POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011

Similar documents
POWER SYSTEM OPERATING INCIDENT REPORT: TRIP OF 837 TARONG MT. ENGLAND 275 KV LINE AND MT. ENGLAND NO KV BUSBAR ON 30 OCTOBER 2011

POWER SYSTEM OPERATING INCIDENT REPORT MULTIPLE CONTINGENCY EVENT IN NORTH WEST TASMANIA ON 6 APRIL 2012

Power System Operating Incident Report Trip of Murray Lower Tumut No kv Transmission Line at Murray End Only on 18 November 2013

POWER SYSTEM OPERATING INCIDENT REPORT TRIPS OF YALLOURN W POWER STATION UNITS W1 AND W3 ON 14 NOVEMBER 2012

POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 UNIT ON 9 FEBRUARY 2012

POWER SYSTEM OPERATING INCIDENT REPORT LIGHTNING STRIKES IN TASMANIA AND PACIFIC ALUMINIUM POTLINE LOAD REDUCTIONS 21 MARCH 2013

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF B 220 KV BUSBAR AT GEORGE TOWN ON 27 NOVEMBER 2012.

POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010

Power System Operating Incident Report Trip of Red Cliffs Horsham and Red Cliffs-Wemen Kerang 220 kv transmission lines on 15 January 2014

POWER SYSTEM INCIDENT REPORT NORTHERN POWER STATION STABILISER OUTAGE APRIL AND MAY 2010

MULTIPLE LINE OUTAGES IN THE MOUNT ENGLAND TARONG AREA IN QUEENSLAND, 13 FEBRUARY 2017

TRIP OF HORSHAM-REDCLIFFS 220 KV TRANSMISSION LINE AND MURRAYLINK INTERCONNECTOR ON 12 NOVEMBER 2015

POWER SYSTEM INCIDENT REPORT: OVERLOAD OF WAUBRA- HORSHAM 220 KV TRANSMISSION LINE AND INSECURE OPERATION OF THE SYSTEM ON 13 DECEMBER 2012

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Final Capacity Auction Results 2018/2019 T-1 Capacity Auction. Date 26/01/2018 Version 1.0

Utilities (Technical Regulation) (Electricity Transmission Supply Code) Approval 2016 (No 1)*

Header. Reasonableness Test RT 007/11 Balhannah & Uraidla 66 / 33 kv Substations. RT Balhannah and Uraidla - Final Draft Page 1 of 8

Final Capacity Auction Results 2019/2020 T-1 Capacity Auction. Date 01/02/2019 Document: FCAR1920T-1 Version 1.0

Reasonableness Test RT 015 /11 Salisbury Substation 11kV Feeders

Guidelines for connection of generators:

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

XXXXX. Kokish River Hydroelectric Project. Interconnection Facilities Study and Project Plan

Jemena Electricity Networks (Vic) Ltd

TRANSMISSION PLANNING CRITERIA

Investigation into UK socket-outlets incorporating USB charging points

Managing Electrical Safety on Boats

SUBSTATION INTERLOCKING SCHEMES

The Energy Queensland Group Notice of no non-network options

Feasibility Study for the Q MW Solar Project

A member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.

Louisville Gas and Electric Company

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance

ELECTRICITY TRANSMISSION USE OF SYSTEM PRICES - 1 JULY 2014 TO 30 JUNE 2015

Procedure PR D Electrical Permits. Engineering Procedure Electrical Distribution Unit. Version 1.0. Date in Force: 4 November 2015

Enquiry Form (Non-Registered Generator With Capacity less than 5 MW)

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Operational Planning Study Report. RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks

Summary of General Technical Requirements for the Interconnection of Distributed Generation (DG) to PG&E s Distribution System

South Australia Victoria (Heywood) Interconnector Upgrade. RIT-T: Project Specification Consultation Report

Heber Light & Power Electric Service Rule No. 14 NET METERING SERVICE

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description

SERVICES INNOVATION. Montreal Symposium March 29, Jack Simpson Director, Generation & Capacity Planning

Enquiry Form for Micro and Small Generators 5MW and Less

PIRS Electrical / electronic

2015 WDC Disturbance and Protection Standards Overview

MINIMUM OIL BURN/AUTOMATIC FUEL SWAPPING CAPABILITY

MMP Investigation of Arthur Kill 2 and 3

New 115 kv Disconnect Switches at Bloomsburg MTS

Reference Number PDS 18 - (RIC Standard: EP SP)

Grid Tied Limiter User Manual

BC Hydro Rate Schedule 1289 Revision 1 Effective: April 20, 2018 Page 6-1

MICROCARE 3 PHASE INVERTER MANUAL

Energy Regulation : Australian Experience. Engr.Khondkar Abdus Saleque

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation

Emerald Reactive Support Alternative Solution Expressions of interest

Guidelines when working near TasNetworks electrical assets

IEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations

The Ultimate Smart Grid Solution INSTRUCTION MANUAL

LED emergency exit signage from Channel Safety Systems

SOUTH AUSTRALIAN HISTORICAL MARKET INFORMATION REPORT SOUTH AUSTRALIAN ADVISORY FUNCTIONS

Feasibility Study for the Q MW Solar Project

Hydro Plant Risk Assessment Guide

Train Examination (Braking System) Addendum. Lesson Plan and WorkBook

NOVA SCOTIA UTILITY AND REVIEW BOARD

Application to Amend Net Metering Service under RS Appendix B. Revised RS 1289 Clean and Black-lined

Volume CHARGESTORM AB. Charging station model EVA Start and Protected. User Manual Start & Protected

GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM

M.P.S.C. No. 2 Electric Third Revised Sheet No. 65 (Rate Case) Cancels Second Revised Sheet No. 65

-and- Peter W. Gurnham, Q.C., Chair. ("Utility"), made application on January 14, 2015, to the Nova Scotia Utility and Review

The 6 th Basic Plan for Long-term Electricity Supply and Demand (2013~2027)

MISSOURI SERVICE AREA

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

Interconnection System Impact Study Report Request # GI

Title Electrical Technical Maintenance Coding System. Reference Number PMP 01 (RIC Standard: EP SP)

2018 Load & Capacity Data Report

Seabrook Substation Reliability Improvement Project

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 RULE NO. 17 NET ENERGY METERING

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Solar-Wind Specific Request for Proposals

Maintenance of Signal Sighting and Signals

COMMISSION REGULATION (EU) / of XXX

Installation Power Management Unit Battery Cables and Battery Harness

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

Sacramento Municipal Utility District s EV Innovators Pilot

The Ultimate Smart Grid Solution INSTRUCTION MANUAL

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel

Grounding Of Standby & Emergency Power Systems

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

NEWFOUNDLAND AND LABRADOR BOARD OF COMMISSIONERS OF PUBLIC UTILITIES AN ORDER OF THE BOARD NO. P.U. 17(2017)

CHAPTER 25. SUBSTANTIVE RULES APPLICABLE TO ELECTRIC SERVICE PROVIDERS.

Substation Lightning Protection. Document Number: 1-11-FR-11

Date of occurrence Location name Holland Park station Local time 18:35 Latitude 51:30:26 North

Volume CHARGESTORM AB. Charging station model EVA Connected. User Manual Connected

MODEL 540 USER MANUAL INCORPORATING MODEL 530 TEMPERATURE CONTROLLER

Equipotential Bonding of Rail Vehicles to Running Rail Potential

City of Palo Alto (ID # 6416) City Council Staff Report

Title High Voltage and 1500 System Earthing References and Definitions. Reference Number PDS 02 (RIC Standard: EP SP)

Runaway and derailment of a locomotive, Toton sidings, Nottinghamshire, 30 October 2016

Metrohm E3640 FLASH TESTER INSTRUCTION MANUAL. Martindale Electric Co Ltd.

Eyre Peninsula electricity supply options investigation

Transcription:

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 PREPARED BY: Electricity System Operations Planning and Performance DATE: 22 March 2012 FINAL

Disclaimer Purpose This report has been prepared by the Australian Energy Market Operator Limited (AEMO) for the sole purpose of meeting obligations in accordance with clause 4.8.15 (c) of the National Electricity Rules (NER). No reliance or warranty This report contains data provided by third parties and might contain conclusions or forecasts and the like that rely on that data. This data might not be free from errors or omissions. While AEMO has used due care and skill, AEMO does not warrant or represent that the data, conclusions, forecasts or other information in this report are accurate, reliable, complete or current or that they are suitable for particular purposes. You should verify and check the accuracy, completeness, reliability and suitability of this report for any use to which you intend to put it, and seek independent expert advice before using it, or any information contained in it. Limitation of liability To the extent permitted by law, AEMO and its advisers, consultants and other contributors to this report (or their respective associated companies, businesses, partners, directors, officers or employees) shall not be liable for any errors, omissions, defects or misrepresentations in the information contained in this report, or for any loss or damage suffered by persons who use or rely on such information (including by reason of negligence, negligent misstatement or otherwise). If any law prohibits the exclusion of such liability, AEMO's liability is limited, at AEMO's option, to the re-supply of the information, provided that this limitation is permitted by law and is fair and reasonable. Abbreviations and Symbols Abbreviation CB kv kw NET Term Circuit Breaker Kilovolt Kilowatt Neutral Earthing Transformer 2012 Australian Energy Market Operator Ltd. All rights reserved 22 March 2012 Page 2 of 7

1 Introduction At 1311 hrs on 26 November 2011, the 220 kv C busbar at Gordon underground hydro power station in Tasmania tripped on the operation of back up protection systems when a 22 kv busbar at Gordon experienced multiple faults during switching operations to restore the 22 kv busbar to service, which had tripped earlier in the day. The auxiliary supplies of Gordon and approximately 100 kw of customer load at Strathgordon were being supplied via this 22 kv busbar when the incident took place. This report has been prepared under clause 4.8.15 (c) of the National Electricity Rules to assess the adequacy of the provision and response of facilities and services and the appropriateness of actions taken to restore or maintain power system security. This report is largely based upon information provided by Hydro Tasmania. Data from AEMO's Energy Management System and Electricity Market Management System has also been used in analysing the incident. All references to time in this report are to National Electricity Market time (Australian Eastern Standard Time). 2 Pre-Contingent System Conditions Prior to the incident, Gordon 1 generating unit was generating 23 MW. Gordon 2 and 3 generating units were out of service. The status of the power system prior to the incident is shown in Figure 1. For clarity, only equipment relevant to this incident has been included in the diagram. 22 March 2012 Page 3 of 7

Figure 1 - Status of the power system prior to the incident To Chapel Street 02 line 01 line B129D B152 A129D A152 220 kv Bypass Bus TRANSEND 220 kv C Bus S752 C752 A752 HYDRO TASMANIA C52 B52 A52 A429 T6 Strathgordon Customer Load ~100 kw T3 T2 T1 22 kv Bus A552 Gordon Power Station 3 2 1 NET A252 Gordon 22 kv internal systems 220 kv Bus 22 kv Bus 220 kv Line 22 kv Line NET Neutral Earthing Transformer Generator Opened Isolator Closed Isolator Existing Fault Open Circuit Breaker Closed Circuit Breaker Transformer 3 Summary of Events The key events that took place during this incident are summarised in Table 1. Table 1 Summary of events Time Operation Comment 0900 hrs 22 kv busbar at Gordon tripped Operation of earth fault protection tripped the busbar. 0903 hrs Standby mini hydro generating unit started automatically but immediately tripped. 0914 hrs The operator at Gordon manually started standby generating unit and attempted to restore 22 kv busbar and it tripped again. The standby generating unit tripped on the operation of over-current protection. Fault on the 22 kv busbar was still present. The standby generating unit tripped on the operation of over-current protection. Fault on the 22 kv busbar was still present. 0948 1026 hrs On-call staff arrived at the power station and Staff noted a burnt smell and damp area 22 March 2012 Page 4 of 7

inspected the outdoor 22kV switch yard and found that the CB A252 had failed to open. The CB was then manually opened and isolated. 1026 1308 hrs The 22 kv busbar was prepared for energising. 13:11:16 22kV busbar was energised by closing CB A552. under the base of the CB. Staff believed that this was caused by the oil from the failed interrupter of CB A252. The underground 415 V and 22 kv systems were tested and found to be satisfactory. Staff carried out visual inspection of the 22kV busbar again but did not observe damage or any other issues. Transend closed CB A552 on the request of Hydro Tasmania. 13:11:26 A bus insulator and the neutral earthing transformer (NET) connected to the 22 kv busbar failed explosively. NET has a time limit of 5 seconds for withstanding fault currents. The CB A552 failed to open. Hydro Tasmania investigation revealed that CB A552 had a burnt trip coil causing it to be inoperable. 13:11:27 220kV C bus at Gordon tripped. Busbar protection of 220 kv C busbar operated tripping CBs A752 and C752 in 10 seconds. Gordon No.1 generating unit was unaffected and continued generating consistent with its dispatch target. 1453 hrs 220 kv C busbar was restored Hydro Tasmania liaised with Transend to restore the busbar. The status of the power system immediately after the incident is shown in Figure 2. 22 March 2012 Page 5 of 7

Figure 2 - Status of the power system after the incident 22 March 2012 Page 6 of 7

4 Immediate Actions Taken At 1325 hrs, AEMO invoked the constraint set T-GO_BUS in market systems to reflect the outage of Gordon C busbar. Hydro Tasmania restored the load at Strathgordon using standby diesel generating units. At 1453 hrs, the C busbar was returned to service. AEMO revoked the constraint set T-GO_BUS at 1500 hrs. In accordance with its operating procedure SO_OP 3715 Power System Security Guidelines 1, AEMO determined that it was not appropriate to declare the loss of 220 kv C busbar at Gordon as a credible contingency because the failed 22 kv busbar and the associated high voltage equipment remained out of service for repairs. 5 Follow-up Actions Hydro Tasmania inspected the 22 kv switchyard and repaired all the failed equipment. After testing the high voltage equipment and the secondary systems, Hydro Tasmania restored the 22 kv switchyard at Gordon on 7 January 2012. Hydro Tasmania conducted a complete investigation of this incident and made a number of recommendations to avoid similar failures in future. In particular, Hydro Tasmania noted that the most likely reason for the explosive failure of the NET was due to the 5 second short term rating of the NET whereas the backup protection was set to operate after 10 seconds. 6 Power System Security Assessment The power system voltages, power flows and frequencies remained within the normal operating limits and the applicable frequency operating standards. The provision and response of facilities and services of Hydro Tasmania were adequate to maintain power system security. 7 Conclusions AEMO is satisfied that Hydro Tasmania has conducted a complete investigation of this incident and is pursuing the recommended corrective actions to minimise the risk of a similar incident occurring in the future. AEMO noted that a more appropriate coordination of the time delay implemented for the back up protection systems of the 22 kv busbar, that was consistent with the rating of the NET could have prevented its failure. AEMO correctly applied the criteria required by clause 4.2.3B of the NER and published in section 11 of its Power System Security Guidelines in assessing that the circumstances of this incident did not warrant reclassifying similar incidents as a credible contingency event. 8 Recommendations Hydro Tasmania will liaise with Transend to review the time delay implemented for its back up protection systems of the 22 kv busbar, to better align with the rating of the NET. Hydro Tasmania will inform the progress of this action to AEMO by the end of July 2012. 1 Clause 4.2.3B of the NER requires that AEMO establish criteria to use when considering whether a noncredible contingency event is reasonably possible. This is published in AEMO operating procedure SO_OP 3715 Power System Security Guidelines, which is available at: http://www.aemo.com.au/electricityops/3715.html 22 March 2012 Page 7 of 7