Station post INSULATORS
station post Station post The GAMMA and GAMMA-CERISOL brand of ANSI solid core porcelain station-post are ideally suited for substation bus support and switch applications. Station posts in this catalog are available in standard strength, high strength, and extra high strength, in ratings from 95kV BIL through 1800kV BIL, and for applications ranging from 7.5kV through 500kV operating voltages. Each insulator body is molded from the highest quality raw materials produced in our state-of-the-art mineral processing facilities, yielding a product of exceptional wet process workability, purity, and uniformity. The entire surface of each station post receives a smooth, uniform glaze, in either gray or brown, to provide maximum mechanical porcelain strength, to resist the accumulation of contaminants on the surface, and to facilitate ease of cleaning via rain or routine maintenance. In addition, the product line features uniform surface drying and voltage distribution to prevent flashover as well as dry-band arc suppression for high performance and long term reliability. All hardware fittings are manufactured using hot dipped galvanized malleable cast iron or ductile cast iron, and are designed specifically for all mechanical and electrical applications to ensure optimum performance and service longevity. Portland base mortar is used to secure the hardware to the porcelain body using a proven system that transfers the load uniformly from the hardware into the porcelain body. A bituminous coating is applied on the porcelain and the interior of the fittings to compensate for thermal expansion in extreme weather applications., 95kV BIL, 110kV BIL 202SU0095 222HU0095 205SU0110 225HU0110, 750kV BIL, 900kV BIL 291SU0750 295HU0750 304SU0900 308HT0900 308HU0900 Small station post 8606 8607 8608 8609 8610, 150kV BIL, 200kV BIL, 250kV BIL 208SU0150 227HU0150 210SU0200 231HU0200 214SU0250 267HU0250, 1050kV BIL, 1300kV BIL 312ST1050 312SU1050 316HT1050 316HU1050 362EU1050 324ST1300 324SU1300 367HT1300 368EU1300 369ET1300, 350kV BIL, 550kV BIL, 650kV BIL 216SU0350 278HU0350 286SU0550 287HU0550 288SU0650 289HU0650, 1470kV BIL, 1550kV BIL, 1800kV BIL 330SU1470 371HT1470 372EU1470 373ET1470 379HT1550 391ST1800 Content
STATION POST INSULATORS Sheds Sheds are designed to provide excellent electrical insulation under highly contaminated conditions, and are strong enough to provide protection against mechanical intrusion. If the shed does break, it is designed to break cleanly, leaving the body undamaged and the insulator serviceable. In addition, our station post insulators utilize sheds that, when accompanied with adequate angle and radius geometry, will ensure the best protection against rain and pollution. 100% Solid Core Porcelain Body Each insulator body is molded from the highest quality raw materials produced in our state-of-the-art mineral processing facilities, yielding a product of exceptional wet process workability, purity, and uniformity. Hardware All our Station Post hardware fittings are manufactured using hot dipped galvanized malleable cast iron or ductile cast iron. Are designed specifically for all mechanical and electrical applications to ensure optimum performance and service longevity. Glaze The entire surface of each Station Post receives a smooth, uniform glaze in either gray or brown to provide maximum mechanical porcelain strength, to resist the accumulation of contaminants on the surface, and to facilitate ease of cleaning via rain or routine maintenance. Cementing With Portland base mortar, hardware fittings are cemented to the porcelain body using a proven system that transfers the load uniformly from the hardware into the porcelain body. A bituminous coating is applied on the porcelain and the interior of the fittings to compensate for thermal expansion in extreme weather applications. World class manufacturing facilities and engineering expertise, along with in-house tooling and development capabilities, give us the ability and skill set required to produce custom designed station posts for a wide variety of applications and customer specifications. Experience the GAMMA Difference!
, 95 kv BIL Ø1/2" - 13 Ø5/8" - 11 7 1/2" 10" 3" Ø4 1/4" Ø7" TR-202 5" Ø6.25" Ø7.24" TR-222 202SU0095 222HU0095 TR-202 TR-222 Leakage distance 10 1/2 10 1/2 4000 4000 7000 15000 6000 0 1 Typical application voltage Note 2: can be ordered with M12 thread size. 7.5 105 30 95 5 50 7.5 105 30 95 5 50
, 110 kv BIL Ø 1/2" - 13 Ø 5/8" - 11 10" 12" 3" 5" Ø4 1/4" Ø6.25" Ø7" Ø7.24" TR-205 TR-225 205SU0110 225HU0110 TR-205 TR-225 Leakage distance 15 1/2 15 1/2 4000 4000 8500 7000 14000 0 Typical application voltage Note 2: can be ordered with M12 thread size. 15 125 45 110 15 125 45 110 10 10 50 50
, 150 kv BIL Ø 1/2" - 13 Ø 5/8" - 11 14" 15" 3" Ø4 1/4" Ø6 1/2" 5" 1" Ø8.46" TR-208 TR-227 208SU0150 227HU0150 TR-208 TR-227 Leakage distance 24 24 4000 4000 0 8000 0 16000 Typical application voltage Note 2: can be ordered with M12 thread size. 23 170 60 150 23 170 60 150 15 15 100 100
, 200 kv BIL Ø 1/2" - 13 Ø 5/8" - 11 18" 20" 3" 5" Ø4 1/4" 1" Ø7 1/2" Ø8.58" TR-210 TR-231 210SU0200 231HU0200 TR-210 TR-231 Leakage distance 37 37 4000 4000 1 0 15000 30000 Typical application voltage Note 2: can be ordered with M12 thread size. 34.5 225 80 200 34.5 225 80 200 22 22 100 100
, 250 kv BIL Ø 1/2" - 13 Ø 5/8" - 11 22" 24" 3" Ø4 1/4" Ø7" 5" 1" Ø8.74" TR-214 TR-267 214SU0250 267HU0250 TR-214 TR-267 Leakage distance 43 43 4000 4000 14000 1 15000 Typical application voltage Note 2: can be ordered with M12 thread size. 46 280 100 250 46 280 100 250 30 30 200 200
, 350 kv BIL Ø1/2" - 13 Ø 5/8" - 11 30" 30" 3" Ø4 1/4" Ø8.1" 5" " Ø9.1" TR-216 TR-278 216SU0350 278HU0350 TR-216 TR-278 Leakage distance 72 72 1500 1500 3000 3000 16000 15000 Typical application voltage Note 2: can be ordered with M12 thread size. 69 390 145 350 69 390 145 350 44 44 200 200
, 550 kv BIL 45 45 Ø6.22 Ø8.46 TR-286 Ø9.4 TR-287 286SU0550 287HU0550 TR-286 TR-287 Leakage distance 99 99 1700 1700 2600 2600 90000 75000 Sheds 610 230 550 Note 2: can be ordered with M16 thread size if 5/8-11UNC diameter. 610 230 550 73 73 200 200 21 21
, 650 kv BIL 54 54 Ø6.22 Ø8.46 TR-288 Ø9.1 TR-289 288SU0650 289HU0650 TR-288 TR-289 Leakage distance 116 116 1400 1400 2200 2200 90000 75000 Sheds 710 275 650 Note 2: can be ordered with M16 thread size if 5/8-11UNC diameter. 710 275 650 88 88 200 200 25 25
, 750 kv BIL 62 62 Ø6.22 Ø8.78 TR-291 Ø9.53 TR-295 291SU0750 295HU0750 TR-291 TR-295 Leakage distance 132 132 1200 1200 1850 1850 90000 75000 Sheds 810 315 750 Note 2: can be ordered with M16 thread size if 5/8-11UNC diameter. 810 315 750 103 103 500 500 27 27
, 900 kv BIL 40 40 40 Ø9.33 80 80 80 40 40 40 Ø6.22 Ø8.39 Ø9.33 Ø9.33 TR-304 TR-308 HT TR-308 HU EXTRA - 304SU0900 308HT0900 308HU0900 TR-304 TR-308 TR-308 Leakage distance 165 165 165 950 950 1450 1450 1450 90000 75000 90000 75000 1010 385 900 1010 385 900 1010 385 900 146 146 146 500 500 500 Sheds unit 1 20 20 20 Sheds unit 2 20 20 20 Note 2: can be ordered with M16 thread size if 5/8-11UNC diameter.
, 1050 kv BIL 46 46 92 92 46 48 Ø6.22 Ø8.46 TR-312 ST Ø6.22 Ø8.46 TR-312 SU Leakage distance Sheds unit 1 Sheds unit 2 Note 2: can be ordered with M16 thread size if 5/8-11UNC diameter. 312ST1050 TR-312 198 800 1210 455 1050 146 500 312SU1050 TR-312 198 800 800 1210 455 1050 146 500 21 21 21 21
, 1050 kv BIL Ø 3/4" - 11UNC 46 46 46 Ø8.98 Ø10.24 92 92 92 46 46 46 Ø9.41 TR-316 HT Ø9.41 TR-316 HU Ø10.43 TR-362 EU EXTRA - 316HT1050 316HU1050 362EU1050 Leakage distance Sheds unit 1 Sheds unit 2 TR-316 198 1250 90000 75000 1210 455 1050 146 500 Note 2: can be ordered with M16 thread size if 5/8-11UNC diameter. Note 3: can be ordered with M20 thread size if 3/4-10UNC diameter. TR-316 198 1250 1250 90000 75000 1210 455 1050 146 500 TR-362 198 2300 2300 1 00 1210 455 1050 146 500 21 21 21 21 21 21
, 1300 kv BIL 53.15 53.15 Ø8.46 106.0 106.0 52.83 52.83 Ø9.06 TR-324 ST Ø9.06 TR-324 SU Leakage distance Sheds unit 1 Sheds unit 2 324ST1300 TR-324 231 90000 75000 Note 2: can be ordered with M16 thread size if 5/8-11UNC diameter. 1410 525 1300 220 25 28 324SU1300 TR-324 231 90000 75000 1410 525 1300 220 28 28
, 1300 kv BIL Ø 3/4" - 11UNC 53.15 53.15 53.15 Ø8.46 Ø10.04 Ø10.04 106.0 106.0 106.0 52.83 52.83 52.83 Ø 3/4" - 11UNC Ø10.04 TR-367 HT Ø10.43 TR-368 EU EXTRA - Ø 3/4" - 11UNC Ø10.43 TR-369 ET EXTRA - 367HT1300 368EU1300 369ET1300 TR-367 TR-368 Leakage distance 231 231 1450 2050 2050 1 00 Sheds unit 1 Sheds unit 2 1410 525 1300 220 Note 2: can be ordered with M16 thread size if 5/8-11UNC diameter. Note 3: can be ordered with M20 thread size if 3/4-10UNC diameter. 1410 525 1300 220 TR-369 231 2050 1410 525 1300 220 25 28 28 28 27 27
, 1470 kv BIL Ø6.22 Ø 3/4" - 11UNC 61 61.0 61.0 61.0 Ø8.78 Ø10.24 Ø9.53 128.0 128.0 128.0 128.0 61 61.0 61.0 61.0 Ø9.53 Ø 3/4" - 11UNC Ø9.72 Ø10.32 Ø 3/4" - 11UNC Ø10.32 TR-330 SU TR-371 HT TR-372 EU TR-373 ET EXTRA - EXTRA - 330SU1470 371HT1470 372EU1470 373ET1470 TR-330 TR-371 TR-372 TR-373 Leakage distance 264 264 264 264 900 1170 1750 1750 900 1750 90000 75000 1610 590 1470 220 1610 590 1470 220 1610 590 1470 220 Sheds unit 1 27 27 28 27 Sheds unit 2 27 28 28 28 Note 2: can be ordered with M16 thread size if 5/8-11UNC diameter. Note 3: can be ordered with M20 thread size if 3/4-10UNC diameter. 1610 590 1470 220
, 1550 kv BIL 64.0 Ø9.53 128.0 Ø10.32 64.0 Ø 3/4" - 11UNC Ø10.83 TR-379 HT 379HT1550 TR-379 Leakage distance 280 1700 Sheds unit 1 Sheds unit 2 Note 2: can be ordered with M16 thread size if 5/8-11UNC diameter. 1710 620 1550 318 27 31
, 1800 kv BIL Ø6.69 Ø10.43 50.67 Ø10.43 152.0 50.67 UNIT 3 Ø10.83 50.67 Ø 3/4" - 11UNC Ø10.83 TR-391 ST 391ST1800 TR-391 Leakage distance 321.5 1400 Sheds unit 1 Sheds unit 2 Sheds unit 3 Note 2: can be ordered with M16 thread size if 5/8-11UNC diameter. 710 1800 318 23 23 22
Small station post 3/8-16 Thread (Galv. Steel) TYP 3/8-16 Thread (Galv. Steel) TYP 3/8-16 Thread (Galv. Steel) TYP 6 3/4" 7" 8" 1" 2 1/4" Ø3 7/10" Ø5 1/2" 1" 2 1/4" Ø3 7/10" Ø5 1/2" 1" 2 1/4" Ø3 7/10" Ø5 1/2" 8606 8607 8608 3/8-16 Thread (Galv. Steel) TYP 3/8-16 Thread (Galv. Steel) TYP 9" 10" 1" 2 1/4" Ø3 7/10" Ø5 1/2" 1" 2 1/4" Ø3 7/10" Ø5 1/2" 8609 8610 8606 8607 8608 8609 8610 Leakage distance 13 9/16 14 1/4 17 1/2 20 7/8 24 3/8 Cantilever strength, pounds, pounds Torsion strenght, inch-pounds Compression strenght, pounds 1200 5000 3000 0 1200 5000 5000 5000 900 5000 5000 5000 3000 5000 5000 5000 5000 5000 Low-frequency withstand, 10 sec. wet 30 30 45 50 60 Basic insulation level (BIL), kv 95 110 125 125 150 Note: ANSI 70 gray is standard. Brown available by request.