MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

Similar documents
Selective Coordination

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

4-Day Power System Analysis, Coordination, System Studies

Protective Device Coordination ETAP Star

A. Submit manufacturer's literature and technical data before starting work.

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

Miniature circuit breaker Application guide

Secondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

Are the New 2005 NEC Selective Coordination Requirements Causing an Increase in Arc Flash Energies and Reducing Distribution System Reliability?

Engineering Dependable Protection

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Table Type FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units

www. ElectricalPartManuals. com Engineering Dependable Protection

Cutler-Hammer Molded Case Circuit Breakers Amperes. January 2001 Vol. 1, Ref. No. [0477] G-Frame

Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current-Limiting Circuit Breakers

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

Cutler-Hammer. January 2001

Design Standards NEMA

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

Evaluating Selective Coordination Between

MAGNETIC MOTOR STARTERS

Published for electrical engineers by EPOWERENGINEERING and available at The ABC s of Overcurrent Coordination

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

Amperes. F-Frame. Price U.S. $ Catalog Number. Price U.S. $ EDH2100 EDH2125 EDH2150 EDH2175 EDH2200 EDH2225

Selective Coordination Enforcement:

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

3.2. Current Limiting Fuses. Contents

Low Voltage Fuses For Motor Protection

Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks

Application of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers

Recommended Procedures

Low-Peak 600V Class RK1

Cutler-Hammer. Molded Case Circuit Breakers Amperes. Product Selection January 2001 Vol. 1, Ref. No ) J-Frame

Switchboards Instant Service

Cutler-Hammer. January 2001

Cutler-Hammer. Molded Case Circuit Breakers Amperes. -" Product Selection M-Frame

Cutler-Hammer. Molded Case Circuit Breakers Amperes F-Frame. January 2001

Cutler-Hammer. Molded Case Circuit Breakers Amperes January J-Frame

ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

XT IEC Power Control Manual Motor Protectors

FUSES VERSUS CIRCUIT BREAKERS FOR LOW VOLTAGE APPLICATIONS

ACHIEVING MAXIMUM BENEFITS WITH A FUSE PROTECTED MOTOR CONTROL CENTER

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

Selection Guide Motor Control Device Solutions

3RV1011-0DA15 CIRCUIT-BREAKER, SIZE S00,

Alternator protection, part 1: Understanding code requirements

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

Source-Side Fuse/Load-Side Recloser Coordination

PROTECTION AND CONTROL

TERMS AND DEFINITIONS

Motor Protection. Presented By. Scott Peele PE

Devices for Branch Circuits and Feeders

Transfer switch OTEC open or delayed transition

OVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

ECET Distribution System Protection. Overcurrent Protection

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

LPSRK30SP 30A 600V TD Dual Elem Class RK1 Low Peak Fuse

Cascading & Discrimination

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

CENTERLINE 2100 Motor Control Centers

A302DN.40/.63A Thermal Current Motor Starter

General Purpose US Fuses

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Self-protected Combination Starters System PKZ 2-SP

Technical Section: Miniature Circuit Breakers

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse

Technical Information

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications

Product Line Overview. The Most Logically Designed Contact Assembly

SECTION MOTOR CONTROL

Molded Case Circuit Breakers Amperes LSIA. LSIG Catalog Number 3-Pole Standard Interrupting Capacity 600V AC Rated V AC 13,950.

OTEC Transfer switch open transition

Motor Branch Circuit Over-Current Protection

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction

Horizontal Circuit Switchers

Table of Contents. Review Answers...84 Final Exam...85 quickstep Online Courses...88

Designed for ease of integration with automation systems

Selective Coordination

Power systems Protection course

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

www. ElectricalPartManuals. com TRI-PAC circuit breakers current limiting protectors for. lighting, power and distribution circuits

SURE-TRIP OEM RELACEMENT TRIP UNIT

Operation and Protection of Motors up to 600Hp at 460Vac (800A)

Now - Up To 400A Mains!

Section 1 Introduction to the Presentation

Tolerance-Based Time-Current Coordination

Transcription:

MOLDED CASE CIRCUIT BREAKER BASICS David Castor, P.E.

History of MCCBs 1904 - Cutter Manufacturing Co., Philadelphia, produces circuit breakers. They called it the Inverse Time Element breaker, or I-T-E breaker and the company later became the I-T-E Co. 1925 - NEC- Circuit breakers required to be enclosed and externally operable. 1932 - Westinghouse introduces their modern molded case air circuit breaker. 1973 First electronic trip unit

Basic MCCB Components Molded Case Line and Load Terminals Operating Mechanism Trip Bar Contacts Arc Extinguisher

Standards In the US, the primary MCCB standard is UL 489. UL 489 covers virtually all types of molded-case circuit breakers. NEC and UL 489 requirements are generally harmonized and consistent NEMA AB3 and AB4 are free standards on application and field inspection/testing of MCCBs.

Thermal-Magnetic MCCB Electro-mechanical Two separate tripping mechanisms: Thermal inverse-time element for low level faults/overloading Magnetic (Instantaneous) trip for short circuits Magnetic trip may be adjustable

Thermal Element Bimetallic Element Unequal thermal expansion causes element to bend Inverse time characteristics higher current, more heat faster tripping. Protects against long-term overloads, low current faults Sensitive to ambient temperature

UL Requirements for Thermal Element Must carry 100% of rated current continuously at 40 deg C ambient IN OPEN AIR. At 200% rated current, maximum trip times are given based on breaker size: Amp Rating Max Time @ 200% 0-30 2 min 31-50 4 min 51-100 6 min 101-150 8 min 151-225 10 min.. 1601-2000 28 min

Magnetic Trip Electro-magnet in series with current. Designed to trip above a certain current with no intentional delay. Detects short circuit current Adjustable in larger breaker sizes Generally will respond to peak asymmetrical current 1.5 cycle fault clearing or less Magnetic trip is why arc-flash levels tend to be low when protected by MCCB. MCCB must have instantaneous trip per UL489. Can create mis-coordination for MCCBs in series

Typical Thermal-Magnetic TCC Thermal Magnetic

Generic MCCBs in EasyPower Provide typical thermalmagnetic TCCs for MCCBs up through 1200 A. TCCs consistent with UL 489 tripping requirements and IEEE 1584. Use in design phase or when exact breaker type is not known. Should be conservative A Generic design sheet is also provided in Auto Design.

Motor Circuit Protectors (MCPs) MCCB with NO THERMAL element. Magnetic-only Can ONLY be used as part of a listed combination motor starter. Overload relay provides the thermal protection Cannot use as a feeder breaker. In EasyPower treated as thermal-magnetic

MCP + Overload Relay

Motor OL Defined with Bkr Data

Advantages of MCPs Special application allows wider range of sizes and trip adjustments than standard thermal-magnetic breakers Specially-designed trip coils with some transient suppression Faster tripping for typical motor faults than fuses.

Solid-State Trip Units Electronic (now all digital) current sensing replaces thermal and magnetic trip elements. Trip mechanism and arcextinguishing same as thermal-magnetic More accurate and more flexible settings Instantaneous still required. Ground fault easy to provide Becoming standard for larger size breakers Required for 100%-rated breakers.

Typical TCC for Large MCCB w/ss Trip Long-time pickup (may be fixed w/rating plug Long-time delay Short-time trip Instantaneous trip Ground trip Metering functions Communications Long-Time Short Time Instant.

MCCB Maintenance & Testing Can be difficult to tell when MCCB needs replacing. No user serviceable parts opening case voids warranty. Thermography has proven useful to get some assessment of breaker condition. UL489 type testing requires two fault interruptions at the breaker max fault rating. IEEE 1458 covers life expectancy and field testing of MCCBs. (Not free!) Arc-Flash calculations assume all breakers will function within published TCC.

NEMA AB4 Covers MCCB Field Inspection and PM Free standard Replace not Repair

MCCB Interrupting Ratings MCCB have a single short circuit rating, stated in rms symmetrical amps using ½ cycle network. However, breaker testing is done at a specific power factor. If your system s X/R exceeds the test value, the breaker must be de-rated. This is done automatically using SmartDuty. Interrupting Rating Test Power Factor Equivalent X/R 10 ka and below 0.5 1.7 >10 ka<20 ka 0.3 3.2 20 ka and above 0.2 4.9

X/R Ratio Key Factor in Breaker Ratings Determines peak ½ cycle current Determines magnitude of interrupting current Even for breakers rated on a symmetrical basis, peak current is still the critical value If system X/R exceeds test X/R, breaker must be de-rated. De-rating is done by INCREASING the DUTY amps

1-1/C-350 MCM CU, 15', [Conduit] 2-1/C-350 MCM CU, 25', [Conduit] Coordination Between MCCBs General case do not coordinate May coordinate below certain levels of fault current if the maximum fault current is less than the instantaneous pickup of the upstream breaker Fault Here May Trip All Three Bkrs SWBD MCC PNLBD 0.48 kv GE THKM8 800A 0.48 kv GE THJK4 400A 0.48 kv L-1 0.1 MW 0.06 MVAR GE TED (480V) 150A

TIME IN SECONDS TIME IN SECONDS MCCBs in Series CURRENT IN AMPERES X 10 AT 480 VOLTS.5.6.8 1 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 100 2 3 4 5 6 7 8 9 1000 2 3 4 5 6 7 8 9 10000 1000 1000 900 900 800 800 700 700 600 600 500 500 400 400 300 SOUTH SLAB MAIN 300 Cutler Hammer Series C 200 HMDL 200 Frame = 800A(700-800T) Trip = 800 Inst = LOW (3200A) 100 100 90 90 80 80 70 70 60 60 50 50 40 S-3 6-PACK BKR 40 Cutler Hammer Series C 30 HFD 30 Frame = 225A (100AT) Trip = 100 20 20 10 10 9 9 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1.9.9.8.8.7.7.6.6.5.5.4.4.3.3.2.2.1.1.09.09.08.08.07.07.06.06.05.05.04.04 NEC Does Not Require Selective Coordination Except for Emergency Power Systems MCCB manufacturers now testing for series coordination between breakers to compete with fuses on selective coordination.03.03.02.02 SOUTH S-3 6-PACK SLAB BKR MAIN 14574A.01.01.5.6.8 1 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 100 2 3 4 5 6 7 8 9 1000 2 3 4 5 6 7 8 9 10000 CURRENT IN AMPERES X 10 AT 480 VOLTS

Series Coordination of MCCBs: Valid only by test Test data shows MCCBs will coordinate even though curves overlap on TCC Limited to same manufacturer Valid up to a maximum fault current Tracked in EasyPower Library Data NOTE: Do not confuse Series Coordination with Series Rating. These are two different concepts.

MCCB Series Ratings Conservative approach: All breakers rated for maximum Isc at their location. (Sleep well) But, when interrupting faults, MCCBs do have a dynamic impedance that is ignored in fault calcs. This reduces fault current to downstream breakers. With proper testing, MCCBs can have a higher interrupting rating when there is another MCCB upstream that will see the same fault. Must be tested combination so must be same manufacturer. Will not coordinate for high levels for fault current Covered in EasyPower library data

Use of Series Ratings Intended for smaller distribution panels and circuits where loads are primarily branch circuits (lighting, receptacles, etc) Cannot safely apply series ratings if there are substantial downstream motor loads. EasyPower defaults to fully rated series rated must be selected.

Motor Contribution Problem Motor contributions may not be seen by the upstream device that is the basis for the series rating. Series rating cannot be used in this case.

100% Rated MCCBs Standard MCCBs rated for 100% current continuously in OPEN AIR. In an enclosure, they are generally limited to 80% continuous current Continuous is defined as 3 hours This is the basis of the NEC load calcs using 125% of continuous load (1/1.25 = 0.8)

Limitations of 100%-Rated MCCBs 100% Rating requires minimum enclosure size to limit heating Requires electronic trip unit Requires 90 deg C insulation applied at 75 deg C ampacity Not always an option More prevalent for larger breakers.

MCCBs and Arc-Flash For buses protected by MCCBs: If arcing fault is cleared on magnetic trip, incident energy will be low - but coordination may be poor If cleared by thermal element, incident energy will be HIGH This assumes the breaker will actually trip!

Arc-Flash Example Let s look at a quick example in EasyPower We ll see how MORE fault current is better than LESS fault current when protected by a molded case circuit breaker.

MCCB Modeling in EasyPower Library Data is based on manufacturer data TCC range varies Lots of breakers with similar names must get exact match Use Find Style whenever possible Generic TCCs are OK for Arc Flash calcs if actual data not available.

MCCBs in EasyPower Library Separate library entries for ANSI/UL and IEC rated devices. If you find an MCCB that is not in the library, send data to Tech Support and we will add it to the library at no cost for all customers on maintenance.

Questions? Please e-mail any additional questions to nicole@easypower.com Thank you!