DISTRIBUTED RESOURCE GENERATION Feed-In-Tariff Single Phase

Similar documents
Northeastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5

Northeastern Rural Electric Membership Corporation Columbia City, Indiana

Document Requirements for Engineering Review PV Systems v1.0 6/9/2017

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018

Noble County Rural Electric Membership Corporation

Louisville Gas and Electric Company

Noble County Rural Electric Membership Corporation

White River Electric Association, Inc. Net Metering Information & Service Requirements

INTERCONNECTION STANDARDS FOR CUSTOMER-OWNED GENERATING FACILITIES 25 kw OR LESS PUBLIC UTILITY DISTRICT NO. 1 OF CHELAN COUNTY

Net Metering Interconnection Requirements

Information Packet Kissimmee Utility Authority Customer-Owned Renewable Generation Interconnection And Net Metering Program

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1

40kW (and under) Solar/Inverter Installations Generation Interconnection Application to Minnesota Power

TILLAMOOK PEOPLE S UTILITY DISTRICT

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

TERMS AND CONDITIONS

Columbia Water & Light Interconnection & Net Metering Agreement Electrical Facility

Definitions. Scope. Customer Generation Interconnection Requirements

New Ulm Public Utilities. Interconnection Process and Requirements For Qualifying Facilities (0-40 kw) New Ulm Public Utilities

REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw

Bulletin Interconnection of electric power production sources Rules 2-010, , , , , , and

Application for Operation of & Net Metering for Member-Owned Generation Name: Mailing Address: City: County: State: Zip Code: _

GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM

Section 6. Generation Interconnection

ENGINEERING SPECIFICATION

INTERCONNECTION for GENERATING FACILITIES Up to 20 MW

RENEWABLE ENERGY PROGRAM Step 1, Section 1 ENROLLMENT FORM FOR LEASED RESIDENTIAL AND SMALL COMMERCIAL PHOTOVOLTAIC AND WIND TURBINE SYSTEMS

Renewable Energy Interconnection Manual for Small Size Systems ( 10kW in NM 20kW in TX) Renewables and Emergent Technologies Group

JACKSON ELECTRIC COOPERATIVE POLICY NO. 305

Overview of State Distributed Generation Interconnection Rules

SCHEDULE NO. ACG33 NET METERING SERVICE

RULES FOR CUSTOMER INTERCONNECTION OF ELECTRIC GENERATING FACILITIES

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 RULE NO. 17 NET ENERGY METERING

Consumer Guidelines for Electric Power Generator Installation and Interconnection

Interconnection Process for Generation Systems

AGRALITE ELECTRIC COOPERATIVE 320 EAST HIGHWAY 12 P.O. BOX 228 BENSON, MN PHONE: (320) FAX: (320)

Guideline for Using IEEE 1547 for Solar PV Interconnection Page 1

Montana-Dakota Utilities Co. A Division of MDU Resources Group, Inc. 400 N 4 th Street Bismarck, ND 58501

Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System

DAKOTA ELECTRIC ASSOCIATION DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS

Southern Company Interconnection Process. Dexter Lewis Research Engineer Research and Technology Management

NET METER REQUEST FORM

STATE OF NORTH DAKOTA DISTRIBUTED GENERATION INTERCONNECTION REQUIREMENTS TABLE OF CONTENTS

INTERCONNECTION REQUIREMENTS POLICY

Net +Plus Connection Code

Policy Bulletin No. 25 Net Metering. Public Utility District No. 1 of Klickitat County 1313 South Columbus Goldendale, WA 98620

CHAPTER 25. SUBSTANTIVE RULES APPLICABLE TO ELECTRIC SERVICE PROVIDERS.

INTERCONNECTION RULES AND REGULATIONS FOR NET ENERGY METERING SYTEMS

Louisiana Net Metering Service. Customer Information Package

City of Washington, Kansas Electric Department. Net Metering Policy & Procedure For Customer-Owned Renewable Energy Resources

Renewable Energy Interconnection Manual for Small Size Systems ( 10kW in NM 20kW in TX) Renewables and Emergent Technologies Group

Technical Requirements for Renewable Energy Power System

RULES & REGULATIONS FOR RENEWABLE GENERATION SYSTEMS 2. SUMMARY OF APPLICATION AND INTERCONNECTION PROCESS

December 13, This document was filed with the Board of Public Utilities on December 13, It is awaiting final approval by BPU staff.

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

MEMBER RELATIONS POLICY NO SUBJECT: INTERCONNECTION OF CUSTOMER GENERATION RESOURCES

REQUIREMENTS FOR GRID INTERCONNECTION OF RENEWABLE GENERATION SYSTEMS

CHOCTAWHATCHEE ELECTRIC COOPERATIVE, INC RESIDENTIAL SERVICE--NET METERING RIDER

COMMUNITY SOLAR PROGRAM

RATE 765 RENEWABLE FEED-IN TARIFF

Legal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:

Application for Interconnection and Net Metering Revision: 1 Revised: November 7, 2017

REVISION NO.: 7 EFFECTIVE: 07/07/16

Rider : NET METERING SERVICE AND ELECTRICAL SYSTEM INTEGRATION

JEA Distributed Generation Policy Effective April 1, 2018

City of, Kansas Electric Department. Net Metering Policy & Procedures for Customer-Owned Renewable Energy Resources

Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)

Douglas Electric Cooperative Roseburg, Oregon

S T A F F R E P O R T

SOUTH HADLEY ELECTRIC LIGHT DEPARTMENT Net Metering Policy As Amended 03/23/16 By the South Hadley Municipal Light Board

PSNH INTERCONNECTION REQUEST

Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System

Xcel Energy Guidelines for Interconnection of Electric Energy Storage with the Electric Power Distribution System

Umatilla Electric Cooperative Net Metering Rules

Distributed Generation Interconnection Policy

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS

MCCOOK PUBLIC POWER DISTRICT McCook, Nebraska BOARD POLICY NUMBER 488

Net Metering Service. Customer Information Package

NET METERING PROGRAM. Technical Interconnection Requirements

Oncor Application for Interconnection of Distributed Generation

3. Customer shall provide space for metering equipment and meter base as per Springville City Power requirements.

Heber Light & Power Electric Service Rule No. 14 NET METERING SERVICE

City of Banning Electric Utility - Residential Self Generating Facility Program (Photovoltaic Systems <48kW)

Adopted: September 24, 2015 Version: Version 1.0

Net Metering Program

Exelon Energy Delivery Interconnection Guidelines for Generators 2 MVA or less

March Commercial Distributed Generation with Optional Energy Storage Systems

To complete the process for a net metering interconnection, please follow the steps below:

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

M.P.S.C. No. 2 Electric Third Revised Sheet No. 65 (Rate Case) Cancels Second Revised Sheet No. 65

Springfield Utility Board Net Metering Policy Adopted on February 13, 2008 (Resolution 08-1)

Application to Amend Net Metering Service under RS Appendix B. Revised RS 1289 Clean and Black-lined

Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less)

ACTION FORM. EXHIBIT #1 Regular Council Meeting of 11/27/2006

REVISED 8/1/2018 SOLAR PHOTOVOLTAIC DISTRIBUTED GENERATION CUSTOMER GUIDELINES, APPLICATION & WGC INTERCONNECTION AGREEMENT

BC Hydro Rate Schedule 1289 Revision 1 Effective: April 20, 2018 Page 6-1

FRENCH BROAD ELECTRIC MEMBERSHIP CORPORATION RATE SCHEDULES

Transcription:

PAGE 1 OF 7 USE: Requirements and guidelines for interconnection of single phase customer owned, (DR) Distributed Resource generation source, to NIPSCO s electric system, configured for. LATEST REVISION: PREVIOUS REVISION 10-01-14 ORIGINATED 01-12 Updated Reference section, Eligibility, and figures. PREVIOUS NUMBER REFERENCE: 170 IAC 4-4.3-12, IURC Rule for Interconnection Electric Service Tariff - Rate 665, latest revision IEEE 1547, latest revision EPRI TR-111489 UL 1741, latest revision ANSI/IEEE C37.2 (Device Function Numbers), latest revision NIPSCO s Standard ER 16-600, latest revision National Electric Safety Code, latest revision IEC/NEC (Indiana Electrical Code/National Electrical Code), latest revision Other applicable national, state, and local codes and ordinances. SPECIFICATION: 1. DEFINITIONS: 1.1 Distributed Resource (DR) Generation - The use of power generation technology, which may be interconnected with NIPSCO s electric system. 1.2 - A tariff that allows a customer to interconnect to NIPSCO s electric system and to sell electric production to NIPSCO. 1.3 Islanding - A condition when the DR generation unit becomes separated from NIPSCO s electric system, but continues to operate in an energized state. Islanding may be intentional for reliability purposes when NIPSCO s electric system has an outage. Intentional islanding is allowed only if the DR generation unit and load are isolated from NIPSCO s de-energized electric system prior to islanding. (See Spec. 6) 1.4 Static Power Converters (SPC) (Also known as Inverter.) - A device used to convert DC power into AC power. SPC s may be line-commutated or self commutated. SPC s solid state components may include such protective functions as over current protection, phase sequence, synchronizing, under/over voltage, under/over frequency, etc. 1.4.1 Line-Commutated - The SPC requires the presence of NIPSCO s electric line frequency for it s internal switching devices, in order to operate. (Also known as Grid Tie Inverter.) 1.4.2 Self-Commutated - The SPC does not require NIPSCO s electric line frequency for it s internal switching devices, in order to operate.

PAGE 2 OF 7 DISTRIBUTED RESOURCE 2. ELIGIBILITY: Any single phase customer in good standing may install, own, and operate a generation source(s), interconnected with NIPSCO s electric system if the following are met: 2.1 The generation source is of a solar or wind type. 2.2 The total nameplate capacity of the generation source is 5 kilowatts (kw) to 10 kw for solar. The total nameplate capacity of the generation source is 3 kw to 10 kw for wind. If multiple units of the same technology are installed, the aggregate total nameplate shall be 10 kw or less. 2.3 A customer shall sell the total production to NIPSCO and shall receive service for their load separately at the appropriate retail rate. A customer may not simultaneously qualify for Net Metering for any generation produced. 2.4 The generation source is located on the eligible customer s premises, is operated by said customer, and is interconnected with NIPSCO s electric system. 2.5 The customer must submit the Interconnection Application to NIPSCO, with proof of insurance coverage to be considered for, and to obtain approval for. 2.6 NIPSCO shall perform a feasibility review for the proposed generation source interconnection as an initial screening for the impact it may have to its electric system. The feasibility review will evaluate system readiness for the interconnection and will determine if there is a need for a more extensive study. If an Interconnection Evaluation Study needs to be performed by NIPSCO, any fees associated with this study will be the responsibility of the customer. Additionally if it is found that the proposed generation source requires system infrastructure upgrades to NIPSCO s electric system, the customer will be required to pay the total cost of the required system improvements. 2.7 Eligible customers shall enter into an Interconnection Agreement with NIPSCO; and if any upgrades to NIPSCO s electric system are required, the customer must pay for these, in full, before the generation source is allowed to interconnect to NIPSCO s electric system. 3. GENERAL: 3.1 Listed below are the minimum requirements for Distributed Resource (DR) generation and more stringent requirements may be imposed if warranted by conditions existing on NIPSCO s electric system. NIPSCO shall be contacted, and the installation must be approved, before any DR generation facility will be interconnected to NIPSCO s electric system. The appropriate Electric Planning Department will approve the interconnection plan. (See 2.5 and 2.6) 3.2 All DR generation facility installations shall comply with all applicable codes and standards, including but not limited to the codes listed in the reference section of this standard. 3.3 DR generation shall not adversely affect NIPSCO s electric system or any of its customers. Refer to standard ER 16-600 for power quality requirements.

PAGE 3 OF 7 3.4 It shall be the responsibility of the DR generation customer to protect their own equipment and facilities. This protection shall include protection against electrical system over voltages, line frequency disturbances, faults, lightning surges, and any other phenomenon resulting from the interconnection. 3.5 The DR generation customer shall be responsible for costs incurred for any modifications to NIPSCO s electric system, which are required for the DR generation interconnection. (See 2.6 and 2.7) 3.6 If a customer-generator facility is to be connected to a single phase shared secondary, the aggregate generation nameplate capacity connected to the shared secondary, including the proposed nameplate capacity, shall not exceed the lesser of twenty (20) kva (kilovolt amps) or the nameplate rating of the service transformer. 3.7 Interconnection will not be allowed to NIPSCO s electric system until the installation has been approved by an authorized municipal, county, or other governmental inspector where such inspection procedures are established.; and, by a final inspection, and system checks if necessary, by a NIPSCO Representative. 4. INTERCONNECTION: 4.1 The eligible customer shall install, operate, and maintain the generation source in accordance with the manufacturer s suggested practices. 4.2 The generation source shall be connected to a dedicated one way feed from the generation source to NIPSCO s electric system in such a manner that the customer shall not have any loads connected to this feed. 4.3 A lockable manual or power operable disconnect switch, or lockable circuit breaker shall be installed between the generation source, and NIPSCO s electric system, and be accessible to NIPSCO personnel at all times. This switch shall be labeled Utility-Generator Disconnect Switch on an engraved plaque. 4.4 Inverters shall comply with IEEE 1547 and UL 1741 Standards and be line-commutated. (Also known as Grid Tie Inverters.) 4.5 DR generation service entrances shall be determined by the NIPSCO Engineer and the customer, and will be group metered (see ER 19-235) or individually metered (see ER 19-240 or ER 19-270) depending on the DR generation installation. The customer will be required to pay for any additional service as needed. (Typically, there is only one service entrance location per property.) 4.6 In all cases, an engraved plaque shall be placed next to NIPSCO s electric meter providing the location of the utility-generator disconnect switch and the generation source. Furthermore, all buildings or structures with both a utility service and a generation source shall have a permanent engraved plaque or directory providing the location of the utility-generator disconnect switch and the generation source.

PAGE 4 OF 7 DISTRIBUTED RESOURCE 4.7 NIPSCO may isolate the eligible customer s generation source at any time if it is believed that continued operation of the generation source will create or contribute to a system emergency. A system emergency is defined as any condition on the electric system likely to result in any of the following: 4.7.1 A significant disruption of service to any NIPSCO customer. 4.7.2 A substantial deviation from NIPSCO s normal service standard. 4.7.3 An endangerment to life or property. 4.8 NIPSCO may perform on-site inspections to verify the proper installation and continued safe operation of the generation source and interconnection equipment facilities. Inspections shall be done at reasonable times, and with reasonable advance notice to the eligible customer. 5. INTERCONNECTION: The DR generation source shall trip offline in the case of any fault conditions existing on NIPSCO s electric system. It shall remain isolated until all faults are cleared and NIPSCO s electric system is reenergized. 6. INTENTIONAL ISLANDING: Intentional islanding is not permitted. Anti-islanding protection shall be incorporated into the inverter per IEEE 1547 and UL 1741 Standards.

PAGE 5 OF 7 7. EXAMPLES - Typical service installations: 7.1 Solar - Two Meter Concept example -

PAGE 6 OF 7 DISTRIBUTED RESOURCE 7.2 Wind - Two Meter Concept example -

PAGE 7 OF 7 7.3 Combination Solar and Wind - Three Meter Concept example -