AXIOM AN SERIES VALVE COMMUNICATION AND CONTROL NONINCENDIVE & I.S. ON/OFF VALVE CONTROLLER. on-off controller AXIOM AN

Similar documents
Prism PI Intelligent features offer advanced performance

Prism PI Intelligent features offer advanced performance

AXIOM AX SERIES VALVE COMMUNICATION AND CONTROL EXPLOSIONPROOF ON/OFF VALVE CONTROLLER. on-off controller AXIOM AX

ADVANCED AUTOMATION SYSTEM. Installation, Maintenance and Operating Instructions

LIMIT SWITCH Axiom - AX

Axiom Explosionproof Advanced performance and reliability in harsh environments

LIMIT SWITCH Axiom - AX

ADVANCED AUTOMATION SYSTEM

LIMIT SWITCH Axiom - AX

valve communication and control

Eclipse Compact and modular with solid state reliability

ValvePoint: valve communication and control

Quartz Explosionproof valve monitoring

JAMESBURY EASYFLOW JT SERIES ANGLE STEM TANK BOTTOM VALVES

VALV-POWR SERIES VPVL MODEL D DOUBLE-ACTING AND SPRING-RETURN RACK- AND-PINION COMPACT PNEUMATIC ACTUATORS

LIMIT SWITCH Prism - PI

Jamesbury High-Performance Actuators. Maximizing cycle life. Lowering Costs.

LIMIT SWITCH Prism - PI

Axiom AX by StoneL. Installation, Maintenance and Operating instructions. StoneL publication revA

Axiom AMI by StoneL. Installation, Maintenance and Operating instructions. StoneL publication revA

Polymerization High cycle valves

valve communication and control

VALV-POWR SERIES VPVL MODEL C DOUBLE-ACTING AND SPRING-RETURN RACK- AND-PINION COMPACT PNEUMATIC ACTUATORS

Installation Manual OPEN. For Corrosive Service. The ONYX integrates electronic sensors and pneumatic valving into a vapor tight enclosure.

Quartz. Save Space with Low Profile Design

VALV-POWR VALUE-LINE DOUBLE-OPPOSED PISTON ACTUATORS MODEL A. Installation, Maintenance and Operating Instructions

Series VC Pneumatic cylinder actuators

JAMESBURY VALVCON QX-SERIES ELECTRIC ACTUATOR

SERIES CLASS 300 FULL-BORE REACTOR DISCHARGE VALVES. Installation, Maintenance and Operating Instructions

3 AND 4 CLASS 300 STANDARD BORE SERIES 730S AND 7300 REACTOR DISCHARGE VALVES. Installation, Maintenance and Operating Instructions

Standard Bore Flanged Ball Valves Series 7150, 730S & , 4 & 6 (DN 80, 100 & 150) Class 150 & 300

NELES BO SERIES BUTTERFLY VALVE FOR RECOVERY OF OXYGEN IN VACUUM PRESSURE SWING ADSORPTION (VPSA) PLANTS

VALVCON Universal ADC-Series Sealed Lead Acid Back-Up Battery Upgrade Kits. Installation, Maintenance and Operating Instructions

JAMESBURY VALVCON ESR-SERIES ELECTRONIC SPRING RETURN ELECTRIC ACTUATOR

REACTOR DISCHARGE VALVES S & DIGESTER BLOW VALVES SB & 5300SB B FLANGED BALL VALVES

Reduced Bore Thread-end Ball Valves Series 33R Model C. 1/2 2 (DN 15-50) AAR No. E079024

3, 4 & 6 (DN 80, 100 & 150) CLASS 150 & 300 STANDARD BORE SERIES 7150, 730S & 7300 FLANGED BALL VALVES EQUIPPED WITH KEROTEST HANDLE ASSEMBLIES

SERIES 2 4 (DN ) 6300, 2 6 (DN ) 6150, 6 (DN 150) 5300 & 530S, 6 & 8 (DN 150 & 200) 5150 BALL VALVES

Railroad Ball Valves Series 5REB3

HAND WHEEL OPERATOR For cylinder actuators Types B1C_K/L/R and B1C_RK/RL/RR Installation, Maintenance and Operating Instructions

M1/M2 POCKET FEEDER. Compact design DESIGN FEATURES. Special ball and seat design. Large ball pocket capacity. Automatic cycling

JAMESBURY ELECTRIC ACTUATORS VALVCON ADC-SERIES WITH OPTIONAL BATTERY BACK-UP POWER

ICV & ICVA Flanged Injection Control Valves 2 (DN 50) Type Installation, Maintenance and Operating Instructions

3-Piece Ball Valves Series 4000 Model A

JT SERIES ANGLE STEM TANK BOTTOM BALL VALVE DN25 DN150. Installation, Maintenance and Operating Instructions

MAPAG Butterfly valve - Type BK For cryogenic applications. Installation, Maintenance and Operating Instructions

NELES SOFT SEATED BALL VALVES, SEAT SUPPORTED, FULL AND REDUCED BORE, SERIES X

LIMIT SWITCH Hawkeye - HX Magnetic Solid State Proximity Sensors Installation, Maintenance and Operating Instructions (HX )

NELES RE2-SERIES V-PORT SEGMENT VALVE

MANUAL GEAR ACTUATORS

1/4 2 (DN 8 50) ELIMINATOR 2000 CWP AND ASME CLASS 600 THREADED END BALL VALVE

True Fail-Safe Technology and Precision Control for Reliable Shutdown

Series 7000 & 9000 Ball Valves

Electrical: Valve monitoring and control circuits

EG Series Installation Manual

REACTOR DISCHARGE VALVES S AND WITH MD, QA AND QC CONVERSIONS AND ESSD STEM SEAL OPTION

Quartz Explosionproof valve monitoring

PNEUMATIC CYLINDER ACTUATORS, SERIES B1

EMERGENCY SHUTOFF AND FIRESAFE VALVES FIGURE 1075

ICV & ICVA Injection Control Valves Series 4000 Model C. Installation, Maintenance and Operating Instructions

PNEUMATIC CYLINDER UNIT. Series CP Installation, Maintenance and Operating Instructions

Valv-Powr VPVL Mod C Value-Line Double-Opposed Piston Actuators. Installation, Maintenance and Operating Instructions

Cryogenic Wafer-Sphere Butterfly Valves

Quartz Explosionproof valve monitoring

Double Acting & Spring Return. SERIES 92/93 Rack & Pinion PNEUMATIC ACTUATOR. The High Performance Company

Tank Car Fire-Tite Top-Loading and Unloading Valves

Innovation in actuation.

Limit Switches. Series NI700 Installation, Maintenance and Operating Instructions

SERIES 835 PROCESS-RATED CLASS 150 WAFER-SPHERE HIGH-PERFORMANCE BUTTERFLY VALVES

CONTROLS. Bray Pneumatic Actuators & Accessories. Technical Manual. A Division of BRAY INTERNATIONAL, Inc.

Automation Selection Guide

VALUE-LINE 3-Piece Ball Valves Series 3A & 3C 1/2 2 (DN15-50) Installation, Maintenance and Operating Instructions

CLINCHER 2-Piece Thread-end Ball Valves Series 2000

1/4" 2" (DN 8 50) A-STYLE MODEL D THREADED END 2000 CWP BALL VALVE

EMISSION-PAK SERIES 7000 AND 9000 BALL VALVES

NELES R-SERIES SEGMENT VALVE Flanged RE and Wafer RE1

reliable actuators to

True Fail-Safe Technology and Precision Control Meet Emergency Shutdown and Demanding Process Applications

NELES RE-SERIES V-PORT SEGMENT VALVE

Crude and vacuum distillation

Steam reforming. The product is then ready to be used in refinery applications or for synthesis of ammonia or methanol. APPLICATION REPORT CLOSEOPEN

APS & APIS ATEX AIRPOWER SWITCH BOXES FEATURES DESCRIPTION

1/4" 2" (DN 8 50) ELIMINATOR 2000 CWP AND ANSI CLASS 600 THREADED END BALL VALVE

JAMESBURY ELECTRIC ACTUATORS VALVCON V-SERIES 115VAC AND 230VAC

1/4" 2" (DN 8 50) Clincher Series 2000 Threaded-End Ball Valves

TECHNICAL BULLETIN. Logix 510si Series Digital Positioner. Experience In Motion FCD LGENTB /09

JAMESBURY VALVCON I-SERIES ACTUATOR 115VAC AND 230VAC

VALVCON V-Series ELECTRIC ACTUATORS 115 VAC AND 230 VAC. Installation, Maintenance and Operating Instructions

Double Acting Cylinder Actuator Series VC Installation, Maintenance and Operating Instructions

Delayed Coker Switch Ball Valve

NELES METAL SEATED BALL VALVES, SEAT SUPPORTED, FULL AND REDUCED BORE, SERIES X

Jamesbury Wafer-Sphere World s Best Gate Crasher

3-Way Flanged Ball Valves 12 (DN300) Series DM150FD Model A

M-VUE The Intelligent Valve Monitor

VALVCON ADC-SERIES ELECTRIC ACTUATOR WITH OPTIONAL BATTERY BACK-UP POWER

PNEUMATIC CYLINDER UNIT. Series CS Installation, Maintenance and Operating Instructions

jamesbury Bulletin A101-1 Issue 10/2001

6D15 DIGESTER CAPPING VALVES

3-Way Flanged Ball Valves 6, 8 & 10 (DN150, 200 & 250) Model D Series DM150FD 6 & 8 (DN150 & 200) Series DM150FB Model D

VALVCON V-Series. ELECTRIC ACTUATORS With Speed Control/Timer Board (Option J ) Installation, Maintenance and Operating Instructions

Transcription:

AXIOM AN SERIES VALVE COMMUNICATION AND CONTROL NONINCENDIVE & I.S. ON/OFF VALVE CONTROLLER on-off controller AXIOM AN 7 AN 20 EN 2/2018

METSO 7 AN 20 EN Axiom AN Advanced performance The Axiom AN series offers unmatched reliability using non-contact position sensing with solid state electronics and contaminant-tolerant pneumatic control. Coupled with its spaceefficient design, corrosion resistance and networking/ Wireless Link capability, the AN offers unrivaled convenience and cost-saving benefits in hazardous and general purpose process applications. Exceptional reliability The proven technologies combined with efficient design and durable materials, delivers long life and exceptional performance. Survives harsh conditions Tolerates air contaminants Provides solid state position-sensing User-friendly advanced technology Designed with the user in mind, the Axiom AN offers the utmost in ease and convenience. Rapid enclosure entry Easy configuration Convenient wiring access Wireless Link app set up Universal application The strategic engineering reduces inventory and ensures universal adaptability in many applications and environments. Universal voltage capability Selectable SR/DA action Direct actuator attachment Space efficient design The Axiom AN encloses all electrical components in a compact package. The automated valve spacing envelope is minimized without compromising performance or maintainability. Requires less than 5 of total clearance Additional 2 clearance for cover removal No tools for cover removal Axiom AN 2 TECHNICAL BULLETIN 2/18

7 AN 20 EN AXIOM AN NONINCENDIVE & I.S. ON/OFF VALVE CONTROLLER Features 1. Impact-resistant cover Vapor tight, Lexan cover screws off for rapid entry without tools. It withstands high-pressure wash downs and typical process environment corrosives. 2. Universal voltage solenoid system Operates from 24 VDC 250 VAC at extended temperate range and features manual override. Single or dual coil available. 3. Convenient settings Touch pad enables position settings to be conveniently locked in. Switch settings remain in place during power cycling. 4. Fully sealed module Solid state, fully potted sensors provide protection against residual moisture, vibration, and corrosives. 5. High flow pneumatic valve 5-way, 2-position valve operates on standard plant air. Rebreather prevents ingestion of contaminated air into actuator. 6. High visibility indication Mechanical and electronic indication confirms open and closed position. Intense LEDs display position status from a distance. 7. Exceptional long life Magnetic position sensor has no bushings or shafts to wear out, delivers reliable performance, and is unaffected by actuator shaft wear. 8. SR/DA plug Plug positions into designated port to enable spring return or double-acting operation. 9. Direct actuator attachment Compact mounting manifold system requires less space and wiring, connects to VDI/VDE 3845 (NAMUR) actuators and adapts to spring return or double-acting actuators. 1 2 5 7 8 9 3 4 6 Proven performance in process industries Chemical Oil and gas Pharmaceutical and biotech Food and beverage Marine Offshore service vessels (OSV) Biofuels And more... TECHNICAL BULLETIN 2/18 3

METSO 7 AN 20 EN Pneumatic control The Axiom s pneumatic valve system consists of a low-power pilot that drives the main highflow spool valve. Pilots may be selected for conventional or bus networking applications. Both stages of the pneumatic valve system have been designed for long life, high tolerance to air line contaminants, and ease of maintenance should components become fouled. Pilots are automatically associated with the appropriate function selected. Special features Solenoid pilot and main spool design offer long life, exceptional tolerance to dirty air, and tight shut-off. Universal voltage solenoid system may be used for standard AC or DC applications. Five-way, two-position spring return configuration may be used for either single- or double-acting actuators. Dual coil shuttle piston versions are also available for fail-in-last position. Rebreather channels exhausted air from pressurized side of actuator into spring side, preventing ingestion of contaminated air from the environment that may corrode springs or actuator internals. Pneumatic manual override is conveniently located on top for easy access. Single or dual pilot configuration The Axiom AN is available in either single or dual pilot configurations. Dual pilot options are available for shuttle piston, fail-in-last position applications. Several external manual override options are also readily available. For special valve configurations with non-standard manual override features, please consult StoneL. General pneumatic valve specifications Valve design Configuration Flow rating Axiom porting Manifold porting Operating pressure Pilot operated spool valve Single pilot Dual pilot 0.8 Cv 1.2 Cv 1/4 NPT (0.8 Cv) 3/8 NPT (1.2 Cv) 1/4 NPT 45 psi to 120 psi (3.1 to 8.2 bar) Operating temperature -40 C to 80 C (-40 F to 176 F) Operating life Manual override Materials of construction Solenoid coil specifications 35 Operating voltage Power consumption Filtration requirements 45 Operating voltage Power consumption Filtration requirements 92 & 97 Operating voltage Power consumption Filtration requirements 1 million cycles 5-way, 2-position, spring return 5-way, 2-position, shuttle piston Internal momentary Optional external momentary available Optional external latching available Spool Body Seal spacers Spool seals O-rings End-caps and fasteners Nickel plated aluminum Epoxy-coated anodized aluminum Polysulfone Nitrile compound Nitrile compound Nickel plated aluminum and stainless steel 20-250 VAC; 20-55 VDC 12 ma @ 20-250 VAC (1.1 watts typical) 20 ma @ 20-55 VDC (0.5 watts typical) 50 micron 12-24 VDC (output of barrier) 0.5 watts @ 12 VDC; 1.0 watt @ 24 VDC 50 micron 24 VDC 0.5 watts 50 micron 4 TECHNICAL BULLETIN 2/18

7 AN 20 EN AXIOM AN NONINCENDIVE & I.S. ON/OFF VALVE CONTROLLER Manifold and mounting system The Axiom is designed to readily adapt to most quarter-turn actuators. The mounting manifold system combines the mounting base and pneumatic manifold to minimize space and simplify installation. It attaches the Axiom directly to the actuator and ports air from the pneumatic valve to the actuator. Included in the manifold system are: 1. Actuator shaft adaptor and fastener. 2. Epoxy-coated anodized aluminum mounting plate manifold with o-rings and stainless steel fasteners. 3. Pneumatic plug for SR/DA configuration. The manifold system readily adapts to VDI/VDE 3845 sizes 1, 2 and 3. Special variations may be made for sizes 3, 4 and non-standard quarter-turn actuator mounting patterns. The mounting manifold system is specified and sold separately. Kits are specific to actuator manufacturer. For kit numbers visit: StoneL.com/mounting. Single or double-acting configuration The same Axiom model is suitable for both single-acting/spring return (SR) and double-acting (DA) actuators. The standard rebreather capability for single-acting/spring return is built in. Field configuration may be made by conveniently removing and reinserting the plug for the appropriate actuator type. For rebreather to function properly, both manifold ports must be tubed to the actuator. Spring return actuator Double-acting actuator Actuator Actuator TECHNICAL BULLETIN 2/18 5

METSO 7 AN 20 EN Sensing and communication module Switching and sensor specifications SST NO sensor (35S) Configuration Voltage range Minimum on current Maximum continuous current Typical leakage current Typical voltage drop Circuit protection Wiring diagram (35S) SST (2) NO 2-wire solid state sensors 20-250 VAC/VDC 2.0 ma 0.1 amps AC circuits 0.35 ma DC circuits 0.25 ma 6.5 volts @ 10 ma 7.2 volts @ 100 ma Protected against short circuits and direct application of voltage with no load. SOL 1 OUT SOL 1 OUT SOL 2 OUT SOL 2 OUT SOL 1 PWR 1 SOL 1 PWR 2 OPEN NO OPEN C CLOSED NO CLOSED C SOL 2 PWR 1 SOL 2 PWR 2 Switching and sensor specifications NAMUR sensor (45S) Configuration Voltage range Current ratings (2) NAMUR sensors (EN 60947-5-6; IS) 5-25 VDC Target present Target absent current < 1.0 ma current > 2.1 ma Use with intrinsically safe repeater barrier. NAMUR sensors conform to EN 60947-5-6 standard. Intrinsically safe solenoid coil Voltage 12-32 volts from output of solenoid barrier to coil* *Note: Use of an intrinsically safe solenoid barrier with internal impedance, or end-to-end resistance, of 500 ohms required for proper solenoid coil operation. Wiring diagram (45S) NAMUR SOL 1 OUT - SOL 1 OUT + SOL PWR + SOL PWR - not used OPEN + OPEN - not used CLOSED + CLOSED - Valve Communication Terminal (VCT) specifications DeviceNet communication (92S & 92W) Communication protocol DeviceNet Configuration (2) Discrete inputs (sensors) (1) Auxiliary analog input (4-20 ma) (2) Discrete outputs (solenoids) Input voltage 11-25 VDC via DeviceNet network Output voltage 24 VDC Analog input impedance 254 ohms Quiescent current No analog input, no outputs energized: 35 ma @ 24 VDC; 57 ma @ 11 VDC Maximum output current 150 ma (all outputs combined) Default address 63 (software assigned) Default baud rate 125K (software selectable 125K, 250K or 500K baud) Messaging Polling, cyclic and change of state DeviceNet type 100 Wiring diagram (92S & 92W) SOL 1 OUT - SOL 1 OUT + SOL 2 OUT - SOL 2 OUT + DeviceNet Bus not used Ain - Ain + V - CAN L S H CAN H V + Valve Communication Terminal (VCT) specifications AS-Interface communication and extended addressing (97S & 97W) Communication protocol AS-Interface v3.0 Configuration (2) Discrete inputs (sensors) (2) Auxiliary discrete inputs (2) Discrete outputs (solenoid) Input voltage 26.5-31.6 VDC (AS-I voltage) Output voltage 24 VDC (+/- 10%) Quiescent current 35 ma Maximum output current 100 ma (all outputs combined) Default address 0A ID/IO codes ID = A; IO = 7; ID1 = F; ID2 = E (S-7.A.E.) Wiring diagram (97S & 97W) SOL 1 OUT - SOL 1 OUT + SOL 2 OUT - SOL 2 OUT + ASi Bus 3 wire RTN Aux IN2 - Aux IN1 - Aux IN + ASi - ASi + ASi - ASi + 6 TECHNICAL BULLETIN 2/18

7 AN 20 EN AXIOM AN NONINCENDIVE & I.S. ON/OFF VALVE CONTROLLER Position sensor and module The Axiom platform has all position sensing, communication or switching integrated into StoneL s C-module. Users may set open/ closed positions conveniently and accurately on all modules. And easy to view instructions, along with bold LED indication, are displayed on the module itself. Continuous sensing with open/closed settings The C-module (continuous sensing) integrates a magnetic resistive sensor system to monitor exact valve position throughout the rotational range. Touch-sensitive or remote open and closed position setting along with microprocessor based operation make this stateof-the-art system convenient, reliable, and smart. Position settings are made using the touch-sensitive buttons on the module s overlay. Simply operate the actuator to the open position (using standard internal manual override) and touch the SET OPEN button. Operate the actuator to the closed position and touch the SET CLOSED button. Position settings remain locked in when power is removed and reapplied. Reliable position sensing An extremely reliable solid state magnetic resistive (mag res) sensor detects the valve position by monitoring the orientation of a magnet attached to the actuator. This design is tolerant of lateral and vertical shaft movement, which may occur in heavily used actuators, without affecting rotational measurement. No cams, shafts or seals - offering exceptional vibration tolerance and nothing to wear out. TECHNICAL BULLETIN 2/18 7

METSO 7 AN 20 EN Axiom AN with Wireless Link Easily access hard-to-reach automated valves Discover convenient remote access of your automated valves when you install the Axiom AN with AS-Interface and DeviceNet featuring Bluetooth technology. Devices may be remotely accessed from up to 50 meters depending on obstructions. Setting changes and solenoid control are enabled through the DeviceNet or AS-Interface network or by the AS-Interface power supply jumper. Special features Improve safety by easily controlling hard-to-reach automated valves without putting plant personnel at risk. Look up factory preset module code and serial number remotely. Electronically enter and store key automated valve system information including user tag and maintenance log. Reduce network commissioning time by accessing the VCT address and baud rate to make changes. Reduce maintenance time by monitoring valve cycle count, cycle times, storing maintenance logs, and accessing multiple valves from one location. Conveniently retrieve installation manuals for additional technical information when connected to internet. Customize the tag for a device, change the address, force the solenoids on or off, wink the device, and set the valve limits. Store and view additional information about a specific valve. View real time valve position, cycle count, cycle timing, current valve temperature, error status, and more. Interfacing devices Conventional Apple devices may be used including: iphone ipad ipad mini Version 4S and above Version 3.0 and above All Contact StoneL regarding additional devices and special enclosures to make these devices suitable for use in hazardous locations. 8 TECHNICAL BULLETIN 2/18

7 AN 20 EN AXIOM AN NONINCENDIVE & I.S. ON/OFF VALVE CONTROLLER Set up and operation Devices with Wireless Link are commissioned and set up identically to the standard AS-Interface or DeviceNet unit. In addition, when powered up with a conventional power source or by the network, it may be accessed by standard ios devices. The Axiom is accessed with the Bluetooth protocol using the StoneL Wireless Link application. Sequence of operation is: 1. Download the StoneL application from the App Store onto your device (free of charge) 2. Start the application in your Apple device 3. All energized wireless modules in range will come up 4. Push wink to positively confirm the device you have linked (device LEDs will flash) 5. Touch the specific ID tag to link with your handheld. You can then monitor all status and diagnostic information and make necessary information changes to the free form fields at any time. Switch settings, address changes, and solenoid operation may be performed only if network- or power supply-enabled. Other information may also be added to the free form fields. Specifications for Wireless Link Standard specifications apply to Axiom AN92W & AN97W. Additional specifications for Wireless Link are as follows: Communication Transmit power Data rate Range Registrations CE compliance VCT identification VCT link Application Hand-helds Bluetooth technology; single mode (not compatible with Bluetooth Classic) 4dBm or ~2.5 milliwatts 1 Mbit/second; effective information transmit rate ~10 Kbits/second Up to 100 meters (330 feet) in free space. Range is reduced by obstructions between hand-held device and Wireless Link VCT. Line of site is not necessary. FCC, IC, CE Exceeds industrial compliance standards VCTs in range will be displayed One device accessed at a time between client (hand-held device) and server (VCT). Each server accessed by one client at a time StoneL Wireless Link available from the App store Compatible with iphone and ipad with ios 8 or later Wireless Link enabled network All settings and inputs are locked when standard network communication is functioning. For fast commissioning and asset management you can import and export electronic tags, model number, serial number, device address, descriptive fields, diagnostic data and more to and from standard CSV/Excel files. TECHNICAL BULLETIN 2/18 9

METSO 7 AN 20 EN Model selector SERIES AN Nonincendive or intrinsically safe FUNCTIONS Sensor/ switching modules Valve communication Terminals (VCTs) 35S SST Universal; 20-250 volt (NO sensor) 92S DeviceNet 45S NAMUR module (EN 60947-5-6; I.S.) 92W DeviceNet with Wireless Link 97S AS-Interface with extended addressing 97W AS-Interface with extended addressing and Wireless Link PNEUMATIC OVERRIDE / CV [standard pneumatic pilot and valve -40 C to 80 C] For single pilot For dual pilot 1N Internal momentary override only / 0.8 Cv 2N Internal momentary override only / 0.8 Cv 1M External momentary & internal override / 0.8 Cv 2M External momentary & internal override / 0.8 Cv 1L External latching & internal override / 0.8 Cv 2L External latching & internal override / 0.8 Cv 1E Internal momentary override only / 1.2 Cv 2E Internal momentary override only / 1.2 Cv 1Y External momentary & internal override / 1.2 Cv 2Y External momentary & internal override / 1.2 Cv 1G External latching & internal override / 1.2 Cv 2G External latching & internal override / 1.2 Cv 9N No pneumatics ENCLOSURE Clear cover Aluminum cover C North American (NEC/CEC) A North American (NEC/CEC) D International (IEC) V International (IEC) CONDUIT/CONNECTORS Standard Mini-connectors Micro-connectors (M12) 02 (2) 1/2 NPT 10 (1) 4-pin 13 (1) 4-pin 05 (2) M20 11 (1) 5-pin 15 (1) 5-pin 19 (1) 6-pin 17 (1) 6-pin 20 (1) 7-pin 18 (1) 8-pin 21 (1) 8-pin VISUAL INDICATOR [see chart below] RM Red closed/green open 1M Three-way 1 XM Special GM Green closed/red open 2M Three-way 2 Model number example AN 35S 1L C 02 RM OPTIONAL MODEL NUMBER Mounting hardware required and sold separately. PARTNERSHIP ID Some models may include 5-digit identification suffix. Visual indicator designations Clearly view valve position status from up to 75 feet with the Axiom s visual indicator. The indicator s rugged Lexan construction makes it resistant to physical damage and tolerant to most corrosives. DESIGNATION 0 90 R RED CLOSED GREEN OPEN G GREEN CLOSED RED OPEN A B A B 1 C C A B A B 2 C C X Specialty configuration - please consult factory 10 TECHNICAL BULLETIN 2/18

7 AN 20 EN AXIOM AN NONINCENDIVE & I.S. ON/OFF VALVE CONTROLLER Specifications Materials of construction Housing and air manifold plate Visual indicator drum Visual indicator cover Fasteners O-rings Operating life Epoxy-coated anodized aluminum Nylon Polycarbonate Stainless steel Nitrile compound 1 million cycles Temperature range -40 C to 80 C (-40 F to 176 F) Warranty Sensing and communication module Mechanical components Unit weights Aluminum Unit dimensions Unit height Cover removal clearance Five years Five years 2.38 kg / 5.25 lb 122 mm [4.81 in] 214 mm [5.80 in] Position sensing Accuracy Within 1 Repeatability Within 1 Setting buffer Dead band Max rotational range 120 Ratings Nonincendive (Class I and II, Div. 2) Intrinsically safe (Ex ia Zone 0; Class I and II, Div. 1) Enclosure protection Type 4, 4X and 6 Ingress Protection 66 and 67 Approvals* 4 from setpoint (Rotational distance from original setpoint where switch will energize on return stroke) 6 from setpoint (Rotational distance from original setpoint where switch will de-energize) All models* Function 45S only* All models All models See StoneL.com/approvals * Only models listed on StoneL s official website are approved per specific rating. Dimensions Clear cover* 4.81 in [122 mm] 2 3 2.48 in [63.0 mm] 2.26 in [57.4 mm] 1/4" NPT (2) 7.01 in [178 mm] E3 S1 E2 1/2" NPT (2) or M20 (2) * Aluminum cover 4.90 in [125 mm] 1/4" NPT (3) [0.8 Cv] or 3/8" NPT (3) [1.2 Cv] 5.88 in [149 mm] TECHNICAL BULLETIN 2/18 11

Metso Flow Control Inc. Europe, Vanha Porvoontie 229, P.O. Box 304, FI-01301 VANTAA, Finland. Tel. +358 20 483 150. Fax +358 20 483 151 North America, 26271 US Hwy 59, Fergus Falls, MN 56537, USA. Tel. +1 218 739 5774. Fax +1 218 739 5776 South America, Av. Independéncia, 2500- Iporanga, 18087-101, Sorocaba-São Paulo, Brazil. Tel. +55 15 2102 9700. Fax +55 15 2102 9748/49 Asia Pacific, 238B Thomson Road, #17-01 Novena Square Tower B, Singapore 307685 Tel. +65 6511 1011. Fax +65 6250 0830 China, 11/F, China Youth Plaza, No.19 North Rd of East 3rd Ring Rd, Chaoyang District, Beijing 100020, China. Tel. +86 10 6566 6600. Fax +86 10 6566 2583. Middle East, Roundabout 8, Unit AB-07, P.O. Box 17175, Jebel Ali Freezone, Dubai, United Arab Emirates. Tel. +971 4 883 6974. Fax +971 4 883 6836 www.metso.com/valves Subject to change without prior notice.