QUESTIONS AND ANSWERS ON UNHCR DIESEL GENERATOR RFP/2017/ JUNE 2017

Similar documents
ANNEX B TECHNICAL SPECIFICATIONS PORTABLE SOLAR-POWERED LIGHTS

Clarifications Note 2 ITB GP

Technical Specification. for. Supply, installation and commissioning of Diesel Generators for UNDP

شركة كهرباء محافظة القدس المساهمة المحدودة

P 602. Voltage kva kw kva kw Amp 400/230 93,00 74,40 85,00 68,00 123,00 OTHER ACCESSORIES

20' STANDARD CONTAINER MTU 16V2000 DS: kva MTU 18V2000 DS: kva

Standby Amper VOLTAGE

Marine Generating Sets 3.7 to 50 kva

EC series GMS30CS-AU 50

GKP 660KVA. GKP Series. Generator Set Specification. Ultra Silent, Extended Life!

GKP 550KVA. GKP Series. Generator Set Specification. Ultra Silent, Extended Life!

NG904PES SERIES. Power Output Ratings. kva 904 kw 723 kva 808 kw 646. Standby Power (ESP) Prime Power (PRP)

EP series WPS100S-AU rpm,3-phase/5-wiring

DIESEL GENERATOR SET MTU 20V4000 DS3250

Standby Amper VOLTAGE

DIESEL GENERATOR SET MTU 16V4000 DS2500

DIESEL GENERATOR SET MTU 4R0113 DS80

P 602. This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

Power (kva) 3 Phase,50 Hz, PF 0.8. STANDBY RATING (ESP) PRIME RATING (PRP) Standby Amper. kw kva kw kva 400/

DIESEL GENERATOR SET MTU 16V2000 DS1000

Voltage kva kw kva kw Amp 400/ ,00 88,00 100,00 80,00 144,00

10,000 Watt Diesel Generator AGi9P E

This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

DIESEL GENERATOR SET MTU 16V4000 DS2250

PGPLS215Kw. 60Hz/1800 r.p.m-p.f.0.8 Prime Power Standby Power Rated Current Genset Engine Alternator Voltage(V) PH kw/kva kw/kva Amps

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

DIESEL GENERATOR SET MTU 12V4000 DS1750

DIESEL GENERATOR SET DS03200D5S

This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

DIESEL GENERATOR SET MTU 18V2000 DS1400

Standby Amper VOLTAGE

DIESEL GENERATOR SET MTU 12V1600 DS660

DIESEL GENERATOR SET DS01650D5S

ITB/2017/869. Solar-powered Lights. Questions and Answers (3) As of 12/12/2017

DIESEL GENERATOR SET DP01800D5S

EP series WPS150BS-AU rpm,3-phase/5-wiring

SIVASA Doosan Series. SD250 Technical Data

AGi20P 2.2 L 20 kw Perkins Powered Diesel Generator AURORA GENERATORS INCORPORATED AURORA STANDARD FEATURES STANDBY POWER RATING 20 KW, 20 KVA, 60 HZ.

PGCLS Hz/1800 r.p.m-p.f.0.8 Prime Power Standby Power Rated Current Genset Engine Alternator Voltage(V) PH kw/kva kw/kva Amps

CMEC POWER GENERATION. PRIME 800 ekw 1000 kva 50 Hz 1500 rpm 400 Volts DIESEL GENERATOR SET WHERE THE WORLD TURNS FOR POWER FEATURES

60Hz/1800 r.p.m-p.f.0.8 Prime Power Standby Power Rated Current Genset Engine Alternator Voltage(V) PH kw/kva kw/kva Amps 240 ( )

DIESEL GENERATOR SET MTU 12V4000 DS2000

13,000 Watt Diesel Generator AGi13P E

CUMMINS 30KVA. Voltage kva kw kva kw Amp 400/230 30,00 24,00 27,00 21,60 38,00

DIESEL GENERATOR SET MTU 20V4000 DS3100

Page 1 of 6 ADDENDUM NO. 1. January 11, Shuttle Bus Service RFP # H General

PGPLS45. 60Hz/1800 r.p.m-p.f.0.8 Prime Power Standby Power Rated Current Genset Engine Alternator Voltage(V) PH kw/kva kw/kva Amps 240 ( )

P 602. This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

DIESEL GENERATOR SET MTU 20V4000 DS4000

EP series WPS800S rpm,3-phase/5-wiring

DIESEL GENERATOR SET MTU 16V2000 DS1100

Voltage kva kw kva kw Amp 400/ ,00 160,00 180,00 144,00 259,00

Engine Model: 4B3.9-G1 Engine Technical Data No. of Cylinders / Alignment: Cycle: 4 / In Line 4 Stroke Bore / Stroke: mm 102/120 Induction: Cooling Me

V550C2 GENERAL CHARACTERISTICS POWER DIMENSIONS COMPACT VERSION DIMENSIONS SOUNDPROOFED VERSION POWER DEFINITION TERMS OF USE.

GE.VO.360/325.SS+0_all

DIESEL GENERATOR SET DP03000D5S

KV550C2 GENERAL CHARACTERISTICS POWER DIMENSIONS COMPACT VERSION DIMENSIONS SOUNDPROOFED VERSION POWER DEFINITION TERMS OF USE.

GZ25 POWER. Fuel System 50 Hz:

DIESEL GENERATOR SET MTU 16V4000 DS2500

DIESEL GENERATOR SET MTU 16V2000 DS KVA

DIESEL GENERATOR SET MTU 20V4000 DS2650

V550C2 GENERAL CHARACTERISTICS POWER DIMENSIONS COMPACT VERSION DIMENSIONS SOUNDPROOFED VERSION POWER DEFINITION TERMS OF USE.

DIESEL GENERATOR SET MTU 20V4000 DS3600

DIESEL GENERATOR SET MTU 12V4000 DS2250

V275C2 GENERAL CHARACTERISTICS POWER DIMENSIONS COMPACT VERSION DIMENSIONS SOUNDPROOFED VERSION POWER DEFINITION TERMS OF USE.

DIESEL GENERATOR SET MTU 12V4000 DS1650

This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

KV500C2 GENERAL CHARACTERISTICS POWER DIMENSIONS COMPACT VERSION. Soundproof version with CE directive (CN09 option) Type soundproofing

K12. Optional Control Panel POWER K12

This generator set has been designed to meet ISO 8528 regulation. This generator set is manufactured in facilities certified to ISO 9001.

PGDLS352KW 380/ / / / / / / / /

34-SDMS-01 SPECIFICATIONS FOR

V500UC2 GENERAL CHARACTERISTICS POWER DIMENSIONS COMPACT VERSION DIMENSIONS SOUNDPROOFED VERSION POWER DEFINITION TERMS OF USE.

WPS137S. EP Series. Generator Set Specification. Super Quiet, Superior Life! 广泛应用于通讯 工业 租赁. Widely applied in Telecom, Industry, Rental, 户外工程 矿山 军事等领域

PGDLS / / / / / / / / /

KV550C2. Frequency (Hz) Voltage (V) Standard control panel Optional control panel Optional control panel Optional control panel POWER

DIESEL GENERATOR SET MTU 12V4000 DS1650

PGKT / / / / / / / / / / / /

Super Silent, Superior Life!

KH275. Frequency (Hz) Optional control panel POWER. Voltage

WPS60/S EP Series. Features:

PGDLS200. Overall Dimensions (mm) & Weight (kg) Length:3900. Width:1140. Height: 1850

Power Solution Supplier

DIESEL GENERATOR SET MTU 16V4000 DS2250

Super Silent, Superior Life!

Power (kva) 3 Phase,50 Hz, PF 0.8. STANDBY RATING (ESP) PRIME RATING (PRP) Standby Amper. kw kva kw kva 400/

American Samoa Power Authority

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

PGPLS10. 60Hz/1800 r.p.m-p.f.0.8 Prime Power Standby Power Rated Current Genset Engine Alternator Voltage(V) PH kw/kva kw/kva Amps 240 ( )

WPS150/S EP Series. Features:

8,000 Watt Diesel Generator

DIESEL GENERATOR SET MTU 16V4000 DS2250

D330 GENERAL CHARACTERISTICS POWER DIMENSIONS COMPACT VERSION DIMENSIONS SOUNDPROOFED VERSION POWER DEFINITION TERMS OF USE.

WPS100/S EP Series. Features:

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

SPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT /

Optional control panel POWER. Voltage

GZ50 POWER. Fuel System 50 Hz:

Transcription:

QUESTIONS AND ANSWERS ON UNHCR DIESEL GENERATOR RFP/2017/863-19 JUNE 2017 Question Could UNCHR please indicate an IP class for the generators and enclosures to be supplied? (a IP class is given for the control panel on page 27 but no IP is given for the generator in total) Answer As such weather proof enclosures do not get categorized as an enclosure of electrical equipment and hence do not have an IP degree of protection. It is important that the enclosure protects from rain and dust, allowing for adequate air flow. If the proposed generator has a specific IP rating, please specify this in your offer. 50 vs 60 HZ, 1500/1800RPM Please price only for 1500rpm and 50Hz. In some cases the models we anticipate to propose deviate slightly from the requested KV: Power requested Actual power pf proposed model 10KVA 16KVA 18KVA 25KVA 30KVA Please confirm that this is acceptable According to the tender documents al models shall be water cooled and 1500 - or 1800RPM. This class of diesel generators (5KVA) most commonly is air-cooled and runs on 3000 - or 3600 RPM. We can produce a watercooled unit running on 1500 - or 1800 unit but the units will costs 4 to 5 times more than a air-cooled units running 3000/3600 RPM. Will an air-cooled units with 3000/3600RPM be acceptable? On page 7 it is indicated that the units shall be able to run on diesel with up to 500ppm sulphur content. We can comply with that however diesel with such ppm level (i.e. 500 ppm) will not comply with EURO Stage II G7D standards as indicated on same page. Please clarify Prime vs Continuous The units shall be prime power units. Do we need to assume that they will run through continuously that is 8000 hours per annum? Internal drawings Yes it is acceptable Yes it is acceptable We cannot guarantee fuel quality in all locations will comply with the G7D standards and this requirement is to ensure that the generator can perform with fuels of a defined quality Please assume that Generators would run for a maximum of 14 hours per day. Yes it is acceptable, detailed drawings would only be required if a contract was to be awarded

On page 17 (12.3 Drawings submissions) it is stated under point "b" that internal layout drawing of each generator showing major components" shall be presented. We assume drawings for common use giving a full lay-out of each generator and components are acceptable? Color The tender documents do speak of the specific UN colors to be uses (white and blue) Are these colors existing RAL numbers of are they specific UN owned colors? If RAL, then please advise numbers if specific colors, we need to know composition. Variable Speed Generator are less reliable and require more expensive maintenance and service. Strongly not recommended for developing countries. Is it mandatory or desirable feature. What is the required housing: On trailers? No trailers? What type of housing: for indoor or outdoor storage? First fills diesel can we simply pay for the first fill from local supplier? Receiving units radiator and sump filled as standard is this OK? Modular combination / hybrid what is the site(s) set up? more information is required for the complexities of integrating Hybrid with Fixed speed engines? Are the Solar PV panels simply to charge the batteries in offline situation in replacement of utility doing this function? Are we to simply provide a remote start signal terminal from the Solar farm to start gens if the capacity drops below a threshold? Design Life are we to consider top overhaul and full overhaul and relate the cost to a new genset Please refer to the online guide https://media.unhcr.org/brand It is not mandatory and only suitable in certain contexts. Please quote only for those applications which the supplier recommends as suitable. No trailer required Enclosure/housing is for outdoor storage Please exclude the first fill of fuel. Please price separately for first fill oil & coolant, from local suppliers acceptable if quality is assured. Please transport units empty of fuel, oil and coolant There is no standard site set up. Hybridisation of generator sets or integration to complementary energy systems will be assessed in each case. This will not for part of this tender. Solar panels are not part of this tender Facility for stop/start control inputs to be included terminals for signals from external systems. Please detail your own specific method of evaluating design life in your offer

in relation to the end of life cycle / disposal? Generator sizing Guide: template for what is requested our standard summary rating will provide all the basic info, do you want a working document (excel) or a pdf file? Central supplier location all order(s) unit and spare parts will come through a certain region but local support will be provided by partner/distributor network, is this OK? No parts that can be touched be in excess of 50DegC 1. Is this with the doors closed in normal running operation 2. Does this include the consideration of ambient 60deg machine(s)? Generator control panel IP rating of 54, is this to be considered even for soundproof canopies where the panel is inside of the canopy? Automatic controls and communications what communication protocol CANBUS / MODBUS / IP / RS485? Panel switches is this OK to be integrated digitally onto the main controller (excluding the E- Stop) Fuel consumption calculated value of consumption with parameters or metered fuel consumption with mass flow meter and temp compensation etc etc? Control interface for remote monitoring what distance considered for volt drop alternatively can this be provided via a communication link like CANBUS or similar? Will there be service power to run the remote panel (with AC/DC converter and supply) Battery monitoring system does this have to be separate from main generator controller or integrated is fine? Can you confirm the Earthing supply 10 METRE lengths or copper and Galvanised Iron Outlet for distribution cable is covered with a rubber flap sealing the genset is this acceptable? Outside mounted exhaust silencer in all our gensets the silencer is housed inside the canopy but in a separate compartment to main engine alternator compartment is this OK? FAT 25%, 50%, 75% & 100% load for a minimum of four hours is this at each power node or full length of the test (e.g an hour at each node)? Working document excel sheet Yes. Please also provide details of the partner/distributor network. Please disregard this condition for parts to be touched in excess of 50degC. The control panel is to be protected to this rating, if this is done by the canopy, this is acceptable IP Please detail the method of calculation from testing and estimations Interface to be IP based. The remote panel is not part of this tender. Integrated is fine As per page 31 of TOR Annex A ISO 8528-5 G3

Start excitation under black start conditions what is the operational procedure multiple sets single sets black start, black sync? two very different functions. Hand priming pump (in case of AC power outage) are both automatic and manual pumps to be fully plumbed into assembly with a changeover valve in event of a AC failure? Please specify the quality of fuel; low or high grade Sulphur, low or high quality of fuel, please provide the quality grade of fuel under which the machine will operate? Black Start Yes, pump to be fully plumbed into assembly with changeover valve The quality of fuel is clearly described in chapter 9: The fuel used is of low sulphur content of either 50 or 10 ppm in general. However, at certain locations there might be only fuel of high sulphur content (about 500 ppm) available. The engines must be able to run on both, the higher sulphur content fuel and the lower sulphur content fuel. The fuel (diesel) level emission permissible shall be in accordance to Euro Stage II G & D standards for non-road diesel constant speed engines measured under ISO 8178-4 C1 or IAPP (International Air Pollution Prevention) Certification/regulation. The fuel is NORMALLY of low sulphur content but the engine must be able to run on high sulphur content as well. As mentioned in the above chapter, the fuel is: for non-road diesel with constant speed engines. Shall meet the respective Euro standards as mentioned In ASTM D975 standard it would be : No 2-D-S15 (low sulfur) and No 2-D S500 (high sulfur) Will the cost of shipping will be proposed in two version, by air and by sea? Bidders do not quote for shipping as prices were requested for FCA (named place) Please specify the temperature range. For the Temperature range, a derating diagram will be given for the temperature from 20-55 deg. Centigrade, and if needed two models can be proposed with two separate prices. (larger temperature range will be more appreciated, and if possible our choice will be for one model only) Can 5-10 KVA generators be air cooled? All generator bids/tenders submitted in the 5-10kva range will be air cooled and not water

Can Anti-vibration springs or silent-block can be proposed? Can generators for different altitudes be proposed? Can you specify the type of manuals to be proposed / submitted? Will it be needed to send special fluids with the generators? cooled Yes, as optional with a separate price. For the Altitude, companies can propose two different Generator s model with separate prices, one from 0 to 1500 or 1700m and the second from there to 2500m, with derate charts in both cases Manuals will have to be sent in a light version with the - A slimmed down generator manual will be submitted for the tender/bid in hyperlink form and an additional hyperlink to the larger complete manual should be included. - The drawing for the schematic of the generators proposed will be done on a simplified version to be send with the offer and if the product is retained, a complete detailed version will be made available via a web site. Only special fluids or oil that cannot be found in the field will have to be sent with the Generator on demand and be billed separately under a price defined in this bid and proposed as optional.