UTK/UTT - Multi-blade Damper. Halton UTK, UTT. Multi-blade Damper

Similar documents
PTS - Single-Blade Damper. Halton PTS. Single-Blade Damper

FDR - Fire Damper for Rectangular and Circular Ducts. Halton FDR. Fire Damper for Rectangular and Circular Ducts

JVR CONTENTS. Page Introduction 2 Models and dimensions 3 Technical data. Selection tables 4 Technical data. Selection charts 5 Product codes 6

HFB - Airflow Management Damper HFB. Airflow Management Damper. Product models and Accessories

Damper actuators with spring return

ESAS Smoke control damper

HFB - Airflow Management Damper. Halton HFB. Airflow Management Damper

PART MATERIAL FINISHING. Frame Carbon steel Painted or galvanised

products 22 º C Ventilation Air Conditioning Refrigeration Inside PROVIDED BY HEINEN & HOPMAN

NMB (X) 24-MFT. Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

CRP. Commissioning damper, Ductwork Leakage Class 0 QUICK FACTS. Perforated damper blade for better damper characteristic

VOLUME CONTROL / REGULATING DAMPERS

U X Y W L. Gear wheels. Linkage. In option: Stainless steel AISI 304L , AISI 316L or painted steel (standard RAL)

Bevent Rasch BSK Fire /04/2017

VAV terminal units. Type TVM. For dual duct systems PD TVM 1

GMX On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 100 to 240 VAC

VARYCONTROL VAV Dual Duct Terminal Boxes

Regulation and shut-off damper SPB and SPC

SafidDampers SPK Description. Standard Construction SPK ( Flange Type )

CRP. Commissioning damper, Ductwork Leakage Class 0

U X Y W L. Gear wheels. Linkage. In option: Stainless steel AISI 304L , AISI 316L or painted steel (standard RAL)

NMQB24-MFT, NMQX24-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

NEW. Iris Control Damper (ICD) For adjustment and measuring of airflow. Features. Quick and simple installation and maintenance

HEAVY DUTY BALANCE AND CONTROL DAMPER B A L A N C E C O N T R O L SERIES

IrisControlDamper. For Adjustment and Measuring of Airflow.

DD Series. Duct Regulating Dampers M A N U F A C T U R E R S O F A I R, F I R E A N D S M O K E C O N T R O L P R O D U C T S. Two blade options.

USS - External Louvre. Halton USS. External Louvre

LMB24-3 (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

ACCESSORIES FOR DUCT FANS

EnergyShield ES. Air Control and Shut off Dampers. Dampers Controls Fancoils. Ruskin Air Management Limited

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

LMCB24-SR LMCB24-SR-T. applications. Dimensions (All numbers in brackets are in millimeters.) 1/4 to 3/4 [6 to 20] 5/16 to 3/4 [8 to 26] 1.

Smoke damper EKO-SRB1

Volume Control Dampers. Series LF upvc-vcd High performance plastic volume control dampers. Incorporating

LMX120-SR. Proportional Control, Non-Spring Return, Direct Coupled,100 to 240 VAC, for 2 to 10 VDC and 4 to 20 ma

Mechanical mixing box MBM

Blade Features. AirShield Control and Shut Off Dampers. AirShield

Shut-off dampers. Type AK-Ex. For low-leakage shut-off of volume flows in potentially. explosive atmospheres (ATEX) PD AK-Ex 1.

GDD - Supply Grille. Halton GDD. Supply Grille

DHL - HEPA terminal filter diffuser DHL. HEPA terminal filter diffuser

VAV TERMINAL BOXES TYPE: BA BT

Particle Filter Box FKU

Volume Control Dampers. Series HVC-VCD Aluminium volume control dampers. Incorporating. Excellent general purpose volume control damper

Actionair Control and Shut Off Dampers

DFB - Conical Ceiling Diffuser. Halton DFB. Conical Ceiling Diffuser

CAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1

Fire/smoke damper EKO-SRBG1

Variable Air Volume Dampers

WDD/WSD - Grille. Halton WDD/WSD. Universal Grille

SafidDampers SPK Standard Construction SPK Description SPK ( Flange Type )

Fire Dampers. Types FKA FRL FRK 4/1/EN/1

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1

Bevent Rasch BSK6. - Fire /04/2017

OPTIVENT Housing HVSA, HVSL

Actionair A-60 Marine Fire Damper Designed for inclusion in Marine and Offshore Projects

Type AK-Ex FOR LOW-LEAKAGE SHUT-OFF OF VOLUME FLOWS IN POTENTIALLY EXPLOSIVE ATMOSPHERES (ATEX)

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1

DCV-CF DCV-CF. DCV-CF Pressure control with airflow measuring CFL Version B03. Pressure controlwith airflow measuring. Product description

THB - Perforated Ceiling Diffuser. Halton THB. Perforated Ceiling Diffuser

Pressure control damper ERPA

ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE

Front panel Perforated galvanised steel Stainless steel AISI 316 as option Casing Galvanised steel Stainless steel AISI 316 as option

7/S5 FIRE DAMPER FD40. v 2.9 (en)

DKR - Multi-nozzle Ceiling Diffuser. Halton DKR. Multi-nozzle Ceiling Diffuser

ceiling swirl diffuser DQJ

TBV - Terminal Unit. Halton TBV. Terminal Unit

ARROW INDUSTRIAL PRODUCTS

MULTI-LEAF & SHUT-OFF DAMPERS Product Catalogue

Mounting Installation Instructions LM, NM, AM, GM

Particle Filter Box Model FKF

DCV-LC DCV-LC. DCV-LC Lab climate control unit. Lab climate control SMART DAMPERS & MEASURING UNITS. Product description. Occupancy AIN AOUT DCV-LC

7/S1 FIRE DAMPER PPZEN. v 2.5 (en)

Accessories. Balancing plenum PRI For balancing & equalising the airflow and attenuating the duct noise

Type KA-EU FOR THE EXTRACT AIR OF COMMERCIAL KITCHENS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type KA-EU

DCS - Ceiling Diffuser. Halton DCS. Ceiling Diffuser

WGA Long throw nozzle grille

Section 21 Actuators. (Electric and Pneumatic) Edition 2

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)

Marine Fire and Gas Dampers

7/S6 FIRE DAMPER FDC40. v 2.9 (en)

Circular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/

SMOKE DAMPERS SMOKE DAMPERS SMOKE DAMPERS

Fire/smoke damper EKO-JBG2

TCM - Conical Ceiling Diffuser. Halton TCM. Conical Ceiling Diffuser

Table of Contents PAGE General Mounting Standard Reversible Clamp Linear Rotary Retrofit Brackets...275

Technical information

For installation into ductwork

DCV-RC DCV-RC. DCV-RC Room climate control unit. Room climate control SMART DAMPERS & MEASURING UNITS. Product description.

Technical documentation

TRH - Plenum for diffusers. Halton TRH. Plenum for diffusers

Fan - Powered Terminal Unit Series Flow

Variable Air Volume (VAV) Pressure Independent Control

THL - Conical Ceiling Diffuser. Halton THL. Conical Ceiling Diffuser

500-YH SINGLE DUCT AIR TERMINAL UNIT FORM EG1 (1101)

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1

VC Series. Volume Control Dampers M A N U F A C T U R E R S O F A I R, F I R E A N D S M O K E C O N T R O L P R O D U C T S

Positive Seal Damper Blades with Vinyl Gaskets 2.5" SERIES 3000 SIDE MOUNT - NO FLANGE ORDERING METHOD FOR BACKDRAFT & MOTORIZED BACKDRAFT DAMPERS

Transcription:

Halton UTK, UTT Multi-blade Damper Temperature operation range up to +100 C, optionally up to +200 C Galvanised steel design Classification of casing leakage EN 1751 class B UTK: Shut-off, adjustment, balancing, adjustment or control damper with opposed blade construction Tightness in closed position fulfills EN 1751 class 1 requirements UTT: Shut-off and balancing damper for outdoor air intake and exhaust air with opposed blade design Damper blades comprise thermal insulation Tightness in closed position fulfills EN 1751 class 3 requirements Product models and Accessories Model with stainless steel (AISI 316) design Model with insulated casing Model with heat-proof design Circular duct connections Several actuator options 1

MATERIAL UTK PART MATERIAL NOTE Casing Galvanised steel Stainless steel AISI 316 also available Blades (envelope design) Galvanised steel Stainless steel AISI 316 also available Damper blade gaskets Silicon Heat-proof model: LTE silicon Duct gasket Rubber compound Circular connections Slide bearings Alloy of polyamide and molybdenum sulphide Drive shaft Galvanised steel Rectangular (15x15 mm) bar Self-lubricated Heat-proof model stainless steel AISI 316 MATERIAL UTT PART MATERIAL NOTE Casing Galvanised steel Stainless steel AISI 316 also available Blades (sandwich design) Galvanised steel Stainless steel AISI 316 also available Damper blade insulation Polyurethane CFC free Damper blade gaskets Silicon Heat-proof model: LTE silicon Gasket inside the casing Silicon Fixed in an aluminium profile Duct gasket Rubber compound Circular connections Slide bearings Alloy of polyamide and molybdenum sulphide Drive shaft Galvanised steel Rectangular (15x15 mm) bar Self-lubricated Heat-proof model stainless steel AISI 316 QUICK SELECTION HxW qmin qmax [mm] [l/s] [m 3 /h] [l/s] [m 3 /h] 200x400 160 576 480 1728 400x400 320 1152 960 3456 400x800 640 2304 1920 6912 800x800 1280 4608 3840 13824 1000x1000 2000 7200 6000 21600 1000x2000 4000 14400 12000 43200 qmin 1 m/s duct velocity qmax 6 m/s duct velocity - recommended maximum airflow for comfort applications 2

DIMENSIONS W H 100,200,...,2400 100,200,...,2400 15x15 90 W+44 W+4 H+44 210 H+4 Models with circular connections CT=D1; CT=D2 ØD WxH 100 150x150 125 150x150 160 200x200 200 200x200 250 250x250 315 300x300 400 400x400 500 500x500 630 600x600 710 800x800 800 800x800 1000 1000x1000 1250 1250X1250 15x15 90 W +44 W +4 H +44 210 Ø D 67 H +4 Product models and Accessories The product models MD=I and MD=J have a double sheet casing with mineral wool insulation. The insulation thickness is 20 mm. The damper is available equipped with either manual adjustment or actuator operation. The adjustment and control arrangement options are: The damper actuator is selected from the list below according to the operating voltage, control arrangement and the required torque of the damper. The torque of the selected actuator can be higher than the required torque of the damper. ADJUSTMENT & CONTROL OPTIONS CODE NOTE Manual handle adjustment MO = MA Manual extension bar adjustment AC = BA Handle extension arrangement Actuator operation MO= See Actuator options 3

Actuator options LM-MODELS Torque, damper size...4 Nm A<0.4 m 2 Manual override operation, mechanical position limit LM 24A B6 On-off, 1- or 2-wire control AC/DC 24 V 2 VA LM 24A-S B7 On-off, 1- or 2- wire control, auxiliary switch AC/DC 24 V LM 230A B8 On-off, 1- wire control AC 230 V 4 VA LM 230A-S B9 On-off, 1- wire control, auxiliary switch AC 230 V LM 24A-SR B0 Control signal DC 0 10 V AC/DC 24 V 2 VA 2 VA 4 VA LF-MODELS Torque, damper size... 4 Nm A<0.4 m 2 Spring return, mechanical position limit LF 24 B1 On-off AC/DC 24 V 7 VA LF 24-S B2 On-off, auxiliary switch AC/DC 24 V 7 VA LF 230 B3 On-off AC 230 V 7 VA LF 230-S B4 On-off, auxiliary switch AC 230 V 7 VA LF 24-SR B5 Control signal DC 0...10 V AC/DC 24 V 5 VA NM-MODELS Torque, damper size... 8 Nm A<1.2 m 2 Manual override operation,mechanical position limit NM 24A C1 On-off, 1- or 2-wire control AC/DC 24 V 4 VA NM 230A C2 On-off, 2- wire control AC 230 V 6 VA NM 24A-SR C3 Control signal DC 0 10 V AC 24 V 4 VA NM 230 C4 On-off, 1- wire control AC 230 V 18 VA BLF-MODELS Torque, damper size... 4 Nm A<0.4 m 2 Spring return, manual operation, position lock BLF24-HL L1 On-off, 2 auxiliary switches AC/DC 24 V 7 VA BLF230-HL L5 On-off, 2 auxiliary switches AC 230 V 7 VA BF-MODELS Torque, damper size...12 Nm A<2.5 m 2 Spring return, manual operation, position lock BF24-2.1HL E1 On-off, 2 auxiliary switches AC/DC 24 V 10 VA BF230-2.1HL E3 On-off, 2 auxiliary switches AC 230 V 12.5 VA BF120 E7 On-off, 2 auxiliary switches AC 120 V 12.5 VA 4

AF-MODELS Torque, damper size... 15 Nm A<2.8 m 2 Spring return, manual operation, position lock AF 24 A6 AC/DC 24 V 10 VA AF 24-S A7 2 auxiliary switches AC/DC 24 V 10 VA AF 230 A8 AC 230 V 11 VA AF 230-S A9 2 auxiliary switches AC 230 V 11 VA AF24-SR A0 Control signal DC 0...10 V or 0...20 V phase-cut AC 24 V 10 VA SM-MODELS Torque, damper size... 18 Nm A<3.3 m 2 Manual override operation, mechanical position limit AM 24A A1 On-off, 1- or 2-wire control AC/DC 24 V 4.5 VA AM 2A4-S A2 On-off, 2-wire control, 2 auxiliary switches AC/DC 24 V 4.5 VA AM 230A A3 On-off, 1- or 2-wire control AC 230 V 25 VA AM 230A-S A4 On-off, 1-wire control, 2 auxiliary switches AC 230 V 25 VA AM 24-SR A5 Control signal DC 0...10 V 24 VAC 5 VA GM-MODELS Torque, damper size...30 Nm A<6 m 2 Manual override operation GM 24A G1 On-off, 1- or 2-wire control AC/DC 24 V 7 VA GM 230A G2 On-off, 2-wire control AC 230 V 7 VA Required torque for damper actuator 0 Pa Pst (Pa) H ( mm) 250 Pa 2400 2200 500 Pa 2000 1800 1600 1400 1000 Pa 1200 1000 800 600 400 400 600 800 1200 1600 2000 1000 1400 1800 B ( mm) 2400 2200 2 3 5 10 20 30 50 Mv (Nm) Mv -max =50 Nm 5

CLASS 2000 1000 500 200 100 4 3 2 1 50 1 3 10 30 100 300 500 1000 2000 DIN 1946/4 UTT UTS UTK Function UTK The UTK dampers are used to shut off, adjust or control airflow in ductwork in applications where damper leakage does not have significant importance. In the closed position the UTK damper leakage class is 1 in accordance with the EN1751 standard. UTT The UTT dampers are used to shut off or control airflow in ductwork where tightness, thermal insulation and reliability are important. In the closed position the UTT damper leakage class is 3 in accordance with the EN1751 standard. In the open position the blades are turned in the direction of flow and do not cause significant pressure losses. Damper sizes conform with the international standards EN 1505, EN1506 and ISO 1707 for rectangular and circular ducts. The maximum operation temperature of a standard damper is +100 C (for optional models +200 C). Heat transmission of the damper is 6 W/(m 2 K). 6

UTK UTT Installation CODE DESCRIPTION 1 Casing 2 Blade 3 Gasket 4 Manual adjustment handle / actuator platform Install the damper in the ductwork with the blades in horizontal or vertical position. Fasten the damper in the ductwork using slip joints. Optional models enable fastening the damper to duct flange by using bolts. Drill holes in the damper flange if necessary (options L1 & L2). Use a seal between the flanges in order to tighten the seam. Fasten the circular connections by riveting or screwing. 24 V AC/DC 230 V AC 24 V AC/DC 230 V AC 24 V AC/DC 230 V AC S1 S2 S3 1 2 3 5 1 2 3 5 Y1 Y1 M LM...A NM...A SM...A GM...A LM...A NM...A SM...A GM...A LF AF BF BLF 24 V AC/DC 24 V AC/DC 0-10 VDC 0-10 VDC 2-10 VDC 2-10 VDC 1 2 3 5 1 2 3 5 Y1 Y1 GM24A-SR AF24A-SR LM24A-SR NM24A-SR LF24-SR SM24A-SR 7

Pressure drop and sound data Sound power level Lw [db] UTK, UTT The sound power level LW in each octave band is computed by adding the corresponding correction factor Kok to the sound pressure level in the selection chart according to the following equation. LW = LPA + Kok + KA The correction factor Kok is the average of the operating area. A[m 2 ] 0,10 0,12 0,25 0,30 0,40 0,50 0,60 1,0 1,6 2,0 KA /db -10-9 -6-5 -4-3 -2 0 +2-3 f/[hz] 63 125 250 500 1000 2000 4000 8000 kok 11 11 9 7 5 3-4 -10 l/db +/-6 +/-6 +/-5 +/-4 +/-3 +/-3 +/-3 +/-3 Suggested specifications The casing and blades shall be made from galvanised steel (or stainless steel AISI 316). The blade gaskets shall be of silicon (or EPDMrubber). The drive shaft socket shall be of galvanised steel with self-lubricating slide bearings. The bearing shall be made from an alloy of polyamide and molybdenum sulphide (or stainless steel AISI 316 or stainless steel AISI 304 or bronze). The damper shall be installed into rectangular ductwork in compliance with EN 1751, or in circular ducts D=100... 1250 mm in accordance with EN 1751. UTK: The damper shall meet the tightness requirements of EN 1751 class 1. UTT: The damper shall meet the tightness requirements of EN 1751 class 3. The casing of the damper shall meet the tightness requirements of EN 1751 class B. The damper shall be suitable for either manual adjustment or actuator operation. 8

Product code UTK/S-W-H-D UTT/S-W-H-D S = Type of duct connections R Rectangular connections C Circular connections W = Width S=R: 100,+1,..,2400 S=C and D=100: 150 S=C and D=125: 150 S=C and D=160: 200 S=C and D=200: 200 S=C and D=250: 250 S=C and D=315: 300 S=C and D=400: 400 S=C and D=500: 500 S=C and D=630: 600 S=C and D=710: 800 S=C and D=800: 800 S=C and D=1000: 1000 S=C and D=1250: 1250 S=C: 150 H = Height S=R: 100,+1,..,2400 S=C: W Specifics and accessories CT = Type of circular connection D2 2 circular connections D1 1 circular connection SF = Flange option NA Standard with no flanges L1 Standard model / Flange on one side L2 Flanges on both sides R2 Flanges with holes on both sides MA = Material CS Steel AS Stainless steel, AISI 316 MD = Model N Standard H Heat-proof I Insulated J Heat-proof and insulated BM = Bearing material ST Standard (Plastic) AS Stainless steel (AISI 316) SS Stainless steel (AISI 304) D = Diameter of duct connection S=C: 100, 125, 160, 200, 250, 315, 400, 500, 630, 710, 800, 1000, 1250 9

MO = Actuator type MA Manual handle NA Not assigned E1 Electric BF24-2.1HL E3 Electric BF230-2.1HL E7 Electric BF120-HL P0 Pneumatic,Rot.AT101 P1 Pneumatic,Lin.RODER 245N P2 Pneumatic,Lin.RODER 300N P5 Pneumatic,Rot.ES65 P6 Pneumatic ON/OFF AVS-cylinde A1 Electric SM24A A2 Electric SM24A-S A3 Electric SM230A A4 Electric SM230A-S A5 Electric SM24A-SR A6 Electric AF24 A7 Electric AF24-S A8 Electric AF230 A9 Electric AF230-S A0 Electric AF24-SR B1 Electric LF24 B2 Electric LF24-S B3 Electric LF230 B4 Electric LF230-S B5 Electric LF24-SR B6 Electric LM24A B7 Electric LM24A-S B8 Electric LM230 B9 Electric LM230A-S B0 Electric LM24A-SR C1 Electric NM24A C2 Electric NM230A C3 Electric NM24A-SR G1 Electric GM24A G2 Electric GM230A L1 Electric BLF24-HL L5 Electric BLF230-HL AC = Accessories BA Bar adjustment S1 SN1 Auxiliary switch S2 SN1/500 auxiliary switch S3 S1A auxiliary switch S4 S2A auxiliary switch L1 Limit switch, 1 pc, IP65 L2 Limit switches, 2 pcs, IP65 L3 EX-proof limit switch, 1 pc, IP66 L4 EX-proof limit switches, 2 pcs, IP66 M1 Solenoid valve 24 VAC M2 Solenoid valve 230 VAC Code example UTK/R-100-100, SF=NA,MA=CS,MD=N,BM=ST, MO=MA 10