HI-LOW-HI MOTOR STARTING AN APPROACH FOR STARTING DEEP WELL SUBMERSIBLE PUMPS

Similar documents
4-Day Power System Analysis, Coordination, System Studies

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

Illinois State University. Electrical Safety Procedure

ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

NFPA 70E Standard for Electrical Safety Requirements for Employee Workplaces. Table Hazard Risk Category Classification

TRANSMISSION SYSTEMS

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

ECET Distribution System Protection. Overcurrent Protection

SIGNAL WORDS QUALIFIED PERSON

NEC REQUIREMENTS FOR GENERATORS

Low Voltage Fuses For Motor Protection

Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

MAGNETIC MOTOR STARTERS

Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2

Service Entrance Methods

Application of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear

Grounding Of Standby & Emergency Power Systems

Transformer Protection

3.2. Current Limiting Fuses. Contents

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Electrical Safety CSA Z462 & NB Regulations

Load Side PV Connections

Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals?

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

MOTOR SURVEY. Solutions for Industry

Cost Benefit Analysis of Faster Transmission System Protection Systems

Extra-High-Voltage SF 6 Gas-Insulated Switchgear

KT7. Methods. of Applying. & Molded Case Circuit Breakers F119. Motor Circuit Controllers

Equipment Protection. Transformers 600V or Less

WELLS RURAL ELECTRIC COMPANY Adopted: March 1976 Revised: March 21, 2017 Reviewed: August 21, 1998 RULE NO. 2

Equipment Protection. Transformers 600V or Less

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

Electrical Depth. Josh Kreutzberger Lighting/Electrical

Now - Up To 400A Mains!

Are the New 2005 NEC Selective Coordination Requirements Causing an Increase in Arc Flash Energies and Reducing Distribution System Reliability?

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

Selective Coordination

take to complete our safety compliance

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

MYRON ZUCKER CALMANUAL POWER FACTOR CORRECTION APPLICATION GUIDE INC.

IAE-101: Electrical Fundamentals for Non-Electrical Personnel

Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

STEP Motor Control Centers

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

SECTION MOTOR CONTROL

Not all Low Voltage Switchgear is created equal

Design Standards NEMA

January 30, Ms. Safety Director Sample Medical Corp. PO Box X Somewhere, CT. Re: NFPA 70E Hazard Assessment. Date of Visit.

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

PROTECTION AND CONTROL

Energized Electrical Work

Electrical Safety and Overcurrent Protection

Compact Circuit Protector (CCP) Application Note

Generator Fire Safety: Generator assemblies should be located outside the building.

Understanding Arc Flash Hazards. White Paper

Benefits of VFD for single to three phase conversion

Low and medium voltage service. Power Care Customer Support Agreements

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

Motor Protection. Presented By. Scott Peele PE

OVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)

90.2 Scope. The installation of electrical conductors, equipment and raceways for:

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

Emergi-Lite Experts in central power supply systems

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

Table of Contents. CHAPTER 1 BASIC ELECTRICAL THEORY (Essential for Journeyman and Master s Licensing Exams)... 1

Table 1.-Elemsa code and characteristics of Type K fuse links (Fast).

Variable Frequency Drive Basics

ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits

Future Proof Your Arc Flash Assessment

Modular Standardized Electrical and Control Solutions for Fast Track Projects

Power Break II Switchboard

Recommended Procedures

Application Description

Electrical Safety and Reliability: Short-Circuit Current Rating (SCCR) Equipment SCCR made easy

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

Busway Construction. Bus Bars

FUSES. Safety through quality

Arc-Flash Mitigation Technologies. Dennis Balickie

ECET 211 Electric Machines & Controls Lecture 3-1 (Part 1 of 2) Motors, Transformers and Distribution Systems

BP OIL -- TOLEDO REFINERY

Motors " GRUNDFOS GROUNDWATER SERVICE MANUAL CONTENTS. Grundfos Motor Specifications... Page 2

ACHIEVING MAXIMUM BENEFITS WITH A FUSE PROTECTED MOTOR CONTROL CENTER

Not all Low Voltage Switchgear is created equal

Arc flash hazard mitigation

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

ECET Circuit Design Motor Loads. Branch Circuits. Article 210

Integrating Roles Within Electric Utilities to Achieve Arc Flash Safety. MIPSYCON Presenters Neil Stiller & Bob Cooke

EPS-ECONOMY PUMP STARTER

T300MVi JK OEM POWER CELLS MEDIUM VOLTAGE VACUUM CONTACTOR. Reliability in motion. Reliability in motion

FUSE: SAFE & RELIABLE

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

Transcription:

ABSTRACT HI-LOW-HI MOTOR STARTING AN APPROACH FOR STARTING DEEP WELL SUBMERSIBLE PUMPS Scott Honeyfield, P.E. Marcelino N. Trujillo, P.E. Parkhill, Smith & Cooper Inc. 501 W. San Antonio El Paso, Texas 79901 In order to be cost effective, deep-well submersible pump designs typically use medium voltage motors (2,400V and above). Running at medium voltage reduces conductor size, and smaller conductors are beneficial to the design and construction of the well. However, medium voltage creates its own challenges for the operator. The number of electricians trained to work on medium voltage equipment is typically less than those who work on 480V equipment. Availability of medium voltage replacement parts is also a common issue. And finally, the Hazard/Risk Category Classification, as defined by NFPA 70E, is higher when performing tasks on medium voltage equipment. The standard approach to starting a medium-voltage motor would be to install a medium-voltage motor starter, however another option available to operators is a Hi-Low-Hi motor starting design. This will cost a little more, take up more overall real estate, and will not eliminate all medium-voltage gear, but it will allow the operator to utilize a low-voltage 480V starter. Motor starters, whether they are across the line, soft starts, or variable speed drives, are typically the piece of equipment that requires the most troubleshooting. Installing a starter that is a make and model already used in the water system, and which the electricians are already familiar with, will go a long way in increasing the reliability of a well field system. This paper will analyze and present a Hi-Low-Hi type motor starting configuration that was designed and built for the Potter County Well Field, which supplies water for Amarillo, Texas. The incoming utility voltage was 13,200V. This voltage was stepped down to 480V for motor starting (and miscellaneous site loads), and then stepped back up to 2,400V for the feeders going to the submersible motor. This paper will address design considerations that are unique to this type of configuration. The overall goal is to provide operators with options when designing their well-gathering systems. KEYWORDS Hi-Low-Hi motor starting, deep well submersible pumps. BACKGROUND Concepts presented in this paper may at first seem atypical. However, with the necessary exploration and development of ever deeper groundwater sources, these concepts become more practical and help address issues and concerns with deep-well development.

Photo 1 Hi-Low-Hi Well Site STEP UP TRANSFORMER MEDIUM VOLTAGE OVERCURRENT PROTECTION LOW VOLTAGE STARTER IN WELL HOUSE Configuring starting equipment in a Hi-Low-Hi configuration was developed out of a necessity to solve a real need, economically, for the groundwater industry. Groundwater depletion in many aquifers has resulted in the need to lower the intake of the pumping equipment commensurate with declining water levels. Deeper aquifers are being explored and developed for new sources of potable or treatable water. Due to this increased depth, engineers are moving away from line shaft pumping equipment toward submersible equipment. Submersible pumping equipment may be preferred over line shaft pumping equipment for the following reasons: Line shaft pump disadvantages: < < < < Not practical to depths exceeding 600 800 feet. Mechanical losses can result in larger horsepower requirements. Line shaft size can become excessively large, requiring increased column pipe sizes. Using oil to lubricate shaft rotating elements can result in the development of biological growth, rendering the well non-potable.

< Biological pathogens can be exceptionally difficult to remove/control/treat once established in a water well and the adjoining aquifer. Submersible pump advantages: < Noise abatement. < Have been used in deep installations without modification. < Higher voltage will typically provide for a smaller motor case, allowing for smaller diameter well casings. < Use of medium voltage motors significantly reduces the cost of the downhole power cable. A typical example would be the comparison between 600 volt three conductor 350 KCML power cable and 5KV three conductor #2 AWG power cable. The 600V cable is six times more expensive. For deep set pumping equipment, this cost can more than offset the capital cost of the medium voltage starting equipment. When considering submersible motors, several factors must be deliberated before their selection. Among these considerations are motor speed, voltage and starting conditions. Efficiency and economics will also require considerable attention, as technical selections can affect both. Unique to submersible motor use is the starting requirement imposed by the manufacturers. Typically, manufacturers require their motors to start as quickly as possible and, across-the-line starting is preferred. This may seem somewhat counterintuitive, especially with large horsepower units. Several criteria contributing to this requirement include the following: < Long, slender motor configuration requires immediate cooling. Cooling is derived from the pumped fluid passing across the outside of the motor. Manufacturers prefer motors be started in in 0.8 seconds or less. < Submersible motors are configured such that their thrust bearings carry the load imposed by the motor, pumping equipment and the pumped water column. Extended periods of nonoperation can result in loss of the lubrication film between the thrust bearing and the thrust plate. Resulting in extreme wear during starting. The quicker the motor is brought up to full speed the sooner the lubricating film is re-established. < Duration of heat is lessened with quicker starting. However, power utilities will likely impose starting restrictions on large motors, in which case alternate methods will have to be considered. The most common alternate starting methods can include soft start and variable frequency drives (VFD). Should the power utility impose starting conditions, most motor manufacturers will capitulate by conceding to allow the motor to develop a third of the full speed immediately, with the remainder of the speed controlled by VFD or soft starting.

CHALLENGES OF MEDIUM VOLTAGE EQUIPMENT It is evident that medium voltage provides an advantage for deep well submersible pumps. However, for most water utilities, using medium voltage equipment (anything over 600V) is a challenge. The following is a summary of those challenges. Real Estate Medium voltage equipment is simply bigger than low voltage equipment. For this project, a medium voltage MCC would have been 6 feet wide by 3 feet deep, versus the low voltage MCC which was 5 feet wide by 2 feet deep. The workspace in front of the starter, as required by NEC 110.34, also would have been one foot longer for medium voltage equipment. The additional space needed for a medium voltage starter adds up quickly, and often will push the well field operator into the next standard size prefabbed electrical building. Training Finding electricians with experience in medium voltage starters is difficult, and when you do find them, they are at a higher fee. In-house medium voltage training will be in addition to the standard electrical training that electricians undertake. Most electricians are typically trained for either Electrical work or Journeyman lineman work as defined in the Texas Occupations Code. Per Texas Occupations Code, 1305.002(11), Electrical work means any labor or material used in installing, maintaining, or extending an electrical wiring system and the appurtenances, apparatus, or equipment used in connection with the use of electrical energy in, on, outside, or attached to a building, residence, structure, property, or premises. The term includes service entrance conductors as defined by the National Electrical Code. Topics on the electrical work exams include services, wiring methods, switchboards, conductors, control devices, motors and generators, special occupancies, and plan reading. Very little, if any, of standard electrical work training involves medium voltage starters. Per Texas Occupations Code, 1305.002(12), Journeyman lineman means an individual who engages in electrical work involving the maintenance and operation of equipment associated with the transmission and distribution of electricity from the electricity's original source to a substation for further distribution. Journeyman lineman training involves medium- and highvoltage equipment, but again, little of the standard training pertains to medium voltage starters. Spare Parts and Equipment Replacement Medium-voltage parts are more expensive and are longer lead items than low voltage. As an example, just a single medium-voltage fuse will cost almost 5 times as much as a low-voltage fuse. Fast Acting Fuse: 480V (250A) - $140 each 2,400V (50A) - $675 each

Electrical Safety The requirements of NFPA 70E are more stringent when working on medium voltage equipment. To begin with, the shock protection boundaries are longer. Table 1 shows the increase in boundary requirements when the nominal system voltage goes above 750V. Table 1 NFPA 70E Table 130.4(C) (a) The higher shock potential of medium voltage also requires a higher rating of PPE equipment. NFPA 70E 130.7 (C)(7)(a) states that rubber insulating gloves shall be rated for the voltage for which the gloves will be exposed. Most electricians will have Class 00 gloves. If they are required to work on 2,400 Volt starters, they will need Class 1 gloves. Table 2 Voltage Classifications for Rubber Gloves Tag Color Class Proof Test Voltage Max Usage Voltage AC/DC AC/DC Beige 00 2,500 / 10,000 500 / 750 Red 0 5,000 / 20,000 1,000 / 1,500 White 1 10,000 / 40,000 7,500 / 11,250 Yellow 2 20,000 / 50,000 17,000 / 25,500 Green 3 30,000 / 60,000 26,500 / 39,750 Orange 4 40,000 / 70,000 36,000 / 54,000 (Table 1 information provided by Workplace Safety Awareness Council, Personal Protective Equipment For the Hands (Gloves), www.wpsac.org)

And finally, for operators who use NFPA 70E to determine their Hazard/Risk Category and arc flash boundary, these values will also increase. Table 3 shows us that performing infrared thermography and other non-contact inspections outside the restricted approach boundary increases the Hazard/Risk Category from 1 for 480V MCCs, to 3 for medium voltage starters. And working on energized electrical conductors and circuit parts, including voltage testing, increases the Hazard/Risk Category from 2 to 4. Table 3 NFPA 70E Table 130.7 (C) (15) (a) Tasks Performed on Energized Equipment 600V class motor control centers (MCCs) Parameters: Maximum of 65 ka short circuit current available; maximum of 0.03 sec (2 cycle) fault clearing time; minimum 18 in. working distance Potential arc flash boundary with exposed energized conductors or circuit parts using above parameters: 53 inches Perform infrared thermography and other non-contact inspections outside the restricted approach boundary CB or fused switch or starter operation with enclosure doors open Work on energized electrical conductors and circuit parts, including voltage testing Hazard/ Risk Category Rubber Insulating Gloves Insulated and Insulating Hand Tools 1 N N 1 N N 2 Y Y NEMA E2 (fused contactor) motor starters, 2.3kV through 7.2kV Parameters: Maximum of 35 ka short circuit current available; maximum of up to 0.2 sec (12 cycle) fault clearing time; minimum 36 in. working distance. Potential arc flash boundary with exposed energized conductors or circuit parts using above parameters: 422 inches Perform infrared thermography and other non-contact 3 N N inspections outside the restricted approach boundary Contactor operation with enclosure doors open 2 N N Work on energized electrical conductors and circuit parts, including voltage testing 4 Y Y For the reasons listed above, water utility operators prefer to use low-voltage equipment whenever possible. And although the Hi-Low-Hi motor starting approach does not eliminate all

medium voltage equipment, it does move the most complex piece of equipment to the low voltage side of the equation. Keeping the motor starter on low voltage will increase reliability, and decrease yearly maintenance costs. COST ANALYSIS The advantages gained by a Hi-Low-Hi arrangement comes at a capital cost. The Hi-Low-Hi motor starting approach has two pieces of equipment that would not be necessary in a typical motor starting arrangement. Those pieces are the step up transformer, and the additional short circuit and overload protection needed after the voltage is stepped up. Figure 1 Cost Comparison This project consisted of 21 wells with motors ranging from 100 to 300 hp. The owner was provided with an Opinion of Probable Cost for using 480V throughout, including the larger low voltage cable, (Option 1). And bids were solicited for using a Hi-Low-Hi configuration (Option 2), and using medium voltage throughout (Option 3), (See Figure 1). As anticipated, the lowest cost solution was Option 3, medium voltage throughout. However, using a Hi-Low-Hi approach was less costly than using low voltage throughout, and only $8,735 more per site than the medium voltage option. For the client, it was worth $8,735 per site to get the added system reliability.

KEY DESIGN ISSUES Hi-Low-Hi motor starting is not a typical arrangement, and there are several key design issues that must be considered closely. Sizing the Step-Up Transformer In most industrial applications, a single motor is only a small fraction of the load for a transformer; therefore, the inrush current of the motor is insignificant compared to the overall capacity of the transformer. However, when a transformer is dedicated to a single motor, the inrush current as a percentage of the transformer capacity is significant, and will affect the sizing of the transformer. Also, a transformer needs time to recover from the inrush current it supplies during a motor start. The greater the number of starts per hour required, the greater the size of the transformer. Even at just one start per hour, the transformer must be sized large enough to handle the Locked-Rotor kva of the motor. It is not simply a one-to-one ratio of matching horsepower to KVA. (The ABB Distribution Transformer Guide provides guidance for sizing dedicated transformers, as well as other reference material dealing with distribution transformer applications.) Medium Voltage Short Circuit and Overload Protection Motor overcurrent and ground fault protection is typically part of the starter. However, NEC 430.225 requires the designer to provide this protection on the motor circuit which in the Hi- Low-Hi approach is at medium voltage. For this project an outdoor medium voltage fusible disconnect with R-rated dual element fuses was used to provide fault-current protection. CTs and PTs were also housed in the medium voltage disconnect that provided current and voltage sensing to a medium voltage motor protection relay. This relay (GE Multilin 469) provides thermal overload, overcurrent, and unbalance protection for the motor as well as multiple metering and status values. This relay, which senses the medium voltage parameters, is wired to trip the low voltage starter when values exceed their trip limits. Transformer Inrush Current vs Motor Inrush Current In the Hi-Low-Hi approach, the starter is energizing a transformer, not a motor. NEMA rated 480V starters are designed to handle the inrush current of a motor. They are not necessarily designed to handle the inrush current of a transformer. Typical motor inrush currents can range from 8 to 12 times the motor full load amps in the first 20 to 30ms. The amount of transformer inrush current can be much higher. The industry standard for transformers is 25 times the full load amps for 10ms, and 12 times the full load amps for a duration of 100ms.

The inrush capacity of motor starters is not typically provided on manufacturers cut-sheets. This information will have to be obtained directly from them. In most cases, some type of current restriction will need to be utilized. For this project, standard off-the-shelf, solid-state reduced-voltage soft starters were used. (Using reduced-voltage starters was also a requirement of the local power utility.) Time vs. Current Curves Given the amount of overcurrent protection coordination that must be achieved at both low and medium voltage, developing a Time vs. Current coordination curve during design is essential. The coordination curves in Figure 2 are for a 300HP well and were developed using SKM System Analysis CAPTOR software. The software allows you to quickly determine the most optimum settings for the motor protection relay, and helps identify any coordination issues that may exist. Figure 2 Well 516 Time vs. Current Curves

CONCLUSIONS The Potter County Well Field has been in service for four years. All 21 well pump motors are starting reliably, and there have been no electrical-related availability issues. This project has successfully met all of the owner s project requirements. Hi-Low-Hi motor starting is not a panacea for all well projects. It is one option to consider when designing deep-well submersible pumps. The operator must weigh the experience and capabilities of his electricians, along with the pros and cons of the Hi-Low-Hi motor starting approach. Table 4 Pros and Cons of Hi-Low-Hi Motor Starting Pros Smaller shock hazard on the motor starter. Availability and cost of replacement parts. Availability of third party electricians with experience working on low voltage starters. Smaller electrical room footprint. Cons Additional capital cost. More complex design. Additional outdoor real estate for step-up transformer and motor overcurrent protection. Efficiency losses in step-up transformer. When confronted with the circumstances of pushing pumping equipment deeper into a well, the Hi-Low-Hi configuration can be a logical and economical approach for operators. REFERENCES NFPA 70: National Electrical Code, 2014 Edition NFPA 70E: Handbook for Electrical Safety in the Workplace, 2012 Edition RSMeans Electrical Cost Data, 36 th Annual Edition, 2013 Edition ABB Distribution Transformer Guide, Distribution Transformer Division, June 1979, Revised March 2002 Workplace Safety Awareness Council, Personal Protective Equipment For the Hands (Gloves), www.wpsac.org SKM Power Tools, Electrical Engineering Software, Copyright 2008, SKM System Analysis, Inc.