Installation & Operation Manual

Similar documents
Product Data Sheet. Flow Sensors. Insert Style Flow Sensors SDI Series DESCRIPTION HOT TAP SENSORS (OPTIONAL) APPLICATIONS FUNCTIONALITY

LEVEL AND FLOW MEASUREMENT WS131 FLOW METER USER MANUAL.

TX 115/215 Hot-tap Insertion Turbine Instructions

SeaMetrics Flow Meters and Flow Computers

BI-DIRECTIONAL INSERTION FLOW TRANSDUCER

Hydro-Flow Model 2200 Fixed Insertion Vortex Flowmeter Installation and Operation Manual

Hydro-Flow Model 2200 Installation and Operation Guide B

F-2700 SERIES INSERTION VORTEX FLOW METER

TX115/215 Hot-tap Insertion Turbine Instructions

Appendix. Clearance. Skewed profiles. Application Schematics

F-1500 SERIES INSERTION TURBINE FLOW METER

Insertion turbine INSTRUCTION SHEET. TECHNICAL PRODUCT

TURBINE METERS - WP Series

F-2600 SERIES INLINE VORTEX FLOW METER

Pipe fi ttings MUST be installed by a certifi ed welder only. Signet will not assume liability of any kind for improper fi tting installations.

F-2700 SERIES INSERTION VORTEX FLOW METER

TX101/201 Insertion Turbine Instructions

Pipe fittings MUST be installed by a certified welder only. +GF+ SIGNET will not assume liability of any kind for improper fitting installations.

Hydro-Flow Model 2300 Installation and Operation Guide B

Hydro-Flow Model 3100 Retractable Insertion Vortex Flowmeter Installation and Operation Manual

IP800-Series FLOW SENSOR INSTRUCTIONS IP810 IP :2008 ISO CERTIFIED COMPANY IP800-SERIES FLOW SENSOR INSTRUCTIONS

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

TX80-Series FLOW SENSOR INSTRUCTIONS TX81 TX :2008 ISO CERTIFIED COMPANY TX80-SERIES FLOW SENSOR INSTRUCTIONS

Signet 2517 Brass Paddlewheel Flow Sensor * *

Hydro-Flow Model 3100

IP800-Series FLOW SENSOR INSTRUCTIONS IP810 IP :2008 ISO CERTIFIED COMPANY IP80-SERIES FLOW SENSOR INSTRUCTIONS

IP80-Series FLOW SENSOR INSTRUCTIONS IP81 IP :2008 ISO CERTIFIED COMPANY IP80-SERIES FLOW SENSOR INSTRUCTIONS

ISTEC MAGNETIC METERS

Installation & Operation Manual. Impeller Flow Sensors. IMPORTANT: This manual contains important information. READ AND KEEP FOR REFERENCE.

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual

Hydro-Flow 2200 Fixed Insertion Vortex Flow Meter

IP800-Series. Insertion Paddlewheel Flow Sensor Instructions PROUDLY MADE IN THE USA

"High Temperature" Sensor Designed for indoor or protected area applications such as hydronic heating loops, boiler feed, and condensate return line m

DIGITAL PRESSURE AND FLOW INDICATOR MODEL FPA500

Electromagnetic flowmeters Series FLOMAT Insertion electromagnetic flowmeter for conductive liquids

TX101/201 Insertion Turbine Instructions

F-1500 SERIES INSERTION TURBINE FLOW METER FEATURES Belcher Road South, Largo, FL USA Tel +1 (727) Fax +1 (727)

From. McCROMETER, INC WEST STETSON AVENUE HEMET, CA Phone (951) Toll Free (800) Fax (951)

WATER METERS OCTAVE ULTRASONIC WATER METER INSTALLATION & USER GUIDE

BI-DIRECTIONAL INSERTION METER

Model 5000 Vortex Meter

TX800-Series FLOW SENSOR INSTRUCTIONS. TX81x TX82x 9 001:2008 ISO CERTIFIED COMPANY TX800-SERIES FLOW SENSOR INSTRUCTIONS

DIGITAL FLOWMETER AND PRESSURE INDICATOR MODEL FPA400

IP800-Series. Insertion Paddlewheel Flow Sensor Instructions PROUDLY MADE IN THE USA

ARCHIVED. EX80 Series. (Includes Dates 6/28/05 to 10/06) EX81 EX82

Low Profile Insertion Vortex

EX80 Series EX81 EX82. E X 8 0 S E R I E S E l e c t r o m a g n e t i C F l o w s e n s o r i n s t r u c t i o n s. The Leader in Flow Meter Value.

UTM10 Series Ultrasonic Transit-time Flowmeters

IMPORTANT!!!! Read this manual before attempting any installation, wiring or operation.

F-2000 MODEL RT INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

FLS F6.60 MAGMETER FLOW SENSOR INSERTION FLOW SENSORS APPLICATIONS MAIN FEATURES

Full Profile Insertion

tekson TS Series Low Cost Ultrasonic Water Energy Flow Measurement

TURBINE FLOW METER SELECTION GUIDE

RUN ACCUM. TOTAL STOP BAT LOW HIGH

LTX RF LEVEL SENSOR. Instruction Manual

Installation and Operation Instructions DLP Series

TURBINE FLOW METER Installation and Operation Guide

Chapter Page. 1 Introduction Description 1

FUNDAMENTALS OF INSERTION TURBINE METERS Les Bottoms Thermo Electron Corporation, Flow Systems

Model Q45H/ Residual Chlorine Monitor...

Figure 1: WPR2 Dimensions and Hardware

TURBINE FLOW METER Installation and Operation Guide

SERIES TBS INSERTION TURBINE TBS-0XX TBS-1XX

Hot Tap Insertion Vortex

Pipe fi ttings MUST be installed by a certifi ed welder only. Signet will not assume liability of any kind for improper fi tting installations.

EX80-Series ELECTROMAGNETIC FLOW SENSOR INSTRUCTIONS EX81 EX82 EX :2008 ISO CERTIFIED COMPANY

TR-QS Wafer-Style Turbine Flow Meters Installation, Operating & Maintenance Manual

M3500 Industrial Pressure Transmitter

flow measurement solutions RIM10 series rotor insertion flowmeters

EX100/200-Series INSERTION MAGNETIC FLOW METER INSTRUCTIONS EX110 EX210 EX150 EX :2008 ISO CERTIFIED COMPANY

EZ-IN Series Turbine Flowmeter

PFA LINED BALL VALVES Installation, Operation and Maintenance Manual

Rosemount 8750WA Magnetic Flowmeter System For Water and Wastewater Industries

SECTION ELECTRONIC ACTUATED PRESSURE REDUCING VALVES AND ACCESSORIES

Operating Manual Model- P282 Digiflow Controller

S-Series. Low Flow Meter Instructions SPX SPT. Precision Flow Measurement An ONICON Brand PROUDLY MADE IN THE USA

MODEL MSD MOTION CONTROL INSTALLATION AND OPERATION

F-2600 SERIES INLINE VORTEX FLOW METER

F-5100 Insertion Thermal Mass Flow Meter Installation and Operation Guide

SmartBob AO. BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE

For additional information, please visit our website at SENSOR SPECIFICATIONS

Advanced Outdoor Airflow Control, DCV Control and Alarm Solution for OA Applications Document Name: QG_EAC1100_A_R3A

ABB Instrumentation. MagMaster MFE Series Electromagnetic Sensors. Specifications. MagMaster - bringing unsurpassed flowmetering performance

Octave Water Meter Installation Manual

The full WeatherTRAK Flow3 Installation and Maintenance Manual is available online at

Electromagnetic Flow Monitor magphant

User's Manual: Series 270I Model 270I Process Current Loop-Powered Isolator

Distributed by: M&M Control Service, Inc MICRO-FLO MICRO-FLO

MFM220 & MFM220DC Plastic-Bodied Magmeter

UniMag DT Series Electromagnetic Flow Tubes

Range of Ultrasonic Flowmeters.

FPI Mag FULL PROFILE INSERTION ELECTROMAGNETIC FLOW METER MODELS 394L AND 395L MAG METER SUBMITTAL

accqpulse Velocity Profiler Sensor Installation Guide

SSI Technologies Application Note PS-AN7 MediaGauge (Model MG-MD) Digital Pressure Gauge Product Overview

Vortex Eggs Delta Flowmeter

Vortex Plate. Model VP General Specification. Product Features

Time Delta S Fixed Transit-Time Flow Meter System

2100 Turbine Flow Sensor

Transcription:

SDI Series Insert Style Flow Sensors Installation & Operation Manual BadgerMeter, Inc. PN# 72034 1-09 Rev B8

(This page intentionally left blank.) 2

Introduction The Data Industrial SDI Series impeller flow sensor offers unparalleled performance for liquid flow measurement in closed pipe systems in an easy to install economical package. Impeller sensors offer a quick response to changes in flow rate and are well suited to flow control and batch type applications in addition to flow monitoring. The new four-bladed impeller design is rugged, non-fouling and does not require custom calibration. Coupled with the proprietary patented digital detection circuit, the sensor measures flows from under 0.3 feet per second to over 20 fps regardless of the conductivity or turbidity of the liquid. The standard frequency output produces a low impedance square wave signal proportional to flow rate that may be transmitted up to 2000 feet without amplification. Models are available to measure flow in one or both directions. All SDI insert sensors are mounted on the pipe using a 1 tap. As with any insert sensor, a pipe saddle or weld-on fitting is preferred over a service tee because it causes fewer disturbances to the flow. Models Available Direct insert sensor models are installed in piping configurations that are not in service or under pressure. Hot tap insert sensor models feature isolation valves and mounting hardware to install or remove the sensor from a pipeline that would be difficult to shut down or drain. In a true hot tap installation the sensor is mounted in the pipe under pressure by attaching a service saddle or weld-on fitting to the pipe and mounting the isolating valve and nipple to the threaded connection. A hole is then cut in the wall of the pipe through the valve using a commercial tapping machine with a 1 size cutter. Once the hole is cut, the tapping machine is removed and the valve is shut. Then the sensor assembly is mounted to the isolation valve and extended into the pipeline to measure flow. Even in new construction a hot tap sensor may be appropriate for service considerations. The small stem diameter allows the sensor to be inserted into the pressurized pipeline by hand without the need for an installation tool. The mounting hardware holds the sensor firmly in place at the 3

correct depth and alignment. Electronic Outputs Standard Frequency Sensor output is a pulse proportional to flow. The signal is similar to all 200 Series Data Industrial flow sensors and will interface with all existing Data Industrial transmitters and monitors. The power supply to the sensor and the output signal from the sensor is carried on the same two wires. Wire connections are made at screw terminals on removable headers inside the NEMA 4X housing. Analog Output The Sensor is also available with a two-wire loop powered 4-20 ma output. The analog output is produced by an on-board micro-controller for precise, drift-free signals. The unit is programmed from a computer using Windows based software and a Data Industrial A-301 connection cable. Units may be pre-programmed at the factory or field programmed. All information is stored in non-volatile memory in the flow sensor. Scaled Pulse Output The scaled pulse is produced by an on-board micro-controller for precise, accurate outputs. This option may be programmed to produce an isolated dry contact closure scaled to any number of engineering units of measure. Sensors may be pre-programmed at the factory or field programmed using a Data Industrial A-301 connection cable and a Windows based software program. All information is stored in non-volatile memory in the flow sensor. This is a four-wire option. Bi-directional Flow- Analog Output This option provides a programmable 4-20 ma signal proportional to flow rate and a contact closure to indicate the direction of flow. All programming is accomplished as previously mentioned. The user can program the unit for pipe size, flow scale and the direction of flow. This is a six-wire option. Bi-directional Flow- Scaled Pulse Output This option provides the user with a choice of outputs. In one case the sensor provides an output scaled to the required number of engineering units on one set of terminals and a contact closure to indicate the direction of flow on another. The other choice provides two isolated scaled pulse outputs, one for each direction. Programming the output choice, pipe size, output scale and direction of flow by the user are also accomplished by using a PC with Data Industrial software and A-301 connection cable. This option SDI Series Direct Insert Ordering Matrix SDI 0 D1 N 0 0-0 2 0 0 Material Stainless Steel/PPS Tip 0 Brass/PPS Tip 1 Stainless Steel/PEE Tip 2 Type Direct Insert for Pipe 1-1/2" thru 10" * D1 Direct Insert for Pipe 12" thru 36" * D2 Direct Insert 36" and UP* D3 Electronic Housing NEMA 4X N Output Standard Frequency Pulse 0 Analog 4-20mA 1 Scaled Pulse 2 Display No Display 0 LCD Option [not available with output option 0] 1 O-Ring Viton 0 Shaft Tungsten Carbide [Standard] 2 Hastelloy C-276 [optional - consult factory] 1 Zirconia Ceramic [optional - consult factory] 0 Impeller Stainless Steel 0 Bearing Torlon 0 *Pipe size for reference only-depending on pipe material, tapping saddle, or existing hardware, longer sensor length may be required. Consult Factory SDI Series Hot Tap Ordering Matrix SDI 0 H1 N 0 0-0 2 0 0 Material Stainless Steel/PPS Tip 0 Stainless Steel/PEE Tip 2 Type Hot Tap for Pipe 1-1/2" thru 10" * H1 Hot Tap for Pipe 12" thru 36" * H2 Hot Tap for Pipe 36" and UP* H3 Electronic Housing NEMA 4X N Output Standard Frequency Pulse 0 Analog 4-20mA 1 Scaled Pulse 2 Bi-Directional, 4-20mA + Direction [PPS tip Only] 5 Bi-Directional, Scaled Pulse [PPS tip Only] 6 Display No Display 0 LCD Option [not available with output option 0] 1 O-Ring Viton 0 Shaft Tungsten Carbide [Standard] 2 Hastelloy C-276 [optional - consult factory] 1 Zirconia Ceramic [optional - consult factory] 0 Impeller Stainless Steel 0 Bearing Torlon 0 *Pipe size for reference only-depending on pipe material, tapping saddle, or existing hardware, longer sensor length may be required. Consult Factory 4

Display Options- All models except the standard frequency output version may also be equipped with a display. Integrated into the NEMA 4 housing, the 8 digit LCD may be programmed to show rate of flow, flow total or toggle between the two. Bidirectional models also show flow direction. Mechanical Installation The accuracy of flow measurement for all insert type flow measuring devices is highly dependent on proper location of the sensor in the piping system. Irregular flow velocity profiles caused by valves, fittings, pipe bends, etc. can lead to inaccurate overall flow rate indications even though local flow velocity measurement may be accurate. A sensor located in the pipe that is partially full or where it can be affected by air bubbles, floating debris, or sediment may not achieve full accuracy and could be damaged. Data Industrial flow sensors are designed to operate reliably under adverse conditions, but the following recommendations should be followed to ensure maximum system accuracy: DATA INDUSTRIAL SDI Series Sensor 10 x Pipe Dia 5 x Pipe Dia FLOW 1) Choose a location along the pipe where there is straight pipe for a distance of 10 pipe diameters upstream and 5 pipe diameters downstream of the sensor. Pipe bends, valves, other fittings, pipe enlargements and reductions or anything else that would cause a flow disturbance should not be present in this length of pipe. 2) The recommended tap location around the circumference of a horizontal pipe is on top. If trapped air or debris will interfere, then the sensor should be located around the pipe from the top preferably not more than 45 degrees from top dead center. The sensor should never be located at the bottom of the pipe, as sediment may collect there. Locations off top dead center cause the impeller friction to increase, which may affect performance at low flow rates. Any circumferential location is correct for installation in vertical pipes. 5

3) Insertion depth is critical to accuracy. The algorithm used to convert impeller motion into flow was developed through flow tests in an independent calibration laboratory. The impeller must be located in the same position in the pipe as it was in the calibration test for the impeller frequency to accurately describe the same liquid velocity. Detailed installation instructions on the following pages include methods for ensuring correct insertion depth. 4) Alignment of the sensor is also important. The impeller shaft must be perpendicular to the flow for accuracy. Alignment instructions are also included on the following pages. 15 3/4 * 4.23 0.660 Handtight Engagement + Wrench Makeup Per ANSI/ASME B1.20.1-1993, R1992 also requires six wires. Installation for Direct insert models * Pipe Sizes for reference only - Depending on pipe material, tapping saddle, or existing hardware longer sensor length may be required - Contact Factory. These instructions are for the installation of flow sensors into piping systems that are not under pressure at the time of installation. If the line must be tapped under pressure, a hot tap style sensor must be used. See following section for hot tap installation instructions. The insertion depth and alignment of the sensor are critical to the accuracy of the flow measurement. The impeller must be at the same location in the pipe as it was during calibration. Data Industrial provides sensors with different stem lengths. Longer stems are intended for use in larger diameter pipes and shorter stems for use in smaller pipelines. However stem length has no affect on the operation of the sensor provided that the impeller is positioned correctly in the pipe. Mounting Adapter Pipe Saddle (ref.) Gasket (ref) Direct insert models are available in one stem length designated D1. They are intended for nominal pipe diameters from 1 1/2 to 10. However, pipe with extra thick walls, existing linings, or unusual tapping hardware may require longer length sensors - Consult factory. For larger pipe sizes hot tap style sensors equipped with an isolation valves are recommended. The preferred method of installation is by means of a saddle with 1 NPT outlet. On steel pipelines a weld-on type fitting may be substituted. 6

1. Attach the saddle to a section of pipe that has at least 10 diameters of straight pipe ahead and five diameters of straight pipe behind the saddle. Drill a minimum 1 1/8 diameter hole in the pipe. 2. Remove the sensor assembly from the mounting hardware by loosening the hex cap over the stem collar and the cover to the mounting adapter and detaching the assembly. Set aside taking care not to damage impeller/shaft assembly. 3. Attach the pipe thread end of the mounting adapter to the saddle/weldo-let using a pipe joint compound and tighten the joint. Do not apply sealing compound to the top thread of the mounting adapter. It is sealed with an o-ring. 4. The sensor rotor assembly is to be located a fixed distance from the center of the pipe. To position the impeller at this depth, a reference measurement for the pipe size and schedule is used. Look up the pipe size and schedule number in Table A and note the reference number. Next, measure from the outside wall of the pipe to the top of the installed mounting adapter B in Figure 3. Add this number to the reference measurement. Hex Cap Stem Collar Cover Mounting Adapter Stem The resulting number, C in Figure 4 is the distance from the recess of the sensor tip to the bottom of the stem collar. Insert the metal tab of a tape measure into the recess of the flow sensor tip. Extend the tape up the stem and mark the shaft with a pencil. Slide the collar along the shaft until its bottom surface is at the mark on the stem. Tighten the cap screw on the collar. When the sensor is reassembled, this will set the insertion depth of the sensor. Pipe Saddle (ref.) Gasket (ref) 5. Attach the sensor to the mounting adapter by gently pushing the flow sensor into the mounting adapter until the cover touches the mounting adapter. Tighten the cover against the o-ring seal. This will seal the sensor assembly. 6. Continue to insert the flow sensor stem until the stem collar meets the cover. Thread the hex cap onto the mounting adapter but don t tighten. Align the flow sensor with the pipe by using the flat cover on the electronics housing as a guide. Place a straightedge along the cover and rotate the sensor until the straightedge is parallel with the pipe. Tighten the hex cap over the collar approximately 10 foot pounds. The hex cap holds the sensor alignment but performs no sealing functions. DO NOT OVERTIGHTEN. 7. Pressurize pipeline and check for leaks. Pipe SDI Flow Sensor Pipe Straight Edge Parallel to Pipe 7

Installation for Hot tap models The insertion depth and alignment of the sensor are critical to the accuracy of the flow measurement. The impeller must be at the same location in the pipe as it was during calibration. Data Industrial provides sensors with three different stem lengths. Longer stems are intended for use in larger diameter pipes and shorter stems for use in smaller pipelines. However stem length has no affect on the operation of the sensor provided that the impeller is positioned correctly in the center of the pipe. Bottom of Housing Stem Collar Ball Valve Hex Cap Cover Stem Measure Insertion Depth From Here Stem length H1 is intended for use in nominal pipe diameters from 1 1/2 to 10, H2 is for nominal pipe diameters from 12 to 36, and stem length H3 is for nominal pipe diameters from 36 and up. However, pipe with extra thick walls, existing linings, or unusual tapping hardware may require longer length sensors - Consult factory. 7 ¾ H1=19 * H2=21½ * H3=27½ * 7.85 4 11/32 2 27/32 * Pipe Sizes for reference only - Depending on pipe material, tapping saddle, or existing hardware longer sensor length may be required - Contact Factory. 8

The preferred method of installation is by means of a saddle with 1 NPT outlet. On steel pipelines a weld-on type fitting may be substituted. 1. Attach the saddle to a section of pipe that has at least 10 diameters of straight pipe ahead and five diameters of straight pipe behind the saddle. 2. Remove the sensor assembly from the mounting/isolation valve by loosening the hex cap over the stem collar and the cover to the mounting/ isolation valve and detaching the assembly. Set aside taking care not to damage impeller/shaft assembly. Ball Valve 3. Attach the pipe thread end of the valve to the saddle using a pipe joint compound and tighten the joint. Do not apply sealing compound to the top thread of the valve. It is sealed with an o-ring. 4. Attach the tapping adapter, Data Industrial part number A-1027 to the top of the valve. 5. Any pipe tapping machine with a 1 pipe thread connection may be used. Use a cutter appropriate for the pipe material being tapped. 6. Attach the tapping machine to the tapping adapter. Ensure that all connections and seals are tight. Pipe Saddle (ref.) Gasket (ref) 7. Slowly open the valve by rotating the handle 90 and lower the cutter past the valve ball to the pipe. Drill the 1 nominal hole according to the manufacturer s instructions. Withdraw the cutter past the valve ball, close the valve and remove the tapping tool. Hex Cap 8. Remove the Data Industrial tapping adapter from the top of the valve. Ball Valve Cover Stem Stem Collar 9. The sensor rotor assembly is to be located a fixed distance from the center of the pipe. To position the impeller at this depth, a reference measurement for the pipe size and schedule is used. Look up the pipe size and schedule number in Table A and note the reference number. Next, measure from the outside wall of the pipe to the top of the ball valve B in Figure 8. Add this number to the reference measurement. Pipe Saddle (ref.) The resulting number is the distance from the recess of the sensor tip to the bottom of the stem collar C in Figure 9. Insert the metal tab of a tape measure into the recess of the flow sensor tip. Extend the tape up the stem and mark the shaft with a pencil. Slide the collar along the shaft until its bottom surface is at the mark on the stem. Tighten the cap screw on the collar. When the sensor is reassembled, this will set the insertion depth of the sensor. Gasket (ref) 9

10. Slide the cover down the stem until it stops. Attach the sensor to the valve by inserting the impeller end of the stem into the valve until the cover touches the top of the valve. The sensor tip and impeller will be in the section of the valve above the ball. Tighten the cover against the o-ring in the top of the valve. This will seal the sensor assembly. Open the ball valve again by slowly rotating the handle 90 If the cover was not at the bottom of the sensor stem, water pressure from the pipe would now push it out until it stops. However, the sensor cannot be ejected from the pipe if the cover is secured to the valve. Check to make sure all joints are tight. 11. Insert the flow sensor stem into the pipe by pushing against the top of the electronics housing with a slight twisting motion until the stem collar meets the cover. The force required to push the sensor into the pipeline is approximately 20% of the line pressure. Be aware of the close spacing between the diameter of the flow sensor, the bore of the ball valve and the hole in the pipe. If the sensor stops or catches before the stem collar meets the cover, apply a gentle rocking/twisting motion to the sensor to continue its travel. While holding the flow sensor collar against the cover, thread the hex cap onto the cover to hold the flow sensor in place but do not tighten. Align the flow sensor with the pipe by using the flat side cover of the electronics housing as a guide. Place a straightedge along the cover and rotate the sensor until the straightedge is parallel to the pipe. Tighten the hex cap to the cover to approximately 10 foot pounds. The hex cap holds the sensor alignment and depth but performs no sealing functions. DO NOT OVERTIGHTEN. 12. Pressurize pipeline and check for leaks. Pipe SDI Flow Sensor Pipe Straight Edge Parallel to Pipe 10

Electrical Installation Access wiring terminals by removing side cover. A wiring diagram is on the side cover, under the gasket. Use care when replacing side cover to insure that the gasket is in place. DO NOT REMOVE CIRCULAR COVER from top of sensor. You may disturb seal and label alignment. A moisture absorbing silica pack has been placed inside the electronics housing during assembly. Leave in place after making wire connections. Standard frequency (Pulse) output - Option 0 in the ordering matrix This two wire sensor is intended for connection to Data Industrial monitors and transmitters or other devices that supply 10-24 DC excitation voltage and accept frequencies from 0 to 1000Hz. Attach the sensor shield terminal 1 to the shield terminal on the transmitter (used for maximum protection from interference). Attach the sensor common terminal 2 to the common (-) terminal on the transmitter. Attach the sensor signal terminal 3 to the signal (+) terminal on the transmitter. 1 2 3 1. Shield 2. Sensor Common 3. Sensor Signal Analog 4-20mA Output - Option 1 in the ordering matrix This option provides a programmable 4-20 ma signal proportional to flow rate. All programming is accomplished as previously mentioned. The user can program the unit for pipe size, flow scale. This is a two-wire option. Attach SDI #1 (Shield) to Earth Ground or Power Supply Common. (This provides maximum power and signal EMI protection). ANALOG OUTPUT WIRED AS CURRENT SINING Attach SDI#2 (Loop -) to the Analog input terminal of device receiving this 4-20mA signal. Attach SDI#3 (Loop +) to +24VDC terminal of device receiving the 4-20mA Signal. ANALOG OUTPUT WIRED AS CURRENT SOURCING (WITH SEPA- RATE 24VDC POWER SUPPLY) Attach SDI#2 (Loop -) to Analog input terminal of device receiving this 4-20mA signal. (Sometimes labeled Loop +). Attach SDI#3 (Loop +) to +24VDC Supply terminal. Attach -24VDC Supply terminal to the Analog Input Common. (Sometimes labeled Loop -). 1 2 3 1. Shield 2. Loop - 3. Loop + Scaled Pulse output - Option 2 in the ordering matrix This option provides a programmable opto-isolated solid state switch closure with internal solid state fuse protection. All programming is accomplished as previously mentioned. The user can program the unit for pipe size, flow scale and the direction of flow. This is a six-wire option. Attach SDI #1 (Shield) to Earth Ground or Power Supply Common. (This provides maximum power and signal EMI protection). Attach SDI #2 (Power -) to the negative terminal of a nominal 12-24VAC/VDC Power Supply. (See data sheet for current draw and voltage limits). Attach SDI#3 (Power +) to positive terminal of power supply. Attach SDI #4 (Pulse -) to the Input pulse (-) of the receiving device. Attach SDI #5 (Pulse +) to the Input pulse (+) of the receiving device. 1 2 3 4 5 1. Shield 2. Power - 3. Power + 4. Pulse - 5. Pulse + 11

Bi-Directional Analog Output - Option 5 in the ordering matrix This option provides a programmable 4-20 ma signal proportional to flow rate and a contact closure to indicate the direction of flow. All programming is accomplished as previously mentioned. The user can program the unit for pipe size, flow scale and the direction of flow. This is a six-wire option. Attach SDI #1 (Shield) to Earth Ground or Power Supply Common. (This provides maximum power and signal EMI protection). Attach SDI #2 (Power -) to the negative terminal of a nominal 12-24VAC/VDC Power Supply. (See data sheet for current draw and voltage limits). Attach SDI#3 (Power +) to positive terminal of power supply. Attach SDI #4 and SDI#5 (Direction +/-) to the device receiving the directional signal. (This connection is not polarity sensitive; and, when active, provides a solid state switch closure for a maximum load of 100mA @30VAC or +/-40VDC). ANALOG OUTPUT WIRED AS CURRENT SINING Attach SDI#6 (Loop -) to the Analog input terminal of device receiving this 4-20mA signal. Attach SDI#7 (Loop +) to +24VDC terminal of device receiving the 4-20mA Signal. ANALOG OUTPUT WIRED AS CURRENT SOURCING SHARING SDI s 24VDC POWER SUPPLY Attach SDI#6 (Loop -) to Analog input terminal of device receiving this 4-20mA signal. Attach SDI#7 (Loop +) to SDI#3. (Sharing terminal with +24VDC Supply). Attach SDI#2 (Loop -) to Analog Input Common. (Sometimes labeled Loop -). ANALOG OUTPUT WIRED AS CURRENT SOURCING (WITH SEPARATE 24VDC POWER SUPPLY) Attach SDI#6 (Loop -) to Analog input terminal of device receiving this 4-20mA signal. (Sometimes labeled Loop +). Attach SDI#7 (Loop +) to +24VDC Supply terminal. Attach -24VDC Supply terminal to the Analog Input Common. (Sometimes labeled Loop -). Bi-Directional Scaled Pulse Output - Option 6 in the ordering matrix This option provides a programmable scaled pulse output signal proportional to flow rate and a contact closure to indicate the direction of flow. All programming is accomplished as previously mentioned. The user can program the unit for pipe size, flow scale and the direction of flow. This is a six-wire option. Attach SDI #1 (Shield) to Earth Ground or Power Supply Common. (This provides maximum power and signal EMI protection). Attach SDI #2 (Power -) to the negative terminal of a nominal 12-24VAC/VDC Power Supply. (See data sheet for current draw and voltage limits). Attach SDI#3 (Power +) to positive terminal of power supply. Attach SDI #4 (Pulse B -) to the Input pulse (-) of the receiving device. Attach SDI #5 (Pulse B +) to the Input pulse (+) of the receiving device. Attach SDI #6 (Pulse A -) to the Input pulse (-) of the receiving device. Attach SDI #7 (Pulse A +) to the Input pulse (+) of the receiving device. 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1. Shield 2. Power - 3. Power + 4. Direction 5. Direction 6. Loop - 7. Loop + 1. Shield 2. Power - 3. Power + 4. Pulse B - 5. Pulse B + 6. Pulse A - 7. Pulse A + 12

Programming Programming the Series SDI is accomplished by installing the Data Industrial programming software on a computer and entering data on templates of the Windows based program. 1. Load the interface software into the computer. 2. Connect the computer to the SDI with the Data Industrial A-301 communications cable to the socket labeled D.I.C Comm Port, taking care to properly align the tab on the plug and socket to maintain polarity. Connect the DB9 connector of the Data Industrial A-301 communications cable to the PC com port of a PC that has the SDI software installed. 3. Connect the Series SDI Flow Sensor to a power supply. 4. Open the interface software and select the appropriate COM PORT as shown in the dialog box below. 5. Open the Parameters Screen as shown below. To go to the calibration settings screen select parameters from either place shown. OR To go to the calibration settings screen select parameters from either place shown. 13

6. Program using diagram below as a reference. Single Direction Analog Output Models Step #1 Select rate units from the pull down values. Step #3 Select the pipe size from the pull down menu, if the pipe size is not present then custom must be selected, or check for an updated pipe.dat table on the Data Industrial web site. Step #5 Enter 4mA flow rate. This is normally zero. Step #2 Select total units from the pull down values. See Note #1 Step #4 If custom was selected in step 3 then click the custom button and see Note #2. Step#6 Enter 20mA flow rate. Step #7 For models with LCD Display Option select the desired LCD Configuration from the pull down menu. If Model has no display then skip to Step #8. Step #8 Press Send to transmit calibration data to the SDI Sensor. Press to reset all parameters back to factory defaults. Send must be pressed to send this data to the SDI. Press to retrieve calibration data from SDI. Step #9 Press to exit parameters screen and to go back to the main screen. Note #1 Press details to see and offset numbers for the selected pipe. The and offset are factors used to convert the sensor frequency to flow rate. They are unique to each pipe size/ material. Note #2 Press custom button to enter and offset numbers for pipe material not listed in pull down menu. The numbers may be obtained by contacting Data Industrial. 14

Single Direction Scaled Pulse Output Models Step #1 Select rate units from the pull down values. Step #3 Select the pipe size from the pull down menu, if the pipe size is not present then select custom or check for an updated pipe.dat table on the Data Industrial web site. Step #2 Select total units from the pull down values. See Note #1. Step #4 If custom was selected in step 3 then click the custom button and see Note #2. Step #6 For models with LCD Display Option select the desired LCD Configuration from the pull down menu. If Model has no display then skip to Step #7. Step#5 Enter the number of units per pulse and select the pulse width required. Step #7 Press Send to transmit calibration data to the SDI Sensor. Press to reset all parameters back to factory defaults. Send must be pressed to send this data to the SDI. Press to retrieve calibration data from SDI. Step #8 Press to exit parameters screen and to go back to the main screen. Note #1 Press details to see and offset numbers for the selected pipe. The and offset are factors used to convert the sensor frequency to flow rate. They are unique to each pipe size/ material. Note #2 Press custom button to enter and offset numbers for pipe material not listed in pull down menu. The numbers may be obtained by contacting Data Industrial. 15

Bi-Directional Analog Output Models Step #1 Select rate units from the pull down values. Step #3 Select the pipe size from the pull down menu, if the pipe size is not present then select custom or check for an updated pipe.dat table on the Data Industrial web site. Step #5 Enter 4mA flow rate. This is normally zero. Step #7 For models with LCD Display Option select the desired LCD Configuration from the pull down menu. If Model has no display then skip to Step #10. Step #9 If the Flow direction label requires changing see Note #3. Step #10 Press Send to transmit calibration data to the SDI Sensor. Step #2 Select total units from the pull down values.. See Note #1. Step #4 If custom was selected in step 3 then click the custom button and see Note #2. Step#6 Enter 20mA flow rate. Step #8 Select Active Direction. Press to reset all parameters back to factory defaults. Send must be pressed to send this data to the SDI. Press to retrieve calibration data from SDI. Step #11 Press to exit parameters screen and to go back to the main screen. Note #1 Press details to see and offset numbers for the selected pipe. The and offset are factors used to convert the sensor frequency to flow rate. They are unique to each pipe size/ material. Note #2 Press custom button to enter and offset numbers for pipe material not listed in pull down menu. The numbers may be obtained by contacting Data Industrial. Note #3 Press Change Label button to change flow direction label. Enter up to 20 characters such as From Pump 16

Bi-Directional Scaled Pulse Output Models Step #1 Select rate units from the pull down values. Step #3 Select the pipe size from the pull down menu, if the pipe size is not present then select custom or check for an updated pipe.dat table on the Data Industrial web site. Step #5 Select the pulse output type that is required. If raw pulse is selected skip Step #6. Step #7 For models with LCD Display Option select the desired LCD Configuration from the pull down menu. If Model has no display then skip to Step #10. Step #9 If the Flow direction label requires changing see Note #3. Step #10 Press Send to transmit calibration data to the SDI Sensor. Step #2 Select total units from the pull down values. See Note #1. Step #4 If custom was selected in step 3 then click the custom button and see Note #2. Step#6 Enter the number of units per pulse and select the pulse width required. Step #8 Select Active Direction. Press to reset all parameters back to factory defaults. Send must be pressed to send this data to the SDI. Press to retrieve calibration data from SDI. Step #11 Press to exit parameters screen and to go back to the main screen. Note #1 Press details to see and offset numbers for the selected pipe. The and offset are factors used to convert the sensor frequency to flow rate. They are unique to each pipe size/ material. Note #2 Press custom button to enter and offset numbers for pipe material not listed in pull down menu. The numbers may be obtained by contacting Data Industrial. Note #3 Press Change Label button to change flow direction label. Enter up to 20 characters such as From Pump 17

Battery Powered SDI Programming Programming the Series SDI is accomplished by installing the Data Industrial programming software on a computer and entering data on templates of the Windows based program. 1. Load the interface software into the computer. 2. Connect the PC to the SDI with the Data Industrial A-303 communications cable. Plug in the the RJ11 plug on the A-303 cable to the RJ11 socket on Battry Powered SDI. Connect the DB9 connector of the A-303 cable to the PC com port to a PC that has the SDI software installed. 3. Open the interface software and select the appropriate COM PORT as shown in the dialog box below. 4. Open the Parameters Screen as shown below. To calibrate select parameters from either place shown. 18

5. Program parameters using diagram below as a reference. Step #1 Enter in a number found in Table B. Step #2 Enter in a offset number found in Table B. Step #3 Enter in a Reference number found in Table A. Step #6 Optional setting, Enter in the gallons/pulse and select pulse width. Skip this step if not using the Scaled pulse output Step #7 Press Send to transmit calibration data to the SDI Sensor. See Note #1 Press to retrieve calibration data from SDI. Step #4 Select the desired flow rate and total units. Step #5 Select the desired display readout mode. Press to reset all parameters back to factory defaults. Send must be pressed to send this data to the SDI. Step #8 Press to exit parameters screen and to go back to the main screen. See Note #2 Note #1 After the send button is pressed the unit could take up to one and a half minutes to program the Battery Powered SDI. The illustration below shows the programming process bar. When the programming process bar disappears and the status bar says updated the Battery Powered SDI is programmed. Programming Process Bar Status Bar Note #2 After the exit button is pressed it takes about 10 seconds to go back to the operating display and refresh flow rate and flow total. 19

Table A Customer Reference Number Pipe Pipe Schedules Size O.D. 10 10s 40 40s/Std 80 1 1/2 1.900.109.58 1 9/16.109.58 1 9/16.145.54 1 9/16.145.54 1 9/16.200.49 1 9/16 SDR21 (200) 2 2.375.109.81 1 13/16.109.81 1 13/16.154.77 1 13/16.154.77 1 13/16.218.71 1 13/16.113.81 1 13/16 2 1/2 2.875.120 1.05 2 1/16.120 1.05 2 1/16.203.97 2 1/16.203.97 2 1/16.276.90 2 1/16.137 1.04 2 1/16 3 3.500 4 4.500 5 5.563 6 6.625 8 8.625 10 10.750 12 12.750 14 14.000 16 16.000 18 18.000.120 1.37 2 3/8.120 1.70 2 11/16.134 1.59 2 5/8.134 1.91 2 29/32.148 2.50 3 17/32.165 3.13 4 5/32.180 3.72 4 25/32.250 2.03 3 5/32.250 2.33 3 7/16.250 2.63 3 3/4.120 1.37 2 3/8.120 1.70 2 11/16.134 1.59 2 5/8.134 1.91 2 29/32.148 2.50 3 17/32.165 3.13 4 5/32.180 3.72 4 25/32.188 2.04 3 3/32.188 2.34 3 13/32.188 2.64 3 23/32.216 1.27 2 3/8.237 1.61 2 23/32.258 1.63 2 21/32.280 1.82 2 31/32.322 2.39 3 19/32.365 3.01 4 1/4.406 3.58 4 7/8.438 1.97 3 9/32.500 2.25 3 5/8.562 2.53 3 31/32.216 1.27 2 3/8.237 1.61 2 23/32.258 1.63 2 21/32.280 1.82 2 31/32.322 2.39 3 19/32.365 3.01 4 1/4.375 3.60 4 27/32.375 1.99 3 1/4.375 2.29 3 17/32.375 2.59 3 27/32.300 1.19 2 3/8.337 1.53 2 3/4.375 1.44 2 11/16.432 1.73 3 1/32.500 2.29 3 21/32.594 2.87 4 11/32.688 3.41 5.750 1.88 3 1/2.844 2.15 3 7/8.938 2.42 4 1/4.167 1.32 2 3/8.214 1.63 3 1/8.316 1.83 3 1/32.410 2.40 3 11/16.511 2.98 4 3/8.606 3.52 5 20

Pipe Table A (cont.) Customer Reference Number Pipe Schedules Size O.D. 10 10s 40 40s/Std 80 20 20.000 22 22.000 24 24.000 26 26.000 28 28.000 30 30.000.250 2.93 4 1/16.250 3.23 4 11/32.250 3.53 4 21/32.312 4.41 5 19/32.218 2.94 4 1/32.250 3.53 4 21/32.312 3.81 5.312 4.11 5 9/32.312 4.41 5 19/32.594 2.82 4 9/32.688 3.39 4 31/32.375 2.89 4 1/8.375 3.19 4 7/16.375 3.49 4 3/4.375 3.79 5 1/32.375 4.09 5 11/32.375 4.39 5 5/8 For sizes above 30", consult factory. Pipe O.D. & Schedule, or pipe O.D. & I.D., or pipe O.D. & wall thickness is required. Copper Tube Type Size O.D. L M DWV 1 1/2 1.625.072.48 1 7/16.060.49 1 7/16.049.50 1 7/16.042.51 1 7/16 1.031 2.69 4 19/32 1.125 2.96 4 31/32 1.219 3.23 5 5/16 2 2.125 2 1/2 2.625.083.72 1 11/16.095.95 1 29/32.070.73 1 11/16.080.97 1 29/32.058.74 1 11/16.065.98 1 29/32.042.76 1 11/16 3 3.125.109 1.19 2 3/16.090 1.21 2 3/16.072 1.23 2 3/16.045 1.25 2 3/16 4 4.125.134 1.54 2 9/16.110 1.56 2 9/16.095 1.57 2 17/32.058 1.60 2 17/32 6 6.125.192 1.72 2 25/32.140 1.75 2 3/4.122 1.76 2 3/4.083 1.79 2 3/4 21

Table A (cont.) Customer Reference Number Ductile Iron Because of the variety of iron pipe classes, sizes, and wall thicknesses, consult factory for customer reference number. Pipe O.D. & Schedule, or pipe O.D. & I.D., or pipe O.D. & wall thickness is required. PVC AWWA C900 Size O.D. CL100 4 4.800.192 1.77 2 27/32 6 6.900.276 1.90 3 1/16 8 9.050.362 2.50 3 23/32 10 11.100 12 13.200.444 3.06 4 3/8.528 3.64 5 1/16 For other types of pipe not listed above, consult factory. Pipe O.D. & Schedule, or pipe O.D. & I.D., or pipe O.D. & wall thickness is required. 22

Table B k & Pipe Pipe Schedules Size O.D. 10 10s 40 40s/Std 80 1 1/2 1.900 2 2.375 2 1/2 2.875 3 3.500 3½ 3.500 4 4.500 5 5.563 6 6.625 8 8.625 10 10.750 12 12.750 14 14.000 16 16.000 18 18.000 20 20.000 22 22.000 24 24.000 26 26.000 28 28.000 30 30.000 0.801632 1.813024 0.801632 1.813024 1.317775 1.756472 2.110168 4.142096 5.144059 3.295640 0.801632 1.813024 0.801632 1.813024 1.317775 1.756472 2.110168 4.142096 5.144059 3.295640 123.735118 3.155189 0.297315 0.859353 0.498124 1.523850 0.699870 1.111784 1.169137 1.609184 1.612333 1.609184 1.872713 4.142096 3.251260 2.093849 4.642584 3.295640 8.730561 2.793790 13.737621 2.937799 19.830912 2.768877 24.238528 2.768877 31.728175 2.768877 41.579656 3.715358 51.751173 3.715358 74.0284944 3.155189 For sizes above 30", consult factory. Pipe O.D. & Schedule, or pipe O.D. & I.D., or pipe O.D. & wall thickness is required. 0.297315 0.859353 0.498124 1.523850 0.699870 1.111784 1.169137 1.609184 1.612333 1.609184 1.872713 4.142096 3.251260 2.093849 4.642584 3.295640 8.730561 2.793790 13.737621 2.937799 20.041272 2.768877 24.702144 2.768877 32.804463 2.768877 43.462537 3.715358 78.201801 3.155189 123.735118 3.155189 0.244927 0.859353 0.654225 1.307587 1.070953 1.307587 1.964629 1.307587 4.237085 2.093849 12.476283 2.937799 17.796906 2.937799 28.663241 2.768877 37.706693 3.715358 46.771847 3.715358 67.789784 3.715358 SDR21 (200) 1.212446 1.056965 23

Table B (cont.) Copper Tube Type Size O.D. L M DWV 1 1/2 1.625 2 2.125 2 1/2 2.625 3 3.125 4 4.125 5 5.125 6 6.125 5.041780 0.198965 0.277993 0.063685 0.509285-0.043054 0.784450-0.126200 1.177171 0.198965 1.750507 4.142096 3.587835 0.198965 4.298570 3.295640 Ductile Iron Because of the variety of iron pipe classes, sizes, and wall thicknesses, consult factory for customer reference number. Pipe O.D. & Schedule, or pipe O.D. & I.D., or pipe O.D. & wall thickness is required. PVC Municipal C900 Schedules Size O.D. 100 4 4.800 6 6.900 8 9.050 10 11.100 12 13.200 For other types of pipe not listed above, consult factory. Pipe O.D. & Schedule, or pipe O.D. & I.D., or pipe O.D. & wall thickness is required. Blank boxes indicate no data at time of printing. 24

SPECIFICATIONS Wetted Materials Sensor stem, mounting adapter, isolation valve, and nipple: - 316 Stainless steel Sensor Tip: - polyphenylene sulfide (PPS) O-rings,bearings,shaft: - see ordering matrix Maximum Temperature Ratings: Fluid measured - 300 F (135 C) continuous service Operating temperature: Electronics: - 150 F (65 C) Operating Temperature: LCD: - 150 F (65 C) Maximum Pressure Rating: - 1000 psi @ 100 F - 900 psi @ 200 F - 750 psi @ 300 F Recommended Design Flow Range: - 0.33 to 20 ft/sec - Initial flow detection below.25 ft/sec Pressure Drop: - 0.5 psi or less @ 10 ft/sec for all pipe sizes 1.5 dia and up. Accuracy: - Standard calibration NIST traceable to +/- 1% of rate - Custom wet calibration NIST traceable to +/- 0.5% of rate raw pulse option 0 Straight Pipe Requirement: - install sensor in straight pipe section with a minimum distance of 10 diameters upstream and 5 diameters downstream to any bend, transition, or obstruction. Repeatability: +/- 0.5% Enclosure: - Polypropylene with Viton sealed acrylic cover. Meets NEMA 4X specifications Wire Connections: - all wire connections are made to removable headers with screw type terminals within the electronics housing, ½ conduit thread provided Programming: - all programmable models utilize Data Industrial A-301 connector cable and SDI Series software Display: (optional) - 8 character, 3/8 LCD - STN (Super twisted Nematic) display - annunciators for: rate, total, input, output flow direction for Bi-directional models Accessories - ASDI Programming it - A1027 Hot Tap Adapter Nipple uni-directional analog loop scaled pulse option 1 option 2 bi-directional analog loop scaled pulse option 5 option 6 Number of wire connections 2 2 4 6 6 Pulse Units Analog Units Operating Voltage Overvoltage protection Quiescent Current Draw @12VDC or 24VAC Short Circuit Current Output Frequency Output Pulse Width Output Isolation 8-35 VDC 30 VAC ±40 VDC 330uA TYP 50mA TYP 800 Hz max 5 ms below 100 Hz N/A N/A ±40 VDC Software controlled current of 3.5-20.5mA N/A N/A N/A N/A 12-30 VAC 12-35 VDC 30 VAC ±40 VDC < 2mA > 100 ma scaled by customer adjustable 50mS to 5.0 second in 50 ms increments Opto-Isolated 12-30 VAC 12-35 VDC 30 VAC ±40 VDC < 5.0 ma for direction > 100 ma N/A N/A Opto-Isolated 12-30 VAC 12-35 VDC 30 VAC ±40 VDC < 5.0 ma > 100 ma scaled by customer adjustable 50mS to 5.0 second in 50 ms increments Opto-Isolated Operating Voltage N/A 8-35 VDC N/A 8-35 VDC N/A Output Response Time N/A varies with programmable filter N/A varies with programmable filter N/A 25

(This page intentionally left blank.) 26

(This page intentionally left blank.) 27

Viton is a registered trademark of DuPont-Dow Elastomers. Torlon is a registered trademark of Amoco Performance Products. Windows is a registered trademark of Microsoft Corporation. Hastelloy is a registered trademark of Haynes Corporation. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specifications without notice, except to the extent an outstanding contractual obligation exists. Please see our website at www.badgermeter.com for specific contacts. Copyright Badger Meter, Inc. 2009. All rights reserved. BadgerMeter, Inc. P.O. Box 581390, Tulsa, Oklahoma 74158 (918) 836-8411 / Fax: (918) 832-9962 www.badgermeter.com