency point (BEP), as specified by the manufacturer. Enter fan pressure at the best efficiency point (BEP), as specified by the manufacturer. Enter maximum pump efficiency, as defined by the manufacturer s performance information. Select fan motor size in horse power, as specified by the manufacturer. Select fan motor speed in RPM, as specified by the manufacturer. Select fan motor enclosure type, as specified by the manufacturer. Enter fan motor full load efficiency, as specified by the manufacturer. Select fan motor service factor, as specified by the manufacturer. Page 14 of 25 Version 1.0.2 5/17/2016

Table 6 Pump System Details Inputs Input Name System Type Input Type Number of Pumps Pump Configuration Control Type Description / Purpose Select existing pump type from pull down Select Advanced if you know the System Design Flow (gpm) and System Design Pressure (ft). Select the number of pumps included in the project. For projects with more than one pump, select pump configuration Select existing pump control type from pull down Version 1.0.2 5/17/2016 Page 15 of 25

Fluid Specific Gravity System Design Flow (gpm) System Design Pressure (ft) System Static Head (ft) Min. Allowable System Pressure (psig) Enter the specific gravity of the fluid being pumped. Examples: Water - 1.0 Seawater - 1.025 Gasoline - 0.7 Corn oil - 0.92 Milk - 1.03 Wine - 1.0 Beer - 1.0 Clarified sewage sludge - 1.1 Glycol Based Water Solution (25% @ 40F) - 1.048 To calculate specific gravity of slurry: S m = 1 + C w ( S l S 1) t S m = Specific gravity of mixture or slurry S l = Specific gravity of liquid phase S t = Specific gravity of solid phase C w = Concentration of solids by weight Enter system flow at design conditions (Centrifugal pumps only). Enter system pressure at design conditions (Centrifugal pumps only). Enter system static head. Static head is the difference in height (ft) between the source and destination of the pumped liquid. Closed systems have a static head of zero feet. If there is a minimum allowable operating pressure for the pumping system, enter it here. Be sure to include static lift in the minimum pressure value. Otherwise, leave blank. S l The Pump Details tab includes the option to set all pumps identical or to provide pump details for each pump. To enter pump details select a pump ID and press the Edit Pump button. Page 16 of 25 Version 1.0.2 5/17/2016

This will open up the input screen detailed in Table 7. Version 1.0.2 5/17/2016 Page 17 of 25

Table 7 Pump Details Input Name Input Type Pump ID Pump Type Pump Stages Pump Flow at BEP (gpm) Pump Pressure at BEP (ft) Pump Efficiency at BEP (%) Motor Size (hp) Motor Speed Motor Enclosure Motor Efficiency (%) Description / Purpose Select advanced if you know the pump efficiency, motor efficiency, motor RPM, motor service factor, and motor enclosure type. Enter an ID for the pump Select existing pump type from pull down Select the number of stages in the pump. Enter pump flow at the best efficiency point (BEP), as defined by the manufacturer's performance information (Centrifugal pumps only). Enter pump discharge pressure at the best efficiency point (BEP), as defined by the manufacturer's performance information (Centrifugal pumps only). Enter maximum pump efficiency, as defined by the manufacturer's performance information. (Centrifugal pumps only). Select fan motor size in horse power, as specified by the manufacturer. Select fan motor speed in RPM, as specified by the manufacturer. Select fan motor enclosure type, as specified by the manufacturer. Enter fan motor full load efficiency, as specified by the manufacturer. Page 18 of 25 Version 1.0.2 5/17/2016

Motor Service Factor Select fan motor service factor, as specified by the manufacturer. Table 8 Operating Modes Input Name Number of Operating Modes VFD Peak Efficiency (%) Description / Purpose Select the number of operating modes for the equipment (fan or pump). Enter the peak efficiency of the proposed VFD, as specified by the manufacturer. Version 1.0.2 5/17/2016 Page 19 of 25

Minimum VFD Speed (%) Enter the minimum allowable VFD speed. Must be between 30% and 100%. To edit the Operating Modes, select an Operating Mode and press the Edit Operating Modes button. This will open up the input screen detailed in Table 9. Table 9 Operating Mode Input Name Operating Mode Name Annual Hours Flow (GPM/CFM) Select Equipment Operating Period Description / Purpose Enter a name to identify the operating mode. Enter the annual operating hours of the equipment (fan or pump). Enter the flow required during the operating profile. CFM for fan measures and GPM for pump measures. Check equipment which operate during the operating mode. Select the operating period. If monthly, select the months the equipment will operate. Once all information is entered, select Next button on the bottom right corner of the Operating Modes tab. The tool will then calculate savings based on the information entered and display the results. Page 20 of 25 Version 1.0.2 5/17/2016

3.3. Tool Outputs Savings Summary The following table describes the tool outputs. Table 9- Measure Energy Savings and Incentive Name Total Estimated Incentives Estimated Annual Electric Bill Reduction Site Baseline, kw Code Baseline, kw Description / Purpose Estimated total incentive for the project in dollars Estimated annual electric bill reduction in dollars Estimated maximum on-peak demand of the existing system Estimated maximum on-peak demand of the code baseline system Version 1.0.2 5/17/2016 Page 21 of 25

Proposed, kw Site Baseline, kwh Code Baseline, kwh Proposed, kwh Savings - Site Baseline, kw Savings - Site Baseline, kwh Savings - Code Baseline, kw Savings - Code Baseline, kwh Estimated Energy Use Incentive ($) Estimated maximum on-peak demand of the proposed system Estimated energy use of the existing system Estimated energy use of the code baseline system Estimated energy use of the proposed system Estimated maximum on-peak demand savings for the measure (difference between site baseline and proposed) Estimated energy savings for the measure (difference between site baseline and proposed) Estimated maximum on-peak demand savings for the measure (difference between code baseline and proposed) Estimated energy savings for the measure (difference between code baseline and proposed) Estimated energy use incentive for the project in dollars Page 22 of 25 Version 1.0.2 5/17/2016

3.1. Tool Outputs Notes and Error Messages While using the Process VFD Calculator, you may see one of the following error messages: This indicates that you have not made a selection or entered an appropriate value in one or more required fields. Please review your inputs and make sure that you have entered appropriate values in the indicated input fields. This indicates that the flow that you have entered for the current operating mode exceeds the system design flow. Please reduce the flow for the current mode or review your input for the system design flow. This indicates that too many operating hours have been entered. The maximum number of hours for all operating modes combined is 8,760. Please review your operating mode inputs. Version 1.0.2 5/17/2016 Page 23 of 25

This indicates that the proposed retrofit qualifies for incentives through the prescriptive incentives program. Measures that qualify through the prescriptive program cannot apply for incentives through the custom incentives program (classic custom or custom-to-go). This indicates that the proposed project exceeds the upper limit of the Custom-to-Go program and is only eligible for incentives through the Classic Custom program. Please submit an application to the Classic Custom program for this project. This indicates that your project will result in negative savings and incentives. Please review your measure inputs and ensure that all inputs are correct. You will not be able to generate a report for a project that has negative savings. Page 24 of 25 Version 1.0.2 5/17/2016

This indicates that your project may not be a good candidate for a VFD due to a system flow that would cause the VFD to operate below its lower limit. Please review your operating mode and minimum VFD speed inputs. This indicates that the motor for the indicated pump appears to be undersized, based on the pump or system flow. Please review your pump and/or fan inputs along with your operating mode inputs. Version 1.0.2 5/17/2016 Page 25 of 25