Commercial 1000VDC String Inverter XGI Installation and Operation Guide Models: XGI XGI

Similar documents
RSDCOM. Installation and Operation Guide. Commercial Rapid Shutdown Combiner. DOCR Published March 2017 Revision C English

CP-250E-60/72-208/240-MC4 Microinverter with Modular Trunk Cable

Inverter / Charger Accessory for Steca Solarix PLI Phase / Parallel Kit. Installation and operating instructions Z01 17.

CP /240-MC4 User Manual

PVI 6500 PVI 7500 INSTALLATION AND OPERATION MANUAL. Residential/Commercial Grid Tied Photovoltaic Inverter. 2012, Solectria Renewables, LLC

Manual. BlueSolar Grid Inverter 1500 / / / / / 230

User Manual. Solar Charge Controller 3KW

RAPID SHUTDOWN COMBINER

STONESTAR AUSTRALIA PTY LTD

User Manual Solar Charge Controller 3KW

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

Operation Manual Pika Islanding Inverter X7602/X Part of the Pika Energy Island M

8 Troubleshooting and Maintenance

CPS Energy Balancer. Version: 1.0

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

SP PRO ABB Managed AC Coupling

SMT. Installation and Operation Manual. Model:SMT WITH MPPT TECHNOLOGY

AeroVironment Universal Solar Pump Controllers

High Frequency SineWave Guardian TM

Solar Hybrid Inverter SP Brilliant Grid Series

2016 Photovoltaic Solar System Plan Review List

User Manual. 3kW Hybrid PV Inverter HX-3000

Foreword

User Manual 1KVA-5KVA INVERTER / CHARGER

UGE-4K Off-Grid Controller OWNER S MANUAL

GV-10 Manual 10.5A / 140W IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. Solar Charge Controllers with Maximum Power Point Tracking

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

SunLink PV System Disconnect with Arc Fault Detection Installation and Operations Manual

HOYMILES MICRO-IVERTER MI-250

User manual. Solar Hybrid 1-5KVA. Uninterruptible Power Supply / Charger

Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC. User s Manual K01-C

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor Installation Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

Off Grid Solar Inverter. LVS 50M User Manual

INSTALLATION AND OPERATOR S MANUAL

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

Installation Manual Pika Islanding Inverter X7601/X7602/X Part of the Pika Energy Island M

MPPT Controller PVTS Series User Manual. User Manual. 800W-4000W Hybrid solar inverter. Version: 1.4

Installation Guide Smart-UPS On-Line SRT1000/1500 UXI-NCLI, SRT1000/1500 UXI-LI, Tower/Rack-Mount

User Manual 1.5KVA-3KVA INVERTER / CHARGER. Version: 1.1

Solar Inverter SUNNY BOY 5000US / 6000US / 7000US

User Manual. Hybrid PV Inverter. Version: 2.1

Operator s Series 300 Generator Paralleling System

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

Operations Manual Pika Harbor Smart Battery

Product Overview. Product Identification. Amps One CT Two CTs Three CTs

User Manual 5KVA/5KW INVERTER / CHARGER. Version: 1.3

Steca Solarix PLI. Inverter / Charger with Solar Charge Controller. Installation and operating instructions. Download manual at

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

User Manual 1KVA/ 2KVA/ 3KVA INVERTER / CHARGER

PV Master OPERATION MANUAL

User Manual 1.5KVA-3KVA INVERTER / CHARGER

User Manual LV 3KVA-24V INVERTER / CHARGER. Version: 1.1

Photovoltaic Solar Plan Review

User Manual 4KVA/ 5KVA INVERTER / CHARGER. With MPPT Controller

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

Enelion Vertica. Installation manual. 22 kw. for the specialists

3 Phase Power Systems - Designed for Canada

Installation Guide Smart-UPS On-Line SRT1000/SRT1500 XLA Tower/Rack-Mount

User Manual 1KVA-5KVA INVERTER / CHARGER

User Manual. Hybrid 4KW PV Inverter. Version: 1.2

FHOTON Drive. Installation Guide

User Manual. SP10000 Premium

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Solar Hybrid Inverter SP Brilliant Series

SP PRO KACO Managed AC Coupling

Solar PV Standard Electrical Plan

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

Solar module user manual Conergy PM 225P-250P

INSTALLATION MANUAL CRYSTALLINE SOLAR MODULES

HANGKAI GROUP HOYMILES MICRO-INVERTER MI-250

GVB-8 (Boost) Manual

Copyright 2012 DelSolar Co. Ltd MQWRD installation manual-iec Ver. 1.4

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

Generator Sets Controller 210. Operation Manual. Ver1.0

1KVA/ 2KVA/ 3KVA/ 4KVA/ 5KVA MS, LV MPPT INVERTER / CHARGER. User Manual. Version: 2.3

1. Introduction OHY1P kW Hybrid Inverter USER MANUAL V2.0

ORVALDI Solar Infini 5kW

Solar Hybrid Inverter SP Efecto Series

Installing a Programmed Fronius SCERT in a Managed AC Coupled system

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

CPS SCA Series Grid-Tied PV-Inverter CPS SCA3/4/5KTL-O/US. Installation and Operation Manual

The Traveler Series: Adventurer

Installation Instructions & Users Manual

Sunny Boy Accessories SUNNY BOY COMBINER BOX TLUS SBCBTL6

Owner's/Installation Manual

User Manual 3KVA-5KVA INVERTER / CHARGER. Version: 1.1

Disconnect Combiner Box Installation Manual

SBCB-6, SCCB-12, 28, 52 6 to 52 Circuit Combiner Boxes

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, P/N: , Revision 1

Solar inverter with MPPT AX II - M series: 4 / 5 kva, AX II - P series: 3 kva. With integrated star point grounding* according to VDE AR-E 2510-

Eco-Propel TM Variable Speed Pump Kit Instruction and Operation Manual, p/n Revision 0

Battery & Energy Meter Quick Guide

User Manual SOLARMAX 1KVA/ 2KVA/ 3KVA INVERTER / CHARGER

Combiner Manual #OMBINER #OMBINER < 2* )NSTALLATION 7(&+12/ i 62/$5

User Manual 1KVA-5KVA (PF1) INVERTER / CHARGER. Version: 1.0

My Reserve 500 Install Guide

1000 Watt Power Inverter INSTRUCTION MANUAL HT87112-AUOXY

Solar Hybrid Inverter SP Efecto Series

Transcription:

Commercial 1000VDC String Inverter XGI 1000 Installation and Operation Guide Models: XGI 1000-60 XGI 1000-65

1. Important Safety Instructions... 4 1.1. Hazard Symbols... 4 1.2. Symbols on Labels... 4 1.3. General Safety Messages... 5 1.4. Status Panel... 6 2. Overview... 7 2.1 Inverter Overview... 7 2.2 Inverter Placement... 8 2.3 Unpacking... 9 3. Installation... 10 3.1 Installation Sequence... 10 3.2 Mounting the Inverter... 10 3.3 Wiring... 13 3.4 AC Connections... 14 3.5 DC Connections... 17 3.6 Communications Connections... 20 4. Startup... 24 4.1 Startup Checklist... 24 4.2 Startup Steps... 24 5. User Interface... 25 5.1 User Interface Overview... 25 5.2 Menu Screens... 29 6. Operation... 31 7. Maintenance and Troubleshooting... 32 8. Specifications... 33 8.1 General Specifications... 33 8.2 Voltage and Frequency Limits and Trip Times... 33 8.3 Temperature... 34 8.4 Enclosure... 34 9. Appendix... 35 9.1 Warranty and RMA Instructions... 35 9.2 Datasheet... 35 DOCR-070733-B Page 2 of 35

9.3 Contact Information... 35 DOCR-070733-B Page 3 of 35

1. Important Safety Instructions 1.1. Hazard Symbols DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION indicates a hazardous situation which, if not avoided, will result in minor or moderate injury. NOTICE indicates a hazardous condition which, if not avoided, could result in equipment working abnormally or property loss. INFO indicates important supplementary information to use the product effectively. 1.2. Symbols on Labels Table 1.1 Hazard Symbols AC Signal DC Signal Equipment Ground Phase Off On Refer to Operating Instructions Caution: Risk of Electric Shock Caution: Risk of Electric Shock Energy storage timed discharge Table 1.2 Explanation of Symbols on Labels DOCR-070733-B Page 4 of 35

1.3. General Safety Messages Electric Shock Hazard Components with hazardous voltage and energy will electrocute operator. Operator shall avoid touching live components with hazardous voltage and energy. Unqualified Operator Hazard Operator may cause a hazardous situation by making incorrect installation or wiring connections. A qualified technician shall do all installation and wiring connections to comply with all local, national, or country specific guidelines for safety. Electrical Shock Hazard Operator may contact components with hazardous voltage and energy. Use proper safety equipment when de-energizing the unit. De-energize the unit, wait 5 minutes, and verify the absence of voltage before opening the equipment or removing any protective shields. General Damage to Equipment Operator may damage the equipment when trying to service it. Contact Yaskawa - Solectria Solar or an installer authorized by Yaskawa - Solectria Solar for maintenance. Read and Follow Instructions Failure to read and follow instructions may void warranty. Install unit according to instructions. SAVE THESE INSTRUCTIONS DOCR-070733-B Page 5 of 35

1.4. Status Panel Figure 1.1 Status Panel Ready (Green) On: Inverter is initialized and ready to operate Off: Inverter is not ready to operate Network and Communication (Blue) On: Network and communication services are working properly Off: Network and communication services are offline Power (Green) On: Inverter is generating AC power Off: Inverter is not generating AC power Maintenance (Yellow) On: Inverter needs maintenance or service Off: Inverter does not need maintenance or service Power Fault (Red) On: Power fault that needs service and may be a hazard Off: There is no power fault Locate Simultaneous On, On, On: Signal to identify a specific inverter in a large field installation. Table 1.3 Explanation of Symbols on Status Panel DOCR-070733-B Page 6 of 35

2. Overview 2.1 Inverter Overview 2.1.1 System Overview Figure 2.1 System Overview for Power (Left) and Communications (Right) 2.1.2 Inverter Features Figure 2.2 Inverter Features for Inverter (Left) and Wiring Box (Right) DOCR-070733-B Page 7 of 35

2.2 Inverter Placement 2.2.1 Inverter Environment The inverter is rated for outdoor use and will operate when exposed to direct sunlight or rain. It is recommended that the inverter be mounted in the shade. 2.2.2 Inverter Angle Figure 2.4 Inverter Environment (Left to Right) Shaded, Direct Sunlight, and Rain The inverter can be mounted vertically down to 5 degrees from horizontal. Make sure that the wiring box is below the inverter box. Figure 2.5 Inverter Mounted Vertically (Left, proper orientation) and Upside Down with Wiring Box Above Inverter Box (Right, not allowed) DOCR-070733-B Page 8 of 35

Figure 2.6 Inverter Angled at 5 Degrees (Left, proper orientation) and Angled with Wiring Box Above Inverter Box (Right, not allowed) Note: It is recommended to install the inverter facing north to minimize the direct sun exposure. 2.3 Unpacking 2.3.1 Unpacking The inverter is shipped in 2 boxes. Box 1 contains: Inverter Box Mounting Bracket Hardware Kit containing o 3 M6 bolts o 4 M5 bolts Box 2 contains: Wiring Box Hardware Kit: 2 of the 3 M6 bolts are used to attach the Wiring Box to the Mounting Bracket. The 3 rd M6 bolt is used at the bottom of the Wiring Box for the Auxiliary Equipment Grounding Connection. The 4 M5 bolts are used to connect the Inverter Box to the Wiring Box. DOCR-070733-B Page 9 of 35

3. Installation 3.1 Installation Sequence 1. Install the mounting bracket in the desired location. 2. Install the wiring box to the bottom portion of the mounting bracket. Lifting Heavy Object Hazard Proper lifting technique must be used in order to avoid injuries. Use a two-man lift to install inverter box. 3. Install the inverter box on the mounting bracket above the wiring box. Connect the inverter box and wiring box together. Ensure that the inverter box connects fully to wiring box. 4. Remove the cover of the wiring box and the plastic shields. 5. Confirm site AC breaker is set to OFF. 6. Connect the AC wires from the grid in the wiring box to the AC terminal block. 7. Connect the input PV circuit wires in the wiring box by connecting to either (depending upon the specific wiring box configuration): 7.1. The DC fuse holders. 7.2. The DC terminal blocks. 8. Connect the communication conductors. 9. Replace the plastic shields and the cover of the wiring box. 10. Connect the antenna to the inverter box using the corner connector. 3.2 Mounting the Inverter 3.2.1 Inverter Spacing and Mounting Space the inverters no closer than shown in the following figure. DOCR-070733-B Page 10 of 35

Figure 3.1 Inverter Minimum Spacing Mount the bracket to a flat surface capable of supporting 186 lbs. (84.4 kg). Acceptable surfaces include concrete, drywall, or plywood as long as they can support this weight. Use M10 or 7/16 in. bolts to attach the mounting bracket to the surface. Use 4 bolts corresponding to the holes shown in the following figure. Torque the bolts as necessary to support the weight. DOCR-070733-B Page 11 of 35

Figure 3.2 Mounting Bracket Place the Wiring Box onto the Mounting Bracket and use 2 of the M6 bolts to attach them. The holes are on the sides of the Wiring Box and Mounting Bracket. Torque the connections to 40 in*lbs. (4.5 N*m). Install the remaining M6 bolt to the bottom of the Wiring Box for the Auxiliary Equipment Grounding Connection. Lifting Heavy Object Hazard Proper lifting technique must be used in order to avoid injuries. Use a two-man lift to install inverter box. Place the Inverter Box on top of the Wiring Box. Line up the Inverter Box so that it matches the Wiring Box. Use the 4 M5 bolts to connect the Inverter Box to the Wiring Box. Torque the connections to 20 in*lbs. (2.3 N*m). DOCR-070733-B Page 12 of 35

3.3 Wiring 3.3.1 Tools Needed for AC and DC Connections 3/16 in or 4.75mm slot torque driver (AC Connections) #2 Phillips head torque driver (DC + and Connections) Multimeter (AC and DC Connections) 3.3.2 Power Connections Use 90 C minimum rated conductors. Connections are rated for 75 C terminal temperatures. Use larger wire than the minimums to avoid a large voltage drop or as needed to comply with local electrical codes. 3.3.3 Remove Plastic Shields Figure 3.3 Wiring Box Connections The Plastic Shields are a safety feature to protect the user from hazardous conditions when the inverter is running. Remove them when wiring the unit. DOCR-070733-B Page 13 of 35

3.4 AC Connections Turn AC Switch OFF before wiring. Turn AC Switch to OFF Ensure no AC power is flowing into inverter. 3.4.1 Transformer Configurations Grid Mismatch Inverter may not start operation. Check with your local electricity supply company before selecting a grid standard. The system must comply with National Electrical Code ANSI/NFPA 70 and with all local rules and safety regulations before the inverter can be operated. The inverter must connect to a transformer that has a Wye configuration on the inverter side. The ground terminal must be connected to the center of the Wye. Connect to the neutral if it is present or use a jumper to connect the ground and neutral terminals together. Make sure such connection is approved by the local AHJ. Figure 3.4 Permitted Transformer Configurations Improper Transformer Configuration Inverter will not run and may have hazardous current. Connect transformer in specified configurations only. DOCR-070733-B Page 14 of 35

3.4.2 AC Connection Wire Specifications Figure 3.5 Not Permitted Transformer Configurations The AC connections include ground and neutral. Wires must be rated for at least 600 V. Use wires according to the table below as required to comply with local electrical codes. 3 Phase Copper: 3 to 1/0AWG (26.7 to 50 mm 2 ) Aluminum: 1 to 1/0 AWG (42.4 to 50 mm 2 ) N Not a current carrying conductor Copper: 8 to 4 AWG (8.4 to 21.2 mm 2 ) (Neutral wire cannot be smaller than ground) Aluminum: 6 to 4 AWG (13.3 to 21.2 mm 2 ) Ground Copper: 8 to 4 AWG (8.4 to 21.2 mm 2 ) Aluminum: 6 to 4 AWG (13.3 to 21.2 mm 2 ) Table 3.1 AC Connection Specifications XGI 1000-60 XGI 1000-65 AC Breaker Size 100 A (3 pole) 100 A (3 pole) Table 3.2 AC Breaker Specifications Electric Shock Hazard Components with hazardous voltage and energy will electrocute operator. Ensure no AC power is flowing into inverter. Verify with a multimeter. DOCR-070733-B Page 15 of 35

Turn AC Switch OFF before Wiring. Wire the AC Connections as shown below. Torque all AC connections to 25 in*lbs (2.8 N*m) with the 3/16 in (4.75mm) slot torque driver. The inverter auto-detects phase rotation. A jumper wire between Ground and Neutral may be used if: Figure 3.6 AC Connections Use of a jumper is approved. There is no Neutral wire Do not use a jumper if the Neutral wire is connected. DOCR-070733-B Page 16 of 35

3.5 DC Connections Turn DC Disconnect to OFF Ensure no DC power is flowing into inverter. Open Fuseholders 3.5.1 MPPT Zones Ensure no DC power is flowing into inverter. Figure 3.7 DC Zones in Individual Mode (Left) and in Parallel Mode with Jumpers (Right) The DC connections are divided into 4 zones with the positive side on the left and the negative side on the right. Each zone consists of 4 fuses and a bus on both sides. To run in individual mode, connect the conductors normally. To run in parallel mode, connect the conductors and bridge the zones. If an external combiner box is used, the outputs of the combiner box can connect directly to the buses for the zones. The conductors should be at least 1000V PV wire. Use copper wire of size 10 to 8 AWG (5.3 to 8.4 mm 2 ) as required to comply with the NEC and local electrical codes. XGI 1000-60 XGI 1000-65 Rated DC power (per zone) 15 kw (26.4 A) 16.25 kw (27.6A) Max DC power allowed 22.5 kw 24.4 Kw Absolute Max open circuit Voltage 1000 VDC Operating voltage 300-950 VDC Max power input voltage range (MPPT) 580 to 850 VDC 600-850 VDC Maximum available PV current (Isc x 1.25) (per zone) 45 A Maximum Allowed DC to AC Ratio 1.5 Fuses 15 A (20 A, 25 A or 30 A also compatible) Table 3.3 DC Input Specifications Per Zone DOCR-070733-B Page 17 of 35

15 A fuses come installed in the fuseholders. For 30 A fuses, skip every other fuseholder. Electric Shock Hazard Components with hazardous voltage and energy will electrocute operator. Ensure no DC power is flowing into unit. Verify with a multimeter. Check Polarity of DC Inputs DC inputs with the wrong polarity may cause damage to inverter. Check polarity with a multimeter. Use Correct Fuses Make sure to size the fuses according to all NEC requirements. Wire connections as shown below. Torque connections to 25 in*lbs (2.8 N*m) with #2 Phillips head torque driver. Figure 3.8 DC Connections for Single Zone DOCR-070733-B Page 18 of 35

3.5.2 Strings DC Overload Exceeding the recommended DC to AC ratio may cause damage to the unit not covered under the warranty. Size strings according to information in this section. Each zone has four inputs, each with a positive and negative side. Connect the same number of PV modules to each string in the same zone. Use the string sizing tool (https://solectria.com/support/string-sizing-tool/) to determine lengths for the strings in each zone. For individual mode, strings must be balanced for optimum performance and AC output. When doing DC/AC ratio sizing, perform calculations at the zone level. Maximum DC/AC oversizing ratio is 1.5 STC conditions of the modules. Each zone maximum input power is 22.5 kw (XGI 1000-60) and 24.4 kw (XGI 1000-65). Note for any application that may experience higher than 1000 W per m 2 on a regular basis, a smaller DC/AC ratio is recommended. Also, the combined Isc rating of all strings multiplied by 1.25 must be less than 45A for Individual mode. If you are running the inverter in parallel mode by bridging the zones, then do the calculations based on the inverter power level. With maximum DC/AC ratio of 1.5 STC conditions, you can connect up to 90 kw (XGI 1000-60) and 97.5 kw (XGI 1000-65). Note for any application that may experience higher than 1000 W per m 2 on a regular basis, a smaller DC/AC ratio is recommended. Also, the Isc rating of all strings multiplied by 1.25 must be less than 180 A for parallel mode. Note all configurations must be below both requirements: DC/AC ratio and Isc. Zones do not have to match, but the strings within each zone must match. Figure 3.9 Matched String Sizes Within Each Zone DOCR-070733-B Page 19 of 35

3.6 Communications Connections 3.6.1 Sample Communications Networks Figure 3.10 Mismatched String Sizes Within Each Zone Connection to the internet is required for the inverter. The modem or gateway must have a direct Ethernet connection to one inverter. The XGI uses TCP/IP Modbus for all Ethernet connections. The inverter can be connected to either SolrenView using the Revenue Grade Meter (RGM) or through a 3 rd party Data Acquisition System (DAS) that can connect using Ethernet. Figure 3.11 Sample Network Configurations with Weather Station and RGM (Left) and DAS (Right) DOCR-070733-B Page 20 of 35

3.6.2 Connecting Multiple Inverters To connect multiple inverters together, set up an Ethernet daisy chain or a star configuration using Ethernet switches. Any number of inverters can be connected using the Ethernet daisy chain. Use Cat6 cable with max length 328 ft. (100m) for these connections. Figure 3.12 XGI Inverters Connected with Ethernet Daisy Chain Figure 3.13 XGI Inverters Connected with Ethernet Switches DOCR-070733-B Page 21 of 35

3.6.3 Connector and Ports The XGI has a 16 pin I/O port with connector and 2 interchangeable Ethernet Ports. Figure 3.14 Communications Connections and Ports: 2 Ethernet Ports (Left) and 16 Pin I/O Port with Connector (Right) Pin Input/ Output Function Description/Notes 1-6 Both RGM Connection See RGM Connection Pinout 7 Input Return for remote shutdown 8 Input Remote shutdown (optoisolated) 24 VDC signal will shut down and keep inverter in shutdown mode. Opto-isolated means that the control (remote shutdown) is electrically separated from the device (inverter). 9-14 Reserved 15 Output Return for 24 VDC Requires operation of auxiliary power supply for the inverter 16 Output Source for 24 VDC, 0.5 ADC for auxiliary devices Table 13.3 Pin Map for 16 Pin I/O Connector Wire Size 28-16 AWG (0.08-1.5 mm 2 ) Torque 5 in*lbs. (0.56 N*m) Torque Screwdriver Size 5/64 in. (2 mm) Table 13.4 Connection Specifications for 16 Pin I/O Connector DOCR-070733-B Page 22 of 35

3.6.4 RGM Connection Pin Signal 1, 5 Negative (-) 2, 6 Positive (+) 3, 4 Communications Ground (Return) Table 13.5 RGM Connection Pinout Make the RGM connection using Belden 89841 Multi-Conductor cable or equivalent. The inverter by default acts as the master and has a software controlled terminating resistor. If the XGI is not the master, disable the resistor. Always make sure the gateway or modem has a direct Ethernet connection to one inverter. 3.6.5 DAS Connection Only use DAS that can connect using Ethernet. To connect a DAS, use an Ethernet connection. For sites with daisy-chained inverters the DAS and the modem or gateway must be at the ends of the chain, with all the inverters in the middle. For a star configuration of inverters using Ethernet switches, the DAS should attach to a switch. Always make sure the gateway or modem has a direct Ethernet connection to one inverter. 3.6.6 Weather Station Connection Only use weather stations that can connect using Ethernet. The weather station must connect to the modem or gateway. DOCR-070733-B Page 23 of 35

4. Startup 4.1 Startup Checklist 4.1.1 Mechanical Installation Make sure the mounting bracket is securely installed and all fasteners are tightened to the torque specifications. See Mounting the Inverter. 4.1.2 Electrical Connections Make sure all cables are connected to the correct terminals. Make sure all connections are tightened to torque specifications. See AC Connections and DC Connections. Make sure the DC Switch on the inverter is in the OFF position. Make sure the AC Switch on the inverter is in the OFF position. 4.1.3 Electrical Check Make sure the AC circuit breaker is appropriately sized. Test whether the AC voltage is within the normal operating range. Test polarity of DC inputs. See DC Connections. Make sure the DC open circuit voltage of input strings is less than 1000V. 4.2 Startup Steps Electrical Shock Hazard Installer may come into contact with components which have hazardous voltage and energy. Use proper safety equipment when de-energizing sources. Follow the instructions on how to energize the unit. 1. Energize the AC breaker for the inverter. 2. Energize the site DC connections to the PV source circuits. 3. Set inverter AC on/off switch to ON. 4. Turn on inverter DC disconnect. 5. Verify that the Status Panel illuminates Ready and neither Maintenance nor Power Fault are illuminated. 5.1. If the LEDs do not match, see Maintenance and Troubleshooting. 6. Connect to the gateway inverter s WiFi network (see User Interface Overview). 6.1. Select the gateway node (in blue) at the top of the list. 6.2. Log in to the inverter (see Inverter Page). 6.3. Select the First Time Start Wizard from the menu under Inverter Configurations. 6.4. Follow the instructions of the First Time Start Wizard. 6.5. Verify that the Status Panel illuminates Ready, Network and Communications, and Power. 7. Measure output power to verify inverter is operating. DOCR-070733-B Page 24 of 35

5. User Interface 5.1 User Interface Overview The front panel display provides status information but does not provide the user the ability to control the inverter. To control the inverter the user must use either a smart device, such as a smartphone or laptop, to access the User Interface to connect to the inverter. The User Interface gives the operator a simple means to control the inverter settings and access the inverter without having to touch it. Default Network ID XGI-01-036 Default Password (Case Sensitive) Solectria Table 5.1 Default Network Credentials If this network is not visible on the list of networks, bring the smart device or laptop closer to an inverter. By accessing the network, all inverters that are part of the network are accessible. 5.1.1 Landing Page The landing page is displayed when the inverter is accessed and acts like a homepage for the network. It provides a list of inverters that exist in the network cluster. This list also shows if there are any inverters with problems. Below is the inverter landing page and a chart that explains the symbols. Note that the node at the top in blue text is the node to which the user is directly connected. To navigate to a particular inverter, select the node name of the inverter. DOCR-070733-B Page 25 of 35

Figure 5.1 Inverter Landing Page Symbol Explanation Inverter OK: This indicates that the inverter is functioning normally. Inverter Missing: This indicates that the inverter included as part of the network is undetected. Inverter Unknown: This indicates that the inverter that was not included as part of the network is detected. Inverter Fault: This indicates that the inverter has an inverter issue that prevents it from producing power. Inverter Warning: This indicates that the inverter has an inverter issue that does not prevent it from producing power. Table 5.2 Explanation of Symbols in User Interface In this example, three nodes are worth noting. Node-F.8D.5D: This node is the node currently connected to and is operating normally. All other nodes communicate through it. Node-19.BB.64: This node is not recognized by the network cluster. Node-19.BB.9B: This node was recognized by the network cluster but cannot communicate with it now. Troubleshooting inverters like the last two on this list is covered in the Maintenance and Troubleshooting section. DOCR-070733-B Page 26 of 35

5.1.2 Inverter Page Each inverter has a status page (see Fig 5.2) that shows an overview of the inverter. At the bottom is the inverter status, which shows which LEDs on the Status Panel are lit. This page also shows the serial number, current AC power, energy produced that day and total lifetime energy. Figure 5.2 Inverter Status Page In the upper left corner, next to the company logo, is a button that displays a drop-down menu to the left. In the upper right corner is a Login button. Before logging in, the user interface is in observer mode. Logging in is necessary to view and access the Inverter Configurations options in the menu in administrator mode. Everything accessible in observer mode is also accessible in administrator mode. If the Logout button is pressed in administrator mode, the user returns to observer mode. Figure 5.3 Inverter Status Page with Drop Down Menu DOCR-070733-B Page 27 of 35

5.1.3 Inverter Menu The following menu is displayed without logging in. To access the sub-menu items like AC Energy, hover over the menu item that contains it, in this case Live AC Measurements, and the sub-menu will populate. Live Measurements Inverter Status o Inverter Status o SolrenView Monitoring (if customer purchased this option) o Inverter Info Network Information o Ethernet Status o WiFi Status o Internet Connection Status Select Inverter to View Note: Select Inverter to View returns back to the landing page. In administrator mode, the following is added to the bottom of the menu list. Inverter Configurations o Inverter Functions o Network Configuration User Access Management Inverter Name Configuration Inverter Last Update Time and Date Configurations Monitoring Configuration Advanced Network Configuration o Firmware Update o System Test o First Time Start Wizard DOCR-070733-B Page 28 of 35

5.2 Menu Screens 5.2.1 Live Measurements The following measurements are shown on this screen. All are accessible in both observer and administrator modes. Section Subsection Measurement AC Measurements Energy Today s Energy Lifetime Energy Reactive Energy (+) Reactive Energy (-) Power Active Power Apparent Power Reactive Power Reactive Available Power Factor Voltage A-N B-N C-N A-B B-C C-A Current A B C Frequency Frequency DC Measurements Power Input 1 Input 2 Input 3 Input 4 Voltage Input 1 Input 2 Input 3 Input 4 Current Input 1 Input 2 Input 3 Input 4 Temperature Internal Heat Sink The DC inputs correspond to the MPPT zones referenced in MPPT Zones. A screenshot of the Live Measurements screen is shown below. DOCR-070733-B Page 29 of 35

Figure 5.4 Inverter Status Page with Drop Down Menu DOCR-070733-B Page 30 of 35

6. Operation 6.1.1 Inverter Start-Up Manual Start-Up: In the User interface, on the inverter page, there is a button that will turn the inverter ON. Automatic Start-Up: The inverter will start up automatically when the output voltage and power from the PV array meet the required values and AC grid is normal. 6.1.2 Inverter Shutdown Manual Shutdown: In the User interface, on the inverter page, there is a button that will turn the inverter OFF. Automatic Shutdown: The inverter will shut down automatically when the output voltage and power of PV modules are lower than the required values or AC grid fails. 6.1.3 Operation Modes System Check This mode occurs when the user has opted to run a System Test, see Inverter Menu. Normal Operation This mode occurs when the inverter is exporting power to the AC grid. Standby This mode occurs when the output voltage and power of the PV modules do not meet the inverter specifications. The inverter will check automatically whether it meets the startup conditions in this mode until it turns back to normal mode. The inverter will switch from standby mode to fault mode if a malfunction occurs. Fault This mode occurs when the inverter is in a fault condition. 6.1.4 Grid-Tied Power Generation The XGI series inverter has an automatic grid-tied power generation process. It will check whether the AC grid meets the conditions for grid-tied power generation constantly and test whether the PV array has enough power. When all conditions are met, the inverter will enter grid-tied power generation mode. While in the grid-tied power generation mode, the inverter detects the grid at all times, and also keeps the photovoltaic array output in maximum power point tracking (MPPT) mode. In case of any abnormality, the inverter will enter the non-operational mode immediately. In low light conditions when the PV power is not sufficient to sustain the inverter operation, the inverter will enter standby mode. When the voltage and power of the PV array become stable and higher than the required value, the inverter will attempt to start grid-tied power generation again. DOCR-070733-B Page 31 of 35

7. Maintenance and Troubleshooting If an inverter is not running correctly, the Status Panel will show there is an issue. When the inverter is working normally, the first 3 LEDs are lit (Ready, Network and Communications, and Power) and the last 2 are unlit (Maintenance and Power Fault). The User Interface will also when an inverter is not running correctly. When the inverter is working correctly, the landing page will show a green checkmark next to the inverter. DOCR-070733-B Page 32 of 35

8. Specifications 8.1 General Specifications XGI 1000-60 XGI 1000-65 Input Voltage Max 1000 VDC Input Voltage Range 580 to 850 VDC 600-850 VDC Max Input Current 105.6 A 110.4 A MPP Trackers 4 Current per MPPT 26.4 A 27.6 A Max Short Circuit Current 45 A per zone or 180 A combined Max Input Back-feed 0 A Output factor Unity > 0.99; Adjustable from -0.85 to 0.85 Grid Type 3 Phase with Ground and Neutral Nominal Output Voltage 480 V Nominal Frequency 60 Hz Output Voltage Range -12/+10% Frequency Range 57-62 Hz Max Output Current 72 A 78 A Max Output Power 60 kw 65 kw Table 8.1 General Specifications 8.2 Voltage and Frequency Limits and Trip Times All models of the XGI 1000 comply with IEEE1547-2003 requirements. The tables below show its standard settings. Voltage Range Clearing Time V < 45% 0.16 s 45% <= V < 70% 1.0 s 70% <= V < 88% 2.0 s 88% <= V < 110% No trip 110% <= V <= 120% 1.0 s V > 120% 0.16 s Table 8.2 Voltage Limits and Trip Times Frequency Range Trip Time F < 57 Hz 0.16 s 57 Hz <= F < 59.5 Hz 2.0 s 59.5 Hz <= F < 60.5 Hz No trip 60.5 Hz <= F <= 62 Hz 2.0 s V > 62 Hz 0.16 s Table 8.3 Frequency Limits and Trip Times DOCR-070733-B Page 33 of 35

8.3 Temperature XGI 1000-60 XGI 1000-65 Ambient Temperature Range -40 F to +140 F (-40 C to +60 C) Derating Temperature 122F (50 C) 113F (45 C) Storage Temperature Range -40 F to +167 F (-40 C to +75 C) Table 8.4 Normal Temperature Ranges Figure 8.1 Derating with Temperature 8.4 Enclosure Enclosure Rating NEMA Type 4 Dimensions 45.8 in x 28.3 in x 11.6 in (1163 x 719 x 295 mm) Weight Inverter: 117 lbs (53.07 kg) Wiring Box: 49 lbs (22.22 kg) Mounting Bracket: 20 lbs (9.07 kg) Mounting Angle Range 5-90 Enclosure Finish and Type Powder Coated Aluminum Table 485 Enclosure Information DOCR-070733-B Page 34 of 35

9. Appendix 9.1 Warranty and RMA Instructions For all warranty information, please visit: http://solectria.com/support/documentation/warranty-information/grid-tied-inverter-warranty-letter/ 9.2 Datasheet https://solectria.com/pv-inverters/commercial-string-inverters/solectria-60-65-1000/ 9.3 Contact Information Telephone 978.683.9700 Fax 978.683.9702 Sales Support inverters@solectria.com Customer Support Website 978.683.9700 x2 www.solectria.com Table 10.2 Contact Information DOCR-070733-B Page 35 of 35