Powervortex 3100/3700TL. Next generation solar battery hybrid inverter and system solution. User Manual Version 1.0

Similar documents
T Series (N6052T) Solar Battery Hybrid System. Installation Manual Version 1.1

GEatom306KHF-5U Three-phase Grid-Tied Battery Inverter. Version 1.1. Global Mainstream Dynamic Energy Technology Ltd. 1

GHESS 3.7_4.8KWH. Next generation solar battery hybrid inverter and system solution. User Manual Version 1.4

GEatom103KHF. Next generation battery inverter and system solution. User Manual Version 1.2

PV Master OPERATION MANUAL

8 Troubleshooting and Maintenance

LS1024BP/ LS2024BP. Solar Charge Controller USER MANUAL

Accessories for Wind Power Inverter WINDY BOY PROTECTION BOX 400 / 500 / 600

HYBRID 5048E. Hybrid Inverter INSTALLATION AND OPERATION MANUAL. Version 2.0E

Inverter / Charger Accessory for Steca Solarix PLI Phase / Parallel Kit. Installation and operating instructions Z01 17.

Manual. BlueSolar Grid Inverter 1500 / / / / / 230

LS1024BP/ LS2024BP. Solar Charge Controller USER MANUAL

On Line UPS. LUC 1000E / LUC 2000E / LUC 3000E User Manual

YSmart Technology Co., Ltd. User Manual. GTI Grid Series. GTI Series Inverters for Grid-connected PV system

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

HOYMILES MICRO-IVERTER MI-250

B-Box Pro 2.5~10.0 User Manual

Wind Power Inverter WINDY BOY 5000A/6000A

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor Installation Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

HANGKAI GROUP HOYMILES MICRO-INVERTER MI-250

PowerLegato User Operation Guide

User Manual. Hybrid PV Inverter. Version: 2.1

Installation and Operating Instructions. Solar System Controller ISC3020

CPS Energy Balancer. Version: 1.0

Portable Solar Power Battery Pack User's Manual

Energy Controler. User Manual. SolaX Power NetworkTechnology(Zhejiang)Co,.Ltd.

DC Master 24/ A

Installation and operating instructions. Solar charge controller MPPT 10 A / 20 A Z Z

3KW Off-grid Solar Power System LFP Battery

User Manual 1KVA/ 2KVA/ 3KVA INVERTER / CHARGER

7 MODES OF OPERATION INVERTER STATUS Standby: The PV string can only provide just enough voltage to minimum requirements of the controller.

Pro Booster 802Li. Please read and fully understand the instructions in this manual before operation. Keep this manual safe for future reference.

362 Clamp Meter. Users Manual

FREQUENCY INVERTER INSTALLATION & USER GUIDE

STONESTAR AUSTRALIA PTY LTD

System description Off-Grid Systems with SUNNY ISLAND 4.4M / 6.0H / 8.0H

B-Box Pro 13.8 User Manual

User s Manual. Wind/Solar Hybrid Controller. Please Read This User Manual Carefully Prior to Installation and Operation of This Product V1.

Operations Manual Pika Harbor Smart Battery

B-Box Res 2.5~10.0 User Manual

Sinewave Inverters. SWING 150VA and 300VA. User s manual

Lithium-Ion Phosphate Battery US2000(Version B) Product Manual

Installing a Programmed Fronius SCERT in a Managed AC Coupled system

Operating instructions. sonnenprotect for operators. KD-337 Part no Version X00.

User Manual. Hybrid 4KW PV Inverter. Version: 1.2

B-Box Pro 2.5~10.0 User Manual

B-Box Pro 2.5~10.0 User Manual

Installation and Operating Instructions. MPPT Solar System Controller ISC3040

Residential SolarEdge StorEdge

PV Inverter SUNNY MINI CENTRAL 9000TL / 10000TL / 11000TL with Reactive Power Control

User Manual V1.1 OptiFlex 1100 / OptiFlex 2000

USER'S GUIDE. WiseHP11 SINGLE PHASE HIGH PRECISION AVR SERVO-MOTOR AUTOMATIC VOLTAGE STABILIZER

Accessories for Stand-alone inverter SUNNY ISLAND GENMAN

Sinewave Inverters. SWING pro 200VA and 350VA. User s manual

Lithium-Ion Phosphate Energy Storage System PowerCube-X1 Operation Manual

Grant Grid-Connected Inverter For Grant Solar PV Systems. Installation & User Instructions

User Manual. 3kW Hybrid PV Inverter HX-3000

User Manual / Manuel utilisateur

SOLAR INVERTER/CHARGER 1000VA/1500VA/2000VA. Appliances. PC TV Light Electricfan

User s Manual. Wind/Solar Hybrid Street Light Controller. Please Read This User Manual Carefully Prior to. Installation and Operation of This Product.

UGE-4K Off-Grid Controller OWNER S MANUAL

User Manual Rittal PMC UPS 6kVA

1. Introduction OHY1P kW Hybrid Inverter USER MANUAL V2.0

SH5K+ Hybrid Inverter Overview & Installation.

User s Manual Wind/Solar Hybrid Controller

1. INTRODUCTION SYSTEM DESCRIPTION Front Panel CONNECTION AND OPERATION TROUBLESHOOTING...8

DLT-U1100 UPS Uninterruptible Power Supply Manual V1.00. Industrial PCs applied in

User manual. Solar Hybrid 1-5KVA. Uninterruptible Power Supply / Charger

Start UP Guide. Symmetra LX Tower Rack-Mount. UPS Models 200 V, 4-8 kva 208/240 V, 4-8 kva 220/230/240 V, 4-8 kva

BYD Battery-Box HV User Manual Battery-Box H 5.1/6.4/7.7/9.0/10.2/11.5

Operating Manual SUNNY ISLAND 3.0M / 4.4M / 6.0H / 8.0H SUNNY REMOTE CONTROL. SI30M-44M-60H-80H-BE-en-33 Version 3.3 SUNNY REMOTE CONTROL

Installation and Operating Instructions. Solar System Controller ISC3030

Instruction Manual. Backup Camera System With Replacement Mirror Display RVS N

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units

Battery Charger Retrofit Kit Q-DCCHG1 for DC Cabinet Retrofit Manual

User Manual Solar Charge Controller 3KW

User s Manual. ClipperCreek, Inc. Innovative Infrastructure for Electric and Hybrid Vehicles. Model PCS-15

SMT. Installation and Operation Manual. Model:SMT WITH MPPT TECHNOLOGY

MICRO-INVERTER OMNIKSOL M-300

RM 12V/24V Series Solar Charge Controller User s Manual

12/24 VOLT AUTOMATIC SOLAR CHARGE CONTROLLER

Getting started with

PV Generation System. Solar Charge Controller SPECIFICATION

Instruction Manual. Blink HQ Charger. Charge on. a CarCharging Company

User Manual. Solar Charge Controller 3KW

2 35W. Product Introduction. 995mm(39.2in) 560mm(22in) 560mm 22in. 400mm 15.7in

User Manual 1KVA-5KVA INVERTER / CHARGER

Manual. EN Appendix. Lynx Ion BMS 400A / 1000A

Operation Manual. imarsbd-hs Energy Storage Integrated Machine

User Manual. SP10000 Premium

Installation and operating instructions. Solar charge controller 10 A / 15 A / 0 A / 30 A PHOTOVOLTAIK - PHOTOVOLTAICS - PHOTOVOLTAIQUE - FOTOVOLTAICA

OHY3P kW Hybrid Inverter (3-Phase) USER MANUAL V2.0

Installation Manual. PowerRouter Solar Battery self-use. Version

Introduction of EzManage Application

BMW i. Freude am Fahren. BMW i Wallbox Plus. Owner's manual

Safe, reliable, long lasting Lithium Iron Phosphate battery. Next generation capture and release technology. Increased efficiency for greater savings

I. Safety precautions

LS0512 Solar Charge Controller

SK-10. Features. Solar Charge Controller User Manual. Important Safety Information

Power InverterTM Watt. Continuous. User's Manual. WAGAN Corp. Limited Warranty Registration Form. Item no

Transcription:

Powervortex 3100/3700TL Next generation solar battery hybrid inverter and system solution User Manual Version 1.0

Content 1. Safety... 1 1.1 How to Use This Manual... 1 1.2 Safety Rules... 1 1.3 Warning Notices Affixed to the Device... 2 1.4 Important Safety Information... 2 1.5 Disposal... 4 1.6 Exclusion of Liability... 4 2.Description... 5 2.1 General System Description... 5 2.2 System connection... 6 3. System installation... 7 3.1 Unpacking the device... 7 3.1.1 Before unpacking... 7 3.1.2 Mounting... 7 3.1.3 Packing List... 9 3.2 Mounting... 11 3.2.1 SolDate 3100 / 3700TL and BM024 installation... 11 3.2.2 Mounting battery cabinet... 12 3.2.3 Mounting energy meter... 14 3.3 System connection... 15 3.3.1 How to make power connecting line... 15 3.3.2 RS485 communication line... 16 3.3.3 System connection... 17 3.3.4 9.6kWh connection... 18 4. System settings... 20 4.1 LCD... 20 4.1.1 LCD Interface... 20 4.1.2 LCD indication lights... 20 Global Mainstream Dynamic Energy Technology Ltd.

4.1.3 LCD Display definition... 21 4.1.4 LCD display menu definition... 21 4.1.5 LCD Setting... 22 4.2 WiFi... 23 4.2.1WiFi function... 23 4.2.2 WiFi Configuration... 23 5 System operation... 27 5.1 System settings... 27 5.2 System starting... 27 5.3 System operating instructions... 28 5.3.1 On-grid operation... 28 5.3.2 Off-grid operation... 28 5.4 System maintenance... 28 6 Troubleshooting... 29 6.1 Safety during Troubleshooting... 29 6.2 Faults... 29 6.3 Fault Messages and Actions List... 29 6.4 Fault Acknowledgement... 31 6.5 Technical Service... 32 Global Mainstream Dynamic Energy Technology Ltd.

Prelude Published by Global Mainstream Dynamic Energy Technology Ltd. (GMDE) Room 604-605, Tongpu Road No.1220, Putuo District, Shanghai, P.R.China. Tel: +86 21 60710809 Fax: +86 21 61730300 www.global-mde.com Legal Disclaimer All information in this documentation has been compiled and checked with most care. Despite of this, faults or deviations cannot be completely excluded. We assume no liability and are hereby acknowledged. The relevant up-to-date version can be obtained from www.global-mde.com Copyright The details of this documentation are the property of GMDE. Using and publicizing this documentation, even if only in parts require the written consent of GMDE. Global Mainstream Dynamic Energy Technology Ltd.

Read this user manual before you start Thank you for purchasing our products, this hybrid solution is highly reliable and efficient. This Powervortex 3100 / 3700TL system device is IP20 what is rated for dusty or humid environments and is only suitable for indoor installation. If you are reading the electronic version of the manual, please note that you can click the content to find information you want quickly. All the characters which contain underline are clickable. A phrase named Back to Top at the bottom of each chapter can help you back to the first page rapidly. Before using this device, please ensure that you have read this manual including installation and safety operation carefully. If you have any difficulties during installation or operation, please refer to this manual or send email to service@global-mde.com, we will help to solve your problems as soon as possible.

1. Safety 1.1 How to Use This Manual Please read the safety instructions in this manual first. Throughout the manual it is assumed that the reader is familiar with AC and DC installations and knows the rules and regulations for electrical equipment and for connecting it to the utility AC grid. It is especially important to be familiar with the general safety rules for working with electrical equipment. This manual is intended for qualified electricians. 1.2 Safety Rules General introduction These safety-related guidelines use the following warning notices to describe the various levels of danger: Death or severe personal injury will occur. DANGER Death or severe personal injury may occur. WARNING Personal injury or material damage may occur. CAUTION Explanations ELECTRIC SHOCK! Electric Shock! Do not open the device! Dangerous voltage may still be applied inside the device even after it has been switched off. 1

WARNING High leakage current! Make absolutely sure you establish connection to ground before connecting the device to the supply circuit! Health risk! WARNING Health risk for persons with cardiac pacemakers, metallic implants, or hearing aids in the immediate vicinity of electrical equipment! Risk of improper handling! Personal injury by crushing, shearing, cutting, or striking. CAUTION Cancellation of the operating license! CAUTION If the GMDE inverter is operated with a wrong country code, the electric supply company may cancel the operating license. Hot surface! Surfaces of the housing can be hot! Risk of injury! Risk of burns. HOT SURFACE! The housing top and the heat sinks may have a surface temperature of 70 C. 1.3 Warning Notices Affixed to the Device 1.4 Important Safety Information The following operating and maintenance instructions must be read before installing, operating or maintaining the inverter. Before installation: 2

Check for damage to the device and package. If you are in doubt, please contact us or the distributor before installing the device. Before connecting the solar modules or battery packs with the product, check the voltages and make sure they are within the limits of the GMDE inverter specifications. Failure to observe these specifications could void your warranty. Installation: Only trained and qualified personnel familiar with local electrical codes may work with the electrical installations. For optimum safety, please follow the steps described in this manual. Disconnecting the product: Please refer to Disconnecting for maintenance in Section 5.4 System maint. Note that wait at least 15 minutes before proceeding, after disconnecting the hybrid inverter from AC grid, PV panels and battery packs. Operating the product: Do not commission the device until the overall system complies with the application-specific national rules and safety regulations. The ambient conditions given in the product documentation must be observed. The machine or installation manufacturer is responsible for compliance with the limit values as prescribed in the national regulations. Only persons who are trained and qualified for the use and operation of this device may work on the device. Maintenance and modification: Only authorized personnel are allowed to repair or modify the inverter. To ensure optimum safety for user and environment, only the original spare parts available from your supplier should be used. Functional safety parameters: Unauthorized changes of functional safety parameters may cause injury or accidents to people or inverter. Additionally it will lead to the cancellation of all inverter operating approval certificates. 3

1.5 Disposal Please dispose the package and replaced parts according to the rules applicable in the country where the device is installed. Do not dispose the GMDE inverter with normal domestic waste. 1.6 Exclusion of Liability GMDE Technology Ltd. will not be liable for any direct, indirect or consequential damages, losses, costs or losses including without restriction any economic losses of any kind, any loss or damage to property, any personal injury, any damage or injury arising from or as a result of misuse or abuse, or the incorrect installation, integration or operation of the product. We disclaim any liability for direct or indirect damages due to: 1. Improper installation or commissioning, 2. Modifications, alterations or repair attempts, 3. Inappropriate use or operation, 4. Insufficient ventilation of the device, 5. Non-compliance with relevant safety standards or regulations, 6. Flood, lightning, overvoltage, storm, fire (acts of nature). We do not assume any liability for an incorrectly set country code. We reserve the right to make alterations that will improve the function of the device. Back to top 4

2.Description 2.1 General System Description Powervortex 3100 / 3700TL hybrid system is designed for the new installation of solar battery hybrid system. Figure 1 Powervortex 3100 / 3700TL hybrid system The system includes four modules: PV inverter, BM024 battery manager, lithium battery packs and energy meter. A B C D Figure 2 Main system components 1) SolDate 3100 / 3700TL PV inverter (Storage ready) The PV inverter converts the DC power generated by PV modules into AC power. The generated electricity from PV is used by the household loads, charged into the battery packs or fed into the grid. 2) BM024 battery manager In connection with the SolDate 3100 / 3700TL via DC bus line, BM024 battery manager charges / discharges the battery packs according to commands from integrated energy management unit. 3) Battery packs 5

Battery packs stores the energy generated from PV generator. Generally, each battery module capacity is 2.4kWh; so two battery modules can constitute 4.8kWh battery pack. 4) Energy meter The 1-phase bi-directional energy meter is for data collection and communication. With the meter data, the hybrid inverter decides when to charge / discharge the battery packs. 2.2 System connection The four main components are connected as displayed in Figure 3, which can not only optimize solar energy self-use and realize peak shaving, but also protect family from power outages. B9 PV 1 PV 2 F1 F2 F1 F2 B7 SolDate 3100/3700TL PV1+/- PV2+/- RS485 To BAT BUS+/- B6 B5 LOAD GRID To Grid F3 F4 To Emergncy Load L 5678 L N Smart Meter N TO PV BUS+/- To Inverter To Meter BAT Connetor B8 BAT+/- BM024 Battery Cabinet Emergency Load Other Load GRID Figure 3 System connection Back to top 6

3. System installation 3.1 Unpacking the device 3.1.1 Before unpacking All products are thoroughly tested and inspected before they re packed and transported. Although they re shipped in reliable package, damage during transportation could still occur. It is important to carefully inspect the shipping package prior to the installation. If any external damage on the package makes you suspect the device could be damaged or if you find that the device is damaged after unpacking it, report the damage immediately to your distributor or the goods forwarder. If it becomes necessary to return the device, please use the original packages in which they were delivered. The gross weight of SolDate 3100 / 3700TL is 25kg, for which BM024 is 10kg. To avoid injury, take the device at the two holding grips that are visible on the side and take the device outside the package. Ensure a second person to assist in the unpacking and installation of the devices. 3.1.2 Mounting 1. Don t install the device in direct sunshine. External heating from exposure to the sun may cause excessive internal heating. This may result in output power being reduced in order to protect the internal components from damage. 2. The SolDate 3100 / 3700TL weights 25 kg, the BM024 weights 10 kg. The installation wall must be vertical and can carry the weight of the devices. 3. Install the Powervortex 3100 / 3700TL in a location that maintains an ambient air temperature that is less than 45 C. The Powervortex 3100 / 3700TL may reduce its output power if the ambient air temperature exceeds 45 C (The cooler the air temperature, the longer the life expectancy of any electronics device). 4. The install position for Powervortex 3100 / 3700TL and battery cabinet, please refer to the device dimension figure and installation space figure (Figure 4~Figure 6). 5. The system should be installed in a location that is inaccessible to children. 6. The device is designed for indoor installation (IP20). 7. We recommend that you mount the device at eye level to ensure optimum user comfort. 8. Do not install the system on flammable construction materials, in areas close to flammable or explosive materials. 7

Figure 4 Powervortex 3100 / 3700TL dimension Figure 5 Battery cabinet dimension Module SolDate 3100 / 3700TL BM024 battery cabinet Dimension 500mm x 380mm x150mm 500mm x 280mm x150mm 700mm x 580mm x350mm Weight 25kg 10kg 20kg Table 1 Main modules specification 8

Figure 6 Installation space 3.1.3 Packing List 3.1.3.1 SolDate 3100 / 3700TL packing list A2 A3 A4 A1 A5 A6 A7 Figure 7 SolDate 3100 / 3700TL packing list Item Description pcs A1 SolDate 3100 / 3700TL PV inverter 1 A2 SolDate3100 / 3700TL mounting bracket 1 A3 Expansion Tube 4 9

A4 Tapping Screws 4 A5 Aviation Plug Female (for AC grid connection) x 1 1 A6 Aviation Plug Male Connector (for emergency load connection) x1 1 A7 Powervortex 3100 / 3700TL user manual 1 Table 2 SolDate 3100 / 3700TL packing list 3.1.3.2 BM024 packing list B2 B3 B4 B5 B1 B6 B7 B8 B9 Figure 8 BM024 packing list Item Description pcs B1 BM024 battery manager 1 B2 BM024 mounting bracket 1 B3 Expansion Tube 4 B4 Tapping Screws 4 B5 DC connection line between BM024 and SolDate 3100 / 3700TL 1 B6 Communication line between BM024 and SolDate 3100 / 3700TL 1 B7 Communication line between BM024 and battery packs 1 B8 DC connection line between BM024 and battery packs 1 B9 Communication line between battery cabinet and energy meter 1 Table 3 SolDate 3100 / 3700TL packing list 3.1.3.3 Unpacking battery packs and battery cabinet C Figure 9 battery cabinet packing list E 10

Item Description pcs C Battery cabinet 1 E 48V50Ah battery module 2 Table 4 battery cabinet packing list 3.1.3.4 Unpacking energy meter Figure 10 energy meter (D) 3.2 Mounting 3.2.1 SolDate 3100 / 3700TL and BM024 installation Choose a proper location to install the system according Figure 11. 3.2.1.1 Mounting SolDate 3100 / 3700TL (A1) 1) Mark the position on the wall of the bracket: hold the wall bracket A2 to the wall, keep the bracket vertical, and mark screw position 2) Remove the wall bracket A2, and then use Φ10 drill holes on marked position 3) Fix the expansion tube A3 in the hole 4) Fix wall bracket A2 on the wall 5) Fix screw A4 through wall bracket A2 to expansion screw A3, adjust the bracket position and screw up 6) Align with wall bracket, move SolDate 3100 / 3700TL (A1) in horizontal direction to proper position 7) Make the hook on wall bracket insert into the hole on SolDate 3100 / 3700TL(A1) 8) Slowly lower SolDate 3100 / 3700TL (A1), ensure the device hang on the hook of wall bracket A2 9) Check if SolDate 3100 / 3700TL (A1) is properly fixed on the wall or not 3.2.1.2 Mounting BM024 (B1) 1) Mark the position on the wall of the bracket B2: hold the wall bracket A2 to the wall, keep the bracket vertical, and mark screw position 2) Remove the wall bracket B2, and then use Φ10 drill holes on marked position 3) Fix the expansion tube B3 in the hole 11

4) Fix wall bracket B2 on the wall 5) Fix screw B4 through wall bracket B2 to expansion screw B3, adjust the bracket position and screw up 6) Align with wall bracket B2, move BM024 (B1) in horizon direction at proper position. 7) Make the hook on wall bracket B2 insert into the hole on BM024(B1) 8) Slowly lower BM024(B1), ensure the device hang on the hook of wall bracket B2 9) Check if BM024(B1) is properly fixed on the wall or not Install demonstration: Figure 11 SolDate 3100 / 3700TL and BM024 install demonstration 3.2.2 Mounting battery cabinet 1) Confirm DC BREAKER is shut off: Figure 12 side view of battery cabinet 2) Open the rear cover 3) Remove the baffle in the middle 4) Put in battery module E 5) Connect the battery power line (Red VCC, Black GND) and communication line (RS485) separately 12

Figure 13 The installation illustration on battery packs 6) Install battery baffle 7) Get the battery connection line B8 connect with DC port in the cabinet through BAT connector hole. The other side of battery connection line B8 is reserved. Close the rear cover, finish battery cabinet assembling 8) Each battery module has its unique address, when the BM024 is powering on, it inquiry the total number of battery modules on the bus line. To ensure that all the battery module is under the monitoring of BM024, battery address setting is necessary; for detailed battery setting, please refer to the Extra 2000 battery module user manual. The 5 in Figure 14 is the code switch, which adopts the 8421 code design; the default address for battery in the system is 2, 3, 4, 5. So please set the address of the 2 battery module in the 4.8kWh system as 2 and 3 respectively. Check Table 5 for details of code switch and battery module address configuration Figure 14 battery module interface illustration Coded bit 1 2 3 4 Address Pack Description ON OFF OFF OFF 1 Pack1 Reserve for corresponding with RS232 OFF ON OFF OFF 2 Pack2 Slave1 ON ON OFF OFF 3 Pack3 Slave2 OFF OFF ON OFF 4 Pack4 Slave3 ON OFF ON OFF 5 Pack5 Slave4 Table 5 illustration on battery module address configuration 13

9) Put on the rear cover to finish the battery packs installation 3.2.3 Mounting energy meter The energy meter should be mounted at the outward of the hybrid system, between the system and grid. Generally the energy meter is mounted on the inboard of household electric meter. Energy meter L/N is to connect with the grid, L /N is to connect with Powervortax3100/3700TL hybrid system. Powervortax3100/3700TL SYSTEM 5 6 7 8 L N Single Energy Meter SET L N GRID Figure 15 Mounting energy meter The meter address set inside the inverter is consisted of 0 + Meter Address. The Meter Address is referring to the Address: marked on every meter label (marked in red as below) as shown in Figure 16. Figure 16 Meter address Note 1: A suitable AC breaker should be installed outside of the inverter GRID port. CAUTION Ensure the grid is cut off before installing the meter 14

3.3 System connection B9 PV 1 PV 2 F1 F2 F1 F2 B7 SolDate 3100/3700TL PV1+/- PV2+/- LOAD GRID RS485 To BAT BUS+/- B6 B5 To Grid F3 F4 To Emergncy Load L 5678 L N Smart MeterN TO PV BUS+/- To Inverter To Meter BAT Connetor B8 BM024 BAT+/- Battery Cabinet Emergency Load Other Load GRID Figure 17 System connecting demonstration Note: A suitable AC breaker should be installed outside of the inverter GRID port. 3.3.1 How to make power connecting line Figure 18~Figure 21 are the connecting demonstration for PV connector, grid connector and emergency load connector. Please choose the proper wire (AWG12 recommended) to make different connectors according to the length of connecting line. Figure 18 PV+ connector(f1) wiring Figure 19 PV- connector (F2) wiring 15

Figure 20 GRID connector (F3) Line Figure 21 LOAD connector(f4) wiring Red is power line (L), black is neutral line (N), yellow green is grounding line (PE). 3.3.2 RS485 communication line GMDE inverter uses RJ45 jacks as the RS485 communication port. The RJ45 plug pin allocation is illustrated by figure 5. Figure 22 RJ45 plug pins allocation Pin No. Illustration 1 -- 2 -- 3 Data+ 4 GND 5 GND 6 Data- 7 5V 8 5V Table 6 RJ45 plug pins allocation 16

5 6 7 8 SE T Powervortex 3100 / 3700TL hybrid system user manual 3.3.3 System connection Please refer to table below and connect the power lines, communication lines with correspond ports on the device respectively. Item Line Illustration Illustration 1 B5 A1- BUS+/- B1- BUS+/- 2 B6 A1- TO BAT B1- TO PV 3 B7 A1- RS485 C- TO Inverter 4 B8 B1- BAT C- BAT Connector L N Single Energy Meter 5 L N B9 C- TO Meter D- 5 & 6 6 Solar panel F1 A1- PV1+ & PV2+ 17

5 6 7 8 SE T Powervortex 3100 / 3700TL hybrid system user manual 7 Solar panel F2 A1- PV1- & PV2- L N Single Energy Meter 8 L N F3 A1- GRID D- L & N 9 Emergency load F4 Table 7 A1- LOAD Connection line and corresponding ports list 3.3.4 9.6kWh connection The difference between 9.6kWh and 4.8kWh system are listed as below: 1) Modify the B8 line in Item 4 listed in Table 7 with Y type connection line to communicate the BM024 with 2 battery cabinets(4.8kwh for each cabinet) 2) Modify the connection listed in Item 5 in Table 7: connect the TO METER port on battery cabinet 1 with the TO INVERTER port on the battery cabinet 2 3) Connect the TO METER port on the battery cabinet 2 with the energy meter port listed in Item 5 in Table 7 4) Configure the battery module address; refer to the Table 5 to configure the address of 4 battery module as 2, 3, 4 and 5 respectively 18

Figure 23 9.6kWh system power line connecting Back to top 19

4. System settings 4.1 LCD 4.1.1 LCD Interface All information related to the inverter can be obtained from the LCD display. There are 4 navigation keys on the LCD display panel. The functions of these navigation keys and indication lights on the LCD screen are illustrated as below: Figure 24 LCD interface Item Symbol Meaning Illustration 1 ESC Cancel Move back to the upper item or close 2 Up Move back to the upper item or previous page 3 Down Move forward to down item or next page 4 OK Enter/ Escape Enter into or escape from the current page Table 8 LCD Function introduction 4.1.2 LCD indication lights Item Definition Description PV operation light Battery operation light WiFi operation light Light on when hybrid inverter system is running smoothly Light on if the communication between PV inverter and Battery manger is fine Light on when the WiFi is running Warning light Light on when system warning happens Table 9 LCD status light definition 20

4.1.3 LCD Display definition Figure 25 LCD display No. Item Definition 1 Time Current date and time 2 Systemstatus Operating status of the inverter (Wait / Start / Normal / Warning / Fault/Off-grid) 3 Energy EIN/EOUT/EPV (EIN: battery charging energy; EOUT: battery discharging energy; EPV: PV generated energy) 4 PV1 Power Power of PV1 5 PV2 Power Power of PV1 6 Grid power Power out/into the grid 7 Load power The current load power 8 Battery power Battery charging / discharging power 9 Menu Menu and data display Table 10 LCD display definition 4.1.4 LCD display menu definition The menu includes display menu and setting menu. The display menu shows system related parameters and its value. The setting menu is to configure parameters to ensure the system is running according to customer demand. Users can change page by, button in setting menu, long press OK button for 3 seconds you can enter setting menu. Choose parameters by press, button if necessary. Display menu definition: Item Description PV1 Voltage / current PV2 Voltage / current BAT Voltage / current AC Voltage / current 21

TEM Temperature FRE Grid frequency ET1 Daily PV generation energy SOC Battery capacity SMC Version No. of communication board SMM Version No. of master CPU SMS Version No. of slave CPU SMB Version No. of BM024 CPU Table 11 LCD menu definition 4.1.5 LCD Setting Setting the device when initial commissioning. Long press the OK button to entry the LCD setting. The initial password to enter the LCD setting is 6666, input the password and enter the LCD setting page. The definition of the LCD setting is as below: Item Description PW Password 6666 TIM Time TYP Battery type 00 Lithium-ion battery (default) 01 Lead battery BVH Battery charging stop voltage (default 54V) BVL Battery discharging stop voltage (lithium default 46V, lead-acid default 46V) Id Max discharging current (default 50A) Ic Max charging current (default 50A) 00 G83 (default) CER Certification 01 VDE 0126/4105 02 AS4777 01 Only PV1 CNY PV connection 02 Only PV2 03 PV independent (default) 04 PV parallel MDE 00 PV self of use Operation 00 charging time mode 01 Forced Time of Use (TOU) 01 discharging time 00 (default) BAT1 Communication mode: RS485 01 BAT2 Communication mode: RS485 BMS 02 BAT3 Communication mode: RS485 03 BAT4 Communication mode: RS485 04 BAT5 Communication mode: CAN ADR Meter address (0-255) Note: regarding meter address setting in the inverter, please refer to Figure 16 in section 3.2.3 Mounting energy meter. 22

FED Grid feed-in power (default value 100%) RST Restore to the default setting (RST 1111) Table 12 LCD parameter setting Note: the LCD background light will be turned off if no actions within 2 mins. 4.2 WiFi 4.2.1WiFi function Powervortex 3100 / 3700TL solar battery hybrid inverter has integrated WiFi module. So the user can be connected to the Internet after WiFi- connecting and setting. Then logging into the GMDE web portal or GMDE APP on your smartphone, you can monitor your system running timely and remotely. There are 2 pre-conditions before setting the WiFi: 1) The WiFi indication light on Powervortex 3100/3700TL panel is lighting ; 2) WiFi signal is available at the installation site to be received by the antenna integrated in the inverter Figure 26 WiFi Antenna 4.2.2 WiFi Configuration 4.2.2.1 Visiting the WiFi portal inside the inverter End user can connect to the WiFi portal inside the inverter via smart ends like smartphone, PC or ipad etc. Choose the Wifi portal created by the corresponding inverter, whose network name is GMDE_XXXXXXXX (XXXXXXXX part is the Monitor SN), as shown in figure below. 23

Figure 27 Powervortex 3100 / 3700TL Wifi network After connecting to the inverter WiFi portal, open your Internet browser, input 11.11.11.1 to enter into the WiFi setting page. Log into the page with: Account: admin Password: admin Tick the checkbox below and click yes to finish the setting. Figure 28 Logging in for WiFi setting 4.2.2.2 Account and password setting Please set your Wifi network name and the password: 1) SSID: key in MDE 2) Key: Wifi password Figure 29 WiFi parameter setting Save your setting result and restart, if the device IP address is no longer 0.0.0.0, then the device is successfully connected to the Internet. 24

Figure 30 IP address If you ve registered on the GMDE web portal: http://portal.global-mde.com/, then log in and add inverter site. If not, please register first. 4.2.2.2 User account registration Registration procedures are as following: 1) Visit our website portal(http://portal.global-mde.com/ ) and log in Figure 31 Log in 2) Key in Username, password, e-mail address and monitor SN. Please notice: the Monitor SN is the Suffix of the GMDE_XXXXXXXX. For example: if the Wifi of one device is GMDE_3E227BB2, then the Monitor SN you should key in is 3E227BB2 25

Figure 32 GMDE registration window 3) Add the plant and inverter information after registration Figure 33 Add plant and inverter information As shown in Figure 33, a couple of plants can be managed under one account. A couple of inverters can be added into under each plant. 1) My sites: plant list 2) Inverter: inverters under the plant 3) Setting: plant related parameter setting 4) Change password: modify the log in password Back to top 26

5 System operation 5.1 System settings 1) Please confirm each connection lines are correctly and securely wired according to Figure 3 2) Turn the DC switch on Figure 34 SolDate 3100 / 3700TL DC switch 3) After the LCD lighting on, users can set parameters including password, time, battery type, county code and operation mode etc. For details please refer to section 4.1.5 LCD Setting. Turn off the DC switch; wait until the LCD screen is black out 5.2 System starting 1) Turn on AC switch, connect to the grid 2) Turn on the DC breaker on the battery cabinet Figure 35 Battery cabinet DC BREAKER 3) Turn on the DC BREAKER 4) The inverter will be ready to work automatically 27

5.3 System operating instructions 5.3.1 On-grid operation The hybrid inverter has 2 options of operation mode: 1. Self-use Mode If there is enough sunshine, PV energy supplies the load first and then charges battery packs; if the load power is covered and battery is full charged, surplus energy will be fed into the public grid to acquire the FiT. If there is no sufficient PV energy, the system discharges the battery pack first; if PV power and battery discharging power is smaller than the load power, then the grid co-supply energy to the load. 2. Time of Use Mode (Peak Shaving) The system charges the battery packs at off-peak time (pre-set charging time); discharges the battery packs at peak time (pre-set discharging time). 5.3.2 Off-grid operation The Powervortex 3100 / 3700TL hybrid inverter has integrated backup function. Note: maximum charging current, maximum discharging current, discharging stop voltage and charging stop voltage should be set before commissioning to maintain battery s lifetime. These parameters are set in LCD screen. 5.4 System maintenance When maintaining the system, power off the Powervortex 3100 / 3700TL. Please obey the following operations: 1) Turn off the AC breaker, which means cut the inverter off the grid 2) Turn off the DC breaker of battery cabinet 3) Turn off DC switch of SolDate 3100 / 3700TL 4) Waiting at least 15 min. before maintenance 5) After disconnecting all the cables, please move the inverter to a proper position for maintenance Note: if the system is not used for a long time, please turn off the whole system for safety. Back to top 28

6 Troubleshooting 6.1 Safety during Troubleshooting High electric voltage! Risk of death or personal injury by electric shock! Never work with live wires! It is prior to all connection and maintenance work. Make sure that the AC and DC wires are not charged. The connection area should only be opened by a licensed electrician. Warning! Danger from residual voltage out of capacitors. You must wait until the capacitors have fully discharged. Discharge takes around15 minutes. Caution! Danger from inadequate grounding. An inadequate grounding conductor connection can cause serious injuries to persons and damage to properties. 6.2 Faults A fault can be divided into two catalogues: a permanent failure and a temporary failure. A permanent failure is defined by a fault having been present for more than 15 minutes and cannot be acknowledged by inverter s auto-restart. Unlike permanent failure, a transient failure" is automatically acknowledged by the inverter. 6.3 Fault Messages and Actions List When failure occurs, warning codes will be displayed on the LCD screen. The latest 20 fault codes will be stored in the EEPROM. Check the history fault information via long-pressing the key ESC. Detailed fault definitions are listed as below: Fault messages Explanation Action E01 The DC injection of grid current is out of Contact the service if the error occurs range. repeatedly. E02 Different value between master and slave Wait until the controller has CPU. re-stabilized. E03 Different value between master and slave Wait until the controller has for GFCI. re-stabilized. E04 The current sensor is abnormal Wait until the controller has 29

re-stabilized. E05 Inverter current is over the tolerable value E06 Residual current is out of range Wait until the controller has re-stabilized. E07 The GFCI detection circuit is abnormal. Wait until the controller has re-stabilized. E08 Isolation resistance of PV-plant out of tolerable range before connecting to the Check insulation of the system. grid. E09 Rly-Warning Wait until the controller has re-stabilized. E10 Re-measure line voltage, contact the Master-grid voltage measurement-value service if grid voltage is within normal out of tolerable range. range. E11 Check system frequency and line The master-frequency is out of tolerable voltage. Contact the Service if system range. frequency is within normal range. E13 No-Utility Re-measure line voltage; contact the Service if line voltage is within normal range. E14 PV input voltage is over the tolerable maximum value. Check the voltage of solar panels E15 Inverter internal communication fail Please contact the service if continue occur E16 PV over temperature Allow the unit to cool down Possibly caused by switching actions on E17 Different value between master and slave the net. Re-measure line voltage. for grid voltage. Contact the Service if line voltage is within normal range. E18 Different value between master and slave Wait until the controller has for output DC current. re-stabilized. E19 Different value between master and slave Wait until the controller has for output DC current. re-stabilized. E20 DC bus soft start is over time Check input voltage E21 PV inverter soft start is over time Check the utility E22 PV inverter bus voltage is too low. Wait until the controller has re-stabilized. E23 PV inverter Bus voltage is too high. Wait until the controller has re-stabilized. E24 Check system frequency and line Different value between master and slave voltage. Contact the Service if system for grid frequency. frequency is within normal range. E25 Boost current is over the tolerable value. Restart system E26 Battery Manager input voltage is too high Re-confirm battery input voltage 30

E27 Battery Manager overtemperature Waiting for Battery Manager cooling down E28 Battery Manager boost current warning Re-start Battery Manager E29 PV inverter fan locked Check fan E30 Battery Manager fan locked Check fan E31 PV inverter GFCI fault Re-start PV inverter, contact the service if continue occur E32 PV inverter current-sensor fault Re-start PV inverter, contact the service if continue occur E33 PV inverter current is over the tolerate Re-start PV inverter, contact the service value if continue occur E35 PV inverter Bus fault Re-start PV inverter, contact the service if continue occur E40 PV inverter relay fault Re-start PV inverter, contact the service if continue occur E41 Communication failure between PV Check communication cable between inverter and Battery Manager PV inverter and Battery Manager E42 Communication failure between PV Please check the energy meter and inverter and energy meter communication line status E43 Communication failure between PV and Please check BMS and communication BMS line status E46 +N Battery (2+N) over voltage warning Re-start battery E47+N Battery (2+N) low voltage warning Re-start battery E48+N Battery (2+N) Charge Over Current Warning Re-start battery E49+N Battery (2+N) discharge Over Current Warning Re-start battery E50+N Battery (2+N) Discharge Temperature Warning Re-start battery E51+N Battery (2+N) Charge Temperature Warning Re-start battery E52+N Battery (2+N) Under Voltage Warning Re-start battery Table 13 Fault lists N = (battery address- 2* 7), only suit for Pylon, Battery address respectively are 2, 3, 4 and 5. 6.4 Fault Acknowledgement After shutdown due to a fault, the device remains locked against reactivation until the fault is acknowledged. The fault can only be acknowledged after the cause of the fault has been eliminated. To acknowledge the fault messages, press the ESC key or turn the GMDE inverter off with the DC switch. Wait for a while and turn the device on again. 31

6.5 Technical Service GMDE Room 604-605, Tongpu Road No.1220, Putuo District, Shanghai 200333, P.R. China TEL: +86 21 60710809-818 FAX: +86 21 61730300 E-mail: Service@global-mde.com WEB: www.global-mde.com SKYPE: GMDE Service Back to top 32