ESD5100 Series Speed Control Unit PART NUMBER ESD5120 ESD (127)

Similar documents
ESD5500E Series Speed Control Unit

ESD5550 / 5570 Series Speed Control Units

ENGINE GOVERNING SYSTEMS

ESD-5550/5570 Speed Control Unit. Manual

ESD-5550/5570 Series - Speed Control Unit

ESD-5500E Series - Speed Control Unit

EDG5500 Electronic Digital Governor With Quikset Display

EDG6000 Electronic Digital Governor

IGA225 Integrated Governor & Actuator

10V. the rack of the oil pump must be on the

EEG6500 Enhanced Electronic Governor

ESC2301. Universal Electronic Governor Controller Operation Manual

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

EG3000. Generator Electronic Governor Controller Operation Manual

EG1069X. Generator Electronic Governor Controller Operation Manual

EG1065X. Compatible with Barber Colman* Dyn1-1065X series * Use for reference purpose only and not a genuine Barber Colman product.

EEG6550 Enhanced Electronic Governor

EG3002. Electronic Engine Governor Controller User Manual

with discrete output (Overspeed) with auxiliary input (Synchronizer and Load Sharing)

PRODUCT SERIES: DPG-2100

PED 5000 ELECTRIC ACTUATOR

225 SERIES ELECTRIC ACTUATOR

KT145 Series John Deere 6076 with Nippondenso Inj. Pump

KT230 Series Caterpillar 3406 Governor System Installation Kit

KT101 Series Governor System Installation Kit Cummins 4B(T) / 6B(T) With CAV/DPA Pump

PM300 VOLTAGE REGULATOR INSTRUCTION MANUAL

DYNA Power Control Manual For Plus 1, Plus 2, Plus 4 and Plus 6 Ft. Lb. Systems

ATB Series - Integral Throttle Body Actuators

ESD5300 Series Speed Control Unit

Product Manual (Revision B) Original Instructions. EPG Electrically Powered Governor Models 501 and Installation and Operation Manual

Product Manual (Revision E) Original Instructions. Min/Max Control Systems. Installation and Operation Manual

MX431 Generator Automatic Voltage Regulator Operation Manual

2301A Load Sharing & Speed Control with Dual Dynamics. Product Manual (Revision NEW, 1990) Original Instructions

Product Manual (Revision D, 5/2015) Original Instructions. 2301A Speed Control. Installation and Operation Manual

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

Product Manual (Revision C) Original Instructions. EPG (Electric Powered Governor) with Position Feedback. Installation and Operation Manual

MAGNAMAX DVR DIGITAL VOLTAGE REGULATOR

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

5001TCP SPEED CONTROLLER

ADVR-12. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

GENSET CONTROL MODULE A121A / A241A

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

DENISON HYDRAULICS Jupiter 500 Driver Card Series S

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

PM300E Voltage Regulator Instruction Manual

Application Information

5001TCP SPEED CONTROLLER

GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start.

ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI

ES52. Auto Start Engine Controller. Full Version. Installation and User Manual for the ES52 Auto Start Engine Controller.

EA16. Generator Automatic Voltage Regulator Operation Manual

INSTALLING, OPERATING AND MAINTAINING THE MODEL D1028 COMPUTER INPUT BI-DIRECTIONAL GENERATOR FIELD REGULATOR INSTRUCTION MANUAL # S-225

MODEL 422 Submersible Pump Controller

ENGEN -100/ENGEN -200 ENGINE GENERATOR CONTROLLER

UG-5.7, UG-8, UG10 Governor

DYNA 8000 DYNA 8200 DYNA

ES52 Auto Start Engine Controller Installation and User Manual for the ES52 Auto Start Engine Controller.

Load Sharing Module. Analog Output Installation, Operation, and Calibration Manual. Manual 26011

12 Series Linear Actuators. Operation & Maintenance Manual, Analog Positioner Installation

Troubleshooting Guide

ISC, QSC8.3, and ISL (FIS )

SECTION 2.00 SPEED GOVERNING SYSTEM DESCRIPTION SPEED GOVERNING SYSTEM DESCRIPTION F18/H24 GOVERNOR

LTX RF LEVEL SENSOR. Instruction Manual

REMOTE MOUNT SOLENOID DRIVER (0-5 VDC/0-20 ma/10k Potentiometer Input)

TRAC-3 TENSION READOUT AND CONTROL

System 350 S350P Proportional Plus Integral Temperature Stage Module

Filtered PWM Speed Control for Permanent Magnet DC Motors

4024 EPG (Electrically Powered Governor) Product Manual (Revision B, 3/2008) Original Instructions

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (0-10VDC Input Version)

Operating Manual For Stepper Driver

EPG Electrically Powered Governor. Installation and Troubleshooting Manual. Models 1712/1724 and 512/524 without Position Feedback

RCP200 Series Motor Controls. Instruction Manual Model RCP Model RCP Model RCP202-BC1 Model RCP202-BC2 Model RCP205-BC2

Application Information

GENSET CONTROL MODULE A121H / A241H. User selectable time delays for engine start and engine stop (cool down).

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

MondoStep 7.8. High Performance Microstepping Driver. User s Manual. Version PROBOTIX All Rights Reserved

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

Dynamic Adjustment Procedure for 700-series Digital Controls. Application Note (Revision A,8/1998) Original Instructions

Product Manual (Revision C) Original Instructions. Load Sharing Module. Analog Output Installation and Operation Manual

User Manual of 2MA2282

INSTRUCTION MANUAL MODEL PS VDC POWER SUPPLY

Application Note. Controllers for Stanadyne Pumps Using DC Integrated Actuators. Calibration Instructions. Manual 36579

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages.

1. AC VOLTS: Displays generator output in voltage. 2. AC FREQUENCY: Displays the speed of the generator set in Hertz.

MDC V, 30A Brushless Controller. User s Guide L East Orangefair Lane, Anaheim, CA

Installation and Operation Manual. Load Sharing Module Vdc Output Manual (Revision B)

CONTROL FEATURES AVAILABLE OPTIONS

Troubleshooting Guide

ST-125 Control System for Stanadyne DB-4 Series Pumps. Product Manual (Revision NEW) Original Instructions

Fincor Series 2230 MKII/2240

ECU. Speed Switch Manual. Contents. ECU is a registered trademark of Engineering Concepts Unlimited Inc.

INSTRUCTION MANUAL FOR

PowerOhm Installation Manual for BM R Series Braking Modules

HT-DDD100 Digital Dual Driver Governor. Instruction manual

ENGINE GOVERNING SYSTEMS

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

150 WATT HEW SINGLE SERIES DC/DC CONVERTERS

SL Series Application Notes. SL Series - Application Notes. General Application Notes. Wire Gage & Distance to Load


Transcription:

ESD5100 Series Speed Control Unit 1 INTRODUCTI The ESD5100 Series speed control unit is an all electronic device designed to control engine speed with fast and precise response to transient load changes. This closed loop control, when connected to a proportional electric actuator and supplied with a magnetic speed sensor signal, will control a wide variety of engines in an isochronous or droop mode. It is designed for high reliability and is hard potted to withstand the engine environment. The ESD5131 is a derivation of the standard GAC ESD5111 Speed Control Unit. All specifi cations, installation procedures, and adjustments, except those noted are identical. The ESD5131 comes with DIP switches which allow for the selection of the Lead Circuit and Soft Coupling features. The ESD5111 comes with the Lead circuit already enabled via a jumper across posts and. See Section 8. 2 SPECIFICATIS PERFORMANCE Isochronous Operation ±0.25 % or better Speed Range /Governor 1K - 7.5K Hz Continuous Speed Drift with Temperature ±0.5% Typical Idle Adjust CW Min. 1200 Hz Below set speed Idle Adjust CCW Min. 4100 Hz Below set speed Droop Range 1-5% Regulation* Droop Adj. Max. (K-L Jumpered) 875 Hz., ±75 Hz per 0 A change Droop Adj. Min. (K-L Jumpered) 15 Hz., ±6 Hz per 0 A change Speed Trim Range ±200 Hz Remote Variable Speed Range 500-7 khz Terminal Sensitivity J L N P 115 Hz., ±15 Hz/Volt @ 5 K Impedance 735 Hz., ±60 Hz/Volt @ 65 K Impedance 148 Hz., ±10 Hz/Volt @ 1 M Impedance 10 VDC Supply @ 20 ma Max. PHYSICAL Dimensions See Outline Diagram 4 Weight 2 lb.(0.545 kg) Mounting Any Position, vertical preferred RELIABILITY Vibration 1G, 20-100 Hz Testing 100% Functionally Tested ENVIRMENTAL Ambient Temperature -40 to +185 F (-40 to +85 C) Relative Humidity up to 95% All Surface Finishes Fungus proof and corrosion resistant RoHS Regulation Compliant INPUT POWER DC Supply 12 or 24 VDC Battery Systems (Transient and Reverse Voltage Protected) Polarity Negative Ground (case isolated) Power Consumption 100 ma (No actuator current) Speed Signal Range 0.5 50 VAC Actuator Current Range 10 Amps continuous @ 77 F (25 C) Speed Signal Range 0 to 50.0 VAC COMPLIANCE / STANDARDS Agency CE Requirements 1 3 PART NUMBER ESD5111 ESD5111T ESD5119 ESD5120 ESD5131 ESD5159 ESD5160 4 OPTIAL ACTUATOR CABLE SHIELDING TO MEET CE DIRECTIVE * ACTUATOR CTROLLER MODELS OUTLINE DIAGRAM MAGNETIC PICK-UP OVERNORS MERICA G A C ORP. CTROL UNIT MODEL: ESD51xx S/N : MADE IN AGAWAM, MA U.S.A. CAUTI PICK-UP - + ACTUATOR BATTERY _ + S1 BATTERY ENGINE CTROL COMPENT. WHEN INSTALLING OR SERVICING REFER TO PRODUCT PUBLICATI. A B C D E F G H J K L M N P FUSE 15A MAX SEE SPECIFIC ACTUATOR PUBLICATI FOR PROPER WIRING OF ACTUATOR BASED BATTERY VOLTAGE CW TRIM FEATURES Multi VDC / Standard Unit Multi VDC / Temperature Compensated Multi VDC / Cummins EFC Reverse Acting (Normally open) Multi VDC / Light-Force (Low Current Optimized) Cummins EFC Forward Acting (Normally Closed) Multi VDC / Switchable Soft Coupling and Lead Circuit Multi VDC / Expanded Frequency Range to 14 khz Multi VDC / Cummins EFC Reverse Acting for Fire Pump Applications / Expanded Frequency Range to 10.5 khz E1 E2 E3 AUX 10V ISOCHROUS EXTERNAL SELECTOR SWITCH (NOT REQUIRED FOR SINGLE ISOCHROUS OPERATI) 1 JUMPER DEAD TIME COMPENSATI JUMPER Ø0.27 (6,8) ACCESSORY POWER SUPPLY ACCESSORY INPUT ADD JUMPER TO INCREASE RANGE GROUND REFERENCE ESD5100 Series Speed Control Unit 17.18 PIB 1000 E 1 Switches On ESD5131 Only SOFT COUPLING ESD5131, ESD513 and ESD5151 o SOFT COUPL 1

5 INSTALLATIS See Section 4 for more dimensions Vertical orientation allows fl uids to drain in moist environments. Mount in a cabinet, engine enclosure, or sealed metal box. Dimensions in (mm) 7 ADJUSTMENTS BEFORE STARING THE ENGINE Make sure the following adjustments are set before starting the engine. Middle Position Middle Position TRIM CTROL Middle Position START ENGINE Avoid Extreme Heat Ø0.27 (7) The speed control unit governed speed setting is factory set at approximately engine idle speed. (1000 Hz., Speed sensor signal or 600 RPM) An overspeed shutdown device, independent of the governor WARNING system, should be provided to prevent loss of engine control which may cause personal injury or equipment damage. Do not rely exclusively on the governor system electric actuator to prevent overspeed. A secondary shutoff device, such as a fuel solenoid must be used. 6 WIRING See Section 3 for the Wiring Diagram TERMINAL DEFINITI S A & B Actuator (+/-) #16 AWG (3 mm sq) or larger wire C & D Magnetic Speed Pickup (D is ground) Wires must be twisted and/or shielded for their entire length Gap between speed sensor and gear teeth should not be smaller than 0.025 in. (.64mm) and no larger than 0.035 in. (.89 mm) Speed sensor voltage should be at least 1VAC RMS during crank #16 AWG (3mm sq) or larger wire Crank the engine with DC power applied to the governor system. The actuator will energize to the maximum fuel position until the engine starts. The governor system should control the engine at a low idle speed. If the engine is unstable after starting, refer to Section ADJUSTING FOR. GOVERNOR SETTING The governed speed set point is increased by clockwise rotation of the adjustment control. adjustment is a 25 turn potentiometer. ADJUSTING FOR Once the engine is running at operating speed and at no load, the following governor performance adjustments can be made to increase engine stability. E & F G H Battery Power (-/+) Ground Signal A 15 amp fuse must be installed in the positive battery lead to protect against reverse voltage Battery positive (+) input is Terminal F Add jumper to increase droop range J Variable Speed Input 5K Resistive Nominal K & L Droop Select Active when closed M & L Idle Select Active when closed N P Accessory Input Accessory Power Supply Sensitivity: 148 Hz ±10 Hz/V @1M Impedance Input is centered at 5.0V ±0.1V Load Sharing / Synchronizing, 0-10V Input Accessory connections must be shielded. +10 Volt Output RECOMMENDATIS Shielded cable should be used for all external connections to the ESD control. One end of each shield, including the speed sensor shield, should be grounded to a single point on the ESD case. PARAMETER A. ADJUSTMENT PROCEDURE Rotate the adjustment clockwise until instability develops. Then, gradually move the adjustment counterclockwise until stability returns. Finally, move the adjustment one division further counterclockwise to insure stable performance (270 potentiometer). If instability persists, adjust the next parameter. B. Follow the same adjustment procedure, steps 1-3, as the parameter. Normally, adjustments made at no load achieve satisfactory performance. If further performance improvements are required, refer to Section 9 SYSTEM TROUBLESHOOTING. Information can be found regarding the adjustment of the DIP switch positions on the ESD. 2 ESD5100 Series Speed Control Unit 17.18 PIB 1000 E

8 SELECTABLE & SOFT COUPLING ESD5131 LY Switch 1(C1) controls the Lead Circuit found in the ESD513 The normal position is. Move the switch to the position if there is fast instability in the system. Switch 2(C2) controls an additional circuit added in the ESD5131 that is designed to eliminate fast erratic governor behavior, caused by very soft or worn couplings in the drive train between the engine and generator. The normal position is. Move to the position if fast erratic engine behavior due to a soft coupling is experienced. IMPORTANT: Speed Adjustment Is a 25 Turn Potentiometer ADDITIAL FEATURES & OPTAL WIRING 1 SETTING After the governor speed setting had been adjusted, place the optional external selector switch in the position. The idle speed set point is increased by the clockwise rotation of the adjustment control. When the engine is at idle speed, the speed control unit applies droop to the governor system to insure stable operation. ESD5111 E1 E2 E3 JUMPER (Cut to disable) ESD5131 SOFT COUPLING All ESD5100 Series speed controllers come with the Lead Circuit enabled. Cut the jumper between posts and to disable. ESD5131 has a switch to disable the Lead Circuit. OPERATI Droop is typically used for the paralleling of engine driven generators. When in droop operation, the engine speed will decrease as engine load increases. The percentage of droop is based on the actuator current change from no engine load to full load. Place the optional external selector switch in the position. is increased by clockwise rotation of the adjustment control. After the droop level has been adjusted, the rated engine speed setting may need to be reset. Check the engines speed and adjust that speed setting accordingly. ACCESSORY INPUT The Auxilliary Terminal N accepts signals from load sharing units, auto synchronizers and other governor system accessories, GAC accessories are directly connected to this terminal. When an accessory is connected to Terminal N, the speed will decrease and the speed adjustment must be reset. When operating in the upper end of the control unit frequency range, a jumper wire or frequency trim control may be required between Terminals G and J. This increases the frequency range of the speed control to over 7000 Hz. If the auto synchronizer is used alone, not in conjunction with a load sharing module, a 3m ohm resister should be connected between Terminals N and P. This is required to match the voltage levels between the speed control unit and the synchronizer. ACCESSORY SUPPLY The +10 voit regulated supply, Terminal P, can be utilized to provide power to GAC governor system accessories. Up to 20 ma of current can be drawn from this supply. Ground reference is Terminal G. CAUTI A short circuit on this terminal will damage the speed control unit. WIDE RANGE REMOTE OPERATI A single remote speed adjustment potentiometer can be used to adjust the engine speed continuously over a specific speed range. Select the desired speed range and corresponding potentiometer value. (Refer to TABLE 1) If the exact range cannot be found, select the next higher range potentiometer. To maintain engine stability at the minimum speed setting, a small amount of droop can be added using the adjustment. At the maximum speed setting the governor performance will be near isochronous, regardless of the droop adjustment setting. An additional fixed resistor may be placed across the potentiometer to obtain the exact desired range. Connect the speed range potentiometer as shown below. Contact GAC for assistance if diffi culty is experienced in obtaining the desired variable speed governing performance. TABLE 1 FREQUENCY RANGE POTENTIOMETER VALUE 900 Hz 1 K 2400 Hz 5 K 3000 Hz 10 K 3500 Hz 25 K 3700 Hz 50 K Conversion Formulas (RPM x #Teeth) Hertz MAG PICKUP = 60sec RPM = (Hertz MAG PICKUP x 60sec) #Teeth Though a wide range of droop is available with the internal control, droop level requirements of 10% are unusual. If droop levels experienced are higher or lower than those required, contact GAC for assistance. Trim Pot. Wiring Wide Range Remote Variable Speed Pot. Wiring G J K L * CW * Select proper potentiometer value from Table 1 3 ESD5100 Series Speed Control Unit 17.18 PIB 1000 E

9 SYSTEM TROUBLESHOOTING INSUFFICIENT MAGNETIC SIGNAL A strong magnetic speed sensor signal will eliminate the possibility of missed or extra pulses. The speed control unit will govern well with 0 VAC speed sensor signal. A speed sensor signal of 3 volts VAC or greater at governed speed is recommended. Measurement of the signal is made at Terminals C and D. The amplitude of the speed sensor signal can be raised by reducing the gap between the speed sensor tip and the engine ring gear. The gap should not be any smaller than 0.025 in (0.64 mm). When the engine is stopped, back the speed sensor out by 3/4 turn after touching the ring gear tooth to achieve a satisfactory air gap. SYSTEM INOPERATIVE If the engine governing system does not function, the fault may be determined by performing the voltage tests described in Steps 1 through Positive (+) and negative (-) refer to meter polarity. Should normal values be indicated during troubleshooting steps, and then the fault may be with the actuator or the wiring to the actuator. Tests are performed with battery power on and the engine off, except where noted. See actuator publication for testing procedure on the actuator. STEP WIRES NORMAL READING 1 F(+) & E(-) Battery Supply Voltage (12 or 24 VDC) DC battery power not connected. Check for blown fuse. Slow Periodic Non-Periodic An irregularity of speed below 3Hz. Erratic Engine Behavior Readjust the and Set DIP switches 1 and 2 to in the following order: First SW1, Second SW2 Check fuel system linkage during engine operation for: a. binding b. high friction c. poor linkage Adjust the DEAD TIME COMPEN- SATI by adding a capacitor from post E2 to E3 (negative on E2) Start with 10 mfds and increase until instability is eliminated. Increasing the should reduce the instability but not totally correct it. If this is the case, there is most likely a problem with the engine itself. Check for: a. engine mis-fi rings b. an erratic fuel system c. load changes on the generator set voltage regulator. If throttle is slightly erratic, but performance is fast, then remove the jumper from to. 2 C(+) & D(-) 0 VAC minimum while cranking 3 P(+) & G(-) 10 VDC, Internal Supply 4 F(+) & A(-) 0-0 VDC while cranking IN Fast Periodic SYMPTOM The engine seems to jitter with a 3Hz or faster irregularity of speed. IN Low battery voltage. Wiring error. Gap between speed sensor and gear teeth too great. Check Gap. Improper or defective wiring to the speed sensor. Resistance between D and C should be 160 to 1200 ohms. See specifi c mag pickup data for resistance. Defective speed sensor. Short on Terminal P. Defective speed control unit. parameter set too low. Short/open in actuator wiring. Defective speed control. Defective actuator, see Actuator Troubleshooting. Instability in a closed loop speed control system can be categorized into two general types. PERIODIC appears to be sinusoidal and at a regular rate. N-PERIODIC is a random wandering or an occasional deviation from a steady state band for no apparent reason. Turn off other electrical equipment that may be causing interference. Readjust the and STABILI- TY for optimum control. SYMPTOM Engine Overspeeds Overspeed Shuts Down Engine After Running Speed is Reached UNSATISFACTORY PERFORMANCE NORMAL READING Do Not Crank. Apply DC power to the governor system. Manually hold the engine at the desired running speed. Measure the DC voltage between Terminals A(-) & F(+) on the speed control unit. After the actuator goes to full fuel, disconnect the speed sensor at Terminal C & D. If the actuator is still at full fuel-speed then the speed control unit is defective. If the voltage reading is 0 to 0 VDC: a. adjustment is set above desired speed b. Defective speed control unit If voltage reading is above 0 VDC then check for: a. actuator binding b. linkage binding Set point of overspeed shutdown device set too low. If the voltage reading is below 0 VDC: a. Defective speed control unit Speed adjustment set too high. OVER set to close to running speed. Actuator or linkage binding. Speed control unit defective. Remove the to jumper (This reduces sensitivity to high frequencies). If system is still unstable, remove the E1 to E2 jumper and readjust and. ESD5100 Series Speed Control Unit 17.18 PIB 1000 E 4

SYMPTOM Overspeed Shuts Down Engine Before Running Speed is Reached Actuator does not energize fully NORMAL READING Check impedance between Terminals C & D. Should be 160 to 1200 Ohms Measure the voltage at the battery while cranking. Momentarily connect Terminals A and F. The actuator should move to the full fuel position. OVER set too low. Adjust 5-6 turns CW. Erroneous speed sensor signal. Check wiring. If voltage is less than 7V for a 12V system, or 14V for a 24V system, check or replace the battery. Actuator or battery wiring in error Actuator or linkage binding Defective actuator Fuse opens. Check for short in actuator or harness. Engine remains below desired governed speed Measure the actuator output, Terminals A & B, while running under governor control. If voltage measurement is within 2 VDC of the battery supply voltage level, then fuel control is restricted from reaching full fuel position, possibly due to mechanical governor, carburetor spring, or linkage interference. parameter set too low. 5 ESD5100 Series Speed Control Unit 17.18 PIB 1000 E